Thermatel® Enhanced Model TA2 Thermal Mass Flow Meter D E S C R I P T I O N The Thermatel® Enhanced Model TA2 Thermal Mass Flow Meter provides reliable mass measurement for air and gas flow applications. The powerful, yet easy to use, electronics are contained in a compact explosion proof enclosure. The TA2 is available with both insertion probes as well as flow body design for smaller pipe sizes. The TA2 offers excellent performance at an exceptional value. T E C H N O L O G Y F E A T U R E S • Direct mass flow measurement of air and gases • High turndown ratios • Excellent low flow sensitivity • Low pressure drop • ISO 17025 and NIST traceable calibrations P R O B E F E A T U R E S • Calibration Verification in the field • All 316 welded stainless steel and Hastelloy® C-276 construction E L E C T R O N I C S F E A T U R E S • Selection of process connections, including threads, welded flange construction, and use with a compression fitting • Compact explosion proof/Type 4X enclosure, mounted either integrally on the probe or at a remote location • Accepts all input power—15 to 30 VDC and 100 to 264 VAC • Process temperatures up to +400° F (+200° C) • Pressure rating to 1500 psig (103 bar) dependent upon process connections • Probe can be field-replaced • Optional pulse output plus second mA output which can be used for temperature or different flow range (mA output passive connection only) • Unique sensor design permits higher mass flow rates yet maintains equivalent thermal mass for varying temperature operation • HART communications with AMS and DTMs available • Optional hot tap retractable probe assembly • H1 FOUNDATION fieldbus protocol available • 2-line ¥ 16-character backlit display with four pushbuttons for ease of configuration A P P L I C A T I O N S • Rotatable housing • Combustion air • Digester/Bio-gas • Two calibration curves optional as well as field adjustment for different gases • Compressed air • Vent lines/Flare headers • Natural gas • Hydrogen lines • Language selections of English, German, French, Spanish, and Russian • Aeration air F L O W B O D Y F E A T U R E S • 1⁄2" to 4" pipe sizes • NPT threads available up to 2" in size • Stainless steel and carbon steel (with stainless steel sensor) construction • Flange connections for all sizes • Optional stainless steel flow conditioning plate for 1.5" and higher • Flow conditioning for 1⁄2" to 1" based on upstream length and sensor design A D D I T I O N A L F E A T U R E S TOTALIZER Two 7-digit flow totalizers, one resettable and one non-resettable are provided. Flow units selectable in user’s choice of engineering units. Totalizer data is electronically stored eliminating the need for backup batteries and provides maximum safeguard data in the event of a power interruption. The totalizer can be reset using the display module, HART or via PACTware ™. TEMPERATURE COMPENSATION Thermal flow technology measures the mass flow rate without the need for pressure and temperature correction as required with most gas flow instruments that measure the flow rate at actual conditions. However, changing temperature will change the properties of the gas which effect convective heat transfer. The Model TA2 measures the gas temperature and automatically adjusts the mass flow measurement for changes in gas properties over the entire temperature range of the instrument. DIAGNOSTICS Diagnostics is an important aspect of the TA2. The Enhanced TA2 has additional diagnostics to check the operation and performance of the unit. Diagnostics includes probe status, a test of RTD drift with automatic recalibration, and overall performance. In order to verify that the calibration and configuration match the original calibration conditions, the user can select a specific signal and compare the TA2 display value against the original calibration certificate. SELECTABLE STP CONDITIONS The TA2 directly measures mass flow of the gas 2 referenced to Standard Temperature and Pressure (STP) conditions. Software permits the user to change STP conditions for their own requirements. AREA COMPENSATION FOR PIPE SIZE The TA2 automatically compensates the flow measurement based on actual area of the pipe. The user simply enters the size or the area of the new pipe, and the instrument automatically calculates the flow including factors for the probe blockage. HART communication Using HART/AMS communication, the user can configure the instrument from a remote location. HART provides the same functionality as the display module interface including all configuration and diagnostic information. FOUNDATION fieldbus The Enhanced Model TA2 transmitter is a FOUNDATION fieldbus™ registered device that communicates with the H1 FOUNDATION fieldbus™ protocol operating at 31.25 kbits/sec. The H1 physical layer is an approved IEC 61158 standard. AIR EQUIVALENCY Using historic air-gas calibration data, an air equivalency calibration can be performed on select gases. Consult Magnetrol® for details and flow ranges. GAS CORRELATION MAGNETROL calibrates on two gases with known thermal properties and then correlates the data based on the NIST blend properties of the actual gas mix. Typical natural gas error is less than 3% from the actual gas calibration. A D D I T I O N A L PROBE F E A T U R E S INSTALLATION Probes can be provided with a variety of process connections, including threads, flanges, or installation through a compression fitting. The sensor will fit pipe sizes of 11⁄2" diameter or larger (2" minimum size with thread connection). The sensor is protected to prevent damage due to “bottoming-out” if inserted too far into a pipe. PULSE OUTPUT The optional pulse output provides a pulse output equivalent to user selected units and multiplier factor. Both active (power from the TA2) or passive (external power supply) connections are provided to match the user’s interface. This output can optionally be used as an alarm to indicate that the flow rate is above or below the desired set point. PORTABLE MODULE DISPLAY A portable display module for configuration and diagnosis of multiple units is available (part number 089-5219-002). This portable module plugs into the electronics in the same manner as the normal display and uses the same software menu. This module permits the user to reduce installation cost by having one display module with keypad for multiple TA2 units. Usage of the display module requires that the housing cover be removed during use and thus may not be useable in hazardous areas. In these cases, the HART option should be utilized. c o n t i n u e d NAMUR COMPLIANCE Model TA2 output signal meets NAMUR NE43 recommendations for the 4–20 mA signal levels. FACTORY CALIBRATION AND CONFIGURATION Each TA2 is calibrated at the factory for the type of gas and the specified flow rate. The instrument is configured for the specific application information. The result is an instrument which can be installed and immediately be placed into operation without field setup. CALIBRATION VERIFICATION MAGNETROL has developed a procedure to verify the calibration of the TA2 in the field. Following this procedure, the user can verify that the heat transfer characteristics of the instrument have not changed from first received. While the calibration is a permanent calibration, the user can now check the calibration without having to return the instrument to the manufacturer. When using a HART handheld or PACTware ™, the user is guided through the procedure. ELECTRICAL WIRING Elevated terminal strips with very visible markings make wiring of the TA2 extremely easy. Portable Display Module 3 PACTware™ P C S O F T W A R E The Most Efficient PC Configuration Tool for TA2 Mass Flow Meters PACTware is the modern, user-friendly adjustment software that enables quick configuration and diagnostics of your TA2 mass flow meters. With your PC connected through a serial interface to the HART loop, all functionality can be managed remotely anywhere on the loop. Parameters Screen Every Parameter in the TA2 can be reviewed and monitored remotely with a few clicks of the mouse. From units of measurement to pipe size, I/O Configuration or Calibration Factors, the parameters can be viewed or changed. Trending Screen Trending is available of the flow rate, temperature, and signal providing useful information on the operation of the TA2. This is especially important for troubleshooting and diagnostics if required. Parameters Screen Process Trend Screen A P P L I C A T I O N S COMPRESSED AIR/GASES Measurement of mass flow in different gas lines to determine compressor efficiency or in plant usage for internal allocation. Advantages: • direct mass flow • high turndown rates • flow totalization • easy installation BOILER COMBUSTION Natural Gas The TA2 measures the inlet air flow to the boiler. This signal is sent to the DCS where it is used to trim the natural gas flow. Advantages: • mass flow measurement • repeatable flow signal • high rangeability 4 A P P L I C A T I O N S NATURAL GAS FLOW The Model TA2 efficiently measures the flow and totalized flow of fuel to furnaces, heaters, or boilers. This data may be used for internal allocation or to report emission rates. Air Natural gas or propane Advantages: • direct mass flow in SCFM • built-in totalizer • ease in setup and operation FLARE LINES Measurement of flow in different sections of flare line. Advantages: • good low flow sensitivity • auto switching capability between multiple calibration curves for highest turndown • easy removal if cleaning is required AERATION AIR FLOW Measurement and balance of the flow to each section of the aeration basin in waste water treatment plants. Advantages: • low installation cost • direct mass flow • high reliability DIGESTER GAS/BIO-GAS The off gas from a digester contains a mixture of methane and carbon dioxide saturated with moisture. This is a difficult flow measurement due to low flow rate and low pressures. Advantages: To engine or flare • excellent low flow sensitivity • high turndown rates • provides measurement of flow and totalized flow 5 T E C H N O L O G Y THERMATEL Model TA2 flow transmitter measures mass flow by detecting heat dissipation from a heated surface. The sensor contains two mass balanced elements with precision matched RTDs. The reference sensor measures the process temperature (up to +400° F [+200° C]); the second RTD measures the temperature of the heated sensor. The power to the heater is varied to maintain a constant temperature difference above the reference temperature. compares the power against the calibration curve and converts the power requirements to the mass flow rate. Temperature is also measured to provide temperature compensation of the mass flow over the operating range of the instrument. For further information on thermal mass flow measurement, request a copy of the MAGNETROL “Thermal Dispersion Mass Flow Measurement Handbook,” Bulletin 54-621. There is an inherent non-linear relationship between power and mass flow. The microprocessor in the TA2 A G E N C Y A P P R O V A L S AGENCY APPROVED MODEL PROTECTION METHOD UNITED STATES & CANADA TA2-AXXX-X3X TA2-AXXX-X4X with TXR-XXXX-XXX (probe) TFT-XXXX-000 (flow body) Explosion Proof Dust Ignition Proof Non-Incendive Suitable for ATEX Class I, Div 1, Groups B, C, D T6 Ta = -40° C to +70° C, T5 Ta = -40° C to +80° C Class II, III, Div 1, Groups E, F, G T6 Ta = -40° C to +70° C, T5 Ta = -40° C to +80° C Class I, Div 2, Groups A, B, C, D T4 Ta = -40° C to +80° C Class II, Div 2, Groups E, F, G Class III, Div 1 T4 Ta= -40° C to +80° C Type 4X, IP 66 II 2 G Ex d IIC T6 Gb, Tamb -40° C to +55° C TA2-AXXX-X3X TA2-AXXX-X4X with TXR-XXXX-XXX (probe) TFT-XXXX-000 (flow body) Explosion proof EN60079-0: 2009 EN60079-1: 2007 TA2-AXXX-XEX TA2-AXXX-XFX with TXR-XXXX-XXX (probe) TFT-XXXX-000 (flow body) Ex d Explosion Proof w/IS probe circuit EN60079-0: 2009 EN60079-1: 2007 EN60079-11: 2007 EN60079-26 : 2007 IEC TA2-AXXX-X3X TA2-AXXX-X4X with TXR-XXXX-XXX (probe) TFT-XXXX-000 (flow body) Explosion Proof IEC 60079-0: 2007-10 IEC 60079-1: 2007-04 EAC TA2-AXXX-X3X TA2-AXXX-X4X Russian Authorization Standards Consult MAGNETROL for Details BRAZIL TA2-AXXX-X3X TA2-AXXX-X4X com TXR-XXXX-XXX (probe) INMETRO TÜV TFT-XXXX-000 (flow body) Note: Maximum surface temperature of the probe is 4° C above process temperature. 6 AREA CLASSIFICATION Explosion proof ABNT NBR IEC 60079-0:2008 ABNT NBR IEC 60079-1:2009 ABNT NBR IEC 60529:2005 II 1/2 G Ex d+ib / d[ib] IIC T4/T3 Ga/Gb T4 : Tamb -40° C to +40° C T3 : Tamb -40° C to +70° C Ex d IIC T6 Gb when T amb= -40° C to +70° C and T medium= -40° C to +55° C Ex d IIc T6 Gb IP66W -40° C < Ta < +55° C TÜV 11.0027 X These units have been tested to EN 61326 and are in compliance with the EMC Directive 2004/108/EC. S P E C I F I C A T I O N S P E R F O R M A N C E Flow range maximum Accuracy flow Accuracy temperature Repeatability Linearity Turn down Calibration Span Response time Cable length SIL 10–54,000 SFPM (0.05–275 Nm/s) air reference to standard conditions Contact MAGNETROL for other gases ±1% of reading +0.5% of calibrated full scale ±2° F (1° C) ±0.5% of reading Included in flow accuracy 100:1 typical (depending on calibrated flow range) NIST traceable Minimum 0 –100 SFPM 1 to 3 second time constant typical 500 feet (150 m); (see page 11 for cable specifications) Safe Failure Fraction (SFF) 88% T R A N S M I T T E R Display Keypad Menu Language Supply voltage Power consumption Signal Output Analog output signal Active Passive Diagnostic Alarm Pulse Output Alarm Output Ambient temperature Temperature effect Humidity Housing Material Shock Vibration Two-line alphanumeric LCD, 16 characters per line Four push button English, French, German, Spanish, Russian 100 –264 VAC, 50–60 Hz 15-30 VDC (lower VDC possible - Consult Factory) DC = 9 W maximum, AC = 20 VA maximum 4–20 mA (active or passive), HART available (3.8 to 20.5 mA usable —meets NAMUR NE 43), FOUNDATION fieldbus available 4–20 mA (isolated) maximum 1000 Ω loop resistance 4–20 mA (isolated) loop resistance dependent on power supply, 11– 36 VDC 3.6 mA, 22 mA, HOLD Active Connection — 24 VDC (±10%) Power, 150 mA Passive Connection — 2.5 to 60 VDC Power, 1.5 AMP Active Connection — 24 VDC (±10%) Power, 100 mA Passive Connection — 2.5 to 60 VDC Power, 1 AMP -40° to +176° F (-40° to +80° C); display not readable below -22° F (-30° C) Approximately ±0.04% of reading per ° C 99% Non-condensing Aluminum A356 (<0.2% copper) ANSI/ISA-S71.03 table 2, level SA1 (Shock), ANSI/ISA-S71.03 table 1, level VC2 (Vibration) P R O B E Materials Process connections Pressure rating Temperature rating F L O W 316/316L stainless steel all welded Hastelloy® C-276/C-22 Refer to model number, hot tap optional 1500 psig @ +70° F (103 bar @ +20° C), 1375 psig @ +400° F (95 bar @ +200° C) -50° to +400° F (-45° to +200° C) ➀ B O D Y Materials Process connections Pressure rating Temperature rating 316/316L stainless steel all welded Carbon steel with stainless steel sensor NPT or 150-pound flange – Refer to model number 1500 psig @ +70° F (103 bar @ +20° C), 1100 psig @ +400° F (76 bar @ +200° C) -50° to +400° F (-45° to +200° C) ➀ ➀ For operating temperatures between +250° and +400° F (+120° and +200° C), either use remote electronics or a longer length insertion probe to provide an additional four inches (100 mm) between the electronics and the compression fitting. 7 M O D E L N U M B E R Models available for quick shipment, usually within one week after factory receipt of a complete purchase order, through the Expedite Ship Plan (ESP) SIGNAL OUTPUT 0 4-20 mA 1 4-20 mA with HART 2 FOUNDATION fieldbus 4 4-20 mA with HART, Pulse/Alarm, second mA Output DISPLAY 0 B None Plug-in display with keypad (with window) CALIBRATION–INSERTION PROBE CALIBRATION – FLOW BODY Actual Gas Calibration 0 Special ➀ 1 Air 2 Nitrogen 3 Hydrogen 4 Natural Gas 6 Digester Gas 7 Propane 8 Oxygen Air Equivalency / Correlation 5 Gas Correlation ➀ 9 Air Equivalency ➀ Consult factory for approval Actual Gas Calibration A Special ➀ B Air C Nitrogen D Hydrogen E Natural Gas G Digester Gas H Propane J Oxygen Air Equivalency / Correlation F Gas Correlation ➀ K Air Equivalency HOUSING LOCATION / AGENCY APPROVAL ¡ 3 Integral, general purpose, non-incendive, & explosion proof FM/FMc/ATEX Ex d/IEC 4 Remote, general purpose, non-incendive, & explosion proof FM/FMc/ATEX Ex d/IEC E Integral, general purpose ATEX, Ex d+ ib (Zone 0) F Remote, general purpose ATEX, Ex d+ ib (Zone 0) ¡ Use digit 3 or 4 for FOUNDATION fieldbus model ENCLOSURE TYPE 0 1 T 8 A 2 A 0 Aluminum, 3⁄4" NPT Aluminum, M20 M O D E L N U M B E R I N S E R T I O N P R O B E THERMATEL PROBE TE TM Probe length in tenth of inches Probe length in centimeters PROBE TYPE R 3 ⁄4" diameter probe MATERIALS OF CONSTRUCTION A B 316/316L Stainless Steel Hastelloy C PROCESS CONNECTION SIZE 00 Compression Fitting Utilized (customer supplied) 3 03 ⁄4" NPT SS compression fitting with Teflon Ferrules 3 04 ⁄4" NPT SS compression fitting with Stainless Steel Ferrules 05 1" NPT SS compression fitting with Teflon Ferrules 06 1" NPT SS compression fitting with Stainless Steel Ferrules 3 11 ⁄4" NPT 21 1" NPT 22 G1 (1" BSP) ANSI FLANGES 23 1" 150# 24 1" 300# 33 11⁄2" 150# 34 11⁄2" 300# 43 2" 150# 44 2" 300# ANSI ANSI ANSI ANSI ANSI ANSI raised raised raised raised raised raised face face face face face face flange flange flange flange flange flange DIN FLANGES BB DN 25 CB DN 40 DA DN 50 DB DN 50 PN PN PN PN 16/25/40 16/25/40 16 25/40 EN EN EN EN 1092-1, 1092-1, 1092-1, 1092-1, Type Type Type Type A A A A INSERTION LENGTH 2.6 to 99.9 inches (example 8.5" = 085) Minimum lengths: 2.6" (026) with threaded process connection 2.8" (028) with flanged process connection 4.5" (045) with compression fitting process connection 7 to 253 centimeters (example: 18 cm = 018) Minimum lengths: 7 cm (007) with NPT or flanged process connection 9 cm (009) with BSP threaded process connection 11 cm (011) with compression fitting process connection The following probes are available through the Expedite Ship Plan: TER-A0XA-080 TER-A0XA-180 T TMR-A0XA-020 TMR-A0XA-046 A 9 M O D E L F L O W N U M B E R B O D Y MATERIALS OF CONSTRUCTION All stainless steel A 1 Carbon steel body with stainless steel sensor SIZE 0 1 2 3 4 5 6 1 ⁄2 inch ⁄4 inch 1 inch 11⁄2 inch 2 inch 3 inch 4 inch 3 PROCESS CONNECTION TYPE 1 NPT Threads ➀ 3 150# Flange ➀ Only when digit 5 = 0, 1, 2, 3, or 4 FLOW CONDITIONING PLATE (stainless steel) A Not provided B Provided ¡ Only when Digit 5 = 3, 4, 5, or 6. Flow conditioning on 1/2" to 1" is already provided due to length of flow body and sensor design. Optional flow conditioning is available on flow bodies larger than 1" which includes additional straight run and conditioning plate. ¡ T 10 F T 0 0 0 C O N N E C T I N G C A B L E FOR CABLE LENGTHS UP TO 150 FEET 037-3313-XXX (Cable length in feet)—10 feet minimum, 150 feet maximum length Example: 50 feet = 050 0 3 7 3 3 1 3 FOR CABLE LENGTHS UP TO 45 METERS 037-3314-XXX (Cable length in meters)—3 meters minimum, 45 meters maximum length Example: 8 meters = 008 0 3 7 3 3 1 4 FOR CABLE LENGTHS BETWEEN 150 AND 500 FEET 037-3319-XXX (Cable length in feet)—10 feet minimum, 500 feet maximum length Example: 300 feet = 300 0 3 7 3 3 1 9 FOR CABLE LENGTHS BETWEEN 45 AND 150 METERS 037-3320-XXX (Cable length in meters)—3 meters minimum, 150 meters maximum length Example: 80 meters = 080 0 3 7 3 3 2 0 11 R E T R A C T A B L E H O T P R O B E A S S E M B L Y T A P Two methods are offered of removing the probe from the pipe without having to shut down the process. The Hot Tap Retractable Probe Assembly (RPA) is designed to meet API (American Petroleum Institute) standards. The less demanding valve and compression fitting (part number 089-5218-001) will have some minor leakage when the probe is removed or re-inserted and does not have the safety cable to prevent “blow out” of the probe when removed under pressure. RPA requires a probe with 3⁄4" NPT process connection (code 11). The valve with compression fitting uses a 1" NPT connection while the RPA uses a 11⁄2" NPT connection. High Pressure Low Pressure 089-5218-001 BASIC MODEL NUMBER RPA Retractable probe assembly DESIGN TYPE 5 6 E F Low pressure (up to 80 psi, 5.5 bar), length in tenths of an inch High pressure (up to 300# class service), length in tenths of an inch Low pressure (up to 80 psi, 5.5 bar), length in centimeters High pressure (up to 300# class service), length in centimeters MATERIALS OF CONSTRUCTION 1 4 Carbon steel (available on flange and high pressure units). Seal gland is 316 stainless steel. 316 stainless steel PROCESS CONNECTION 0 11⁄2" NPT 1 11⁄2" 150# flange 2 11⁄2" 300# flange BALL VALVE 0 None 1 Carbon steel 2 Stainless steel PROBE LENGTH 10 to 99.9 inches (example: 12" = 120) 25 to 253 centimeters (example: 30 cm = 030) 1000 900 Pressure (psig) 800 700 600 500 400 300 200 R P A 100 0 0 100 200 300 Temperature F 150 lb. flange 12 400 500 Threaded or 300 lb. flange D I M E N S I O N A L H O T T A P — S P E C I F I C A T I O N S i n c h e s ( m m ) S Dimension Threaded conn. 4.0 (102) Flanged conn. 5.0 (127) Retaining bar Adjustment rods Seal nut Adjustment nuts Safety cable T Seal nut S 11/2" NPT *Dimension of ball valve if supplied by MAGNETROL. Ball valve V V X X Ball valve Customer connection Customer connection Vessel wall Vessel wall Y Y Hot Tap Model RPA-6X12-XXX Minimum Probe Length: T = 2(X+Y) I N T E G R A L Hot Tap Model RPA-5402-XXX Minimum Probe Length = S+X+Y M O U N T 4.49 (114) 3/4" NPT or M20 connection Dimension V: Ball valve dimension (see chart) Dimension X: Length from wall to top of ball valve Dimension Y: Insertion length into pipe — i n c h e s A B Valve with Compression Fitting (0895218-001) ( m m ) Optional compression fitting C Pipe centerline " or 1" NPT recommended Insertion Length Insertion Length BSP (G1) Insertion Length NPT Insertion Length 1" (25 mm) ∅ .75 (19) Integral Mount Model TA2 Front and Side Views Process Conn. Size Height C 1" NPT 3.1 (79) 011-4719-009 (100 psi maximum) 011-4719-007 (1500 psi maximum) 3 2.6 (66) 011-4719-008 (100 psi maximum) 011-4719-006 (1500 psi maximum) ⁄4" NPT 8.00 Typical (200) 1" NPT customer supplied 5.18 (132) 6.69 (170) Typical height when compression fitting is used with half coupling or threadolet Ball Valve Dimensions* Size V 11⁄2" NPT 4.4 (112) 11⁄2" 150# flange 6.5 (165) 11⁄2" 300# flange 7.5 (191) Compression fitting Teflon ferrules Stainless steel ferrules TXR with Threaded Connection ∅ .75 (19) TXR with Flanged Connection Dimension A: 3.33 (85) without display 3.88 (99) with display Dimension B: 3.88 (98) 13 D I M E N S I O N A L R E M O T E M O U N T S P E C I F I C A T I O N S — i n c h e s ( m m ) 4.00 (102) 4.49 (114) ¾" NPT or M20 3.72 (94) 6.50 (165) 2.75 (70) 2 Holes .38 (10) dia. Insertion length 3.00 (76) 2.00 (51) 3.50 (89) ¾" NPT or M20 Transducer Cable Connector 3.75 (95) 3/4" (19) Remote Mount Model TA2 F L O W B O D Y - i n c h e s ( m m ) A A B B L1 L L1 L Length (L) Code L1 Height to Size Centerline With Flow Without Flow With Flow Without Flow (A) Conditioning Conditioning Conditioning Conditioning 0 1 1 3 NPT Flange ⁄2" 8 (203) — 5 (127) — 8.0 (203) 8.4 (213) 9.7 (246) ⁄4" 11.25 (285) — 7.5 (190) — 8.0 (203) 8.5 (216) 9.9 (251) 2 1" 15 (381) — 10 (254) — 8.0 (203) 8.6 (218) 10.1 (257) 3 1 1 ⁄2" 19.5 (495) 7.5 (191) 12 (305) 3.75 (95) 8.3 (210) 9.2 (234) 10.8 (274) 4 2" 26 (660) 7.5 (191) 16 (406) 3.75 (95) 9.5 (241) 10.7 (272) 12.5 (318) 5 3" 39 (991) 10 (254) 24 (610) 5 (127) 9.5 (241) N/A 13.3 (338) 6 4" 52 (1321) 12 (305) 36 (914) 6 (152) 9.5 (241) N/A 14.0 (356) Flow conditioning on ⁄2" to 1" is provided due to length of flow body and sensor design. Optional flow conditioning plate and straight run is available on flow bodies 11⁄2" and larger. 1 14 Overall Height (B) F L O W C O N D I T I O N I N G Part Number 004-8986-001 Description 4" 316 Stainless Steel Part Number 004-8986-010 Description 8" 316 Stainless Steel 004-8986-002 4" Carbon Steel 004-8986-011 8" Carbon Steel 004-8986-003 4" PVC 004-8986-012 8" PVC 004-8986-004 5" 316 Stainless Steel 004-8986-013 10" 316 Stainless Steel 004-8986-005 5" Carbon Steel 004-8986-014 10" Carbon Steel 004-8986-006 5" PVC 004-8986-015 10" PVC 004-8986-007 6" 316 Stainless Steel 004-8986-016 12" 316 Stainless Steel 004-8986-008 6" Carbon Steel 004-8986-017 12" Carbon Steel 004-8986-009 6" PVC 004-8986-018 12" PVC P R E S S U R E D R O P C H A R T S Pressure Drop (inches of water) 1000 1.5" 2" 3" 4" 5" 6" 100 8" 10" 12" 10 1 0.1 0.01 0.001 0.0001 10 100 1000 Flow Rate (SCFM) 1000 1.5" 10000 2" 3" 4" 5" 6" 100 Pressure Drop (millibar) P L A T E S 8" 10" 12" 10 1 0.1 0.01 0.001 0.0001 10 100 1000 Flow Rate (Nm3/h) 10000 15 Q U A L I T Y The quality assurance system in place at MAGNETROL guarantees the highest level The MAGNETROL quality assurance system is registered to ISO 9001 affirming its of quality throughout the company. MAGNETROL is committed to providing full commitment to known international quality customer satisfaction both in quality products and quality service. standards providing the strongest assurance of product/service quality available. E S P Expedite Ship Plan Several TA2 Models are available for quick shipment, usually within one week after factory receipt of a purchase order, through the Expedite Ship Plan (ESP). ESP service may not apply to orders of ten units or more. Contact your local representative for lead times on larger volume orders, as well as other products and options. W A R R A N T Y All MAGNETROL electronic level and flow controls are warranted free of defects in materials or workmanship for one full year from the date of original factory shipment. If returned within the warranty period; and, upon factory inspection of the control, the cause of the claim is determined to be covered under the warranty; then, MAGNETROL will repair or replace the control at no cost to the purchaser (or owner) other than transportation. MAGNETROL shall not be liable for misapplication, labor claims, direct or consequential damage or expense arising from the instal-lation or use of equipment. There are no other warranties expressed or implied, except special written warranties covering some MAGNETROL products. Additional information The following additional THERMATEL literature is available from your local representative: 54-631 54-100 54-105 54-110 54-131 54-210 54-621 THERMATEL Model TA2 Mass Flow Transmitter Instruction Manual and Parts List THERMATEL Technology brochure THERMATEL TG1 Flow and Level Switch sales literature THERMATEL Model TD1/TD2 Thermal Dispersion Flow and Level Switch sales literature THERMATEL Model TA2 Probe location literature Thermal Dispersion Mass Flow Meter Applications Thermal Dispersion Mass Flow Measurement Handbook 705 Enterprise Street • Aurora, Illinois 60504-8149 • 630-969-4000 • Fax 630-969-9489 [email protected] • www.magnetrol.com Copyright © 2015 Magnetrol International, Incorporated. All rights reserved. Printed in the USA. Performance specifications are effective with date of issue and are subject to change without notice. MAGNETROL, MAGNETROL logotype and THERMATEL are registered trademarks of MAGNETROL INTERNATIONAL, INCORPORATED. CSA logotype is a registered trademark of Canadian Standards Association HART is a registered trademark of the HART Communication Foundation Hastelloy is a registered trademark of Haynes International, Inc. BULLETIN: 54-140.1 EFFECTIVE: January 2015 SUPERSEDES: May 2013