GPFC110 Safety Certificates

File E135803
Project 99SC41107
February 23, 1999
REPORT
ON
COMPONENT - POWER SUPPLIES,
INFORMATION TECHNOLOGY EQUIPMENT,
INCLUDING ELECTRICAL BUSINESS EQUIPMENT
Condor D C Power Supplies Inc.
Oxnard, California
Copyright  1999
Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above named company to
reproduce this Report provided it is reproduced in its entirety.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce that portion of this Report consisting of this Cover Page through
Page 2.
File E135803
Vol. 1
Sec. 42
and Report
Page 1
Issued:
Revised:
02-23-99
07-25-02
DESCRIPTION
PRODUCT COVERED:
*
USR/CNR - Switching Power Supply, Models SP1749, and GPFC110-X-C
where X represents the output voltage which may be any number from 5 thru
48. Suffix –C indicates optional cover is provided.
ELECTRICAL RATINGS:
Input: 100-240 V ac, 50/60 Hz, 2.3 A.
MODEL
GPFC110-12
GPFC110-12.6
GPFC110-15
GPFC110-24
GPFC110-28
GPFC110-48
GPFC110-5
*
Input:
Output:
12 V
12.6 V
15 V
24 V
28 V
48 V
5.1 V
Outputs:
No Cover
0 LFM
100 LFM
6.7 A
9.2 A
6.3 A
8.7 A
5.3 A
7.3 A
3.4 A
4.6 A
2.9 A
3.9 A
1.7 A
2.3 A
ll.O A
15.O A
With Cover
0 LFM
100 LFM
6.3 A
9.2 A
6.0 A
8.7 A
5.O A
7.3 A
3.1 A
4.6 A
2.7 A
3.9 A
1.6 A
2.3 A
9.O A
15.O A
100-240 V ac, 50/60 Hz, 2.3 A (GPFC110 Series)
Ratings for output voltages 5 thru 11
75 W max., with a min. of 100 LFM, with or without cover.
55 W max., no airflow, without cover.
45 W max., no airflow, with cover.
Ratings for output voltages 12 thru 48
110 W max., with a min. of 100 LFM, with or without cover.
80 W max., no airflow, without cover.
75 W max., no airflow, with cover.
Input:
Output:
110-240 V ac, 50/60 Hz, 2.3 A (SP1749)
6.4 V dc @ 13.0 A (0 LFM) at 50 °C ambient
or 6.4 V dc @ 14 A (0 LFM) at 45 °C ambient
or 6.4 V dc @ 14 A (50 LFM) at 50 °C ambient.
File E135803
Vol. 1
Sec. 42
and Report
*Page 1A
Issued:
New:
02-23-99
07-25-02
ENGINEERING CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE'S USE):
This product is for use only in (or with) complete equipment where
the acceptability of the combination is determined by Underwriters
Laboratories Inc.
USR/CNR indicates investigation to the U.S. and Canadian
(Bi-National) Standard for Safety of Information Technology Equipment, CSA
C22.2 No. 60950
UL 60950, Third Edition.
The equipment is for building in, Class I (earthed), for use on a TN
power system.
File E135803
Vol. 1
Sec. 42
and Report
Page 2
Issued:
Revised:
02-23-99
07-25-02
Conditions of Acceptability - When installed in the end-use
equipment, the following are among the considerations to be made:
1.*
This component has been judged on the basis of the required spacings
in the Standard for Information Technology Equipment, Including
Electrical Business Equipment, CSA C22.2 No. 60950
UL 60950, Third
Edition, which would cover the component itself if submitted for
unrestricted listing.
2.
A11 secondary output circuits are SELV and are not hazardous energy
levels.
3.
The terminals and connectors have not been evaluated for field
wiring.
4.*
The power supply shall be properly bonded to the main protective
earthing termination in the end product as this unit was investigated
for Class I construction as defined in CSA C22.2 No.60950
UL 60950.
An additional evaluation shall be made if the power supply is
intended for use in other than Class I equipment.
5.
Bonding terminals provided on this equipment have not been evaluated
as protective earthing terminals.
6.
Magnetic device transformer T2 employs an OBJY2 electrical insulation
system designated Class F. Inductor T1 employs bobbin material rated
130°C in the thickness used.
7.
The equipment has been evaluated for use in a Pollution Degree 2
environment.
8.
The component shall be installed in compliance with the enclosure,
mounting, spacing, casualty markings and segregation requirements of
the end-use application.
9.
This power supply was evaluated for use in a 50°C ambient. An
additional evaluation should be made if the power supply is intended
to be used in an elevated ambient.