3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols SE-330 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR REVISION 10-K-090815 LITTELFUSE STARTCO NEUTRAL-GROUNDING-RESISTOR MONITOR SE-330 RESISTOR FAULT GROUND FAULT DIAGNOSTIC TRIP TRIP CALIBRATED RELAY K1 8 6 10 20 40 60 80 4 100 2 MEM GF TRIP LEVEL (% CT RATING) 0.5 0.7 1.0 0.4 0.3 0.2 0.1 2.0 3.0 5.0 10.0 POWER 170 130 100 200 340 800 1200 60 1700 20 2000 VN TRIP LEVEL (S5 CAL GF TRIP TIME (s) 20 K Ω VN x 1 100 K Ω) VN x 5 1.8 2.0 2.2 1.6 2.4 1.4 2.6 1.2 2.8 1.0 3.0 PULSE PERIOD (s) RESET Copyright 2015 Littelfuse Startco All rights reserved. Document Number: PM-1200-EN Printed in Canada. SE-330 Neutral-Grounding-Resistor Monitor This page intentionally left blank. Page i Rev. 10-K-090815 Page ii Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor TABLE OF CONTENTS SECTION PAGE General ................................................................. 1 1.1 Modern Resistance-Grounded Systems ................ 1 1.2 SE-330 NGR Monitoring ...................................... 1 2 Operation ............................................................. 2 2.1 Settings.................................................................. 2 2.1.1 GF Trip Time ............................................. 2 2.1.2 GF Trip Level ............................................ 2 2.1.3 VN Trip Level............................................. 2 2.1.4 Pulse-Period Adjustment ........................... 3 2.1.5 Configuration Settings ............................... 3 2.1.5.1 Relay K1 Function (S1) ................ 4 2.1.5.2 Trip-Relay Mode and Trip-Memory Mode (S2) ........................... 4 2.1.5.3 Ground-Fault-Trip Latch (S3) ....... 4 2.1.5.4 Resistor-Fault-Trip Latch (S4) ...... 4 2.1.5.5 Sensing-Resistor Selection (S5) .... 4 2.1.5.6 Frequency (S6) .............................. 4 2.1.5.7 Upgrade Mode (S8)....................... 4 2.1.6 Resistor-Fault Trip Time ........................... 4 2.1.7 Resistor-Fault Trip Level ........................... 4 2.1.8 Geo-Magnetic Filter ................................... 4 2.2 Calibration............................................................. 4 2.3 Pulsing Operation .................................................. 5 2.4 Trip Indication and Reset ...................................... 5 2.5 Remote Operation ................................................. 5 2.6 Relay K1 LED....................................................... 5 2.7 Unit Healthy Output .............................................. 5 2.8 Diagnostic LED..................................................... 5 2.9 Analog Output ....................................................... 6 3 Installation ........................................................... 6 3.1 SE-330 .................................................................. 6 3.2 Sensing Resistor .................................................. 12 3.3 Ground-Fault CT ................................................. 20 3.4 Isolated Ground Connection ............................... 25 3.5 Pulsing Connection ............................................. 25 4 Data Interfaces .................................................. 26 4.1 SD Card............................................................... 26 4.1.1 Datalogging.............................................. 26 4.1.2 Firmware Upgrade ................................... 26 4.2 USB Interface...................................................... 26 4.3 Network Communications .................................. 26 5 Troubleshooting ................................................ 27 6 Technical Specifications.................................... 29 6.1 SE-330 ................................................................ 29 6.2 Sensing Resistors ................................................ 31 6.3 Current Sensors ................................................... 32 7 Ordering Information ....................................... 33 8 Warranty ........................................................... 34 9 Test Procedures ................................................. 34 9.1 Resistor-Fault Tests............................................. 34 1 9.1.1 Calibration and Open Test ........................34 9.1.2 Voltage Test .............................................34 9.2 Sensing-Resistor Test ..........................................34 9.3 Analog-Output Test .............................................34 9.4 Ground-Fault Performance Test ..........................35 Appendix A SE-330 Revision History ............................. 36 LIST OF FIGURES FIGURE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 PAGE Configuration Switches ............................................3 Analog-Output Connections .....................................6 SE-330 Connection Diagram ....................................7 SE-330 Outline and Panel-Mounting Details ...........8 SE-330 Outline and Surface-Mounting Details ........9 SE-IP65CVR-G Weatherproof Cover Outline .......10 SE-IP65CVR-G Weatherproof Cover Installation .11 ER-600VC Sensing Resistor ..................................12 SE-MRE-600 Moisture-Resistant Enclosure Outline 13 ER-600VC Installed in SE-MRE-600 ......................14 ER-5KV Sensing Resistor ......................................15 ER-5WP Sensing Resistor ......................................16 ER-15KV Sensing Resistor ....................................17 ER-25KV Sensing Resistor ....................................18 ER-35KV Sensing Resistor ....................................19 EFCT-1 Ground-Fault Current Sensor .....................................................................21 SE-CS30-70 Ground-Fault Current Sensor ........................................................22 EFCT-26 and SE-CS30-26 GroundFault Current Sensors .............................................23 RK-332 Remote Indication and Reset ....................24 PGA-0520 Analog Percent Current Meter .............24 Simplified Isolated-Ground Connection .................25 Simplified Pulsing Connection ...............................25 Ground-Fault-Test Circuits ....................................35 LIST OF TABLES TABLE 1 2 3 PAGE Typical Values for Tripping Systems .......................3 Ground-Fault Trip Levels for Selected CT’s ............3 Ground-Fault-Test Record......................................35 DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. SE-330 Neutral-Grounding-Resistor Monitor This page intentionally left blank. Page iii Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 1. GENERAL 1.1 MODERN RESISTANCE-GROUNDED SYSTEMS A high-resistance-grounded system uses a neutralgrounding resistor (NGR) with a low let-through current to limit ground-fault current. This is an improvement over low-resistance or solidly-grounded systems because, in those systems, a ground-fault flash hazard exists and a ground fault can result in substantial point-of-fault damage. High-resistance grounding eliminates these problems and modern ground-fault protection operates reliably at low current levels. Furthermore, the probability of an arc-flash incident is significantly reduced in a high-resistance-grounded system. NGR selection depends on system charging current and whether the system is an alarm-only or a tripping system. Alarm-only systems are usually restricted to system voltages up to 5 kV with NGR let-through currents of 5 A or less. Occasionally, alarm-only systems up to 15 kV and up to 10 A are used; however, they are not common because a ground fault on such a system tends to escalate to a phase-to-phase fault before the ground fault can be located and cleared. Consult CEC 10-1102, NEC 250.36, and NEC 250.186 for application details. System charging current is the capacitive current that flows to ground when a bolted ground fault occurs. This current can be calculated or measured. For small systems, the magnitude of charging current can be conservatively estimated as ½ A per 1,000 kVA on low-voltage systems and 1 A per 1,000 kVA on medium-voltage systems. In an alarm-only system or in a tripping system without selective coordination, choose an NGR with a let-through current larger than the system charging current and set the pick-up current of ground-fault devices at or below 50% of the NGR let-through current. In a tripping system with selective coordination, use ground-fault devices with a definite-time characteristic to achieve time coordination. Use the same pick-up current for all ground-fault devices—this value must be larger than the charging current of the largest feeder. Select an NGR with a let-through current between five and 10 times the pick-up current of the ground-fault devices. Do not use a grounding transformer with a low-voltage resistor: The combined cost of a transformer and a lowvoltage resistor is more than the cost of a resistor rated for line-to-neutral voltage. A transformer saturated by a ground fault through a rectifier can make ground-fault protection inoperative. Transformer inrush current up to 12 times rated current can cause a ground-fault voltage larger than expected. A parallel transformer winding makes it difficult to monitor NGR continuity. Page 1 Rev. 10-K-090815 A transformer can provide the inductance necessary to cause ferroresonance if the NGR opens. Following these guidelines will reduce the flash hazard, reduce point-of-fault damage, achieve reliable groundfault protection, and ensure a stable system not subject to ferroresonance. 1.2 SE-330 NGR MONITORING The SE-330 is a microprocessor-based neutralgrounding-resistor monitor that detects NGR failures and ground faults in resistance-grounded systems. The SE-330 measures NGR resistance, NGR current, and transformer or generator neutral-to-ground voltage. The components required to monitor an NGR are an SE-330, a 20- or 100-k ER-series sensing resistor, and a current transformer (CT). Power-circuit elements, other than neutral-connected NGR’s, that purposefully connect the power system to ground are often not compatible with SE-330 NGR monitoring. These elements include single-phase grounding transformers, grounded-wye-primary potential transformers (PT’s), and grounded-wye-primary power transformers. The SE-330 continuously measures NGR resistance in an unfaulted system. It will trip on resistor fault if NGR resistance varies from its calibrated value. When a ground fault occurs, voltage is present on the neutral and NGR current will flow if the NGR is healthy. The SE-330 will trip on ground fault if fault current exceeds the GF TRIP LEVEL setting for an interval equal to the GF TRIP TIME setting. However, if the NGR fails open during a ground fault, it is possible for fault resistance to satisfy the NGR resistance measurement. To detect this double-fault condition, the SE-330 measures neutral voltage. If neutral voltage exceeds the VN TRIP LEVEL setting and if NGR current is less than 5% of the current transformer (CT) rating, the SE-330 will trip on resistor fault. If the resistor-fault circuit is tripped and the neutral voltage exceeds the VN TRIP LEVEL setting for an interval greater than the GF TRIP TIME setting, the ground-fault circuit will also trip. Ground-fault current is sensed by a CT with a 1- or 5-A secondary, or by a CT (EFCT-x or SE-CS30-x) with a 50-mA secondary. The trip level of the ground-fault circuit is adjustable from 2 to 100% of the CT rating and trip time is adjustable from 0.1 to 10.0 seconds. The SE-330 has four output relays. Relay K1 can be assigned a trip or a pulsing function. Relays K2 and K3 provide ground-fault and resistor-fault indication. K4 is a solid-state relay that provides UNIT HEALTHY indication. When relay K1 is assigned the trip function, it will operate on either a resistor fault or ground fault, and it can be set to operate in the fail-safe or non-fail-safe mode for undervoltage or shunt-trip applications. When SE-330 Neutral-Grounding-Resistor Monitor the pulsing function is selected, relay K1 is used to control a contactor to assist in locating faults. Additional features include LED trip indication, trip memory, front-panel and remote reset, 4-20-mA analog output, trip event recorder, USB local communications, microSD™ data logging, and optional network communications. The SE-330 provides additional features over the SE-330 legacy model (revision 04 or less): When the trip level is set to MEM, the ground-fault trip setting is defined by an internal non-volatile memory variable. Range is 2 to 100% in 1% increments of the CT-primary rating. Indication relays can be set to fail-safe or non-failsafe. The number of trip records has been increased to 100 and includes date and time stamping. A microSD™ card interface can be used for longterm data logging and firmware updates. A microSD™ card and a microSD-to-SD adapter is included. See Section 4.1. For ease of connection to new devices, the RS-232 interface has been replaced by a Mini B USB port. Dual Ethernet ports are available with support for fiber-optic and RJ45 interfaces. The IEC 61850 protocol has been added. 2. OPERATION 2.1 SETTINGS 2.1.1 GF TRIP TIME GF TRIP TIME (definite time) is adjustable from 0.1 to 10.0 seconds. Time-coordinated ground-fault protection requires this setting to be longer than the trip times of downstream ground-fault devices. A trip-time accumulator provides a ground-fault memory function for detection of intermittent faults. The accumulated time increases when a ground fault is detected and decreases when a ground fault is not detected. A trip will eventually occur when the time for fault current above the trip level is greater than the time for fault current below the trip level. Page 2 Rev. 10-K-090815 2.1.2 GF TRIP LEVEL The SE-330 uses a Discrete-Fourier Transform (DFT) Algorithm to measure the fundamental component of NGR current. Choose an NGR let-through current and a ground-fault trip level according to the guidelines in Section 1.1. Set the ground-fault trip level as a percentage (2 to 100) of the CTprimary rating. When the GF Trip Level is set to MEM, the ground-fault setting stored in non-volatile memory is used. This parameter must be set using a PC running the SE-MON330 software connected to the USB interface. The setting range is 2 to 100% of CT primary rating in 1% increments. The default value is 15%. Inputs are provided for 5-, 1-, and 0.05-A-secondary CT’s. Typical values for 5-, 15-, and 25-A tripping systems are shown in Table 1. Ground-fault trip levels for selected CT’s are shown in Table 2. For other systems, refer to the NGR Monitor SetPoint Assistant at www.littelfuse.com/ relayscontrols. The Set-Point Assistant is included with the SE-MON330 software. 2.1.3 VN TRIP LEVEL The SE-330 uses a DFT algorithm to measure the fundamental component of neutral voltage (VN). If neutral voltage is greater than the VN TRIP LEVEL setting for the duration of the resistor-fault trip time and ground-fault current is less than 5% of the CT rating, the SE-330 will trip on resistor fault. If the resistor-fault circuit is tripped and the neutral voltage exceeds the VN TRIP LEVEL setting for an interval greater than the GF TRIP TIME setting, the ground-fault circuit will also trip. The VN TRIP LEVEL range is 20 to 2,000 V with switch S5 in the 20-k (Vx1) position, and the range is 100 to 10,000 V with switch S5 in the 100-k (Vx5) position. Calculate the voltage across the NGR when NGR current is equal to the pick-up current of the ground-fault circuit. Set the VN TRIP LEVEL at the next largest value. See Fig. 1 and Section 2.1.5.5. Typical values for 5-, 15-, and 25-A tripping systems are shown in Table 1. For an NGR resistance greater than 2 k, use a 100-k sensing resistor. For other systems, refer to the NGR Monitor Set-Point Assistant at www.littelfuse.com/relayscontrols. NOTE: A resistor-fault trip is held off if the ground-fault current is above 5% of the CT rating. Page 3 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor TABLE 1. TYPICAL VALUES FOR TRIPPING SYSTEMS SYSTEM VOLTAGE (LINE-LINE) (VOLTS) 480 600 2,400 4,160 480 600 2,400 4,160 7,200 14,400 4,160 7,200 14,400 25,000 35,000 NEUTRAL-GROUNDING RESISTOR CURRENT (AMPERES) 5 5 5 5 15 15 15 15 15 15 25 25 25 25 25 RESISTANCE (OHMS) 55 69 277 480 18 23 92 160 277 554 96 166 332 577 808 SENSING RESISTOR MODEL GROUNDFAULT TRIP LEVEL VN TRIP LEVEL (AMPERES) (VOLTS) 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 3.0 3.0 5.0 5.0 5.0 5.0 5.0 60 100 340 800 60 100 340 800 170x5=850 340x5=1,700 800 170x5=850 340x5=1,700 800x5=4,000 1,200x5=6,000 200:1 200:5 (AMPERES) * * 12 16 20 40 80 120 160 200 400:1 400:5 (AMPERES) * 16 24 36 40 80 160 240 320 400 RESISTANCE (SWITCH S5 SETTING) 20 k 20 k 20 k 20 k 20 k 20 k 20 k 20 k 100 k 100 k 20 k 100 k 100 k 100 k 100 k ER-600VC ER-600VC ER-5KV ER-5KV ER-600VC ER-600VC ER-5KV ER-5KV ER-15KV ER-15KV ER-5KV ER-15KV ER-15KV ER-25KV ER-35KV TABLE 2. GROUND-FAULT TRIP LEVELS FOR SELECTED CT’S GF TRIP LEVEL(1) (%) 2 4 6 8 10 20 40 60 80 100 EFCT-x 5:0.05 (AMPERES) SE-CS30-x 30:0.05 (AMPERES) 50:1 50:5 (AMPERES) * * * * 5 10 20 30 40 50 100:1 100:5 (AMPERES) * * * 8 10 20 40 60 80 100 0.10 0.60 0.20 1.20 0.30 1.80 0.40 2.40 0.50 3.00 1.00 6.00 2.00 12.0 3.00 18.0 4.00 24.0 5.00 30.0 (1) When set to MEM, range is 2 to 100% in 1% increments. * Setting not recommended. 2.1.4 PULSE-PERIOD ADJUSTMENT Pulse period is the cycle time of relay K1 when the SE-330 is configured for pulsing operation. Pulse period is adjustable from 1.0 to 3.0 seconds with a fixed duty cycle of 50%. For example, with the 1.0-s setting, relay K1 will alternately be energized for 0.5 seconds and deenergized for 0.5 seconds when pulsing is enabled. See Section 2.3 for detailed pulsing operation information. NOTE: For pulsing configuration, set switch S1 to K1 = PULSING and install an external pulse-enable switch. CALIBRATION BUTTON K1 = TRIP K1 FAIL-SAFE S2 K1 NON-FAIL-SAFE LATCHING GF TRIP S3 NON-LATCHING GF TRIP LATCHING RF TRIP S4 NON-LATCHING RF TRIP 20 kΩ S5 100 kΩ 50 Hz S6 60 Hz NOT USED RUN 2.1.5 CONFIGURATION SETTINGS Eight configuration switches (S1 to S8) and a calibration button are located behind the access cover on the front panel. See Fig. 1. S1 K1 = PULSING S7 S8 UPGRADE NOTE: 1. DEFAULT SETTINGS SHOWN. FIGURE 1. Configuration Switches. SE-330 Neutral-Grounding-Resistor Monitor 2.1.5.1 RELAY K1 FUNCTION (S1) Set switch S1 to K1 = TRIP to assign the trip function to relay K1 and to activate switch S2. Relay K1 will change state when a resistor-fault or ground-fault trip occurs. Set switch S1 to K1 = PULSING to configure relay K1 for pulsing operation. See Section 2.3. 2.1.5.2 TRIP-RELAY MODE AND TRIP-MEMORY MODE (S2) Set switch S2 to select the operating mode of trip relay K1. In the non-fail-safe mode, relay K1 energizes and its contact closes when a trip occurs. The non-fail-safe mode can be used to trip shunt-trip circuit breakers. In the non-fail-safe mode, SE-330 trips are reset when supply voltage is cycled. In the fail-safe mode, relay K1 energizes and its contact closes if there are no trips. Contacts open if there is a trip, a loss of supply voltage, or a processor failure. In the fail-safe mode, SE-330 trips are not reset when supply voltage is cycled. NOTE: Switch S2 does not affect the operating modes of relays K2, K3, and K4. NOTE: Switch S2 only affects relay K1 operating mode when K1 is assigned the trip function (switch S1 set to K1 = TRIP). Trip memory is enabled when K1 is set to the fail-safe mode, regardless of the switch S1 setting. 2.1.5.3 GROUND-FAULT-TRIP LATCH (S3) Set switch S3 to select latching or non-latching groundfault-circuit operation. Non-latching operation defeats ground-fault-trip memory. See Sections 2.1.5.2 and 2.4. 2.1.5.4 RESISTOR-FAULT-TRIP LATCH (S4) Set switch S4 to select latching or non-latching resistor-fault-circuit operation. Non-latching operation defeats resistor-fault-trip memory. See Sections 2.1.5.2 and 2.4 2.1.5.5 SENSING-RESISTOR SELECTION (S5) Set switch S5 to the resistance of the sensing resistor. For the ER-600VC, ER-5KV, and ER-5WP, select 20 k. For the ER-15KV, ER-25KV, and ER-35KV, select 100 k. Switch S5 sets the resistor-fault trip value and the VN TRIP LEVEL range. See Section 2.1.3. 2.1.5.6 FREQUENCY (S6) Set switch S6 to 50 or 60 Hz to tune the digital filter to the line frequency of the monitored system. 2.1.5.7 UPGRADE MODE (S8) The microSD™ card is used for firmware upgrades. See Section 4.1.2 for upgrade instructions. NOTE: An upgrade causes an SE-330 restart and this may cycle the output relays. Page 4 Rev. 10-K-090815 2.1.6 RESISTOR-FAULT TRIP TIME The resistor-fault trip time can be adjusted from 12 (default) to 60 seconds using the SE-MON330 software or via network communications. 2.1.7 RESISTOR-FAULT TRIP LEVEL The resistor-fault trip level can be adjusted using the SE-MON330 software or via network communications. See Section 6.1. 2.1.8 GEO-MAGNETIC FILTER A low-frequency ground current can be caused by the Earth’s magnetic field and from charged clouds passing overhead during a thunderstorm. In some rare conditions, this can cause a false resistor-fault trip. Enabling the geomagnetic filter and increasing the resistor-fault trip time can help counteract these effects. A trip time of 30 seconds is recommended when the geo-magnetic filter is enabled. The geo-magnetic filter is disabled by default, but can be enabled using the SE-MON330 software or via network communications. 2.2 CALIBRATION The SE-330 measures the resistance change of the NGR relative to the NGR-resistance value determined at the time of calibration. When the resistance change is greater than a threshold amount (500 Ω for 20-kΩ systems, 2,500 Ω for 100-kΩ systems), a resistor-fault trip occurs. Calibrate the SE-330 on new installations, if the NGR is changed, or if the sensing resistor is changed. NOTE: If the SE-330 is not calibrated and is supplied from the load side of the breaker (non-fail-safe mode), calibrate within the resistor-fault trip time after power-up or it may trip and interrupt its supply. See Section 2.1.6. The CALIBRATION button is located behind the access cover on the front panel, and it is recessed to prevent inadvertent activation. NOTE: Calibration must be performed with the SE-330 connected to the sensing resistor and NGR of the installed system. To calibrate, press and hold the CALIBRATION button until the green CALIBRATED LED turns off and returns to on (if the LED is already off, press and hold until the LED turns on). Calibration takes approximately two seconds. If calibration is not successful, a resistor-fault trip occurs, the RESISTOR FAULT TRIP LED will be on, the CALIBRATED LED will be off, and the DIAGNOSTIC LED will flash the calibration-error code. See Section 2.8. The SE-330 may be calibrated remotely using the SE-MON330 software with the USB interface or the communications options. SE-330 Neutral-Grounding-Resistor Monitor If latching resistor fault (switch S4) is selected, the calibration-error code flashes until RESET is pressed even if the CALIBRATED LED is on. The calibration value is stored in non-volatile memory. 2.3 PULSING OPERATION If switch S1 is set to K1 = PULSING, pulsing occurs when terminal 16 is connected to terminal 17. Relay K1 operates at a 50% duty cycle and cycle time is adjustable from 1.0 to 3.0 seconds. When terminals 16 and 17 are not connected, K1 is not energized and its contact is open. Relay K1 can be used to control a contactor rated for use at the line-to-neutral voltage. The contactor causes changes in neutral-to-ground resistance by adding or shorting portions of the NGR. See Section 3.5. Pulsing ground-fault current appears as zero-sequence current upstream from the fault. Pulsing ground-fault current is distinguishable from charging current and noise, and it can be traced with a clip-on ammeter or current probe. If pulsing current is detected on a cable or conduit, the fault is downstream. Systematic testing allows faults to be located without isolating feeders or interrupting loads. Stop pulsing when a fault is located. 2.4 TRIP INDICATION AND RESET Red LED's and indication relays indicate ground-fault and resistor-fault trips. The indication relays K2 (GF) and K3 (RF) operate in fail-safe or non-fail-safe mode. The default is non-fail-safe mode. In this mode, the relays are energized when a fault occurs. The relay mode setting is stored in non-volatile memory and can be set using the SE-MON330 software or network communications. When a trip occurs with latching operation selected, the SE-330 remains tripped until reset with the front panel button or the remote-reset input. See Sections 2.1.5.3 and 2.1.5.4. Terminals 15 and 16 are provided for remote reset as shown in Fig. 3. The reset circuit responds only to a momentary closure so that a jammed or shorted button does not prevent a trip. The front-panel RESET button is inoperative when terminal 15 is connected to terminal 16. If non-latching operation is selected, trips and corresponding indication automatically reset when the fault clears and power-up trip memory is defeated even when configuration switch S2 is set to fail-safe. The maximum automatic reset time is 2.8 s. The red DIAGNOSTIC LED annunciates latched calibration-error and remote trips. See Section 2.8. When supply voltage is applied with switch S2 set to FAIL-SAFE, the SE-330 returns to its state prior to loss of supply voltage unless switch S3 or S4 is set to nonlatching. When supply voltage is applied with switch S2 set to NON-FAIL-SAFE, SE-330 trips are reset. When a local, remote, or network reset is issued, both trip LED's will flash if they are off. Resistor-fault-trip reset can take up to one second. Resistor-fault trip-memory trip can take up to three seconds after SE-330 power up. Page 5 Rev. 10-K-090815 2.5 REMOTE OPERATION Relays K2 and K3 can be used for remote indication, and terminals 15 and 16 are provided for remote reset. RK-332 Remote Indication and Reset components are shown in Fig. 19. Connect them as shown in Fig. 3. RK-332 components are not polarity sensitive. Indication relays can be set to fail-safe or non-fail-safe operation using the SE-MON330 software or network communications. The default mode is non-fail-safe. In non-fail-safe mode, relays energize on fault. Network-enabled SE-330’s can be remotely tripped and reset by the network master. The red DIAGNOSTIC LED indicates a network-initiated trip. See Section 2.8. Refer to the appropriate SE-330 communications manual. 2.6 RELAY K1 LED The yellow RELAY K1 LED follows the state of relay K1 and is on when K1 is energized (contact closed). 2.7 UNIT HEALTHY OUTPUT UNIT HEALTHY relay K4 is energized when the processor is operating. It can be ordered with N.O. or N.C. contacts. See Section 7. NOTE: The K4 output changes state momentarily during a processor reset. NOTE: K4-contact rating is 100 mA maximum. 2.8 DIAGNOSTIC LED The DIAGNOSTIC LED is used to annunciate trips without individual LED indication. The number of short LED pulses between pauses indicates the cause of the trip. See Section 5. SE-330 Neutral-Grounding-Resistor Monitor 2.9 ANALOG OUTPUT An isolated 4–20-mA output indicates NGR current with full-scale output corresponding to the CT rating. An internal 24-Vdc supply allows the analog output to be connected as a self-powered output. Power from an external supply is required for loop-powered operation. See Fig. 2. A PGA-0520 analog meter can be panelmounted to display the NGR current. See Fig. 20 and Section 7. +24V 18 + 19 - 20 0V 21 SELF-POWERED PGA-0520 +24V 18 + + 19 - 20 0V 21 LOOP SUPPLY PGA-0520 LOOP POWERED FIGURE 2. Analog-Output Connections. Page 6 Rev. 10-K-090815 3. INSTALLATION 3.1 SE-330 Outline and panel-cutout dimensions for the SE-330 are shown in Fig. 4. To panel mount the SE-330, insert it through the panel cutout and secure it with the four included 8-32 locknuts and flat washers. If an optional SE-IP65CVR-G Hinged Cover is used, follow the included installation instructions. See Figs. 6 and 7. All connections to the SE-330 are made with plug-in, wire-clamping terminal blocks. Each plug-in terminal block can be secured to the SE-330 by two captive screws for reliable connections. Outline dimensions and mounting details for surface mounting the SE-330 are shown in Fig. 5. Fasten the optional surface-mount adapter to the mounting surface and make connections to the adapter terminal blocks. Follow Fig. 5 instructions to mount or remove the SE-330. Ground terminal 7 (G) and connect terminal 6 (R) to the sensing-resistor R terminal. Use terminal 1 (L1) as the line terminal on ac systems, or the positive terminal on dc systems. Use terminal 2 (L2/N) as the neutral terminal on ac systems or the negative terminal on dc systems. Connect terminal 3 ( ) to ground. Connect terminal 4 (SPG) to terminal 5 (SPGA). NOTE: Disconnect terminal 1 (L1) and terminal 2 (L2/N) before performing dielectric strength testing of the control panel. Page 7 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor TRANSFORMER OR GENERATOR NOTE 1 NOTE 12 XXX:1 OR S 9 EFCT-X OR SE-CS30-X XXX:5 1 10 5 11 8 C 9 S 5 1 NOTE 4 G 1 NOTE 6 L2/N L1 K1 22 6 7 25 K3 28 K4 REMOTE RESET PULSE ENABLE 15 16 17 UNIT HEALTHY NOTE 7 +24V NO CONNECTION + ANALOG OUTPUT RESET 5 RESISTOR FAULT 0V 19 SE-330 INDICATION R GROUND-FAULT TRIP R RESISTORFAULT TRIP R DIAGNOSTIC G CALIBRATED Y RELAY K1 G POWER 2. LOCATE THESE COMPONENTS NEAR TRANSFORMER OR GENERATOR. 3. ALTERNATE SENSING-RESISTOR TERMINAL-N CONNECTION. THE NEUTRAL CONNECTION IS NOT MONITORED. 5. SEE SECTION 3.4 FOR ISOLATED-GROUND CONNECTION. PGA-0520 SPG OPTIONAL NETWORK COM NOTE 10 1. USE SEPARATE LUG TO CONNECT SENSINGRESISTOR TERMINAL N TO NEUTRAL. NOTE 15 USB PORT NOTE 9 SPGA NOTES: NOTE 8 20 21 NOTE 5 4. VOLTAGE BETWEEN SENSING-RESISTOR TERMINALS R AND G IS LIMITED TO 100 V BY INTERNAL CLAMP. 18 PULSE ENABLE 3 4 GROUND FAULT 13 12 NOTE 14 C 27 RF 14 NOTE 13 & 14 24 GF 29 N/- SUPPLY 2 23 K2 26 G R R ALTERNATE CT CONNECTIONS L/+ SUPPLY NGR C 5A 1A EFCT SE-330 C NOTE 3 ER-SERIES SENSING RESISTOR NOTE 17 10 11 NOTE 16 NOTE 2 NOTES 11 & 12 N 8 NEUTRAL MICRO SD SLOT 6. RELAY CONTACTS SHOWN WITH SE-330 DE-ENERGIZED. 7. OPTIONAL N.C. K4 AVAILABLE. 8. LOOP-POWERED CONNECTION USES TERMINALS 19 AND 20 ONLY. 9. MINI B USB DEVICE CONNECTOR. 10. REFER TO APPROPRIATE SE-330 COMMUNICATIONS INTERFACE MANUAL. 11. TWO-CONDUCTOR TWISTED CABLE REQUIRED, SHIELDED RECOMMENDED. 12. CT CONNECTION IS NOT POLARITY SENSITIVE. 13. CONNECT CONTACTS K1, K2, K3, AND K4 AS REQUIRED FOR PROTECTION, INDICATION, AND CONTROL. 14. EXTERNAL LIGHTS AND SWITCHES NOT INCLUDED WITH SE-330. 15. SELF-POWERED 4-20 mA OUTPUT. 16. TYPICAL TRIPPING SYSTEM. 17. GROUND CURRENT SENSOR AT TERMINAL 11 ONLY. FIGURE 3. SE-330 Connection Diagram. Page 8 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 16.0 132.0 (5.20) (0.63) 98.3 PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) (3.87) LITTELFUSE STARTCO NEUTRAL-GROUNDING-RESISTOR MONITOR SE-330 RESISTOR FAULT GROUND FAULT DIAGNOSTIC TRIP 1 2 3 4 5 CALIBRATED 20 40 60 80 4 100 2 MEM GF TRIP LEVEL (% CT RATING) 0.5 0.7 1.0 0.4 0.3 0.2 0.1 2.0 3.0 5.0 10.0 POWER 170 130 100 200 340 800 1200 60 1700 20 2000 VN TRIP LEVEL (S5 CAL GF TRIP TIME (s) 20 K Ω VN x 1 185.4 (7.30) 10 212.6 (8.37) RELAY K1 8 6 12 13 NC - 14 15 RESET 16 PULSE ENABLE 17 + 24V - 18 + - 19 ANALOG OUTPUT - - 20 0V - 2 1 UNIT HEALTHY K4 TRIP 100 K Ω) VN x 5 1.8 2.0 2.2 1.6 2.4 1.4 2.6 1.2 2.8 1.0 3.0 - L1 L2/N SPG SPGA ATTENTION DISENGAGE CAPTIVE RETAINING S C R E W S BE F O R E R E M O V I N G P L U G -I N T ER M I NA L B LO CK S 6 - R 7 - G SENSING RESISTOR PULSE PERIOD (s) 8 9 10 11- RESET FRONT VIEW SIDE VIEW 92.7 (3.65) 7.0 (0.28) PANEL-MOUNT CUTOUT FIGURE 4. SE-330 Outline and Panel-Mounting Details. RESISTOR FAULT K3 24 25 26 27 28 29 REAR VIEW 1. DIMENSIONS IN MILLIMETRES (INCHES). R=4.8 (0.19) MAXIMUM 4.75 (0.187) DIA 4 LOCATIONS GROUND FAULT K2 22 23 NOTES: 76.2 (3.00) 186.0 (7.32) 200.0 (7.87) 8.2 (0.32) S E 1 F 5 5 A1 C T C A K1 Page 9 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 114.3 8.0 (0.31) RETAINER SCREW RETAINER 6.4 (0.25) (4.50) 98.3 (3.87) 138.0 (5.43) LITTELFUSE STARTCO NEUTRAL-GROUNDING-RESISTOR MONITOR RESISTOR FAULT GROUND FAULT DIAGNOSTIC TRIP L1 - 1 L2/N - 2 - 3 SPG - 4 SPGA - 5 20 40 60 80 100 2 MEM GF TRIP LEVEL (% CT RATING) 0.5 0.7 1.0 POWER R - 6 G - 7 2.0 3.0 5.0 10.0 (S5 CAL GF TRIP TIME (s) GROUND FAULT K2 RESISTOR FAULT K3 S - 8 E 1 - 9 F C 1 T A 5 5 -1 0 A C -1 1 340 800 1200 20 K Ω VN x 1 100 K Ω) VN x 5 1.8 2.0 2.2 1.6 2.4 1.4 2.6 1.2 2.8 1.0 3.0 6 7 PULSE PERIOD (s) 8 9 10 11 RESET FRONT VIEW SE-330-SMA 25.4 (1.00) 200 60 1700 20 2000 VN TRIP LEVEL FRONT VIEW 63.5 (2.50) SIDE VIEW 5.0 (0.20) 24 25 26 27 28 29 SENSING RESISTOR 0.4 0.3 0.2 0.1 170 130 100 225.4 (8.87) RELAY K1 10 4 K1 1 2 3 4 5 CALIBRATED 8 6 22 23 TRIP 212.6 (8.37) 12 NIT K4 U HEALTHY 13 14 - NC 15 RESET 16 PULSE ENABLE 17 18 - + 24V 19- + ANALOG OUTPUT 20 - 2 1 - 0V SE-330 NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). (NOTE 2) 2. MOUNTING SCREWS: M4 OR 8-32 PANHEAD. INSTALLATION 215.9 (8.50) 1. LOOSEN RETAINER SCREWS, MOVE RETAINERS OUTWARD AND TIGHTEN RETAINER SCREWS. 2. MATE MONITOR WITH ADAPTER PLUG-IN TERMINALS. LOOSEN RETAINER SCREWS TO LET RETAINERS SNAP OVER MONITOR BACKPLATE. 3. ENSURE THAT RETAINERS ARE AGAINST MONITOR BODY AND TIGHTEN RETAINER SCREWS. REMOVAL 1. LOOSEN RETAINER SCREWS, SLIDE RETAINERS AWAY FROM MONITOR BODY AND TIGHTEN RETAINER SCREWS. BEZEL OUTLINE ADAPTER PANEL OUTLINE MOUNTING DETAIL FIGURE 5. SE-330 Outline and Surface-Mounting Details. 2. PULL MONITOR FORWARD. Page 10 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 34.0 (1.34) TO PREVENT UNAUTHORIZED ENTRY: 1. USE WIRE SEAL THROUGH HOLES IN WEATHERPROOF COVER ASSEMBLY, OR 2. SECURE WITH THE PLASTIC THREAD FORMING SCREW SUPPLIED IN KIT. SHOWN WITH SEAL (9.84) 250.0 TOP VIEW HOLE FOR SEAL WIRE 127.0 (5.00) FRONT VIEW NOTES: 1. DIMENSIONS SHOWN IN MILLIMETRES (INCHES). 2. SHOWN WITH WEATHERPROOF SNAPS CLOSED. 3. REFER TO PANEL MOUNTING CUTOUT (FIGURE 4) FOR PANEL MOUNTING DETAIL. FIGURE 6. SE-IP65CVR-G Weatherproof Cover Outline. SIDE VIEW Page 11 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor INSTALL O-RING INTO GROOVE IN THE REAR OF WEATHERPROOF WINDOW INSERT THE SE-330 THROUGH OPENING OF THE WEATHERPROOF WINDOW, UNTIL IT IS SECURELY NESTED TO THE BACK OF THE DARK GREY PVC PANEL. FRONT-PANEL DETAILS NOT SHOWN. INSTALL O-RING INTO THE GROOVE IN THE REAR OF WEATHERPROOF WINDOW ASSEMBLY. INSERT ASSEMBLY INTO PANEL AND FASTEN WITH THE HARDWARE PROVIDED WITH THE SE-330. FIGURE 7. SE-IP65CVR-G Weatherproof Cover Installation. SE-330 Neutral-Grounding-Resistor Monitor If a ground fault in the sensing-resistor conductor is unlikely, a minimal loss of protection will result if it does not pass through the ground-fault-CT window. See Note 3 in Fig. 3. 3.2 SENSING RESISTOR Outline and mounting details for the ER-600VC, ER-5KV, ER-5WP, ER-15KV, ER-25KV, and ER-35KV sensing resistors are shown in Figs. 8, 11, 12, 13, 14, and 15. Install the NGR and the sensing resistor near the transformer or generator. When installed outdoors, a sensing resistor must be installed in a suitable enclosure. An optional SE-MRE-600 Moisture-Resistant Enclosure is available for applications which may expose an ER-600VC to moisture. See Figs. 9 and 10. The weather-protected ER-5WP shown in Fig. 12 is an ER-5KV with moisture-resistant terminal covers. Use an ER-5WP in applications in which it might be exposed to moisture. The ER-15KV, ER-25KV, and ER-35KV include moisture-resistant terminal covers. Use suitable water-tight fittings. Ground sensing-resistor terminal G. Pass the sensing-resistor-to-neutral conductor and the NGR-to-neutral conductor through the ground-fault-CT window as shown in Fig. 3. Separately connect sensingresistor terminal N and the NGR to the neutral to include neutral connections in the monitored loop. Alternately, if the NGR connection to system neutral need not be monitored, connect terminal N to the NGR neutral terminal. NOTE: Voltage at terminal N rises to line-to-neutral voltage when a ground fault occurs. The same clearances are required for sensing resistors as for NGR’s. NOTE: A parallel ground path created by moisture can result in a false resistor-fault trip. Moisture sources include wind-driven rain or snow, and condensation. Sensing-resistor terminal R and its connection to SE-330 terminal R, including interposing terminal blocks, must remain dry. NOTE: The neutral-to-sensing-resistor-terminal-N connection is not a neutral conductor as defined in Canadian Electrical Code Section 10-1108 and National Electrical Code Section 250.36(B). It is not required to be 8 AWG (8.36 mm2) or larger. Since current through this conductor is always less than 250 mA, a 14 AWG (2.08 mm2) conductor insulated to the system voltage is more than sufficient. RATINGS: MAXIMUM VOLTAGE . 600 Vac MAXIMUM CURRENT . 30 mA RESISTANCE . . . . . . . 20 kΩ THERMAL: 600 Vac . . . . . . . . . . 6 MINUTES ON, 60 MINUTES OFF 420 Vac . . . . . . . . . . CONTINUOUS 41.5 40.0 (1.63) (1.57) 89.0 (3.50) (0.31) (4.13) 105.0 C 4.5 (0.18) DIA C’BORE 10.0 (0.39) DIA 3.2 (0.13) DEEP FRONT 8.0 Use with: Duty Cycle: Rating: SENSING RESISTOR Serial No: GC131105487 LR 53428 US I E E E 3 2 ER-600VC Revision: 02 SENSI NG RES I STOR 2 0 KΩ 6 0 0 V AC MA X NOTE 3 R ER-600VC 1-800-TEC-FUSE (1-800-832-3873) Made in Saskatoon, Canada 105.0 G (4.13) R SE-325, SE-330, SE-330AU 10.5 (0.41) 600 Vac 50/60 Hz 30 mA Max 20 KΩ 19.0 (0.75) 6 Minutes On, 60 Minutes Off at 600 Vac Continuous at 420 Vac 10.5 (0.41) 8.0 22.2 (0.87) (0.31) 40.0 (1.57) N SIDE MOUNTING DETAIL NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. 3. MOUNTING SCREWS: M4 OR 8-32. 4. ON REVISION 2 UNITS ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING. 5. ON REVISION 1 UNITS, SCREW IS NOT PRESENT AND ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G. 6. NOT ALL CERTIFICATIONS SHOWN. FIGURE 8. ER-600VC Sensing Resistor. Page 12 Rev. 10-K-090815 Page 13 Rev. 10-K-090815 (4.80) 122.0 (4.80) 122.0 SE-330 Neutral-Grounding-Resistor Monitor GASKET 120.4 (4.74) 120.4 (4.74) ENCLOSURE - TOP VIEW COVER - INSIDE VIEW (COVER REMOVED) 122.0 (4.80) ENCLOSURE - TOP VIEW MOUNTING DETAIL 120.4 (4.74) 20.4 (0.80) NOTES: 84.6 (3.33) 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M6 OR 0.25-20. ENCLOSURE - SIDE VIEW FIGURE 9. SE-MRE-600 Moisture-Resistant Enclosure Outline. 82.5 120.4 (4.74) (13.25) M6 OR 0.25-20 19.1 82.5 (3.25) (0.75) 9.5 (0.38) Page 14 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor NOTE 2 MOUNTING SCREWS 4 LOCATIONS NOTE 4 N R G NOTE 3 ER-600VC SENSI NG RES I STOR 2 0 KΩ 6 0 0 V AC M A X NOTE 2 ENCLOSURE - TOP VIEW COVER - INSIDE VIEW (COVER REMOVED) ASSEMBLY INSTRUCTIONS 1. DRILL HOLE FOR ENCLOSURE WIRE ENTRY. USE LIQUID-TIGHT FITTING. 2. REMOVE NYLON NUTS AND WASHERS. INSERT ER-600VC INTO ENCLOSURE. REPLACE NUTS AND WASHERS. 3. ATTACH GROUND WIRE FROM ENCLOSURE TO COVER AND TO ER-600VC TERMINAL G. 4. MOUNT SE-MRE-600 IN PLACE USING M6 OR 0.25-20. 5. COMPLETE OTHER WIRING AND REPLACE COVER. FIGURE 10. ER-600VC Installed in SE-MRE-600. Page 15 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor RATINGS: 381.0 (15.00) 21.0 (0.83) ALTERNATE NEUTRAL CONNECTION 12.0 NEUTRAL CONNECTION (0.47) E R - 5 KV S E NS IN G R E S I S TO R 2 0 KΩ 2500 VAC MAX N 0.25-20 UNC THREADED INSERT N 10-32 THREADED INSERT N 7.9 (0.31) 52.5 (2.07) 105.0 (4.13) MAXIMUM VOLTAGE . 2,500 Vac MAXIMUM CURRENT. 125 mA RESISTANCE . . . . . . . 20 kΩ THERMAL . . . . . . . . . . CONTINUOUS TORQUE TERMINAL N (3 LOCATIONS) 10-32 INSERT. . . . . 5.6 N-m (50 in-lb) OTHERS . . . . . . . . . 9.0 N-m (80 in-lb) TOP VIEW 316.0 (12.44) 188.0 (7.40) 0.25-20 UNC STUD NOTE 2 RG NOTES 5 & 6 SIDE VIEW FRONT VIEW NOTES: MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 MINIMUM CLEARANCE FROM BASE 254.0 (10.00) 4. THIS DEVICE CAN DISSIPATE 300 WATTS. TO MINIMIZE SURFACE TEMPERATURES FOR SYSTEMS ALLOWED TO OPERATE CONTINUOUSLY WITH A GROUND FAULT, MOUNT VERTICALLY WITH R & G TERMINALS DOWN. 355.6 5. ON REVISION 2 UNITS BASE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING. 6. ON REVISION 0 & 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G. 7. CERTIFICATIONS NOT SHOWN. FIGURE 11. ER-5KV Sensing Resistor. 50.7 (2.00) (14.00) 457.0 (18.00) MOUNTING DETAIL 254.0 (10.00) 3. MOUNTING SCREWS: M6 OR 0.25-20. 127.0 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. (5.00) 1. DIMENSIONS IN MILLIMETRES (INCHES). Page 16 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor RATINGS: MAXIMUM VOLTAGE . 2,500 Vac MAXIMUM CURRENT. 125 mA RESISTANCE . . . . . . . 20 kΩ THERMAL . . . . . . . . . . CONTINUOUS TORQUE TERMINAL N (3 LOCATIONS) 10-32 INSERT. . . . . 5.6 N-m (50 in-lb) OTHERS . . . . . . . . . 9.0 N-m (80 in-lb) ER-5WP S E NS IN G R E S I S TO R 2 0 KΩ 2500 VAC MAX N 0.25-20 UNC THREADED INSERT N 10-32 THREADED INSERT N 7.9 (0.31) 52.5 (2.07) 105.0 (4.13) 381.0 (15.00) 21.0 (0.83) ALTERNATE NEUTRAL CONNECTION 12.0 NEUTRAL CONNECTION (0.47) TOP VIEW 316.0 (12.44) 188.0 (7.40) 0.25-20 UNC STUD NOTE 2 AND 5 SIDE VIEW FRONT VIEW NOTES: MINIMUM DISTANCE TO ADJACENT OBJECTS MINIMUM CLEARANCE FROM BASE 254.0 (10.00) 3. MOUNTING SCREWS: M6 OR 0.25-20. 4. THIS DEVICE CAN DISSIPATE 300 WATTS. TO MINIMIZE SURFACE TEMPERATURES FOR SYSTEMS ALLOWED TO OPERATE CONTINUOUSLY WITH A GROUND FAULT, MOUNT VERTICALLY WITH R & G TERMINALS DOWN. 5. BASE IS ELECTRICALLY CONNECTED TO TERMINAL G THROUGH JUMPER FROM TERMINAL G TO SCREW. THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING. 6. CERTIFICATIONS NOT SHOWN. FIGURE 12. ER-5WP Sensing Resistor. 355.6 50.7 (2.00) (14.00) 457.0 (18.00) MOUNTING DETAIL (5.00) NOTE 3 254.0 (10.00) 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25 CABLE ACCESS OPENING IS 1/2 NPT. USE A LIQUID-TIGHT FITTING FOR CABLE ENTRY. 127.0 1. DIMENSIONS IN MILLIMETRES (INCHES). Page 17 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 422.0 RATINGS: E R - 1 5 KV 132.0 (5.20) 144.0 (5.67) (16.61) SENS IN G RESISTO R R 1 0 0 KΩ 84 0 0 V A C M A X 1 M I N UT E M A X N G MAXIMUM VOLTAGE . . 8,400 Vac MAXIMUM CURRENT . 84 mA RESISTANCE . . . . . . . . 100 kΩ THERMAL 8,400 Vac . . . . . . . . . . 1 MINUTE ON, 120 MINUTES OFF 1,900 Vac . . . . . . . . . . CONTINUOUS NOTES 2 AND 4 0.25-20 BINDING HEAD 215.0 (8.46) TOP 20.5 (0.81) TORQUE TERMINAL N . . . . . . . . 9.0 N-m (80 in-lb) SIDE FRONT 444.0 (17.50) 365.0 (14.37) 90.0 (3.53) 39.5 (1.56) MINIMUM DISTANCE TO ADJACENT OBJECTS 39.5 (1.56) NOTES: 90.0 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. NOTE 3 MINIMUM CLEARANCE FROM BASE 305.0 (12.00) 3. MOUNTING SCREWS: M6 OR 0.25-20. 4. USE LIQUID-TIGHT FITTING FOR TERMINAL-BLOCKENCLOSURE CABLE ENTRY. (3.53) 280.0 (11.00) 100.0 (3.94) 1. DIMENSIONS IN MILLIMETRES (INCHES). 5. CERTIFICATIONS NOT SHOWN. MOUNTING DETAIL FIGURE 13. ER-15KV Sensing Resistor. Page 18 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 780.0 (30.70) 100 K Ω 1 4,4 00 V A C MA X 1 M I N UT E MA X R N 0.25-20 BINDING HEAD NOTES 2 AND 4 20.5 G (0.81) 144.0 (5.67) RATINGS: E R - 2 5 KV SE NS I NG R ES I ST OR 320.0 (12.60) TOP MAXIMUM VOLTAGE . 14,400 Vac MAXIMUM CURRENT. 144 mA RESISTANCE . . . . . . . 100 kΩ THERMAL 14,400 Vac . . . . . . . . . 1 MINUTE ON, 120 MINUTES OFF 2,500 Vac . . . . . . . . . CONTINUOUS TORQUE TERMINAL N . . . . . . . 9.0 N-m (80 in-lb) FRONT 60.0 (2.40) 800.0 (31.50) 340.0 (13.38) SIDE 340.0 (13.38) 217.0 (8.50) 534.0 (21.00) 100.0 (3.94) NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). NOTE 3 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. MINIMUM CLEARANCE FROM BASE 508.0 (20.00) MINIMUM DISTANCE TO ADJACENT OBJECTS 3. MOUNTING SCREWS: M6 OR 0.25-20 4. USE LIQUID-TIGHT FITTING FOR TERMINAL-BLOCKENCLOSURE CABLE ENTRY. 5. MOUNT AS SHOWN WITH BASE HORIZONTAL. 6. CERTIFICATIONS NOT SHOWN. MOUNTING DETAIL FIGURE 14. ER-25KV Sensing Resistor. Page 19 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 20.5 132.0 (5.20) 1000.0 (39.40) E R - 3 5 KV S E N SIN G R E SIS TO R R 10 0 K Ω 22 , 2 0 0 V AC MA X 1 M I N UT E M AX N G (0.81) RATINGS: MAXIMUM VOLTAGE . 22,000 Vac MAXIMUM CURRENT . 220 mA RESISTANCE . . . . . . . 100 kΩ THERMAL 22,000 Vac . . . . . . . . . 1 MINUTE ON, 120 MINUTES OFF 3,000 Vac . . . . . . . . . . CONTINUOUS TORQUE TERMINAL N . . . . . . . 9.0 N-m (80 in-lb) 0.25-20 BINDING HEAD NOTES 2 AND 4 459.0 (18.10) TOP FRONT SIDE 1600.0 (63.00) MINIMUM CLEARANCE FROM BASE 685.0 (27.00) 100.0 (3.90) 400.0 (15.70) 400.0 (15.70) NOTE 3 350.0 (13.80) 800.0 (31.50) 350.0 (13.80) MINIMUM DISTANCE TO ADJACENT OBJECTS MOUNTING DETAIL NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25. 3. MOUNTING SCREWS: M6 OR 0.25-20. 4. USE LIQUID-TIGHT FITTING FOR TERMINAL-BLOCK-ENCLOSURE CABLE ENTRY. 5. MOUNT AS SHOWN WITH BASE HORIZONTAL. 6. CERTIFICATIONS NOT SHOWN. FIGURE 15. ER-35KV Sensing Resistor. SE-330 Neutral-Grounding-Resistor Monitor 3.3 GROUND-FAULT CT Select and install a ground-fault CT that will provide the desired trip level. Typically, the CT-primary rating should be approximately equal to the NGR let-throughcurrent rating. This provides an appropriate GF TRIP LEVEL setting range and analog-output scaling. See Sections 2.1.2 and 2.9. Outline and mounting details for the EFCT- and SE-CS30-series current sensors are shown in Figs. 16, 17, and 18. Ground-fault-CT connections and the typical ground-fault-CT location are shown in Fig. 3. For SE-325 replacement applications, the existing CT200 current sensor will typically have to be replaced. However, where replacement is not necessary or possible, the CT200 can be connected to either the 1- or 5-A input. This CT has a 200:5 current ratio. If connected to the 1-A input, the ground-fault trip level will be a percentage of 40 A. See Section 2.1.2. The accuracy of a typical current sensor, including the CT200, decreases below 5% of its current rating. CTprimary current-injection testing is recommended to verify trip levels below 5% of the CT-primary rating. See Section 9.4. Littelfuse Startco current sensors are designed for use at low levels and respond linearly to 2% current rating. NOTE: The current-sensor insulation class is of no consequence if its secondary is grounded and the conductors through its window are insulated for the system voltage. Medium-voltage systems may require a bushing-type CT. Page 20 Rev. 10-K-090815 Page 21 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. 3. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. 4. RoHS COMPLIANT. 5. EN 60044-1 COMPLIANT. 121.0 (4.76) 121.0 (4.76) 20.5 (0.81) 56.0 (2.21) 46.0 (1.81) 30.0 (1.18) 80.0 (3.15) NOTE 2 M5 SCREWS TOP MOUNTING DETAIL 25.0 (0.98) 30.0 (1.18) EFCT-1 EARTH FA ULT CT 600 V CLASS, INSULATION CLASS A R R LR 53428 5.0 (0.20) Ø RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP 22.0 (0.87) EFCT - 1FC FLUX CONDITIONER (OPTIONAL) .0 82 23) . 3 ( 69. (2.7 8 5) 126.0 (4.96) US (5.43) 138.0 MAX C 5.5 (0.22) 110.0 (4.33) FRONT FIGURE 16. EFCT-1 Ground-Fault Current Sensor. 5.5 (0.22) 56.0 (2.21) SIDE Page 22 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 121.0 (4.76) 121.0 (4.76) 20.5 80.0 (3.15) 56.0 (2.21) 46.0 (1.81) 30.0 (1.18) (0.81) NOTE 3 M5 SCREWS TOP MOUNTING DETAIL 25.0 (0.98) (1.18) 30.0 SE-CS30-70 CURRENT SENSOR R R LR 53428 22.0 Ø 5.0 (0.20) RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP 5.5 110.0 5.5 (0.22) (4.33) (0.22) 56.0 (2.21) SIDE FRONT MOUNTING FOOT INSTALLATION TOOL 126.0 69. 8 (2.7 5) NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’). 3. MOUNTING SCREWS: M4 OR 8-32. DETAIL ‘A’ FIGURE 17. SE-CS30-70 Ground-Fault Current Sensor. (4.96) US (0.87) (5.43) 138.0 MAX C 4. RoHS COMPLIANT. 5. EN 60044-1 COMPLIANT. Page 23 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 68.0 (2.68) 34.0 (1.34) 68.0 (2.68) M4 OR 8-32 TAP 26.5 (1.04) 52.5 (2.07) 42.6 (1.68) 17.0 (0.67) MOUNTING DETAIL TOP (0.43) 110.0 MAX M5 SCREWS 25.0 (0.98) 26.5 (1.04) SE-CS30-26 CURRENT SENSOR R R LR 53428 US 4.0 (0.16) Ø 0 6. 2) .0 (1 7.0 2 RECESSED FOR 7-mm HEX NUT 3.0 (0.12) DEEP 58.0 (2.28) (0.87) 34.0 (1.34) 72.0 (2.83) C 5.0 (0.20) 5.0 (0.20) 52.5 (2.07) FRONT SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL ‘A’). MOUNTING FOOT INSTALLA TION TOOL 3. MOUNTING SCREWS: M4 OR 8-32. 4. RoHS COMPLIANT. 5. EN 60044-1 COMPLIANT. DETAIL ‘A’ 6. SE-CS30-26 SHOWN. FIGURE 18. EFCT-26 and SE-CS30-26 Ground-Fault Current Sensors. Page 24 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 30.0 (1.18) RESISTOR FAULT GROUND FAULT LEGEND PLATE NOTE 4 (0.59) X1 X2 22.5 (0.89) 15.0 43.5 (1.71) 25.0 (0.98) RESET 22.2 (0.87) DIA 17.3 (0.68) 29.9 (1.17) 36.6 (1.44) NOTES: LEGEND PLATES 1. TWO RED LED LIGHTS 24-120 VAC/DC, NOT POLARITY SENSITIVE. 36.6 (1.44) 30.0 MINIMUM (1.18) 29.9 (1.17) MOUNTING DETAIL PUSH BUTTON 2. YELLOW PUSH BUTTON 3 A @ 240 VAC - A600, 0.5 A @ 125 VDC - Q600. (1.57) 40.0 MINIMUM 43.5 14.9 (0.59) (1.71) PILOT LIGHTS 3. DIMENSIONS IN MILLIMETRES (INCHES). 4. ----- INDICATES CLEARANCE REQUIRED. 5. PANEL THICKNESS 1.0 TO 6.0 (0.04 TO 0.24). 6. NEMA 4X. FIGURE 19. RK-332 Remote Indication and Reset. 67.5 (2.657) 67.5 (2.657) 48.0 (1.890) 66.0 (2.598) R1.25(0.049) MAXIMUM TOP MOUNTING CUTOUT 100 60 40 ® 20 65.0 (2.559) 80 1. DIMENSIONS IN MILLIMETRES (INCHES). 71.0 (2.795) % NOTES: 0 PGA-0520 ANALOG % CURRENT METER FRONT FIGURE 20. PGA-0520 Analog Percent Current Meter. SIDE REAR Page 25 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 3.4 ISOLATED GROUND CONNECTION An isolated ground bed can prevent a ground potential rise (GPR) from being transferred to remote equipment. If the G terminals on the sensing resistor and the SE-330 are connected to an isolated ground, the SE-330 will be exposed to the GPR. If the GPR is greater than the terminal-block rating, the SE-330 must be isolated from station ground and precautions must be taken with the power supply and the trip contacts. See Technical Note RG-1 “NGR Monitoring with Isolated Ground Beds” at www.littelfuse.com/relayscontrols. A configuration which allows an SE-330 to be connected to station ground is shown in Fig. 21. The SE-330 monitors the series combination of the NGR and the two ground beds. This configuration is acceptable provided the series resistance of the NGR and the ground beds is within the NGR calibration range and groundbed- resistance changes remain within the trip range. See Section 6.1. TO SENSING RESISTOR TERMINAL N NEUTRAL NOTE 1 NGR L 22 23 K1 16 SE-330 PULSE 17 ENABLE C N NOTE 2 NOTES: 1. ALTERNATE NGR CONFIGURATION. 2. SET SWITCH S1 TO K1 = PULSING. FIGURE 22. Simplified Pulsing Connection. NEUTRAL ER-SERIES N SENSING RESISTOR STATION TRIP CIRCUIT 22 NGR 23 R STATION CONTROL SUPPLY 1 2 K1 L1 R L2/N G G 6 7 SE-330 3 STATION GROUND BUS STATION GROUND BED ISOLATED GROUND BED REMOTE GROUND FIGURE 21. Simplified Isolated-Ground Connection. 3.5 PULSING CONNECTION Set switch S1 to K1 = PULSING and use an external switch as shown in Fig. 22 to use relay K1 to control a pulsing contactor. Relays K2 and K3 can be used for tripping and can be configured in the fail-safe or nonfail-safe mode using the SE-MON330 software. SE-330 Neutral-Grounding-Resistor Monitor 4. DATA INTERFACES 4.1 SD CARD The SE-330 supports microSD™ data storage. The microSD™ card port is located on the front panel just below the USB port. The microSD™ card is used for long-term data logging of measured values and for firmware upgrades. 4.1.1 DATALOGGING When a microSD™ card is installed, the SE-330 looks for a directory called “Datalogging”. If this directory exists, data logging will automatically start after the card is indexed (indexing may take several minutes depending on the size of the card and the number of files). The log is updated every two seconds and it includes measured values, configuration parameters, and trip status. A new log file is created at the start of each day. If previous log files exist and the microSD™ card has less than 20 MB of free space, the oldest datalogging file will automatically be deleted before a new file is created. The red DIAGNOSTIC LED may indicate an SD Card error. See Section 5. Approximately 3 GB of data is generated per year of logging. 4.1.2 FIRMWARE UPGRADE Firmware upgrades are performed using a microSD™ card in conjunction with configuration switch S8. See Section 2.1.5.7. The SE-Flash software is not required. To upgrade the SE-330 firmware, insert a microSD™ card containing the firmware upgrade file (.S19 format) in the root directory of the SD card and set switch S8 to UPGRADE within 30 s of card installation. If S8 is switched to UPGRADE after 30 s, the upgrade process will not occur. If the microSD™ card is inserted after S8 is switched to UPGRADE, switch S8 to RUN and then back to UPGRADE. The SE-330 evaluates firmware upgrade files found in the root directory of the microSD™ card and uses the first valid file. Ensure that the DIAGNOSTIC LED is off before beginning the firmware upgrade process. The red DIAGNOSTIC LED blinks rapidly while the firmware upgrade is running and the SE-330 will restart when the upgrade is complete. If the upgrade is not successful, the DIAGNOSTIC LED will indicate an SD Upgrade Error. See Section 5. Set switch S8 back to RUN for normal operation. If a firmware upgrade fails, the existing firmware is not overwritten. A record of the upgrade can be found in “upgrade_log_<SN>.txt” on the microSD™ card. This file is updated each time an upgrade is performed. NOTE: The included microSD™ card has a temperature rating of -25 to 85°C (-13 to 140°F). For applications colder than -25°C (-13°F), use an Industrial-Grade microSD™ card. NOTE: The maximum recommended microSD™ card storage capacity is 4 GB. Page 26 Rev. 10-K-090815 4.2 USB INTERFACE Use the SE-MON330 software (version 3.5 or newer) to access set-points, measured values, and trip records through the mini B USB interface located on the front panel. The following data can be viewed: Front-panel and configuration-switch settings Neutral voltage and neutral current Resistance change from the calibrated value Trip status Trip records, 100 date and time stamped Firmware version and serial number The following values can be viewed and adjusted: Ground-fault trip setting (when front-panel GF Trip Level is set to MEM) K2 ground-fault relay output operating mode K3 resistor-fault relay output operating mode Clock settings Trip records can be cleared Remote calibration Resistor-fault trip time Resistor-fault trip level Geo-magnetic filter Ensure the real-time clock is set to the correct time prior to normal operation. Trip records and on-board datalogging information include date and time readings from the clock. Refer to the SE-MON330 software help file. 4.3 NETWORK COMMUNICATIONS The optional communications interfaces include a single CAN port and dual Ethernet ports supporting cable, fiber(1), or both cable and fiber. Protocols include: DeviceNet over CAN (ordering option 1) EtherNet/IP over cable or fiber (ordering options 3, 4, and 5) Modbus TCP over cable or fiber (ordering options 3, 4, and 5) IEC 61850 over cable or fiber (ordering options 6, 7, and 8) Refer to the appropriate SE-330 communicationsinterface manual for details. (1) Uses the plug-in style SC connector. Page 27 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 5. TROUBLESHOOTING PROBLEM DIAGNOSTIC LED FLASH CODE(1) POWER LED off. POWER LED flashes. Calibration-Error Trip DIAGNOSTIC LED flash code 1L-1S-1L Remote Trip DIAGNOSTIC LED flash code 1L-2S-1L A/D-Converter-Error Trip DIAGNOSTIC LED flash code 1L-4S-1L SD Card DIAGNOSTIC LED flash code 1L-5S-1L Watchdog Trip DIAGNOSTIC LED flash code 1L-6S-1L CPU Trip DIAGNOSTIC LED flash code 1L-7S-1L Non-Volatile Memory Error Trip DIAGNOSTIC LED flash code 1L-8S-1L SD Upgrade Error DIAGNOSTIC LED flash code 1L-9S-1L DIAGNOSTIC LED = Solid Red Pressing RESET does not clear trips. UNIT HEALTHY relay K4 momentarily changes state. SOLUTION Check if supply voltage is present on terminals 1 and 2. If present, an overvoltage may have caused the power supply to shutdown. Cycle supply voltage. If POWER LED remains off, return unit for repair. A power-supply overload has occurred. Cycle supply voltage. If problem persists, consult Littelfuse Startco. The total resistance of the NGR and sensing-resistor circuit is outside the calibration range. Verify that switch S5 is set to match the resistance of the sensing resistor, check the resistance of the NGR, and verify the sensing-resistor circuit. See Section 9.2 for sensing-resistor tests. Repeat the calibration procedure after the open or shorted condition has been corrected. GF LED(2): No Change, RF LED(2): ON, K1:Trip The SE-330 was tripped by a signal from network communications. Press RESET to clear the trip. GF LED(2): ON, RF LED(2): ON, K1:Trip An A/D-converter error was detected. Press RESET to clear the trip. If the problem persists, consult Littelfuse Startco. GF LED(2): No Change, RF LED(2): ON, K1:Trip SD Card is full or a write error occurred. Delete files or use a different microSD™ card. GF LED(2): No Change, RF LED(2): No Change, K1:No Change If this diagnostic was caused during an attempt to upgrade the firmware, follow this alternate process: - remove supply from SE-330 - insert a microSD card containing the firmware upgrade file in the root directory of the SD card - power on the SE-330 - set switch S8 to UPGRADE within 30 s - the upgrade should continue as described in Section 4.1.2 A watchdog trip results in a processor reset. During reset, UNIT HEALTHY relay K4 will be de-energized. After a reset, UNIT HEALTHY relay K4 will be energized. Press RESET to clear the trip. If the problem persists, consult Littelfuse Startco. GF LED(2): ON, RF LED(2): ON, K1:Trip The CPU has detected a system fault. Press RESET to clear the trip. GF LED(2): ON, RF LED(2): ON, K1:Trip An error was detected in the Non-Volatile Memory. Press RESET to clear the trip. If the problem persists, consult Littelfuse Startco. GF LED(2): ON, RF LED(2): ON, K1:Trip An error occurred during the flash-memory upgrade procedure. Ensure that the firmware upgrade file is correct or use a different microSD™ card. GF LED(2): No Change, RF LED(2): No Change, K1:No Change SE-330 processor failed to start. Cycle supply. If problem persists, consult Littelfuse Startco. K1: De-energized. Trip condition is still present. Locate and correct. The RESET button is disabled if remote-reset terminals 15 and 16 are connected. Replace shorted remote-reset switch or issue Reset command from the communications network. Occurs when processor is reset. Page 28 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor PROBLEM No analog-output current. DIAGNOSTIC LED FLASH CODE(1) SOLUTION The output at terminals 19 and 20 requires a voltage source. See Fig. 2 for analog-output connections. See Section 9.3 for the analog-output tests. NOTES: (1) L = long pause, S = short flash. (2) When LED is on, corresponding indication relay is energized when in the non-fail-safe mode or de-energized when in the fail-safe mode. SE-330 Neutral-Grounding-Resistor Monitor 6. TECHNICAL SPECIFICATIONS 6.1 SE-330 Supply: Option 0 .............................. 30 VA, 120 to 240 Vac (+10, -45%), 50/60 Hz; 20 W, 110 to 250 Vdc (+10, -25%) Option 2 .............................. 20 W, 48 Vdc (+50, -25%); 35 VA, 48 Vac (+10, -45%), 50/60 Hz Power-Up Time ........................ 3 s at 120 Vac AC Measurements .................... Discrete Fourier Transform. 16 samples per cycle, 50 or 60 Hz Resistor-Fault Circuit: Neutral-To-Ground Voltage Trip Levels(1): ER-600VC or ER-5KV .....20; 60; 100; 130; 170; 200; 340; 800; 1,200; 1,700; 2,000 Vac ER-15KV to ER-35KV .....100; 300; 500; 650; 850; 1,000; 1,700; 4,000; 6,000; 8,500; 10,000 Vac Accuracy .............................10% of setting 3 dB Frequency Response: S6 = 50 Hz .......................25 to 85 Hz S6 = 60 Hz .......................30 to 90 Hz NGR Calibration Range: ER-600VC, ER-5KV, or ER-5WP ..............................0 to 2 k ER-15KV to ER-35KV ......0 to 10 k Trip Resistance, VN = 0: ER-600VC, ER-5KV, or ER-5WP: Range(5) ............................250 to 750- change ± 200 Default .............................500- change ER-15KV to ER-35KV: Range(5) ............................1.25 to 3.75-k change ± 1 k Default .............................2.5-k change Neutral-To-Ground DC-Voltage Rejection: ER-600VC, ER-5KV, or ER-5WP ..............................25 Vdc ER-15KV to ER-35KV ......125 Vdc Trip Time ...............................12 to 60 s ± 1 s Trip Hold-Off Level ..............5% of CT-Primary Rating Trip Mode ..............................Latching/Non-Latching Ground-Fault Circuit: Trip Level ..............................2, 4, 6, 8, 10, 20, 40, 60, 80, 100% of CT-Primary Rating or 2 to 100% using MEM parameter Trip Time ...............................0.1, 0.2, 0.3, 0.4, 0.5, 0.7, 1.0, 2.0, 3.0, 5.0, 10.0 s Page 29 Rev. 10-K-090815 Trip-Level Accuracy ............. Maximum of 1% of CTPrimary Rating or 3% of Setting(2) Trip-Time Accuracy ............. 10% of Setting, 20 ms minimum 3 dB Frequency Response: S6 = 50 Hz .......................... 25 to 85 Hz S6 = 60 Hz .......................... 30 to 90 Hz Maximum CT lead resistance: EFCT & SE-CS30.............. 5 Other CT’s .......................... Consult CT Curve. CT-Input Burden: 5-A Input ............................ < 0.01 1-A Input ............................ < 0.05 EFCT Input......................... < 10 Thermal Withstand: 1-A and 5-A Inputs: Continuous ...................... 2 x CT Rating 1-Second .......................... 20 x CT Rating EFCT Input: Continuous ...................... 10 x CT Rating 1-Second .......................... 25 x CT Rating Measurement Range ............. 25 x CT-Primary Rating Trip Mode.............................. Latching/Non-Latching Pulsing Circuit: Pulse Period ........................... 1.0 to 3.0 s, 0.2-s increments Duty Cycle............................. 50% Time Accuracy ...................... 10% of Setting Trip/Pulsing Relay K1 Contacts: Configuration ........................ N.O. (Form A) Operating Mode .................... Fail-Safe or Non-Fail-Safe CSA/UL Contact Ratings ..... 8 A resistive 250 Vac, 5 A resistive 30 Vdc Supplemental Contact Ratings: Make/Carry 0.2 s ................ 30 A Break: dc....................................... 75 W resistive, 35 W inductive (L/R = 0.04 s) ac ....................................... 2,000 VA resistive, 1,500 VA inductive (PF = 0.4) Subject to maximums of 8 A at 250 Vac, 5 A resistive at 30 Vdc, and 0.4 A resistive at 250 Vdc. GF (K2) and RF (K3) Relay Contacts: Configuration ........................ N.O. and N.C. (Form C) Operating Mode(5) ................. Non-Fail-Safe or Fail-Safe CSA/UL Contact Ratings ..... 8 A resistive 250 Vac, 8 A resistive 30 Vdc Supplemental Contact Ratings: Make/Carry 0.2s ................. 20 A Break: dc....................................... 50 W resistive, 25 W inductive (L/R = 0.04 s) SE-330 Neutral-Grounding-Resistor Monitor ac .......................................2,000 VA resistive, 1,500 VA inductive (PF = 0.4) Subject to maximums of 8 A at 250 Vac, 8 A resistive at 30 Vdc, and 0.4 A resistive at 150 Vdc. Unit Healthy Output K4 (Option 0): Configuration.........................N.O. (Form A) Operating Mode.....................Closed when Healthy Ratings ...................................100 mA, 250 V (ac or dc) Closed Resistance..................30 to 50 Unit Healthy Output K4 (Option 1): Configuration.........................N.C. (Form B) Operating Mode.....................Open when Healthy Ratings ...................................100 mA, 250 V (ac or dc) Closed Resistance..................25 to 50 Auto-reset time ............................2.8 s maximum 4-20-mA Analog Output: Type .......................................Self Powered and Loop Powered Range .....................................4 to 22 mA Loop Voltage .........................8 to 36 Vdc Load .......................................500 (maximum with 24-Vdc supply) Isolation .................................120 Vac Parameter ...............................NGR Current, 20 mA = CT Primary Current USB Communications: Baud Rate ..............................12 Mbit/s Protocol ..................................USB Device Connector...............................Mini B SD Memory Card: Type .......................................Standard Grade Form Factor ...........................microSD™(3) Format ....................................FAT32 Capacity .................................512 MB to 4 GB (microSD™ and microSDHC™) Operating Temperature: Standard Grade (Included)............................-25 to 85°C (-13 to 140°F) Industrial Grade ..................-40 to 85°C (-40 to 140°F) Terminal-Block Ratings ..............10 A, 300 Vac, 12 AWG (2.5 mm2) PWB Conformal Coating ............MIL-1-46058 qualified, UL QMJU2 recognized Mounting Configurations ............Panel Mount and Optional Surface Mount Dimensions: Height ......................................213 mm (8.4”) Width .......................................99 mm (3.9”) Page 30 Rev. 10-K-090815 Depth ....................................... 132 mm (5.2”) Shipping Weight ......................... 2.0 kg (4.4 lb) Environment: Operating Temperature ......... -40 to 60°C (-40 to 140°F) Storage Temperature ............. -55 to 80°C (-67 to 176°F) Humidity................................ 85% Non-Condensing IP Rating ................................ IP30 Surge Withstand .......................... ANSI/IEEE C37.90.11989 (Oscillatory and Fast Transient) EMC Tests: Verification tested in accordance with EN 60255-26:2013. Radiated and Conducted Emissions ........................... CISPR 11:2009, CISPR 22:2008, EN 55022:2010 Class A Current Harmonics and Voltage Fluctuations .......... IEC 61000-3-2 and IEC 61000-3-3 Class A Electrostatic Discharge ....... IEC 61000-4-2 ± 6 kV contact discharge (direct and indirect) ± 8 kV air discharge Radiated RF Immunity ....... IEC 61000-4-3 10 V/m, 80-1,000 MHz, 80% AM (1 kHz) 10 V/m, 1.0 to 2.7 GHz, 80% AM (1 kHz) Fast Transient ..................... IEC 61000-4-4 Zone B ± 2 kV (power supply port), ± 1 kV (all other ports) Surge Immunity .................. IEC 61000-4-5 Zone B ± 1 kV differential mode ± 2 kV common mode Conducted RF Immunity .... IEC 61000-4-6 10 V, 0.15-80 MHz, 80% AM (1 kHz) Magnetic Field Immunity ............................ IEC 61000-4-8 50 Hz and 60 Hz 30 A/m and 300 A/m SE-330 Neutral-Grounding-Resistor Monitor Power Frequency(4) ............. IEC 61000-4-16 Zone A: differential mode 100 Vrms Zone A: common mode 300 Vrms 1 MHz Burst ....................... IEC 61000-4-18 ± 1 kV differential mode (line-to-line) ± 2.5 kV common mode Voltage Interruption ........... IEC 61000-4-11, IEC 61000-4-29 0% for 10, 20, 30, 50 ms (dc) 0% for 0.5, 1, 2.5, 5 cycles (60 Hz) IEC 61000-4-17 Level 4, 15% of rated dc value Certification .................................CSA, Canada and USA R C LR 53428 US UL Listed Australia N11659 CE, European Union FCC To:CSA C22.2 No. 14 Industrial Control Equipment UL 508 Industrial Control Equipment UL 1053 Ground Fault Sensing and Relaying Equipment CE Low Voltage Directive IEC 61010-1:2010 (3rd Edition) FCC CFR47, Part 15, Subpart B, Class A – Unintentional Radiators Compliance .............................. RoHS Pending NOTES: (1) See sensing resistor specifications for applicable voltage limits. (2) Accuracy included for EFCT-x and SE-CS30-x current sensors only. (3) microSD™ and microSDHC™ are trademarks of SD-3C, LLC. (4) Remote-reset and pulse-enable wiring is limited to 10 m (32’). (5) This value can only be modified using SE-MON330 software. See Section 4.2. Page 31 Rev. 10-K-090815 6.2 SENSING RESISTORS Environment: Operating Temperature ......... -40 to 60°C (-40 to 140°F) Storage Temperature ............. -55 to 80°C (-67 to 176°F) Extended Operating Temperature .......................... -55 to 60°C (-67 to 140°F)(1) ER-600VC: Maximum Voltage .............. 600 Vac Maximum Current .............. 30 mA Resistance ........................... 20 k Thermal: 420 Vac............................ Continuous 600 Vac............................ 6 minutes on, 60 minutes off Shipping Weight ................... 300 g (0.7 lb) ER-5KV: Maximum Voltage .............. 2,500 Vac Maximum Current .............. 125 mA Resistance ........................... 20 k Thermal ................................. Continuous Torque: Terminal N: 10-32 Insert ..................... 5.6 N-m (50 in-lb) Others .............................. 9.0 N-m (80 in-lb) Shipping Weight ................... 5.0 kg (11 lb) ER-5WP: Maximum Voltage .............. 2,500 Vac Maximum Current .............. 125 mA Resistance ........................... 20 k Thermal ................................. Continuous Torque: Terminal N: 10-32 Insert ..................... 5.6 N-m (50 in-lb) Others .............................. 9.0 N-m (80 in-lb) Shipping Weight ................... 5.0 kg (11 lb) ER-15KV: Maximum Voltage .............. 8,400 Vac Maximum Current .............. 84 mA Resistance ........................... 100 k Thermal: 8,400 Vac............................ 1 minute on, 120 minutes off 1,900 Vac............................ Continuous Torque (Terminal N)............. 9.0 N-m (80 in-lb) Shipping Weight ................... 5.0 kg (11 lb) SE-330 Neutral-Grounding-Resistor Monitor ER-25KV: Maximum Voltage .............. 14,400 Vac Maximum Current .............. 144 mA Resistance ........................... 100 k Thermal: 14,400 Vac ..........................1 minute on, 120 minutes off 2,500 Vac ............................Continuous Torque (Terminal N) .............9.0 N-m (80 in-lb) Shipping Weight....................20 kg (44 lb) ER-35KV: Maximum Voltage .............. 22,000 Vac Maximum Current .............. 220 mA Resistance ........................... 100 k Thermal: 22,000 Vac ..........................1 minute on, 120 minutes off 3,000 Vac ............................Continuous Torque (Terminal N) .............9.0 N-m (80 in-lb) Shipping Weight....................40 kg (88 lb) Certification.............................. CSA, Canada and USA R C LR 53428 US UL Listed CE, European Union NOTES: (1) Electrical specifications have been verified at a Littelfuse lab. 6.3 CURRENT SENSORS Environment: Operating Temperature .........-40 to 60°C (-40 to 140°F) Storage Temperature .............-55 to 80°C (-67 to 176°F) EFCT-1: Current Ratio ...................... 5:0.05 A Insulation ............................ 600-V Class Window Diameter............... 82 mm (3.2”) Shipping Weight ................. 0.9 kg (2.0 lb) Certifications ...................... CSA, UL, CE Compliance ......................... RoHS, IEC 60044-1 Extended Operating Temperature...........................-55 to 60°C (-67 to 140°F)(1) Supplemental Specifications: Trip Level Accuracy: ≤ 1 A ..........................1% of CT-Primary Rating > 1 A ..........................3% of CT-Primary Rating Page 32 Rev. 10-K-090815 EFCT-26: Current Ratio....................... 5:0.05 A Insulation ............................ 600-V Class Window Diameter ............... 26 mm (1.0”) Shipping Weight ................. 0.45 kg (1.0 lb) Certifications ....................... CSA, UL, CE Compliance ......................... RoHS, IEC 60044-1 Extended Operating Temperature ...........................-55 to 60°C (-67 to 140°F)(1) Supplemental Specifications: Trip Level Accuracy: ≤ 1 A ..........................1% of CT-Primary Rating > 1 A ..........................3% of CT-Primary Rating SE-CS10-2.5: Current Ratio....................... 1,000:5 A Insulation ............................ 600-V Class Window Diameter ............... 63 mm (2.5”) Shipping Weight ................. 0.7 kg (1.5 lb) Certifications ....................... CE Compliance ......................... IEC 60044-1 SE-CS30-26: Current Ratio....................... 30:0.05 A Insulation ............................ 600-V Class Window Diameter ............... 26 mm (1.0”) Shipping Weight ................. 0.45 kg (1.0 lb) Certifications ....................... CSA, UL, CE Compliance ......................... RoHS, IEC 60044-1 Extended Operating Temperature ...........................-55 to 60°C (-67 to 140°F)(1) SE-CS30-70: Current Ratio....................... 30:0.05 A Insulation ............................ 600-V Class Window Diameter ............... 70 mm (2.7”) Shipping Weight ................. 1.2 kg (2.5 lb) Certifications ....................... CSA, UL, CE Compliance ......................... RoHS, IEC 60044-1 Extended Operating Temperature ...........................-55 to 60°C (-67 to 140°F)(1) CT200: Current Ratio....................... 200:5 A Insulation ............................ 600-V Class Window Diameter ............... 56 mm (2.2”) Shipping Weight ................. 1 kg (2.2 lb) Certifications ....................... CSA, UL Compliance ......................... RoHS Extended Operating Temperature ...........................-55 to 60°C (-67 to 140°F)(1) NOTES: (1) Electrical specifications have been verified at a Littelfuse lab. SE-330 Neutral-Grounding-Resistor Monitor 7. ORDERING INFORMATION SE-330- - K4 Contact: 0 N.O. UNIT HEALTHY Contact 1 N.C. UNIT HEALTHY Contact Options: 0 No Options Network Communications:(1) 0 None 1 DeviceNet™ 3 Ethernet (Dual RJ45) 4 Ethernet (SC Fiber & RJ45) 5 Ethernet (Dual SC Fiber) 6 IEC 61850 (Dual RJ45) 7 IEC 61850 (SC Fiber & RJ45) 8 IEC 61850 (Dual SC Fiber) Supply: 0 Universal ac/dc Supply 2 48 Vdc Supply NOTE: Please refer to the SE-330 Product Change Notice (PCN) document for updated ordering information and new revision details, available at www.littelfuse.com/se-330. NOTE: The SE-330-SMA Surface Mount Adapter is available as an accessory only. Sensing Resistors: ER-600VC ............................ For system voltages up to 1 kVac ER-5KV ................................ For system voltages up to 5 kVac ER-5WP ................................ For system voltages up to 5 kVac, weather protected ER-15KV .............................. For system voltages up to 15 kVac ER-25KV .............................. For system voltages up to 25 kVac ER-35KV .............................. For system voltages up to 35 kVac Current Sensors: EFCT-1 ..................................Current Sensor, 5-A-primary rating, 82-mm (3.2”) Window, 6 m (19.5’) of 22 AWG (3.3 mm2) shielded cable included EFCT-26 ................................Current Sensor, 5-A-primary rating, 26-mm (1.0”) Window, 6 m (19.5’) of 22 AWG (3.3 mm2) shielded cable included SE-CS10-2.5 ....................... Current Sensor, 30-Aprimary rating, 63 mm (2.5”) window Page 33 Rev. 10-K-090815 SE-CS30-26 ........................ Current Sensor, 30-A-primary rating, 26-mm (1.0”) window SE-CS30-70 ...........................Current Sensor, 30-A-primary rating, 70-mm (2.7”) window CT200 ................................. Current Sensor, 200-A-primary rating, 56-mm (2.2”) window 5SHT-101-E...........................Current Sensor, 100-A-primary rating, 40-mm (1.6”) window 5SHT-151-E...........................Current Sensor, 150-A-primary rating, 40-mm (1.6”) window 5SHT-500-E...........................Current Sensor, 50-A-primary rating, 40-mm (1.6”) window 7SHT-301-E...........................Current Sensor, 300-A-primary rating, 64-mm (2.5”) window 7SHT-401-E...........................Current Sensor, 400-A-primary rating, 64-mm (2.5”) window Accessories: RK-332 ................................... Remote Indication and Reset, includes two 120-V pilot lights, a reset push button, and legend plates SE-IP65CVR-G ...................... Hinged transparent cover, IP65 SE-MRE-600 .......................... Moisture-resistant enclosure for ER-600VC PGA-0520 ............................... Percent Analog Meter SE-330-SMA .......................... Surface Mount Adapter AC300-MEM-00 .................... Industrial-Grade microSD™ Card Software:(2) SE-MON330 Software........... SE-330 Data-Display Program for PC, version 3.5 or newer NGR Monitor Set-Point Assistant ................. Setting Guide NOTES: (1) Profibus models only available on legacy SE-330. (2) Available at www.littelfuse.com/relayscontrols. SE-330 Neutral-Grounding-Resistor Monitor 8. WARRANTY The SE-330 Neutral-Grounding-Resistor Monitor is warranted to be free from defects in material and workmanship for a period of five years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco’s option) repair, replace, or refund the original purchase price of an SE-330 that is determined by Littelfuse Startco to be defective if it is returned to Littelfuse Startco, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse Startco does not warrant products repaired or modified by non-Littelfuse Startco personnel. 9. TEST PROCEDURES NOTE: Ensure the real-time clock is set. See Section 4.2. 9.1 RESISTOR-FAULT TESTS Perform tests with system de-energized and supply voltage applied to the SE-330. 9.1.1 CALIBRATION AND OPEN TEST Test Equipment: 20-k and 100-k, 1/4-watt, 1% calibration resistors (calibration resistors are supplied with SE-330). Procedure: Remove connections to terminals 6 and 7. Connect the 20-k resistor to terminals 6 and 7. Set switch S5 to the 20-k position. Perform calibration as per Section 2.2. The CALIBRATED LED should be on. Press RESET. Remove the 20-k resistor and wait for the resistor-fault trip time. PASS: The SE-330 should trip on resistor fault. Connect the 100-k resistor to terminals 6 and 7. Set switch S5 to the 100-k position. Perform calibration as per Section 2.2. The CALIBRATED LED should be on. Press RESET. Remove the 100-k resistor and wait for the resistorfault trip time. PASS: The SE-330 should trip on resistor fault. NOTE: Resistor-fault-trip reset can take up to one second. 9.1.2 VOLTAGE TEST Test Equipment: 0 to 120 Vac voltage source, multimeter, and ER sensing resistor. Page 34 Rev. 10-K-090815 NOTE: Use an isolation transformer if the test-voltage source does not provide dc continuity for the SE-330 resistancemeasuring circuit. NOTE: Applying the test voltage to the R and G terminals will damage the SE-330 and the ER sensing resistor. The VN TRIP LEVEL is the trip voltage at terminal N, not terminal R. Procedure: Connect the ER sensing resistor to the SE-330 and calibrate the SE-330. Disconnect the wire from sensing-resistor terminal N. A resistor-fault trip will occur. Set the voltage source to 0 V. Connect the voltage source between sensing resistor N and G terminals. Set the VN TRIP LEVEL (VAC) to 20. Press RESET. The RESISTOR FAULT TRIP LED should be off. Increase the test voltage to 25 Vac for 20-k sensors or 120 Vac for 100-k sensors and wait for the resistorfault trip time. PASS: The SE-330 should trip on RESISTOR FAULT. A time-delayed ground-fault trip follows the resistor-fault trip if neutral voltage persists after the resistor fault. For legacy units with firmware revision 6 or less, this does not apply. 9.2 SENSING-RESISTOR TEST Test Equipment: Multimeter. Procedure: Disconnect the sensing resistor. Measure the resistance between sensing-resistor terminals R and N. PASS: Resistance should be between 19.6 and 20.4 k for 20-k sensing resistors. Resistance should be between 98 and 102 k for 100-k sensing resistors. Measure the resistance between sensing-resistor terminals R and G in both directions. PASS: Resistance should be greater than 10 M in both directions. 9.3 ANALOG-OUTPUT TEST Test Equipment: Multimeter with a mAdc scale. Procedure: Connect the 4–20-mA output as a self-powered output as shown in Fig. 3. Measure the current from terminal 20 to terminal 21. PASS: With no CT current, the analog output should be 4 mA. Output is linear to 20 mA. Output is 20 mA when CTprimary current is equal to the CT-primary rating. Page 35 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor 9.4 GROUND-FAULT PERFORMANCE TEST To meet the requirements of the National Electrical Code (NEC), as applicable, the overall ground-fault protection system requires a performance test when first installed. A written record of the performance test is to be retained by those in charge of the electrical installation in order to make it available to the authority having jurisdiction. A test-record form is provided for recording the date and the final results of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel: a) USING SE-400 NEUTRAL TO SE-330 TO SENSING RESISTOR TERMINAL N 3 5 N 8 REMOTE INPUT 9 OP2 OP1 12 L1 L2 1 SE-400 RMT1 RMT2 b) USING SE-100T NEUTRAL TO SE-330 TO SENSING RESISTOR TERMINAL N c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths. d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled ground-fault current. To simulate ground-fault current, use CT-primary current injection (does not apply for bushing-type CT’s). Fig. 23a shows a test circuit using an SE-400 Ground-Fault-Relay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 120% of GF TRIP LEVEL. Fig. 23b shows a test circuit using an SE-100T Ground-Fault-Relay Tester. The SE-100T provides a test current of 0.65 or 2.75 A for testing 0.5- and 2.0A trip levels. Inject the test current through the current-sensor window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and re-test until the proper reaction is verified. 11 L a) Evaluate the interconnected system in accordance with the overall equipment manufacturer’s detailed instructions. b) Verify proper installation of the ground-fault current sensor. Ensure the cables pass through the groundfault-current-sensor window. This check can be done visually with knowledge of the circuit. The connection of the current-sensor secondary to the SE-330 is not polarity sensitive. NGR NGR C LO L L1 HI N L2 REMOTE TEST 0.65 A 2.75 A SE-100T RMT FIGURE 23. Ground-Fault-Test Circuits. TABLE 3. GROUND-FAULT-TEST RECORD DATE TEST RESULTS e) Record the date and the results of the test on the attached test-record form. NOTE: Do not inject test current directly into CT-input terminals 8, 9, 10, and 11. Retain this record for the authority having jurisdiction. NOTE: For accurate trip-time measurement, the fault current should not be re-applied for the time defined by the GF TRIP TIME setting to allow the trip accumulator to initialize. SE-330 Neutral-Grounding-Resistor Monitor MANUAL RELEASE DATE APPENDIX A SE-330 REVISION HISTORY HARDWARE REVISION MANUAL (REVISION NUMBER REVISION ON PRODUCT LABEL) September 8, 2015 10-K-090815 June 22, 2015 10-J-062215 May 20, 2015 10-I-052015 March 3, 2015 10-H-030315 July 7, 2014 10-G-070714 14 April 14, 2014 10-F-041414 13 January 8, 2014 10-E-010814 November 29, 2013 10-D-112913 October 8, 2013 10-C-100813 September 12, 2013 10-B-091213 August 30, 2013 10-A-083013 MANUAL REVISION HISTORY REVISION 10-K-090815 SECTION 4 Section 4.1.2 updated. SECTION 5 SD card diagnostic troubleshooting updated. REVISION 10-J-062215 SECTION 2 Section 2.1.7 added. SECTION 4 SD Card approximate yearly data logging usage updated. SE-MON330 software version updated. SECTION 6 Resistor-fault trip level ranges added. REVISION 10-I-030315 SECTION 4 SD Card storage capacity updated. SECTION 6 SD Card storage capacity specification updated. REVISION 10-H-030315 SECTION 2 Sections 2.1.6 and 2.1.7 added. SECTION 4 Section 4.2 new features added. SECTION 6 Resistor-fault circuit trip time updated. REVISION 10-G-070714 SECTION 6 Added CE, C-Tick, and FCC information. REVISION 10-F-041414 APPENDIX A Hardware revision updated. Page 36 Rev. 10-K-090815 FIRMWARE REVISION 2.52 15 2.50 2.40 12 2.31 2.30 2.20 11 2.10 10A 2.08 2.07 10 2.07 SE-330 Neutral-Grounding-Resistor Monitor REVISION 10-E-010814 SECTION 6 Extended operating temperatures added to all sensing resistors and SE-CS30 current sensors. REVISION 10-D-112913 SECTION 6 CE added to sensing resistors. SECTION 7 Ordering information updated. REVISION 10-C-100813 SECTION 2 Section 2.8 updated. SECTION 4 Real Time Clock note added in Section 4.2. SECTION 5 LED and relay status added to troubleshooting solutions. SECTION 7 Ordering information updated. REVISION 10-B-091213 APPENDIX A Hardware revision updated. REVISION 10-A-083013 SECTION 1 Faceplate updated. New features added. SECTION 2 Communications options updated. Configuration switches updated. Indication relays explanation added. Non-volatile-memory error added. SECTION 3 Connection drawing updated. SECTION 4 Section heading changed to Data Interfaces. Updated with microSD™ and USB interfaces. Upgrade procedure added. SECTION 5 Non-volatile-memory error added. Switch S8 diagnostic LED error removed. SECTION 6 Ground-fault circuit trip level updated. USB communications specifications added. Resistor-fault accuracy changed. microSD™ memory card specifications added. SECTION 7 Ordering information updated. SE-330-SMA Surface Mount Adapter is now listed as an accessory only. APPENDIX A Added revision history. Page 37 Rev. 10-K-090815 SE-330 Neutral-Grounding-Resistor Monitor Page 38 Rev. 10-K-090815 HARDWARE REVISION HISTORY HARDWARE REVISION 15 RTC circuit updated. HARDWARE REVISION 14 Added CE and C-Tick compliance. HARDWARE REVISION 13 Reduced ESD sensitivity of front-panel dials. HARDWARE REVISION 12 Improved Fiber Ethernet support. HARDWARE REVISION 11 Reduced ESD sensitivity of USB and SD card connectors. HARDWARE REVISION 10A Update to RTC circuit. HARDWARE REVISION 10 Updated SE-330 platform to include USB and microSD™ interfaces, programmable trip level (MEM) feature, and ability to add future options. Real-time clock added. Added dual cable and fiber Ethernet ports. FIRMWARE REVISION HISTORY FIRMWARE REVISION 2.52 Improved compatibility with Internet Explorer™ web browser. FIRMWARE REVISION 2.50 Added support for adjustable resistor-fault trip level. Web page functionality re-enabled for Ethernet options. FIRMWARE REVISION 2.40 Added support for geo-magnetic filter. Added support for 12 to 60 s resistor-fault trip time. Improved log file descriptions. IEC 61850 GOOSE network input support now always enabled. Improved compatibility for Modbus TCP. Web page disabled for Ethernet options. This will be enabled in a future firmware release. IP setting changes for Ethernet options now require power cycle to take effect. FIRMWARE REVISION 2.31 SD Card and USB diagnostic events no longer cause a trip. FIRMWARE REVISION 2.30 Remote calibration feature added. FIRMWARE REVISION 2.20 Added support for EtherNet/IP protocol. IED name now reported correctly through IEC 61850 interface. EtherNet/IP and Modbus communications card LED status updated. Hardware version viewable in the SE-MON330 software and through the Modbus and IEC 61850 servers. FIRMWARE REVISION 2.10 Added support for IEC 61850 and DeviceNet protocols. FIRMWARE REVISION 2.08 Added support for communications options. FIRMWARE REVISION 2.07 Updated firmware to include USB and microSD™ interfaces, datalogging, and firmware update via microSD™. K2 and K3 indication relays can be configured for fail-safe or non-fail-safe operation. Trip records increased to 100 with date and time stamping.