Click Here to download this file: http://www.murata-ps.com/data/acdcsupplies/tps_txd2000.pdf

2000 WATT
AC/DC POWER SUPPLY
TXD2000
DESCRIPTION
The TXD2000 Series is a flexible, modular, 2000 Watt
design offering two high current outputs in a 5 x 8 x 12
package. Output voltages from 2.5 VDC through 48
VDC are standard. With Power Factor Correction, EMI
compliance to FCC and CISPR22, CE Mark and
immunity to EN61000-4, the TXD2000 Series is ready
for global deployment. Standard features include
Remote Sense Compensation, Output Voltage
Adjustment, Active Current Sharing, Remote Inhibit,
Power Fail Warning, DC OK Signal and Thermal
Shutdown. An optional ORing diode is offered on
models with an output voltage of 12 VDC or above.
FEATURES
T
C
U
D t Model
O
R
P
en
m
E
e
c
T r Repla
E
L
O ctory fo
S
B
O act Fa
z Wide Range Input of 90-264VAC, 1000 Watts,
High Range Input of 180-264VAC, 2000 Watts,
z Harmonic Correction to EN61000-3-2
ont
z Active Current Sharing
C
z No Load Operation
z Optional ORing Diode
z 70-80% Efficiencies
z FCC / CISPR 22 Class A EMI Filtering
z Self-Cooled 5”x 8”x 12” Chassis
AGENCY APPROVALS
z EN61000-4 Immunity
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000
Input Specifications
Parameters
Conditions
Min
Typ
Max
Units
VAC
Operating Range
1000W
2000W
Inrush Current
47-63Hz
90
264
47-63Hz
180
264
VAC
80
Apk
120VAC, 250C, cold start
240VAC, 250C, cold start
Efficiency
160
Nominal line, full load
70
Holdup
Full load
20
Power Factor (1)
Full load
75
80
Apk
%
m sec
0.99
Notes: (1) Harmonic currents meet EN61000-3-2
Output Voltage Modules and Maximum Rated Load
Output
Output Voltage
Voltage Code
Voltage
Output Current
(Maximum Continuous)
Output Power
(Maximum Continuous)
A
5.0
200A
1000W
B
12.0
83A
1000W
C
15.0
67A
1000W
D
18.0
55A
1000W
E
24.0
42A
1000W
F
28.0
36A
1000W
G
36.0
28A
1000W
H
48.0
21A
1000W
J
20.0
K
3.3
L
2.5
T
C
U
D t Model
O
R
P
en
m
E
e
c
T r Repla
E
L
O ctory fo
S
B
O act Fa
40A
800W
182A
600W
200A
500W
t
n
Output Specifications Co
Parameter
Conditions
Output Power
All environmental and line conditions
Min
Typ
90-264VAC
180-264VAC
Limited by output module selection
Voltage Adjustment Range
Relative to nominal output voltage
Output Regulation
Line, load or cross
Minimum Load
Max
Units
1000
Watts
2000
+5
+0.2
0
PARD
Measured at output terminals, 20MHz
Temperature Coefficient
00 to 500C
Watts
%
%
Amps
50 mv or 1%
+0.2
pk-pk
%/0C
Environmental Specifications
Parameter
Conditions
Ambient Temperature
(Operating)
Output de-rated linearly to 50% of
rated capacity between 500C and 700C
Ambient Temperature
Non-operating
Altitude (Operating)
Altitude (Non-operating)
Min
Typ
Max
Units
0
+70
0
C
-50
C
+85
0
-200
+10,000
Feet
-200
+50,000
Feet
Shock
Per MIL-STD-810D, Method 516.3, Procedure II, in each axis, including NTSA drop test
Vibration
Per MIL-STD-810D, Method 514.3, Procedure II, in each axis, including NTSA drop test
Cooling
The TXD2000 is provided with internal cooling fans.
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000
Product Features
Features
Characteristic
Remote Sense
500mV compensation
Active Current Sharing
Single Wire; 5% current share if outputs are over 25% of rated load
ORing Diode
Optional (not available on modules below 12V)
OVP
125% of nominal (+7.5%)
Thermal Shutdown
Automatic Restart
DC OK Signal
Logic “1” when output is within +3% of nominal
Power Fail Warning
Transition to Logic “0” at least 5msec before loss of output regulation
Remote Inhibit
Logic “0” applied will inhibit output (referenced to –Sense terminal)
Product Compliances
Approval
Characteristic
UL and cUL
UL1950, 3rd Edition
VDE
EN60950
FCC
Class A requirements for conducted emissions
CISPR 22
Class A requirements for conducted emissions
EN61000-4-2
Electrostatic Discharge, Level 4
EN61000-4-4
Electrical Fast Transients, Level 3
(1)
T
C
U
D t Model
O
R
P
en
m
E
e
c
T r Repla
E
L
Ordering Information
O ctory fo
S
B
O act Fa
EN61000-4-5
Input Surge Immunity, Level 3
EN61000-3-2
Harmonic Currents, Class A
CE Mark
Low Voltage Directive
Notes: (1) UL1950, 3 Edition incorporates the requirements of CSA 950.
rd
Model Designation
BASE MODEL
t
Con
TXD2000
F
L
L
H
Chassis: “8” = 5” x 8” x 12”; “M” = modified
Output Voltage Module A: (see chart below)
Output Voltage Module B: (see chart below)
Standard Fan: “F”:
Remote Inhibit - TTL Logic Level “0” turns the power supply OFF:
Power Fail Warning - TTL Logic Level “0” indicates AC is LOST:
ORing Diode - “D” indicates an ORing Diode is installed in each module; “N” = None:
DC OK - TTL Logic Level “1” indicates DC is OK:
OUTPUT VOLTAGES
A = 5V
G = 36V
B = 12V
H = 48V
C = 15V
J = 20V
D = 18V
K = 3.3V
E = 24V
L = 2.5V
F = 28V
www.murata-ps.com
Technical enquiries - email: [email protected], tel: +1 508 339 3000
T
C
U
D
del
O
o
M
R ement
P
E
T r Replac
E
L
O ctory fo
S
B
O act Fa
t
Con