THERMATEL® TA2
Thermal Mass
Flow Transmitter
DESCRIPTION
Thermatel Model TA2 Thermal Mass Flow Transmitter provides reliable mass measurement for air and gas flow applications. The powerful, yet easy to use, electronics are contained in a compact explosion proof enclosure. The TA2
offers excellent performance at exceptional value.
For air and gases
F E AT U R E S
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Direct mass flow measurement of air and gases.
No need for temperature/pressure correction.
High turndown ratio 100:1.
Excellent low flow sensitivity.
Low pressure drop.
Flow, temperature and totalized flow available over
HART®.
Advanced diagnostics check condition of probe, electronics, and wiring.
Rotatable plug in display module provides display of flow
rate, temperature, totalized flow, plus diagnostic messages and integrates four push button keypad for ease of
configuration.
Process temperatures up to +200 °C (+400 °F).
Pressure rating to 103 bar (1500 psig) dependent upon
process connections.
Probe can be field replaced.
Sensor is protected to prevent damage if inserted too far
into pipe.
Optional:
- hot tap retractable probe assembly or valve with compression fitting
- flow body for 1/2" to 4" pipe sizes
- flow conditioning plate for flow bodies 11/2" and higher.
Suited for SIL 1 and SIL 2 loops (full FMEDA report available).
FE T Y I
EGRITY
V EL
LE
A P P L I C AT I O N S
•
•
•
•
•
•
•
TA2 with sensor with flow body
NT
SA
TA2 with insertion probe
Combustion air
Digester/Bio-gas
Compressed air/gas
Vent lines/flare headers
Natural gas
Hydrogen piping
Aeration lines
A G E N C Y A P P R O VA L S
Agency
Approval
ATEX
FM/CSA
ATEX II 2G EEx d II C T6, explosion proof
Non Incendive
Explosion proof (Groups B, C and D)
RosTechnadzor /
Russian Authorisation Standards
GOST-R
Worldwide level and flow solutions
P R I N C I P L E O F O P E R AT I O N
Thermatel Model TA2 flow transmitter measures mass flow
by detecting heat dissipation from a heated surface. The
sensor contains two mass balanced elements with precision
matched RTD’s. The reference sensor measures the
process temperature (up to +200° C [+400° F]); the second
RTD measures the temperature of the heated sensor. The
power to the heater is varied to maintain a constant temperature difference above the reference temperature. There
is an inherent non-linear relationship between power and
mass flow. The microprocessor in the TA2 compares the
power against the calibration curve and converts the power
requirements to the mass flow rate. Temperature is also
measured to provide temperature compensation of the
mass flow over the operating range of the instrument.
flow
no flow
A D D I T I O N A L F E AT U R E S
TEMPERATURE COMPENSATION
Thermal flow technology measures the mass flow rate without the need for pressure and temperature correction as
required with most gas flow instruments that measure the
flow rate at actual conditions. However, changing temperature will change the properties of the gas which effect convective heat transfer. The Model TA2 measures the temperature and automatically corrects the mass flow measurement for changes in gas properties over the entire temperature range of the instrument.
TOTALIZER
The software totalizer provides a nine-digit display of the
total flow in the user’s choice of engineering units. The use
of EEPROM for storage of totalized data eliminates the
need for backup batteries, and provides maximum safeguard of data in the event of a power interruption. The totalizer can be reset using the display module or HART.
SELECTABLE STP CONDITIONS
(Normalized conditions)
The TA2 directly measures mass flow of the gas at Standard
Temperature and Pressure (STP) conditions. Software permits the user to change STP conditions for their own
requirements.
DIAGNOSTICS
Diagnostics is an important aspect of the TA2. The unit has
the ability to check the probe status and indicate either normal operation, short or open circuit in the PT 1000, or heater
circuit.
In order to verify that the calibration and configuration match
the original calibration conditions, the user can select a specific signal and compare the TA2 display value against the
original calibration certificate.
AREA COMPENSATION FOR PIPE SIZE
Insertion of the sensor into a pipe reduces the flow area,
thus increasing the velocity for a given flow rate. The TA2
automatically compensates the flow measurement based
on actual area of the pipe. The user simply enters the size
or the area of the pipe, and the instrument automatically
compensates the flow measurement for the probe blockage.
PROBE INSTALLATION
Probes can be provided with a variety of process connections, including threads, flanges, or installation through a
compression fitting. The sensor will fit pipe sizes of
1 1⁄2" diameter or larger (2"/DN 50 minimum size with thread
connection).
The sensor is protected to prevent damage due to “bottoming-out” if inserted too far into a pipe. When using an insertion probe with compression fitting, the user can adjust the
position of the sensor in the pipe to obtain the optimum location. Typically, this will be with the bottom of the probe
25 mm (1.0") lower than the center line of the pipe.
PORTABLE DISPLAY MODULE
A portable display module for configuration and diagnosis of
multiple units is available (part number 089-5219-001). This
portable module plugs into the electronics in the same manner as the normal display and uses the same software
menu. This module permits the user to reduce installation
cost by having one display module with keypad for multiple
TA2 units.
Usage of the display module requires that the housing cover
be removed during use and thus may not be useable in hazardous areas. In these cases, the HART option should be
utilized.
PROBE SIMULATION MODULE
The Model TA2 has an optional probe simulation module
(part number 089-5220-001). Using this module, the user
can disconnect the probe from the electronics and verify the
operation of the transmitter electronics against a known
standard.
FACTORY CALIBRATION AND CONFIGURATION
Each TA2 is calibrated at the factory for the type of gas and
the specified flow rate. The instrument is configured for the
specific application information. The result is an instrument
which can be installed and immediately be placed into operation without field setup.
AIR EQUIVALENCY
Using historic air-gas calibration data, an air equivalency
calibration can be performed on select gases. Consult your
Magnetrol contact for details and flow ranges.
Portable display module
2
A P P L I C AT I O N S
COMPRESSED AIR/GASES
Measurement of mass flow in different gas lines to determine in plant usage for internal allocation.
Advantages:
• direct mass flow
• high turndown rates
• flow totalization
• easy installation
FLARE LINES
Measurement of flow in different sections of flare line.
Advantages:
• good low flow sensitivity
• high turndown
• easy removal if cleaning is required
BOILER COMBUSTION
The TA2 measures the inlet air flow to the boiler. This signal is sent to the DCS where it is used to trim the natural
gas flow.
Advantages:
• mass flow measurement
• repeatable flow signal
• high rangeability
AERATION AIR FLOW
Measurement and balance of the flow to each section of the
aeration basin in waste water treatment plants.
Advantages:
• low installation cost
• direct mass flow
• high reliability
Natural Gas
NATURAL GAS FLOW
The Model TA2 efficiently measures the flow and totalized
flow of fuel to furnaces, heaters, or boilers. This data may
be used for internal allocation or to report emission rates.
Advantages:
• direct mass flow in Nm3/h
• built in totalizer
• easy in setup and operation
DIGESTER GAS/BIO-GAS
The off gas from a digester contains a mixture of methane
and carbon dioxide saturated with moisture. This is a difficult flow measurement due to low flow rate and low pressures.
Advantages:
• excellent low flow sensitivity
• high turndown rates
• provides measurement of flow and totalized flow
Air
To engine
or flare
Natural Gas
or propane
3
DIMENSIONS IN mm (inches)
Integral Mount TA2
114 (4.49)
A
3/4" NPT or M20
connection
(2 entries - one
plugged)
99 (3.89)
5.18
(132)
165
(6.49)
Optional
compression
fitting
Typical height
when compression
fitting is used with
half coupling or
threadolet
3/4" or 1" NPT
recommended
Consult page 6 for
dimension “A”
Dimension A:
85 (3.33) without display
99 (3.88) with display
A
Insertion
length
Pipe
centerline
25 mm (1)
Remote Mount TA2
114 (4.49)
3/4" NPT or M20
(2 entries - one plugged)
3/4" NPT
or M20
118 (4.63)
70
(2.75)
160
(6.30)
2 holes
Ø 10
(0.38)
82
(3.23)
70
(2.75)
76
(3.00)
51
(2.00)
89
(3.50)
Insertion
length
BSP thread /
compression fitting
Insertion
length
NPT thread
95
(3.75)
3/4" NPT
or M20
transducer
cable connector
3/4"
S E L E C T I O N D ATA
A complete measuring system consists of:
1.
2.
3.
4.
4
Thermatel® TA2 mass flow electronics.
Thermatel® TA2 mass flow transmitters require an application report for performing pre-calibration from factory. Ask
your magnetrol® contact for assistance when specifying a device.
Thermatel® TA2 mass flow insertion probe or Thermatel® TA2 mass flow sensor with flow body.
Connecting cable for remote mount Thermatel® TA2 mass flow transmitters
Options:
- portable display module – order number: 089-5219-001 (for more details see page 2)
- probe simulation module – order number: 089-5220-001 (for more details see page 2)
- retractable probe assembly (RPA) – for order code see page 10
- valve and compression fitting – order number: 089-5218-001 (for more details see page 10)
- duct mounting bracket – order number: 089-7247-001 (for more details see page 4)
- compression fittings – for order code see page 6.
1. Order code for Thermatel® TA2 mass flow transmitter
BASIC MODEL NUMBER
T A 2 Thermatel® TA2 Mass Flow transmitter
2
1
0
INPUT VOLTAGE
24 V DC
240 V AC
120 V AC
SIGNAL OUTPUT
1
4-20 mA with HART communication
0
B
ACCESSORIES
Blind transmitter (can receive the plug in display as future option)
Plug in digital display and keypad
1
3
4
MENU LANGUAGE (HART communication is only available in English language)
English
French
German
ACTUAL GAS CALIBRATION
For TA2 with insertion probe
0
1
2
3
Special. Specify medium separately
Air
Nitrogen or Oxygen
Hydrogen
4
5
6
7
Natural gas
Methane
Digester gas
Propane
E
F
G
H
Natural gas
Methane
Digester gas
Propane
For TA2 with sensor with flow body
A
B
C
D
Special. Specify medium separately
Air
Nitrogen or Oxygen
Hydrogen
AIR EQUIVALENCY CALIBRATION
Air equivalency values are available for various gases, consult factory for gases and
flow rates.
9
K
For TA2 with insertion probe
For TA2 with sensor with flow body
3
4
C
D
MOUNTING/CLASSIFICATION (Consult factory for FM/CSA approvals)
Integral, General Purpose (FM/CSA explosion proof)
Remote, General Purpose (FM/CSA explosion proof)*
Integral, ATEX II 2G EEx d II C T6, explosion proof
Remote, ATEX II 2G EEx d II C T6, explosion proof*
* Bracket for electronics and probe housing included
1
0
T A 2
1
HOUSING MATERIAL / CABLE ENTRY
IP 66, Cast aluminium - M20 x 1,5 cable entry (2 entries - one plugged)
IP 66, Cast aluminium - 3/4" NPT cable entry (2 entries - one plugged)
complete order code for Thermatel® TA2 Mass Flow transmitter
5
DIMENSIONS IN mm (inches)
insertion
length
insertion
length
BSP (G1)
ø 19 (0,75)
insertion
length
insertion
length
NPT
ø 19 (0,75)
ø 19 (0,75)
TMR for mounting with
compression fitting
Process
Conn. Size
Height
A
1" NPT
79 (3.1)
⁄ " NPT
66 (2.6)
34
TMR with
threaded connection
TMR with
flanged connection
Compression fitting
Teflon ferrules
Stainless steel ferrules
011-4719-009
011-4719-007
(6,90 bar maximum)
(69 bar maximum)
011-4719-008
011-4719-006
(6,90 bar maximum)
(69 bar maximum)
min 3 m – max 15 m
Connecting cable
ELECTRICAL WIRING
Supply power: 24 V DC or 240 / 120 V AC
Output
Shield to ground
Shielded twisted
pair cable
Active or Passive output
A- / A+ = active output: power supplied by TA2
P- / P+ = passive output: power supplied by
external 24 V DC source
Ex
6
Non Ex
S E L E C T I O N D ATA
2. Order code for Thermatel® TA2 mass flow insertion probe
BASIC MODEL NUMBER
T M R Thermatel® TA2 Mass Flow probe
A
B
MATERIALS OF CONSTRUCTION
316/316L (1.4401/14404) stainless steel
Hastelloy C (2.4819) - not available with compression fitting
PROCESS CONNECTION
0 0 0
Compression fitting - min 11 cm insertion length (compression fittings are not included,
for proper order numbers – see page 6). Only available with 316/316L (1.4401/1.4404).
Consult factory for Hastelloy C (2.4819)
Threaded
1 1 0 3/4" NPT - default selection in combination with a retractable probe assembly (RPA) see page 6
2 1 0 1" NPT
2 2 0 1" BSP (G1)
2
2
3
3
4
4
ANSI flanges
3 0 1"
4 0 1"
3 0 1 1/2"
4 0 1 1/2"
3 0 2"
4 0 2"
150
300
150
300
150
300
lbs
lbs
lbs
lbs
lbs
lbs
B
B
C
C
D
D
EN/DIN flanges
A 0 DN 25
B 0 DN 25
A 0 DN 40
B 0 DN 40
A 0 DN 50
B 0 DN 50
PN
PN
PN
PN
PN
PN
16
25/40
16
25/40
16
25/40
-
RF
RF
RF
RF
RF
RF
flange
flange
flange
flange
flange
flange
EN
EN
EN
EN
EN
EN
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
Type
Type
Type
Type
Type
Type
A
A
A
A
A
A
INSERTION LENGTH - consider process connections
Min probe length
0 0 7
0 0 9
7 cm (2,6") fix length
9 cm (3,5") fix length
- for NPT threaded
- for BSP threaded
Selectable probe length - specify per 1 cm (0,39") increments
0
0
0
2
T M R
0
0
1
2
5
9
1
5
3
min. 9 cm (3,5")
min. 11 cm (4,5")
min. 25 cm (10")
max. 253 cm (99,9")
-
for
for
for
for
NPT threaded and flanged
BSP threaded and compression fitting
use with RPA (Retractable Probe Assembly)
all probe connections
complete order code for Thermatel® TA2 mass flow insertion probe
3. Order code for connecting cable remote mount Thermatel® TA2 mass flow transmitter
0 3 7 – 3 3 1 4
0 0 9 – 8 2 7 0
General purpose connecting cable - 8 wire shielded instrument cable
ATEX explosion proof connecting cable - 8 wire shielded instrument cable
CABLE LENGTH - specify per 1 m (3.28') increments
0 0 3 min 3 m (10') length
0 1 5 max 15 m (50') length
0
complete order code for connecting cable
7
DIMENSIONS IN mm (inches)
A
A
B
B
L1
L
L1
L
Flanged flow body
Threaded flow body
Length (L)
Code
Size
0
1/2"
1
3/4"
2
1"
3
11/2"
4
L1
With Flow
Without Flow
Conditioning Conditioning
mm (inches)
mm (inches)
203 (8)➀
286
(11.25)➀
381
(15)➀
—
—
—
Overall Height (B)
Height to
Centerline
(A)
NPT-F
Flange
mm (inches) mm (inches) mm (inches)
With Flow
Conditioning
mm (inches)
Without Flow
Conditioning
mm (inches)
127 (5)➀
—
203 (8.0)
221 (8.7)
248 (9.75)
—
203 (8.0)
221 (8.7)
251 (9.9)
190
(7.5)➀
254
(10)➀
—
203 (8.0)
221 (8.7)
257 (10.1)
495 (19.5)
191 (7.5)
305 (12)
95 (3.75)
212 (8.35)
236 (9.3)
276 (10.85)
2"
660 (26)
191 (7.5)
406 (16)
95 (3.75)
235 (9.25)
264 (10.4)
311 (12.25)
5
3"
991 (39)
254 (10)
610 (24)
127 (5)
235 (9.25)
N/A
330 (13.0)
6
4"
1321 (52)
305 (12)
914 (36)
152 (6)
235 (9.25)
N/A
349 (13.75)
➀ The upstream length in pipe sizes < 1 1/2" dia. is sufficient to create the flow conditioning effect without need for a flow conditioning plate.
Flow body sizing
The following table is a general guide on flow sizing. Contact your Magnetrol contact for specific application information.
Max flow rate
Code
8
Size
⁄2"
0
1
1
3
2
1"
3
11⁄2"
4
2"
5
3"
6
4"
⁄4"
Air, N2, O2
Natural Gas,
Methane
Digester
Gas
Propane
Hydrogen
CO2, Argon
110 NM3/h
65 SCFM
76 NM3/h
45 SCFM
42 NM3/h
25 SCFM
51 NM3/h
30 SCFM
27 NM3/h
15 SCFM
105 NM3/h
60 SCFM
204 NM3/h
120 SCFM
340 NM3/h
200 SCFM
140 NM3/h
85 SCFM
238 NM3/h
140 SCFM
76 NM3/h
45 SCFM
127 NM3/h
75 SCFM
93 NM3/h
55 SCFM
161 NM3/h
95 SCFM
52 NM3/h
30 SCFM
85 NM3/h
50 SCFM
190 NM3/h
110 SCFM
320 NM3/h
190 SCFM
833 NM3/h
490 SCFM
580 NM3/h
340 SCFM
310 NM3/h
180 SCFM
395 NM3/h
230 SCFM
208 NM3/h
120 SCFM
790 NM3/h
465 SCFM
1220 NM3/h
715 SCFM
3000 NM3/h
1765 SCFM
5490 NM3/h
3230 SCFM
855 NM3/h
505 SCFM
2110 NM3/h
1240 SCFM
3845 NM3/h
2260 SCFM
480 NM3/h
280 SCFM
1180 NM3/h
695 SCFM
2145 NM3/h
1265 SCFM
600 NM3/h
350 SCFM
1470 NM3/h
860 SCFM
2675 NM3/h
1575 SCFM
332 NM3/h
195 SCFM
812 NM3/h
475 SCFM
1478 NM3/h
865 SCFM
1155 NM3/h
680 SCFM
2855 NM3/h
1680 SCFM
5210 NM3/h
3060 SCFM
S E L E C T I O N D ATA
2. Order code for Thermatel® TA2 sensor with flow body
BASIC MODEL NUMBER
T F T Thermatel® TA2 sensor with mass flow body
MATERIALS OF CONSTRUCTION
A
1
316/316L (1.4401/1.4404) stainless steel body and sensor
Carbon steel body / stainless steel sensor
THREADED FLOW BODY - ø size and connection
1/2"
NPT
0 1
3/4"
1 1
NPT
2 1
1"
NPT
3 1
11/2"
NPT
2"
NPT
4 1
FLANGED FLOW BODY - ø size and connection
1/2"
150 lbs RF flange
0 3
3/4"
1 3
150 lbs RF flange
2 3
1"
150 lbs RF flange
3 3
11/2"
150 lbs RF flange
4 3
2"
150 lbs RF flange
5 3
3"
150 lbs RF flange
6 3
4"
150 lbs RF flange
0
1
T F T
Accessoires
None
Stainless steel flow conditioning plate - for flow body sizes ≥ 11/2"
0 0 0
complete order code for Thermatel® TA2 sensor with flow body
Flow
Flow conditioning plate
9
S E L E C T I O N D ATA
4. Order code for retractable probe assembly
BASIC MODEL NUMBER
R P A Retractable probe assembly
DESIGN TYPE
E
F
Low pressure - up to 5,5 bar (80 psi)
High pressure - up to 300 lbs / service
MATERIALS OF CONSTRUCTION
1
Carbon steel with 316 SST (1.4401) seal gland
4
316 SST (1.4401)
PROCESS CONNECTION
0
1
2
1 1/2" NPT
1 1/2" - 150 lbs RF flange
1 1/2" - 300 lbs RF flange
0
1
2
BALL VALVE
No ball valve supplied
Carbon steel ball valve
Stainless steel ball valve
– not available for RPA-E1
– select material code 1
– select material code 4
PROBE LENGTH
0 2 5 min 25 cm (10")
2 5 3 max 253 cm (99,9")
complete order code for retractable probe assembly
R P A
High Pressure RPA
Hot Tap retractable probe assembly
70 (1000)
Pressure bar (psig)
60 (900)
55 (800)
50 (700)
40 (600)
35 (500)
30 (400)
20 (300)
Low Pressure RPA
max. 5,5 bar (80 psig)
15 (200)
High Pressure
0
40
(100)
95
(200)
150
(300)
205
(400)
Temperature °C (°F)
150 lb. flange
Valve with compression
fitting
Threaded or
300 lb. flange
Order code:
089-5218-001
10
T R A N S M I T T E R S P E C I F I C AT I O N S
FUNCTIONAL/PHYSICAL
Description
Power supply
Power consumption
Active
Signal Output
Passive
Resolution
Analog
Display
Calibration
Damping
Diagnostic Alarm
User Interface
Display
Displayed values
Menu Language
Housing Material
Approvals
SIL (Safety Integrity Level)
Net and gross weight
Specification
19 – 29 V DC
204 – 260 V AC, 50-60 Hz
102 – 132 V AC, 50-60 Hz
6W–9VA
4-20 mA isolated (3,8 – 20,5 mA useable as per NAMUR NE 43) max 1000 Ω loop resistance
4-20 mA isolated (3,8 – 20,5 mA useable as per NAMUR NE 43) max loop resistance depending power supply
0,01 mA
0,01 Nm/s
Pre-calibrated from factory - NIST traceable
Adjustable 0-15 s time constant
Adjustable 3,6 mA, 22 mA or Hold
4-button keypad and/or HART® communicator
2-line x 16-character LCD
Flow (eg. Nm3/h, Nl/h) and/or mass flow (eg. kg/h) and/or temperature (°C/°F)
and/or loop current (mA) and/or totalized flow (eg. Nm3/h, Nl/h)
English, French or German
IP 66, Aluminium A 356 (< 0,2 % copper) dual compartment
ATEX II 2G EEx d IIC T6, explosion proof
FM, explosion proof (Groups B, C and D) and non incendive
CSA, explosion proof (Groups B, C and D)
RosTechnadzor/GOST-R, Russian authorisation standards
Functional safety to SIL1/SIL2 in accordance to IEC 61508 – SFF: 69 %.
Full FMEDA report and declaration sheets available at request.
3,3 kg (7.3 lbs) net; 4,0 kg (8.8 lbs) gross (amplifier with 25 cm threaded probe)
PERFORMANCE
Description
Turn down ratio
Flow range
Max
Min
Linearity
Accuracy
Flow
Temperature
Repeatability
Response time
Remote electronics
Ambient temperature
Operating temp. effect
Humidity
Electromagnetic Compatibility
Specification
100:1 typical (depending upon calibration)
0,13 - 200 Nm/s (25 - 40,000 SFPM) reference of air at STP conditions
0,13 - 2,5 Nm/s (25 - 500 SFPM) reference of air at STP conditions
Included in flow accuracy
± 1 % of reading + 0,5 % of calibrated full scale
± 1 °C (2 °F)
± 0,5 % of reading
Time constant of 1 to 2 s
Max 15 m (50') away from probe - for longer lengths, consult factory
-40 °C up to +70 °C (-40 °F up to +160 °F) – display not readable below -20 °C (-4 °F)
± 0,04 % per °C
99 %, non-condensing
Meets CE requirements (EN-61000-6-4, EN 61000-6-2) and are in compliance with
EMC directive 89/336/EEC
PROBE SPECIFICATIONS
Description
Insertion probe
Sensor with flow body
Materials – wetted parts
316/316L (1.4401/1.4404) or Hastelloy C (2.4819)
Sensor: 316/316L (1.4401/1.4404)
Flow body: stainless steel or carbon steel
Mounting
Threaded, compression fitting, ANSI-DIN flanged
or with Retractable probe assembly
Threaded or flanged
Probe length
Max. process temperature
Max pressure rating
From 70 mm up to 2530 mm (2.6" up to 100")
Flow body sizes from 1/2" up to 4"
-45 °C up to +120 °C
Integral electronics:
-45 °C up to +200 °C with 100 mm (4")
longer probe serving as heat extension
Remote electronics:
-45 °C up to +200 °C
103 bar (1500 psi) @ +20 °C (+70 °F)
95 bar (1375 psi) @ +200 °C (+400 °F) – direct insertion
75 bar (1100 psi) @ +200 °C (+400 °F) – with flow body
11
DIMENSIONS IN mm (inches)
Safety cable
Retaining bar
Adjustment
rods
S Dimension
Threaded connection
Flanged connection
Seal nut
Seal nut
1 1/2" NPT
Adjustment
nuts
S
Ball Valve Dimensions*
Size
V
11⁄2" NPT
112 (4.4)
11⁄2" 150# flange
165 (6.5)
11⁄2" 300# flange
190 (7.5)
V
X
Ball valve
T
102 (4.00)
127 (5.00)
Customer
connection
Vessel wall
Y
Ball valve
*Dimension of ball valve if supplied by the factory.
V
X
Vessel wall
Hot tap
Model RPA-E402-XXX
Customer
connection
Y
200 (8)
minimum probe length: S + X + Y
Typical
1" NPT
customer
supplied
Hot tap
Model RPA-FX12-XXX
1" NPT ball valve with
compression fitting (TFE ferrules)
(089-5218-001)
minimum probe length: T = 2 (X + Y)
Duct mounting bracket
3/4" NPT
connection
Ø 152,4
(6.00)
Duct mounting bracket with 3⁄4" NPT
part number 089-7247-001 or
089-7247-002 (includes hardware)
QUALITY ASSURANCE - ISO 9001:2000
THE QUALITY ASSURANCE SYSTEM IN PLACE AT MAGNETROL GUARANTEES THE HIGHEST LEVEL OF QUALITY DURING THE DESIGN,
THE CONSTRUCTION AND THE SERVICE OF CONTROLS.
OUR QUALITY ASSURANCE SYSTEM IS APPROVED AND CERTIFIED TO ISO 9001:2000 AND OUR TOTAL COMPANY IS COMMITTED TO
PROVIDING FULL CUSTOMER SATISFACTION BOTH IN QUALITY PRODUCTS AND QUALITY SERVICE.
:2000
PRODUCT WARRANTY
ALL MAGNETROL ELECTRONIC AND ULTRASONIC LEVEL CONTROLS ARE WARRANTED FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR ONE FULL YEAR FROM THE DATE OF ORIGINAL FACTORY SHIPMENT. IF RETURNED WITHIN THE WARRANTY PERIOD; AND, UPON FACTORY INSPECTION OF THE CONTROL, THE CAUSE OF THE CLAIM IS DETERMINED TO BE COVERED UNDER THE WARRANTY; THEN, MAGNETROL INTERNATIONAL WILL REPAIR OR
REPLACE THE CONTROL AT NO COST TO THE PURCHASER (OR OWNER) OTHER THAN TRANSPORTATION.
MAGNETROL SHALL NOT BE LIABLE FOR MISAPPLICATION, LABOR CLAIMS, DIRECT OR CONSEQUENTIAL DAMAGE OR EXPENSE ARISING FROM THE INSTALLATION
OR USE OF THE EQUIPMENT. THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED, EXCEPT, SPECIAL WRITTEN WARRANTIES COVERING SOME MAGNETROL
PRODUCTS.
®
UNDER RESERVE OF MODIFICATIONS
Heikensstraat 6, 9240 Zele, België
Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: [email protected]
DEUTSCHLAND
Alte Ziegelei 2-4, D-51491 Overath
Tel. 02204 / 9536-0 • Fax. 02204 / 9536-53 • E-Mail: [email protected]
FRANCE
40 - 42, rue Gabriel Péri, 95130 Le Plessis Bouchard
Tél. 01.34.44.26.10 • Fax. 01.34.44.26.06 • E-Mail: [email protected]
ITALIA
Via Arese 12, I-20159 Milano
Tel. (02) 607.22.98 (R.A.) • Fax. (02) 668.66.52 • E-Mail: [email protected]
UNITED
KINGDOM
Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
Tel. (01444) 871313 • Fax (01444) 871317 • E-Mail: [email protected]
INDIA
E-22, Anand Niketan, New Delhi - 110 021
Tel. 91 (11) 41661840 • Fax 91 (11) 41661843 • E-Mail: [email protected]
www.magnetrol.com
BENELUX
BULLETIN N°:
EFFECTIVE:
SUPERSEDES:
OUR NEAREST REPRESENTATIVE
BE 54-130.6
JULY 2006
May 2006