GLC110 Safety Certificates

File E135803
Vol. 1
Sec. 44
and Report
Page 1
Issued:
Revised:
1999-09-01
2006-01-04
DESCRIPTION
PRODUCT COVERED:
USR - Switching Power Supply, Model SP1683 and Model GLC110 followed by
suffixes -12, -15, -24, -212, -215, or -524, may or may not be followed by -L
or -LC and/or –XXX, where XXX may be any number from 001 thru 999.
ELECTRICAL RATINGS:
Input:
100-240 V ac, 50/60 Hz, 3.1 A
Outputs:
Maximum output power is 75 W with convection
cooling; 110 W with airflow specified below.
0 CFM 26 CFM
75 Watts Max
MODEL Output
GLC110-12
GLC110-15
GLC110-24
GLC110-212
#2
GLC110-215
#2
GLC110-524
#2
SP1683
110 Watts Max
Volts Amps Amps
#1
#1
#1
#1
-12
#1
−15
#1
+5
#1
12 6.3
15 5.0
24 3.2
+12
6.3
2.5
3.0
+15
6.3
2.5
3.0
+24
3.2
1.5
2.0
12 6.3
9.1
7.3
4.6
9.1
7.3
4.6
9.1
ENGINEERING CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE'S USE):
This product is for use only in (or with) complete equipment where the
acceptability of the combination is determined by Underwriters Laboratories
Inc.
USR/CNR indicates investigation to the U.S. and Canadian (Bi-National)
Standard for Safety of Information Technology Equipment – Safety – Part 1:
General Requirements, CSA C22.2 No. 60950-1-03 * UL 60950-1, First Edition.
The equipment is:
power system.
For building in, Class I (earthed), for use on a TN
File E135803
Vol. 1
Sec. 44
and Report
Page 2
Issued:
Revised:
1999-09-01
2006-01-04
Conditions of Acceptability - When installed in the end-use equipment,
the following are among the considerations to be made:
1.
This component has been judged on the basis of the required spacings in
the Standard for Information Technology Equipment – Safety – Part 1:
General Requirements, CSA C22.2 No. 60950-1-03 * UL 60950-1, First
Edition, which would cover the component itself if submitted for
unrestricted listing.
2.
All secondary output circuits are SELV and are not hazardous energy
levels.
3.
The terminals and connectors have not been evaluated for field wiring.
4.
The power supply shall be properly bonded to the main protective
earthing termination in the end product as this unit was investigated
for Class I construction as defined in UL 60950-1. An additional
evaluation shall be made if the power supply is intended for use in
other than Class I equipment.
5.
Bonding terminals provided on this equipment have not been evaluated as
protective earthing terminals.
6.
Magnetic device transformer T3 employs an OBJY2 electrical insulation
system designated Class F. Inductor T2 employs bobbin material rated
150°C in the thickness used.
7.
The equipment has been evaluated for use in a Pollution Degree 2
environment.
8.
The component shall be installed in compliance with the enclosure,
mounting, spacing, casualty markings and segregation requirements of the
end-use application.
9.
This power supply was evaluated for use in a 50°C ambient. An
additional evaluation should be made if the power supply is intended to
be used in an elevated ambient.
File E135803
Vol. 1
Sec. 44
and Report
Page 3
Issued:
Revised:
1999-09-01
2006-01-04
CONSTRUCTION DETAILS:
See Section General for additional details.
Operating/Instruction/Safety Manual - Provided with each unit.
ILL. 2.
See
Printed Wiring Board - See Section General for details.
General appearance of trace layout same as in ILL. 1.
Board rated
130°C.
Model Differences - All models are the same, except for output ratings
and differences in secondary, low voltage circuitry. Suffix L indicates
chassis is provided. Suffix LC indicates a cover and chassis is provided.
Models followed by the suffix –XXX represents value added configurations
that have no impact on safety.
Model SP1683 is identical to GLC110-12 except that it uses an alternate
PWB that provides an alternate pinout on the secondary output connector, and
the value for the Line-to-Ground capacitors C3 and C4 is reduced to 1500 pF.