3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols MPS DEVICENET INTERFACE REVISION 12-C-061015 QUICK SETUP Use the OPI to access the Setup | Hardware | Network Comms menu. Set the Network ID for the device. Set the Baud Rate as DN 125K, DN 250K, or DN 500K. Select the DeviceNet producing assembly (input) from the DeviceNet Produce menu and the DeviceNet consuming assembly (output) from the DeviceNet Consume menu. Select DeviceNet from the Network Type menu. The assembly types can also be set using parameter 472 and 473 via configuration software. Configure the scanner’s polled connections for the selected assembly sizes. The scanner may issue a configuration warning if an I/O size other than the default is used. Disregard the warning. Copyright 2015 Littelfuse Startco All rights reserved. Document Number: PM-1131-EN Printed in Canada MPS DeviceNet Interface This page intentionally left blank. Page i Rev. 12-C-061015 Page ii Rev. 12-C-061015 MPS DeviceNet Interface DISCLAIMER TABLE OF CONTENTS SECTION PAGE 1 2 General ................................................................. 1 DeviceNet Interface ............................................. 1 2.1 Network Settings ................................................... 1 2.2 Product Manual Notes ........................................... 1 2.3 Communication Status Display ............................. 2 2.4 DeviceNet LED Indication.................................... 2 2.5 Network Errors...................................................... 2 2.6 Configuration Using RSNetWorx ......................... 2 3 DeviceNet Objects ............................................... 2 3.1 Identity Object ...................................................... 3 3.2 Message Router ..................................................... 3 3.3 DeviceNet Object .................................................. 4 3.4 DeviceNet Connection Object............................... 5 3.5 Assembly Object ................................................... 7 3.6 Control Supervisor Object................................... 11 3.7 Overload Class 0x2C .......................................... 16 3.8 Set Point Class 0x64 ........................................... 18 3.9 Acceleration Class 0x65...................................... 23 3.10 Digital Input Class 0x66 ..................................... 24 3.11 Analog I/O Class 0x67 ........................................ 26 3.12 RTD Module Class 0x68..................................... 27 3.13 RTC Class 0x69 .................................................. 34 3.14 User Register Class 0x6A ................................... 35 3.15 Data Logging Class 0x6B ................................... 36 Appendix A MPS DeviceNet EDS Files ...................... 38 Appendix B MPS DeviceNet Interface Revision History ........................................................................... 39 LIST OF FIGURES FIGURE 1 PAGE Outline Drawing ...................................................... 1 Specifications are subject to change without notice. Littelfuse Startco. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. MPS DeviceNet Interface This page intentionally left blank. Page iii Rev. 12-C-061015 Page 1 Rev. 12-C-061015 MPS DeviceNet Interface 1. GENERAL Network Type to None. Set Network ID to the slave number. Set the Baud Rate to DN 125K, DN 250K or DN 500K. Select the producing assembly instance using the DeviceNet Produce menu and the consuming assembly instance using the DeviceNet Consume menu. See Section 3.5 for assembly details. Once the changes have been made, select DeviceNet from the Network Type menu. This document describes the DeviceNet features supported by the MPS. The MPS supports Explicit and Polled I/O. It does not support the Unconnected Message Manager (UCMM). The MPS requires supply voltage connected to L1 and L2 to power the control unit and 24-Vdc supply voltage to power the isolated DeviceNet transceiver circuit. The DeviceNet transceiver circuit requires 70 mA @ 24-Vdc from the DeviceNet power supply. 2.2 PRODUCT MANUAL NOTES Appendix E, Register 383: Baud rate selections (Type T17 in Appendix F) includes DeviceNet selections 5:125 kb, 6:250 kb, and 7: 500 kb. Appendix E, Register 385: Network ID range is 0 to 63. Values greater than 63 will be forced to 63. 2. DEVICENET INTERFACE 2.1 NETWORK SETTINGS DeviceNet settings are located in the Setup Hardware Network Comms menu. Prior to making changes to network settings via the OPI, it is recommended to set the 33 32 31 5A 1A A 30 29 28 27 26 5A 1A B PHASE CURRENT 24 23 22 25 5A 1A C 20 V N 21 5A 1A EFCT EARTH LEAKAGE 19 V A 18 V B 17 V C VOLTAGE DeviceNet C D C V A R A V + N AI N H N L 5 4 3 2 1 I/O MODULE AN IN IRIG 2 COMM 4 PTC V + - + + HS - V0 + 62 61 60 59 58 57 56 55 54 53 52 62 61 60 59 58 57 56 55 54 53 52 S 0 2 H V PTC 4 IRIG AN IN V COMM I/O MODULE MOTOR PROTECTION SYSTEM CONTROL UNIT P OW E R TRIP ALARM ERROR OPERATOR INTERFACE RESET AN OUT COMM S H 35 36 37 39 40 + + FIGURE 1. Outline Drawing. 24 VDC SOURCE 41 42 DIGITAL INPUTS C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I 43 44 45 46 47 48 49 50 51 MPS-CTU Page 2 Rev. 12-C-061015 MPS DeviceNet Interface 2.3 COMMUNICATION STATUS DISPLAY The DeviceNet communication status can be viewed using the Metering Comm State menu. This menu indicates the connection state as ONLINE or OFFLINE. The last communication error is also displayed. The MPS can be programmed to trip if the connection is OFFLINE. The MPS is OFFLINE when there are no connections established and ONLINE when at least one connection is established. 2.4 DEVICENET LED INDICATION Two LED’s labelled MODULE STATUS (MS) and NETWORK STATUS (NS) are located on the left side of the control unit as shown in Fig. 1. The MS LED is green when the DeviceNet driver is operational. If this LED is off, verify that DeviceNet is selected from the Setup Hardware Network Comms Network Type menu. The NS LED is off when the MPS is the only device on the network. It flashes green when the MPS is physically connected to a network containing other devices but has no established communication connections. It is solid green when a Polling or Explicit Messaging connection is established. It flashes red when one or more connections have timed out. It is solid red if a Duplicate MAC ID or Bus-off error has occurred. Red LED indication requires a restart of the DeviceNet driver. This is done by unplugging and re-connecting the DeviceNet connector, cycling supply voltage or by using the Setup Hardware Network Comms Network Type menu. Select None to shut down the driver and then select DeviceNet to restart. ERROR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 DEVICENET ERROR CODES DESCRIPTION Receive Overrun Transmit Overrun CAN Overrun IO Send Duplicate MAC Bus Sense MAC Was Set ID Reset 0 ID Reset 1 Bus Off CAN ESET CAN ERESET Explicit Timeout IO Timeout IO Delete No CAN Interface 2.6 CONFIGURATION USING RSNETWORX Use the EDS Wizard to register the eds file. The device will register as a Motor Starter named MPS. Select device properties to view Device Parameters. When there is a request to upload from device, select this option. This will load the present configuration from the MPS. 3. DEVICENET OBJECTS (In Order of Class Number) The module supports the following objects: CLASS 2.5 NETWORK ERRORS The MPS can be configured to trip or alarm on a network error using the Setup Hardware Network Comms Network Error menu, or by using attribute 0x64 of the DeviceNet object. The Network Error set point sets the action to be taken when the module is off line. Selections are Trip, Alarm, Trip and Alarm, or No Trip or Alarm. Network errors can originate from network watchdog timeouts or the network hardware in the MPS. The last error code is displayed in the Metering Comm State menu. The error codes are listed in the following table. 0x01 0x02 0x03 0x04 0x05 0x29 0x2C 0x64 0x65 0x66 0x67 0x68 0x69 0x6A (1) DESCRIPTION Identity (1) Message Router (1) DeviceNet (1) Assembly (1) Connection (1) Control Supervisor (1) Overload (1) Set Point Acceleration Digital Input Analog I/O RTD Module RTC Clock User Register Conformance tested using DeviceNet Conformance Test Software Version A-17. Protocol Page 3 Rev. 12-C-061015 MPS DeviceNet Interface 3.1 IDENTITY OBJECT Identity Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Identity Class (1), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DEFAULT, MINIMUM, MAXIMUM 1 1 DESCRIPTION Revision of this object. Maximum number of instances. DATA TYPE UINT UINT Identity Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modify the specified attribute. Reset: Performs reset services based on the parameter. No Parameter or Parameter = 0: The DeviceNet driver is reset with the existing MAC ID and baud rate. Parameter = 1: The MAC ID is set to 63 and the baud rate is set to 125 kb. The MPS will then perform a reset that emulates cycling control power. Identity Class (1), Instance (1) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 Vendor ID Get 2 3 4 Device Type Product Code Revision Get Get Get 5 Status Get 6 Serial Number Get 7 Product Name Get PARAM 100 (0x64) 467 Revision Get 101 (0x65) 468 System Name Get/Set 102 (0x66) 469 Password Get/Set 3.2 MESSAGE ROUTER No attributes supported for this object. DESCRIPTION Identification of each vendor by number. Motor Starter Platform Type Major revision must match the EDS value. Summary Status of the Device Serial Number Human Readable Identification Revision of Firmware 100 = 1.00 22 characters. Only 20 significant. 22 characters. Only 4 significant. DEFAULT, MINIMUM, MAXIMUM 691 22 201 4.100 0, 0, 255 N/A, 0, 999999999 “Startco MPS” N/A, 100, N/A “Startco MPS” “1111” DATA TYPE COMM REGISTER UINT UINT UINT A2 02 C6 C6 WORD 0 UDINT 2 SHORT_ STRING UINT 1 SHORT_ STRING SHORT_ STRING 600 590 Page 4 Rev. 12-C-061015 MPS DeviceNet Interface 3.3 DEVICENET OBJECT DeviceNet Object Class Services Get_Attribute_Single: Returns contents of specified attribute. DeviceNet Class (3), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 Revision Get DESCRIPTION Revision of the DeviceNet object class. Definition upon which the implementation is based. DEFAULT, MINIMUM, MAXIMUM 1 DATA TYPE UINT DeviceNet Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modify specified attribute. Allocate_Master/Slave_Connection_Set: Release_Master/Slave_Connection_Set: DeviceNet Class (3), Instance (1) Attributes ATTRIBUTE NAME SERVICES 1 2 MAC ID Baud Rate Get/Set Get/Set 3 Buss-Off Interrupt Get/Set 4 Buss-Off Counter Get/Set 5 Get Get/Set Get/Set ATTRIBUTE NUMBER DEVICENET PARAMETER 100 (0x64) 470 Allocation Information Net Trip Action 101 (0x65) 471 Net Alarm Action DESCRIPTION Node Address The baud rate of the device: 0 = 125 kb 1 = 250 kb 2 = 500 kb Define Processing of BOI 0 = Hold CAN in Reset 1 = Automatic CAN Reset Set to 0 on powerup or when ID Reset is used. In both cases, existing connections are lost. Number of times CAN went to the bus-off state. Writing any value clears the counter. Count held at 255. Master/Slave Allocation Indication Trip Action taken on communication error. 0 = Disable 1 = Trip1 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 Action taken on communication error. 0 = Disable 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 DEFAULT, MINIMUM, MAXIMUM 63, 0, 63 0, 0, 2 USINT USINT 0, 1, 0 BOOL 0, 0, 255 USINT Array 0, 0, 7 BYTE, USINT UINT 0, 0, 7 UINT DATA TYPE Page 5 Rev. 12-C-061015 MPS DeviceNet Interface 3.4 DEVICENET CONNECTION OBJECT Connection Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modify specified attribute. DeviceNet Connection Class (5), Instance (0) Attributes ATTRIBUTE NUMBER DEVICENET PARAMETER 1 ATTRIBUTE NAME SERVICES Revision Get 100 (0x64) 472 Polled Cons ID Get/Set 101 (0x65) 473 Polled Prod ID Get/Set (1) (2) DESCRIPTION Revision of this Connection Object Class. Specifies output assembly ID. (1) 0 = None (Default) 1 = Basic Overload (0x02) 2 = Basic Motor Starter (0x03) 3 = Extended Contactor (0x04) 4 = Extended Motor Starter (0x05) Specifies input assembly ID. (2) 0 = None (Empty EPATH) 1 = Basic Overload (0x32) 2 = Extended Overload (0x33) 3 = Basic Motor Starter (0x34) 4 = Extended Motor Starter 1 (0x35) 5 = Extended Motor Starter 2 (0x36) (Default) 6 = Status/Meters/RTD's (0x64) 7 = Status/Meters (0x65) 8 = Status (0x66) 9 = User Registers (0x67) DEFAULT, MINIMUM, MAXIMUM 1 UINT 0, 0, 4 UINT 5, 0, 9 UINT DATA TYPE Can also be set using Class 5, Instance 2, Attribute 16 path. See 3.5 for byte sizes. Can also be set using Class 5, Instance 2, Attribute 14 path. See 3.5 for byte sizes. Connection Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modify specified attribute. Delete: Delete specified connection instance. Reset: Reset the connection instance. DeviceNet Connection Class (5), Explicit Connection Instance (1) Attributes ATTRIBUTE NAME SERVICES 1 State Get 2 Instance Type Get 3 Get 4 Transport Class Trigger Produced Cnxn ID 5 Consumed Cnxn ID Get 6 Initial Comm Characteristics Get ATTRIBUTE NUMBER DEVICENET PARAMETER Get DESCRIPTION State of the Object 0 = Nonexistent 1 = Configuring 3 = Established 4 = Timed out 5 = Deferred Delete Indicates either IO or messaging connection. Defines behavior of the connection. Placed in CAN Identifier field when the connection transmits. CAN Identifier Field value that denotes message to be received. Defines the Message Group(s) across which productions and consumptions associated with this Connection occur. DEFAULT, MINIMUM, MAXIMUM 1, 0, 5 USINT 0, 0, 0 USINT 0x83 BYTE DATA TYPE UINT UINT BYTE Page 6 Rev. 12-C-061015 MPS DeviceNet Interface DeviceNet Connection Class (5), Explicit Connection Instance (1) Attributes (Continued) ATTRIBUTE NUMBER DEVICENET PARAMETER 7 ATTRIBUTE NAME Produced Connection Size Consumed Connection Size Expected Packet Rate Watchdog Timeout Action 8 9 12 (0x0C) 13 (0x0D) 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) SERVICES Get Get Get/Set Get/Set Produced Connection Path Length Produced Connection Path Consumed Connection Path Length Consumed Connection Path Get Production Inhibit Time Get/Set Get Get Get DESCRIPTION Maximum number of bytes transmitted across this connection. Maximum number of bytes received across this connection. Defines timing (ms) associated with this connection. Resolution is 10 ms. Defines how to handle inactivity/watchdog timeouts: 1 = Auto Delete 3 = Deferred Delete Number of bytes in the produced_connection_path length attribute. Application Object producing data on this connection. Number of bytes in the consumed_connection_path length attribute. Specifies the Application Object(s) that are to receive the data consumed by this Connection Object. Defines minimum time (ms) between new data production. DEFAULT, MINIMUM, MAXIMUM 254 UINT 254 UINT 2500, 0, 65535 1, 1, 3 Set to 1 or 3 UINT DATA TYPE USINT 0 UINT {} EPATH 0 UINT {} EPATH 0 UINT DeviceNet Connection Class (5), Polled I/O Connection Instance (2) Attributes ATTRIBUTE NAME SERVICES 1 State Get 2 Instance Type Get 3 Get 4 Transport Class Trigger Produced Cnxn ID 5 Consumed Cnxn ID Get 6 Initial Comm Characteristics Get 7 Produced Connection Size Get 8 Consumed Connection Size Get Maximum number of bytes received across this connection. 9 Expected Packet Rate Watchdog Timeout Action Get/Set Defines timing (ms) associated with this connection. Defines how to handle inactivity/watchdog timeouts: 0 = Transition to Time Out 1 = Auto Delete 2 = Auto Reset ATTRIBUTE NUMBER 12 (0x0C) DEVICENET PARAMETER Get Get DESCRIPTION State of the object: 0 = Nonexistent 1 = Configuring 3 = Established 4 = Timed Out Indicates either IO or messaging connection: 0 = Explicit Message 1 = I/O Message Defines behavior of the connection. Placed in CAN Identifier field when the Connection Transmits. CAN Identifier Field value that denotes message to be received. Defines the Message Group(s) across which productions and consumptions associated with this connection occur. Maximum number of bytes transmitted across this connection. DEFAULT, MINIMUM, MAXIMUM 0, 0, 4 USINT 1, 0, 1 USINT 0x83 BYTE DATA TYPE UINT UINT BYTE Defined by Assembly Instance Defined by Assembly Instance 0, 0, 65535, N/A, N/A 0, 0, 0 UINT UINT UINT USINT Page 7 Rev. 12-C-061015 MPS DeviceNet Interface DeviceNet Connection Class (5), Polled I/O Connection Instance (2) Attributes (Continued) ATTRIBUTE NUMBER DEVICENET PARAMETER 13 (0x0D) ATTRIBUTE NAME SERVICES Produced Connection Path Length Produced Connection Path Consumed Connection Path Length Consumed Connection Path 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) Production Inhibit Time Get Get/Set Get Get/Set Get/Set DESCRIPTION Number of bytes in the produced_connection_path length attribute. Symbolic notation. Application Object producing data on this connection. Number of bytes in the consumed_connection_path length attribute. Symbolic notation. Specifies the Application Object(s) that are to receive the data consumed by this Connection Object. Defines minimum time (ms) between new data production. DEFAULT, MINIMUM, MAXIMUM 3, 3, 3 UINT 62 33 36 EPATH 3 UINT {} EPATH 0 UINT DATA TYPE 3.5 ASSEMBLY OBJECT Assembly Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Assembly Class (4), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DEFAULT, MINIMUM, MAXIMUM 1 0x67 DESCRIPTION Revision of this object. Maximum instance of assembly. DATA TYPE UINT UINT Assembly Object Instance Services Get_Attribute_Single: Returns assembly-instance data. Applies to both output and input instances. Set_Attribute_Single: Set assembly instance data. Applies to output instances only. Service not supported for input instances. The following static input instances are supported and can be selected by setting parameter 473 to the desired ID: PRODUCING DATA SIZE IN SYMBOLIC IO INSTANCE DESCRIPTION BYTES CONNECTION PATH ASSEMBLY ID 6 7 8 9 1 2 3 4 5 (1) 100 (0x64) 101 (0x65) 102 (0x66) 103 (0x67) 50 (0x32) 51 (0x33) 52 (0x34) 53 (0x35) 54 (0x36) Status/Meters/RTDs Status/Meters Status User Registers (1) Basic Overload Extended Overload Basic Motor Starter Extended Motor Starter 1 Extended Motor Starter 2 (Default) 244 132 6 32 1 1 1 1 1 62 36 34 62 36 35 62 36 36 62 36 37 62 33 32 62 33 33 62 33 34 62 33 35 62 33 36 Requires configuration of the User Defined Registers defined by parameters 451 to 466 and set via RSNetWorx or the User Registers menu. SIZE IS FIXED AT 32 BYTES. See Assembly Class 4, Instance 0x67, Attribute 3. The following static output instance are supported and can be selected by setting parameter 472 to the desired ID: CONSUMING SYMBOLIC IO DATA SIZE IN INSTANCE (1) DESCRIPTION BYTES CONNECTION PATH ASSEMBLY ID 1 2 3 4 2 (0x02) 3 (0x03) 4 (0x04) 5 (0x05) Basic Overload Basic Motor Starter Extended Contactor Extended Motor Starter 1 1 1 1 62 30 32 62 30 33 62 30 34 62 30 35 Page 8 Rev. 12-C-061015 MPS DeviceNet Interface (1) Default is None. Assemblies are configured using attributes 0x64 and 0x65 of Class 5, or selected by setting the Produced and Consumed connection path attribute in the Polled I/O connection instance. Setting the path to empty (no data), will disable production or consumption and the corresponding connection size will be zero. Assemblies are accessed using Polled I/O or can be read using Explicit Messaging. For explicit messaging, the Class is 4, the Attribute is 3, and the Instance is the assembly instance number. INSTANCE SERVICES CLASS_INSTANCE_ ATTRIBUTE 0x02 0x03 0x04 0x05 0x32 0x33 0x34 0x35 0x36 0x64 0x65 0x66 0x67 Get/Set Get/Set Get/Set Get/Set Get Get Get Get Get Get Get Get Get 04_02_03 04_03_03 04_04_03 04_05_03 04_32_03 04_33_03 04_34_03 04_35_03 04_36_03 04_64_03 04_65_03 04_66_03 04_67_03 Assembly Class (4), Instance (0x64), Attribute (3) – Input Produced Connection Path = “62 36 34” BYTE (Low to High) DESCRIPTION 0, 1 2, 3 4, 5 6, 7 8, 9 10, 11 12, 13 14, 15 16, 17 18, 19 20, 21, 22, 23 24, 25, 26, 27 28, 29, 30, 31 32, 33, 34, 35 36, 37, 38, 39 40, 41, 42, 43 44, 45, 46, 47 48, 49, 50, 51 52, 53, 54, 55 56, 57, 58, 59 60, 61, 62, 63 64, 65, 66, 67 68, 69, 70, 71 72, 73, 74, 75 76, 77, 78, 79 80, 81, 82, 83 84, 85, 86, 87 88, 89, 90, 91 92, 93, 94, 95 96, 97, 98, 99 100, 101, 102, 103 104, 105, 106, 107 108 to 115 116 to 123 124 to 131 Trip and Alarm Status Motor Status Starter Status Digital Inputs Relay Outputs Message 0 Message 1 Message 2 Message 3 Message 4 Phase A Current (A) Phase B Current (A) Phase C Current (A) Ground-Fault Current (A) Vab (V) Vbc (V) Vca (V) Apparent Power (S) (kVA) Reactive Power (Q) (kVAR) Real Power (P) (kW) Power Factor (±1) Used Thermal Capacity (%) Analog Input (mA) Thermal Trend (%) Positive Sequence Current (pu) Negative Sequence Current (pu) Unbalance Current (pu) Frequency Negative Sequence Voltage (pu) Unbalance Voltage (pu) Motor Speed From Tach (RPM) Running Time (Seconds) kW Seconds kVA Seconds kVAR Seconds CLASS-INST-ATTR TYPE 29-01-90 29-01-91 29-01-92 29-01-93 29-01-94 29-01-98 29-01-99 29-01-9A 29-01-9B 29-01-9C 2C-01-90 2C-01-91 2C-01-92 2C-01-93 2C-01-94 2C-01-95 2C-01-96 2C-01-97 2C-01-98 2C-01-99 2C-01-9A 2C-01-9B 67-01-0D 2C-01-9C 2C-01-9D 2C-01-9E 2C-01-9F 2C-01-A0 2C-01-A1 2C-01-A2 65-01-0A 2C-01-A3 2C-01-A4 2C-01-A5 2C-01-A6 WORD WORD WORD WORD WORD UINT UINT UINT UINT UINT REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL ULINT ULINT ULINT Page 9 Rev. 12-C-061015 MPS DeviceNet Interface Assembly Class (4), Instance (0x64), Attribute (3) – Input (Continued) BYTE (Low to High) DESCRIPTION 132, 133, 134, 135 136, 137, 138, 139 140, 141, 142, 143 144, 145, 146, 147 148, 149, 150, 151 152, 153, 154, 155 156, 157, 158, 159 160, 161, 162, 163 164, 165, 166, 167 168, 169, 170, 171 172, 173, 174, 175 176, 177, 178, 179 180, 181, 182, 183 184, 185, 186, 187 188, 189, 190, 191 192, 193, 194, 195 196, 197, 198, 199 200, 201, 202, 203 204, 205, 206, 207 208, 209, 210, 211 212, 213, 214, 215 216, 217, 218, 219 220, 221, 222, 223 224, 225, 226, 227 228, 229, 230, 231 232, 233, 234, 235 236, 237, 238, 239 240, 241, 242, 243 Module 1 #1 Temperature (°C) Module 1 #2 Temperature (°C) Module 1 #3 Temperature (°C) Module 1 #4 Temperature (°C) Module 1 #5 Temperature (°C) Module 1 #6 Temperature (°C) Module 1 #7 Temperature (°C) Module 1 #8 Temperature (°C) Module 2 #1 Temperature (°C) Module 2 #2 Temperature (°C) Module 2 #3 Temperature (°C) Module 2 #4 Temperature (°C) Module 2 #5 Temperature (°C) Module 2 #6 Temperature (°C) Module 2 #7 Temperature (°C) Module 2 #8 Temperature (°C) Module 3 #1 Temperature (°C) Module 3 #2 Temperature (°C) Module 3 #3 Temperature (°C) Module 3 #4 Temperature (°C) Module 3 #5 Temperature (°C) Module 3 #6 Temperature (°C) Module 3 #7 Temperature (°C) Module 3 #8 Temperature (°C) Maximum Stator Temperature (°C) Maximum Bearing Temperature (°C) Maximum Load Temperature (°C) Maximum Ambient Temperature (°C) Assembly Class (4), Instance (0x65), Attribute (3) – Input Produced Connection Path = “62 36 35” Assembly definition is the same as Byte 0 to 131 of Assembly Instance 0x64. Use this for applications where RTD temperature protection is not used. Assembly Class (4), Instance (0x66), Attribute (3) – Input Produced Connection Path = “62 36 36” Assembly definition is the same as Bytes 0 to 5 of Assembly Instance 0x64. Use this assembly if network traffic must be minimized. CLASS-INST-ATTR TYPE 68-01-29 68-01-2A 68-01-2B 68-01-2C 68-01-2D 68-01-2E 68-01-2F 68-01-30 68-02-29 68-02-2A 68-02-2B 68-02-2C 68-02-2D 68-02-2E 68-02-2F 68-02-30 68-03-29 68-03-2A 68-03-2B 68-03-2C 68-03-2D 68-03-2E 68-03-2F 68-03-30 68-00-12 68-00-13 68-00-14 68-00-15 REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL Assembly Class (4), Instance (0x67), Attribute (3) Produced Connection Path = “62 36 37” This assembly is used to access any combination of sixteen user-defined registers. Assembly size is fixed at 32 bytes. User defined registers are programmed using the Setup Hardware Network Comms User Registers menu, or by explicit messaging to Class 0x6A via the configuration tool. Register values are defined in Appendix E of the MPS manual. Each comm register in Appendix E defines a 16-bit value. For 32-bit float type (DeviceNet REAL), only the first register of the pair needs too be entered. For example, to configure an assembly to read the first four RTD temperatures in RTD Module 1, enter register numbers 902, 904, 906, 908 in sequence. The first 16 bytes of the assembly will contain the RTD data and the other 16 bytes do not contain any valid data. Register definitions resulting in more than 32 bytes of data will be ignored. Scanner byte size must be set to 32 bytes in all cases. Overload/Starter Instances Instances 2 to 5 and 0x32 to 0x36 are assemblies containing attribute values from the Control Supervisor. Page 10 Rev. 12-C-061015 MPS DeviceNet Interface ASSEMBLY BIT Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 NAME CLASS NAME Faulted/Trip Warning Running 1 Running 2 Ready Control From Net Control Supervisor Control Supervisor Control Supervisor Control Supervisor Control Supervisor Control Supervisor Assembly Class (4), Instance (0x32), Attribute (3) – Input Produced Connection Path = “62 33 32” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved Assembly Class (4), Instance (0x33), Attribute (3) – Input Produced Connection Path = “62 33 33” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved Assembly Class (4), Instance (0x34), Attribute (3) – Input Produced Connection Path = “62 33 34” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved Assembly Class (4), Instance (0x35), Attribute (3) – Input Produced Connection Path = “62 33 35” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved CntrlfrmNet Ready Assembly Class (4), Instance (0x36), Attribute (3) – Input Produced Connection Path = “62 33 36” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved CntrlfrmNet Ready Assembly Class (4), Instance (0x02), Attribute (3) – Output Consumed Connection Path = “62 30 32” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved Assembly Class (4), Instance (0x03), Attribute (3) – Output Consumed Connection Path = “62 30 33” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved Assembly Class (4), Instance (0x04), Attribute (3) – Output Consumed Connection Path = “62 30 34” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved CLASS INSTANCE ATTRIBUTE 0x29 0x29 0x29 0x29 0x29 0x29 1 1 1 1 1 1 10 11 7 8 9 15 BIT 3 BIT 2 BIT 1 BIT 0 Reserved Reserved Reserved Faulted/ Trip BIT 3 BIT 2 BIT 1 BIT 0 Reserved Reserved Warning Faulted/ Trip BIT 3 BIT 2 BIT 1 BIT 0 Reserved Running1 Reserved Faulted/ Trip BIT 3 BIT 2 BIT 1 BIT 0 Reserved Running1 Warning Faulted/ Trip BIT 3 BIT 2 BIT 1 BIT 0 Running2 Running1 Warning Faulted/ Trip BIT 3 BIT 2 BIT 1 BIT 0 Reserved FaultReset Reserved Reserved BIT 3 BIT 2 BIT 1 BIT 0 Reserved FaultReset Reserved Run1 BIT 3 BIT 2 BIT 1 BIT 0 Reserved Reserved Run2 Run1 Page 11 Rev. 12-C-061015 MPS DeviceNet Interface Assembly Class (4), Instance (0x05), Attribute (3) – Output Consumed Connection Path = “62 30 35” BYTE BIT 7 BIT 6 BIT 5 BIT 4 0 Reserved Reserved Reserved Reserved BIT 3 BIT 2 BIT 1 BIT 0 Reserved FaultReset Run2 Run1 3.6 CONTROL SUPERVISOR OBJECT State Transition Diagram Start/Stop control can be performed using the control supervisor class attributes. The control supervisor issues commands to the MPS as shown in the state diagram. NOTES: Commands issued are only processed if the CtrlFromNet (Attribute 15) is 1. For this bit to be set, the following conditions must be met: 1) A starter type must be selected (Attribute 0x73). 2) MPS must be in REMOTE CONTROL - Default setting. 3) Network control must be in the remote group (Attribute 0x72) - Default setting. The starter-sequence state is given by Attribute 0x92. The user is responsible for setting Run1 and Run2 bits (Attributes 3 & 4) to zero when a stop or trip condition occurs. Control Supervisor Object Class Services Get_Attribute_Single: Returns contents of specified attribute. CAUTION: Run1 and Run2 in the Output Assembly are used in applications where DeviceNet controls starter operation. If a dual-control method is required, use Explicit Messaging commands via Class 0x29, Instance 1, Attribute 0x64. Control Supervisor Class (0x29), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT Page 12 Rev. 12-C-061015 MPS DeviceNet Interface Supervisor Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. Reset: Issues a STOP and transition to idle state. Supervisor Class (0x29), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES DESCRIPTION 3 4 7 8 9 10 (0x0A) 11 (0x0B) 12 (0x0C) 15 (0x0F) 157 158 159 160 161 162 163 164 165 Run 1 (1) Run 2 (1) Running 1 (1) Running 2 (1) Ready Faulted Warning Fault Rst Ctrl From Net Get/Set Get/Set Get Get Get Get Get Get/Set Get Run 1 input from master. Run 2 input from master. Starter Sequencer is running. Starter Sequencer is running. Starter is ready. One or more trips present. One or more alarms present. Reset issued on 0 1 transition. 1 = Network control enabled. A command “Set” will cause the requested command to be issued. A “Get” will read the last command. 0 = Stop 1 = Start 1 2 = Start 2 3 = Reset Trips 4 = Set RTC 5 = Clear Data Logging Records 6 = Clear Trips Counters 7 = Clear Energy Totals 8 = Clear Running Time 9 = Emergency I²t Reset 10 = Select Local-Input Ctrl 11 = Release Local-Input Ctrl 12 = Re-enable Temperature Protection Differential module enable. DIF Module Error trip action. 0 = Disable 1 = Trip1 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 DIF Module Error alarm action. 0 = Disable 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 Module error trip count (1) DEFAULT, MINIMUM, MAXIMUM 0, 0, 1 0, 0, 1 0, 0, 1 0, 0, 1 0, 0, 1 0, 0, 1 0, 0, 1 0, 0, 1 N/A BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL 0, 0, 12 USINT 0,0,1 0,0,7 UINT UINT 1277 1278 0,0,7 UINT 1279 UINT 1194 DATA TYPE COMM REGISTER Not applicable in Protection Only mode. 100 (0x64) 166 Command Get/Set 101 (0x65) 102 (0x66) 544 545 DIF Enable DIF Error Trip Action Get/Set Get/Set 103 (0x67) 546 DIF Error Alarm Action Get/Set 104 (0x68) 547 DIF Error Trip Count Reserved Get 105(0x69) Page 13 Rev. 12-C-061015 MPS DeviceNet Interface Supervisor Class (0x29), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 106 (0x6A) 167 Trip Action Get/Set 107 (0x6B) 168 # of OPI's Get/Set 108 (0x6C) 169 OPI Remote Get/Set 109 (0x6D) 170 OPI Control Get/Set 110 (0x6E) 171 OPI Local Get/Set 111 (0x6F) 112 (0x70) 172 173 OPI Trips RemGrpDig Get Get/ Set 113 (0x71) 174 RemGrpNet Get/Set 114 (0x72) 175 RemGrpOPI Get/Set 115 (0x73) 176 Starter Type Get/Set 116 (0x74) 117 (0x75) 118 (0x76) 119 (0x77) 177 178 179 180 Start Time Start Delay 1 Start Delay 2 Start Delay 3 Get/Set Get/Set Get/Set Get/Set DESCRIPTION OPI Loss Trip Action: 0 = Disable 1 = Trip1 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 Selects the number of OPI's connected to the control unit. 0 = Enable OPI to select REMOTE 1 = OPI cannot select REMOTE 0 = Enable OPI motor control 1 = Disable OPI motor control 0 = Enable OPI to select LOCAL 1 = OPI cannot select LOCAL Number of OPI comm trips. Bind digital start sources to the REMOTE group. 0 = Include in Group 1 = Do not Include in Group Bind OPI start sources to the REMOTE group. 0 = Include in Group 1 = Not in Group Bind Net start sources to the REMOTE group. 0 = Include in Group 1 = Not in Group Selects the starter type. 0 = Protection Only 1 = Full Voltage Non-Reversing 2 = Adjustable-Speed Drive 3 = Soft Start 4 = Full Voltage Reversing 5 = Two Speed * 6 = Reactor/Resistor Closed Transition 7 = Reactor/Resistor Open Transition 8 = Slip Ring 9 = Soft Start With Bypass 10 = Port Winding * 11 = Double Delta * 12 = Autotransformer 13 = Two Winding * 14 = Wye-Delta Open Trans. * 15 = Wye-Delta Closed Trans. * * Uses Full-Load Current 2 See Main Product Manual See Main Product Manual See Main Product Manual See Main Product Manual DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 DATA TYPE COMM REGISTER UINT 237 1, 0, 3 UINT 238 0, 0, 1 UINT 239 0, 0, 1 UINT 240 0, 0, 1 UINT 241 0, 0, 1 UINT UINT 1185 242 0, 0, 1 UINT 243 0, 0, 1 UINT 244 0, 0, 15 UINT 248 20, 0.1, 500 20, 0.1, 500 20, 0.1, 500 20, 0.1, 500 REAL REAL REAL REAL 249/250 251/252 253/254 255/256 Page 14 Rev. 12-C-061015 MPS DeviceNet Interface Supervisor Class (0x29), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 120 (0x78) 181 Backspin Enable Get/Set 121 (0x79) 122 (0x7A) 123 (0x7B) 182 183 184 Backspin Delay Sequence Trips Stop Count Get/Set Get Get 124 (0x7C) 125 (0x7D) 185 186 RY Status Trips Transfer Type Get Get/Set 126 (0x7E) 187 Transfer Level Get/Set 127(0x7F) 128 (0x80) 188 Local Start-OPI RY1 Function Get/Set Get/Set 129 (0x81) 130 (0x82) 131 (0x83) 132 (0x84) 133 (0x85) 134 (0x86) 135 (0x87) 136 (0x88) 137 (0x89) 138 (0x8A) 189 190 191 192 193 194 195 196 197 523 RY1 Mode RY2 Function RY2 Mode RY3 Function RY3 Mode RY4Function RY4 Mode RY5 Function RY5 Mode RY Pulse Time Get/Set Get/ Set Get/Set Get/ Set Get/Set Get/ Set Get/Set Get/ Set Get/Set Get/Set 144 (0x90) 198 TA Summary Get DESCRIPTION 0 = Backspin Timer Enabled 1 = Backspin Timer Disabled Backspin delay in seconds. Number of starter sequence trips Number of trips caused by STOP when starter type is set to Protection Only. Number of contactor status trips. Soft-start transfer type: 0 = Time Transfer 1 = Current Transfer Level in % FLA Local Start Source – OPI Function Assigned to Relay 1 0 = None 1 = Starter RLYA 2 = Starter RLYB 3 = Starter RLYC 4 = Starter RLYD 5 = Trip1 6 = Alarm1 7 = Aux 8 = Interlock 9 = Local 10 = Current Detected 11 = Run Mode 12 = Start Sequence Complete 13 = Thermal Lockout 14 = None 15 = Watchdog 16 = Trip3 17 =Alarm2 18 = Alarm3 19 = Trip1 Pulse 20 = Reduced OC 0 = Fail Safe, 1 = Non Fail Safe See Attribute 0x80 0 = Fail Safe, 1 = Non Fail Safe See Attribute 0x80 0 = Fail Safe, 1 = Non Fail Safe See Attribute 0x80 0 = Fail Safe, 1 = Non Fail Safe See Attribute 0x80 0 = Fail Safe, 1 = Non Fail Safe Specifies the duration of the trip pulse when the RY function is set to “Trip1 Pulse”. Trip, Alarm, Status Summary Bit 0: 1 = Trip (Trip1 or Trip3) Bit 1: 1 = Alarm (Alarm 1, 2, 3) Bit 2: 1 = Trip2 Bit 3: 1 = Interlocks Not Valid Bit 4: 1 = Start Lock Active Bit 5: 1 = Stop Input Active DEFAULT, MINIMUM, MAXIMUM 1, 0, 1 DATA TYPE COMM REGISTER UINT 257 REAL UINT UINT 258/259 1184 1186 UINT UINT 1148 260 1.25, 1.0, 3.0 0, 0, 1 0, 0, 18 REAL 261/262 UINT UINT 245 334 0, 0, 1 0, 0, 18 0, 0, 1 0, 0, 18 0, 0, 1 0, 0, 18 0, 0, 1 0, 0, 18 0, 0, 1 0.25, 0.05, 10 UINT UINT UINT UINT UINT UINT UINT UINT UINT REAL 335 336 337 338 339 340 341 342 343 344 WORD 1096 5, 0.1, 100 0, 0, 1 Page 15 Rev. 12-C-061015 MPS DeviceNet Interface Supervisor Class (0x29), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES DESCRIPTION 145 (0x91) 199 Motor Status Get 146 (0x92) 200 Starter Status Get 147 (0x93) 201 Digital Inputs Get 148 (0x94) 202 Relay Outputs Get Bit 0: 1 = I > Threshold Bit 1: 1 = 10% < I < 125% for 10 s Bit 2: 1 = Tach at Full Speed Bit 3: 1 = I > 120% FLA Bit 4: 1 = Temperature Bypassed 1 = Start 1 2 = Run 1 (Sequence Complete) 3 = Start 2 4 = Run 2 (Sequence Complete) 5 = Stop 6 = Backspin Timer Active Bit 0: IN1 Voltage Detected Bit 1: IN2 Voltage Detected Bit 2: IN3 Voltage Detected Bit 3: IN4 Voltage Detected Bit 4: IN5 Voltage Detected Bit 5: IN6 Voltage Detected Bit 6: IN7 Voltage Detected Bit 0: Relay 1 Energized Bit 1: Relay 2 Energized Bit 2: Relay 3 Energized Bit 3: Relay 4 Energized Bit 4: Relay 5 Energized 149..151 152 (0x98) 203 Reserved Trip/Alarm Msg 0 Get 153 (0x99) 204 Trip/Alarm Msg 1 Get 154 (0x9A) 205 Trip/Alarm Msg 2 Get 155 (0x9B) 206 Trip/Alarm Msg 3 Get 156 (0x9C) 207 Trip/Alarm Msg 4 Get Trip and Alarm FIFO. See Main Product Manual Appendix F T27. 255= No trip or alarm. Trip and Alarm FIFO. See Main Product Manual Appendix F T27. 255= No trip or alarm. Trip and Alarm FIFO. See Main Product Manual Appendix F T27. 255= No trip or alarm. Trip and Alarm FIFO. See Main Product Manual Appendix F T27. 255= No trip or alarm. Trip and Alarm FIFO. See Main Product Manual Appendix F T27. 255= No trip or alarm. DEFAULT, MINIMUM, MAXIMUM DATA TYPE COMM REGISTER WORD 1097 UINT 1098 WORD 1099 WORD 1100 UINT 1104 UINT 1105 UINT 1106 UINT 1107 UINT 1108 Page 16 Rev. 12-C-061015 MPS DeviceNet Interface 3.7 OVERLOAD CLASS 0x2C Overload Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Overload Class (0x2C), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT Overload Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modify specified attribute. Overload Class (0x2C), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 100 (0x64) 1 Trip Action Get/Set 101 (0x65) 2 Thermal Model Get/Set 102 (0x66) 3 Start Inhibit Get/Set 103 (0x67) 104 (0x68) 105 (0x69) 106 (0x6A) 107 (0x6B) 4 5 6 7 8 K-Factor LR Current LR Time Cold LR Time Hot Cooling Factor Get/Set Get/Set Get/Set Get/Set Get/Set 108 (0x6C) 9 Thermal Lock Level Get/Set 109 (0x6D) 110 (0x6E) 10 11 Overload Alarm Alarm Action Get/Set Get/Set 111 (0x6F) 12 V Connection Get/Set 112 (0x70) 13 CT Primary Get/Set 0 = Disable 1 = Trip1 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 0 = NEMA 1 = I²t Inhibits start if I²t < Thermal Lockout Level 0 = Enable 1 = Disable Used in I²t Algorithm Locked Rotor Current (x FLA) Locked Rotor Time Cold (s) Locked Rotor Time Hot (s) Multiples of Running Time Constant Thermal Reset/Inhibit Level per Unit Level where alarm occurs. 0 = Disable 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 Voltage Input Connection 0 = None 1 = 1PT 2 = 2PT 3 = 3PT CT Primary Rating (A) 113 (0x71) 14 EFCT Primary Get/Set EFCT Primary Rating (A) DESCRIPTION DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 DATA TYPE COMM REGISTER UINT 8 0, 0, 1 UINT 9 1, 0, 1 UINT 10 6, 1, 10 6, 1, 10 10, 0.2, 100 5, 0.2, 100 2, 0.1, 50 REAL REAL REAL REAL REAL 11/12 12/14 15/16 17/18 19/20 0.3, 0.1, 0.9 REAL 21/22 1.0, 0.5, 1.0 1, 0, 7 REAL UINT 23/24 25 0, 0, 3 UINT 209 100, 1, 5000 5, 1, 5000 REAL 210/211 REAL 212/213 Page 17 Rev. 12-C-061015 MPS DeviceNet Interface Overload Class (0x2C), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 114 (0x72) 15 Vin Rating Get/Set 115 (0x73) 16 Frequency Get/Set 116 (0x74) 17 FLA Rating 1 Get/Set Input Voltage at Rated System Voltage (kV) System Frequency 0 = 50, 1 = 60 Hz Full-Load Current #1 117 (0x75) 18 System Voltage Get/Set Line-to-Line Voltage (kV) 118 (0x76) 19 Sync Speed Get/Set 119 (0x77) 120 (0x78) 20 21 Service Factor FLA Rating 2 Get/Set Get/Set Motor Synchronous (RPM) Motor Service Factor Full-Load Current #2 121 (0x79) 122 (0x7A) 22 474 Trip Count Run-Mode Delay Get Get/Set 123(0x7B) 124(0x7C) 125(0x7D) 535 536 537 SPH Trip Action SPH Alarm Action Starts Per Hour Get/Set Get/Set Get/Set 126(0x7E) 538 Get/Set 127(0x7F) 128(0x80) 539 540 Time Between Starts SPH Trip Count Overload Reset Type Counts Overload Trips Time delay defines when motor is in run mode. Starts per hour trip action. Starts per hour alarm action. Starts per hour setting. 0= 1 Start Per Hour 9= 10 Starts Per Hour Time in minutes between starts. Get Get/Set Number of SPH trips. Thermal Overload Reset Type 144 (0x90) 145 (0x91) 146 (0x92) 147 (0x93) 148 (0x94) 149 (0x95) 150 (0x96) 151 (0x97) 152 (0x98) 153 (0x99) 154 (0x9A) 155 (0x9B) 156 (0x9C) 157 (0x9D) 158 (0x9E) 159 (0x9F) 160 (0xA0) 161 (0xA1) 162 (0xA2) 163 (0xA3) 164 (0xA4) 165 (0xA5) 166 (0xA6) 167(0xA7) 168(0xA8) 168(0xA9) 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 541 542 543 IA IB IC 3IO Vab Vbc Vca S Q P PF Used I²t Thermal Trend +Seq I -Seq I Unbalance I Frequency -Seq V Unbalance V Run Time KWs KVAs KVARs DIF Ia DIF Ib DIF Ic Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get DESCRIPTION Speed Phase A Current (A) Phase B Current (A) Phase C Current (A) Ground-Fault Current (A) Line-to-Line Voltage (kV) Line-to-Line Voltage (kV) Line-to-Line Voltage (kV) Apparent Power (kVA) Reactive Power (kVAC) Real Power (kW) Power Factor Used Thermal Capacity (%) Thermal Trend (%) Positive Sequence Current (Pu) Negative Sequence Current (Pu) Current Unbalance (Pu) Frequency (from Vab) Negative Sequence Voltage (Pu) Voltage Unbalance (Pu) Running time in seconds KW seconds KVA seconds KVAR seconds Differential current, phase A Differential current, phase B Differential current, phase C DEFAULT, MINIMUM, MAXIMUM 0.12, 0.03, 0.6 1, 0, 1 DATA TYPE COMM REGISTER REAL 214/215 UINT 224 REAL 225/226 REAL 227/228 REAL 229/230 REAL REAL 233/234 235/236 10, 5, 60 UINT REAL 1132 216/217 0,0,7 0,0,7 4,0,9 UINT UINT UINT 1270 1271 1272 0,0,500 REAL 1273/1274 0,0,2 UINT UINT 1193 26 REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL UDINT LREAL LREAL LREAL REAL REAL REAL 860/861 862/863 864/865 866/867 868/869 870/871 872/873 874/875 876/877 878/879 880/881 882/883 886/887 888/889 890/891 892/893 966/967 896/897 898/899 1210 1212..15 1216..19 1220..23 1224/1225 1226/1227 1228/1229 100, 1, 5000 0.6, 0.12, 25 1800, 100, 10k 1, 1, 1.25 100, 1, 5000 1 to 1 Page 18 Rev. 12-C-061015 MPS DeviceNet Interface 3.8 SET POINT CLASS 0x64 Set Point Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Set Point Class (0x64), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. Set Point Object Instances Set Point Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. The set point class consists of seven attributes. Each set-point instance may use some or all of these attributes. Attribute 1 - Trip Action Specifies the action to take on a trip. 0 = Disable 1 = Trip1 (1) 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 DEFAULT, MINIMUM, MAXIMUM 5 22 DATA TYPE UINT UINT Attribute 2 - Alarm Action Specifies the action to take on an alarm. 0 = Disable 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 Attribute 3 - Trip Level Attribute 4 - Trip Delay Attribute 5 - Alarm Level Attribute 6 - Alarm Delay Attribute 7 - Trip Counter for the set point (1) Initiates a STOP when a starter function is enabled. Class 0x64, Instance 1 - Overcurrent ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 3 4 7 46 47 48 49 Trip Action Trip Level Trip Delay Trip Count Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 10, 1, 15 0.1, 0, 10 DATA TYPE COMM REGISTER UINT REAL REAL UINT 32 33/34 35/36 1130 DATA TYPE COMM REGISTER UINT REAL REAL UINT 40 41/42 43/44 1131 Class 0x64, Instance 2 - Aux. Overcurrent ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 3 4 7 50 51 52 53 Trip Action Trip Level Trip Delay Trip Count Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 10, 1, 15 0.1, 0, 10 Page 19 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x64, Instance 3 - Earth Fault ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 54 55 56 57 58 59 60 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 1, 0, 7 0.4, 0.05, 1 0.25, 0, 100 0.20, 0.05, 1 1, 0, 100 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 48 58 50/51 52/53 54/55 56/57 1133 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 64 73 65/66 67/68 69/70 71/72 1136 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 80 89 81/82 83/84 85/86 87/88 1134 DATA TYPE COMM REGISTER UINT UINT REAL UINT 96 95 97/98 1144 DATA TYPE COMM REGISTER UINT REAL UINT 99 100/101 1143 Class 0x64, Instance 4 - Jam ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 61 62 63 64 65 66 67 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 1, 0, 7 6, 1, 10 5, 1, 100 3, 1, 10 5, 1, 100 Class 0x64, Instance 5 - Current Unbalance (I) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 68 69 70 71 72 73 74 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 1, 0, 7 0.25, 0.05, 1 15, 1, 100 0.10, 0.05, 1 10, 1, 100 Class 0x64, Instance 6 - Phase Reverse (I) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 4 7 75 524 76 77 Trip Action Alarm Action Phase Reverse Delay Trip Count Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 2, 1, 100 Class 0x64, Instance 7 - Phase Loss (I) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 4 7 78 79 80 Trip Action Phase Loss Delay Trip Count Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 5, 1, 100 Page 20 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x64, Instance 8 - Voltage Unbalance ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 81 82 83 84 85 86 87 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 1, 0, 7 0.1, 0.05, 1 15, 1, 100 0.05, 0.05, 1 10, 1, 100 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 104 113 105/106 107/108 109/110 111/112 1135 DATA TYPE COMM REGISTER UINT REAL UINT 120 121/122 1146 DATA TYPE COMM REGISTER UINT REAL UINT 123 124/125 1145 DATA TYPE COMM REGISTER UINT UINT 128 137 REAL REAL REAL REAL UINT 129/130 131/132 133/134 135/136 1137 DATA TYPE COMM REGISTER UINT UINT UINT 144 145 1145 Class 0x64, Instance 9 - Phase Reverse (V) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 4 7 88 89 90 Trip Action Phase Reverse Delay Trip Count Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 2, 1, 100 Class 0x64, Instance 0x0A - Phase Loss (V) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 4 7 91 92 93 Trip Action Phase Loss Delay Trip Count Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 5, 1, 100 Class 0x64, Instance 0x0B - Undercurrent ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 94 95 Trip Action Alarm Action Get/Set Get/Set 3 4 5 6 7 96 97 98 99 100 Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.5, 0.1, 1 10, 1, 100 0.8, 0.1, 1 20, 1, 100 Class 0x64, Instance 0x0C - PTC Temperature ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 7 101 102 103 Trip Action Alarm Action Trip Count Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 Page 21 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x64, Instance 0x0D - Overvoltage ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 104 105 106 107 108 109 110 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 1, 0, 7 1.2, 1, 1.4 5, 1, 500 1.1, 1, 1.4 5, 1, 500 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 176 185 177/178 179/180 181/182 183/184 1138 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 192 201 193/194 195/196 197/198 199/200 1139 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1230 1248 1231/1232 1233/1234 1235/1236 1237/1238 1188 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1239 1249 1240/1241 1242/1243 1244/1245 1246/1247 1189 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 166 175 167/168 169/170 171/172 173/174 1187 Class 0x64, Instance 0x0E - Undervoltage ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 111 112 113 114 115 116 117 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.7, 0.5, 1 5, 1, 500 0.8, 0.5, 1 5, 1, 500 Class 0x64, Instance 0x0F - Underfrequency ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 118 119 120 121 122 123 124 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 45, 30, 80 5, 0.5, 500 48, 30, 80 1, 0.5, 500 Class 0x64, Instance 0x10 - Overfrequency ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 125 126 127 128 129 130 131 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 65, 30, 80 5, 0.5, 500 62, 30, 80 1, 0.5, 500 Class 0x64, Instance 0x11 - Power Factor Quadrant 4 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 132 133 134 135 136 137 138 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.8, 0.5, 1 5, 0.2, 500 0.9, 0.5, 1 10, 0.2, 500 Page 22 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x64, Instance 0x12 - Power Factor Quadrant 3 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 139 140 141 142 143 144 145 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.8, 0.5, 1 5, 0.2, 500 0.9, 0.5, 1 10, 0.2, 500 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1250 1259 1251/1252 1253/1254 1255/1256 1257/1258 1192 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1280 1289 1281/1282 1283/1284 1285/1286 1287/1288 1195 DATA TYPE COMM REGISTER UINT REAL UINT 45 46/47 1196 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1070 1079 1071/1072 1073/1074 1075/1076 1077/1078 1197 DATA TYPE COMM REGISTER UINT UINT REAL REAL REAL REAL UINT 1080 1089 1081/1082 1083/1084 1085/1086 1087/1088 1198 Class 0x64, Instance 0x13 - Differential ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 525 526 527 528 529 530 531 Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 1, 0.1, 15 0.1, 0, 10 1, 0.1, 15 0.1, 0, 10 Class 0x64, Instance 0x14 – Reduced Overcurrent ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 3 7 532 533 534 Trip Action Trip Level Trip Count Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 1, 1, 15 Class 0x64, Instance 0x15 – Underpower ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME 1 2 3 4 5 6 7 N/A N/A N/A N/A N/A N/A N/A Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count SERVICES Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.8, 0.1, 1.0 5, 0.5, 500 0.8, 0.1, 1.0 1, 0.5, 500 Class 0x64, Instance 0x16 – Reversepower ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME 1 2 3 4 5 6 7 N/A N/A N/A N/A N/A N/A N/A Trip Action Alarm Action Trip Level Trip Delay Alarm Level Alarm Delay Trip Count SERVICES Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 0, 0, 7 0.2, 0.1, 1.0 5, 0.5, 500 0.2, 0.1, 1.0 1, 0.5, 500 Page 23 Rev. 12-C-061015 MPS DeviceNet Interface 3.9 ACCELERATION CLASS 0x65 Motor speed is measured using a digital tach connected to Digital Input 8, or a 4–20 mA speed sensor. This class defines parameters for speed protection. Acceleration Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Acceleration Class (0x65), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DEFAULT, MINIMUM, MAXIMUM 1 1 DESCRIPTION Revision of this object. Maximum number of instances. DATA TYPE UINT UINT Acceleration Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. Instance 1 Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 1 146 Accel Action Get/Set 2 147 Speed1 Get/Set 3 148 Time1 Get/Set 4 149 Speed2 Get/Set 5 150 Time2 Get/Set 6 151 Speed3 Get/Set 7 152 Time3 Get/Set 8 153 Tach Enable Get/Set 9 154 Pulses Per Rev Get/Set 10 (0x0A) 11 (0x0B) 155 156 Tach Speed Trip Count Get Get DESCRIPTION Specifies the action to take on a trip. 0 = Disable 1 = Trip1(1) 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 (1) Initiates a STOP when a starter function is enabled. Motor must reach Speed1 in the time defined by Time1. (%FS) Defines the time when Speed1 must be reached. (s) Motor must reach Speed2 in the time defined by Time2. (%FS) Defines the time when Speed2 must be reached. (s) Motor must reach Speed3 in the time defined by Time3. (%FS) Defines the time when Speed3 must be reached. (s) Enables speed measurement even if protection is disabled. 0 = Enabled, 1 = Disabled Sets the number of pulses per revolution for digital tach. Motor Speed from Tach Counts Number of Accel Trips DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 DATA TYPE COMM REGISTER UINT 152 30, 1, 100 REAL 153/154 5, 1, 1000 REAL 155/156 60, 1, 100 REAL 157/158 10, 1, 1000 REAL 159/160 90, 1, 100 REAL 161/164 15, 1, 1000 REAL 163/164 1, 0, 1 UINT 330 60, 1, 100 REAL 331/332 REAL UINT 900/901 1147 Page 24 Rev. 12-C-061015 MPS DeviceNet Interface 3.10 DIGITAL INPUT CLASS 0x66 Digital Input Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Digital Input Class (0x66), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. Digital Input Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. DEFAULT, MINIMUM, MAXIMUM 1 7 DATA TYPE UINT UINT Attribute 2 - Bypass Enable/Disable Attribute applies when the input function is trip. When enabled, the input is bypassed for the time defined by the Bypass Delay when a motor is started using starter control. 0 = Enable, 1 = Disable The digital-input class consists of 5 attributes. Attribute 3 - Bypass Delay Defines the Trip bypass time duration on start. Attribute 1 - Function Selects the function of the digital input. 0 = Input not used 1 = Start1 (N.O. Contact) 2 = Start2 (N.O. Contact) 3 = Stop (N.C. Contact) 4 = Starter RLYA contactor status 5 = Starter RLYB contactor status 6 = Starter RLYC contactor status 7 = Starter RLYD contactor status 8 = Interlock (N.C.) 9 = Trip1 (N.C.) 10 = Reset (N.O.) 11 = Local Select 12 = Local Start1 13 = Local Start2 14 = 2-Wire Start1 15 = 2-Wire Start2 16 = FLA2 Select 17 = Limit1 Select 18 = Limit2 Select 19 = Reduced OC Attribute 4 - Trip Delay Applies only to the trip function. Attribute 5 - Trip Count The trip counter only applies to the trip function. Class 0x66, Instance 1 - Input 1 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 208 209 210 211 212 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 264 265 266/267 268/269 1149 Page 25 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x66, Instance 2 - Input 2 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 213 214 215 216 217 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 274 275 276/277 278/279 1150 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 284 285 286/287 288/289 1151 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 294 295 296/297 298/299 1152 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 304 305 306/307 308/309 1153 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 314 315 316/317 318/319 1154 Class 0x66, Instance 3 - Input 3 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 218 219 220 221 222 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 Class 0x66, Instance 4 - Input 4 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 223 224 225 226 227 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 Class 0x66, Instance 5 - Input 5 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 228 229 230 231 232 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 Class 0x66, Instance 6 - Input 6 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 233 234 235 236 237 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 Page 26 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x66, Instance 7 - Input 7 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 238 239 240 241 242 Function Bypass Enable/Disable Bypass Delay Trip Delay Trip Counter Get/Set Get/Set Get/Set Get/Set Get DEFAULT, MINIMUM, MAXIMUM 0, 0, 19 1, 0, 1 5, 0.5, 100 0.1, 0.01, 100 DATA TYPE COMM REGISTER UINT UINT REAL REAL UINT 324 325 326/327 328/329 1155 3.11 ANALOG I/O CLASS 0x67 Analog I/O Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Analog I/O Class (0x67), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT Analog I/O Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. Analog I/O Class (0x67), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 1 243 Analog In Type Get/Set 2 244 High Trip Get/Set 3 245 Low Trip Get Set 4 5 246 247 Trip Delay High Alarm Get/Set Get/Set 6 248 Low Alarm Get/Set 7 8 249 250 Alarm Delay ASD_4mA Get/Set Get/Set DESCRIPTION Defines the analog-input type. 0 = Disabled 1 = Generic (Trip1, Alarm1 enabled) 2 = ASD sets sampling frequency 3 = Motor speed Sets high trip level for generic input type. (mA) Sets low trip level for generic input type. (mA) Applies to generic type. (s) Sets high alarm level for generic input type. (mA) Sets low alarm level for generic input type (mA) Applies to Generic Type (s) Applies to type 2 input. Frequency corresponding to 4 mA input. (Hz) DEFAULT, MINIMUM, MAXIMUM 0, 0, 3 DATA TYPE COMM REGISTER UINT 350 16, 0.1, 20 REAL 351/352 7, 0.1, 20 REAL 353/354 5, 0.01, 100 14, 0.1, 20 REAL REAL 355/356 357/358 9, 0.1, 20 REAL 359/360 1, 0.01, 100 10, 0, 70 REAL REAL 361/362 363/364 Page 27 Rev. 12-C-061015 MPS DeviceNet Interface Analog I/O Class (0x67), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 9 251 ASD_20mA Get/Set 10 (0x0A) 252 Tach_4mA Get/Set 11 (0x0B) 253 Tach_20mA Get/Set 12 (0x0C) 254 Out Param Get/Set 13 (0x0D) 14 (0x0E) 15 (0x0F) 255 256 257 Reading High Trips Low Trips Get Get Get DESCRIPTION Applies to type 2 input. Frequency corresponding to 20 mA input. (%FS) Applies to type 3 input. % Speed corresponding to 4 mA input. (%FS) Applies to type 3 input. % Speed corresponding to 20 mA input. (%FS) Specifies the analog output parameter 0 = Phase Current 1 = Earth Leakage 2 = Thermal Capacity 3 = Max Stator RTD 4 = Max Bearing RTD 5 = Max Load RTD 6 = Max Ambient RTD 7 = Voltage 8 = Unbalance (I) 9 = Power Factor 10 = Real Power 11 = Reactive Power 12 = Apparent Power 13 = Zero (4 mA) 14 = Full Scale (20 mA) 15= Speed 16 = Differential Current Analog input reading. (mA) Input-High Trip Count Input-Low Trip Count DEFAULT, MINIMUM, MAXIMUM 10, 0, 70 DATA TYPE COMM REGISTER REAL 365/366 10, 0, 100 REAL 367/368 100, 0, 100 REAL 369/370 0, 0, 16 UINT 373/374 0, 0, 20 REAL UINT UINT 884/885 1140 1141 DATA TYPE COMM REGISTER 3.12 RTD MODULE CLASS 0x68 RTD Module Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. Class 0x68, Instance 0, Attributes ATTRIBUTE NUMBER PARAM 1 2 100 (0x64) 258 ATTRIBUTE NAME SERVICES Revision Number Max Instance Get Get Modules Used Get/Set DESCRIPTION Revision number of this class. Maximum number of RTD modules. Specifies the number of RTD modules used. DEFAULT, MINIMUM, MAXIMUM 1 3 UINT UINT 0, 0, 3 UINT 390 Page 28 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 0, Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 101 (0x65) 259 Sensor Trip Action Get/Set 102 (0x66) 260 Sensor Alarm Action Get/Set 103 (0x67) 261 Module Error Trip Action Get/Set 104 (0x68) 262 Module Error Alarm Action Get/Set 105 (0x69) 263 Get 106 (0x6A) 264 107 (0x6B) 265 108 (0x6C) 109 (0x6D) 266 267 Module1 Comm Trip Count Module2 Comm Trip Count Module3 Comm Trip Count Sensor Trip Count HMC Enable Get Get/Set 110 (0x6E) 268 HMC Max Bias Get/Set 111 (0x6F) 269 HMC Min Bias Get/Set 112 (0x70) 113 (0x71) 114 (0x72) 115 (0x73) 116 (0x74) 117 (0x75) 118 (0x76) 119 (0x77) 270 271 272 273 274 275 276 277 Max Stator Temp Max Bearing Temp Max Load Temp Max Amb Temp Min Stator Temp Min Bearing Temp Min Load Temp Min Ambient Temp Get Get Get Get Get Get Get Get Get Get DESCRIPTION Specifies trip action to take on a sensor error. 0 = Disable Trips 1 = Trip1(1) 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 (1) Initiates a STOP when a starter function is enabled. Specifies alarm action to take on a sensor error. 0 = Disable Alarms 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 Specifies trip action to take on a module error. Action list is the same as Attribute 9. Specifies alarm action to take on a module error. Action list is the same as Attribute A. Number of module1 communication-error trips. Number of module2 communication-error trips. Number of module3 communication-error trips. Number of RTD sensor trips Hot Motor Compensation control. 0 = Enable, 1 = Disable Stator temperature (°C) where compensation ends at 100% I²t. Stator temperature (°C) where compensation begins at 0% I²t. Max Stator Temperature (°C) Max Bearing Temperature (°C) Max Load Temperature (°C) Max Ambient Temperature (°C) Min Stator Temperature (°C) Min Bearing Temperature (°C) Min Load Temperature (°C) Min Ambient Temperature (°C) DEFAULT, MINIMUM, MAXIMUM 0, 0, 7 DATA TYPE COMM REGISTER UINT 388 1, 0, 7 UINT 379 0, 0, 7 UINT 389 1, 0, 7 UINT 380 UINT 1180 UINT 1181 UINT 1182 UINT UINT 1183 550 REAL 551/552 REAL 553/554 REAL REAL REAL REAL REAL REAL REAL REAL 950/951 952/953 954/955 956/957 958/959 960/961 962/963 964/965 150, 40, 200 40, 40, 200 Page 29 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 0, Attributes (Continued) ATTRIBUTE NUMBER PARAM 120 (0x78) 524 Temperature Trip Action Get/Set Specifies trip action to take on a sensor error. 0 = Disable Trips 1 = Trip1(1) 2 = Trip2 3 = Trip3 4 = Trip1 & Trip2 5 = Trip1 & Trip3 6 = Trip1 & Trip2 & Trip3 7 = Trip2 & Trip3 (1) Initiates a STOP when a starter function is enabled. 121 (0x79) 525 Temperature Alarm Action Get/Set Specifies alarm action to take on a sensor error. 0 = Disable Alarms 1 = Alarm1 2 = Alarm2 3 = Alarm3 4 = Alarm1 & Alarm2 5 = Alarm1 & Alarm3 6 = Alarm1 & Alarm2 & Alarm3 7 = Alarm2 & Alarm3 ATTRIBUTE NAME SERVICES DESCRIPTION DEFAULT, MINIMUM, MAXIMUM 1, 0, 7 DATA TYPE COMM REGISTER UINT 548 1, 0, 7 UINT 549 Page 30 Rev. 12-C-061015 MPS DeviceNet Interface RTD Module Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. 4= Stator Voting 5= Bearing Voting 6= Load Voting 7= Ambient Voting Object Instance Attributes 1 to 8 define the RTD type. Selecting an RTD will enable trip and alarm set points. The trip action is fixed as Trip1 and the alarm action is fixed as Alarm1. 0 = RTD Disabled 1 = Platinum 100 ohm 2 = Nickel 100 ohm 3 = Nickel 120 ohm 4 = Copper 10 ohm Object Instance Attributes 0x11 to 0x20 define the trip and alarm settings in degrees C. The trip action is fixed as Trip1 and the alarm action is fixed as Alarm1. Object Instance Attributes 0x09 to 0x10 define the RTD function. 0 = Stator 1 = Bearing 2 = Load 3 = Ambient Object Instance Attributes 0x31 to 0x38 are the trip counters for each of the RTD's. Object Instance Attributes 0x21 to 0x28 define an 18character name. Object Instance Attributes temperature readings. 0x29 to 0x30 are Class 0x68, Instance 1 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 8 9 10 (0x0A) 11 (0x0B) 12 (0x0C) 13 (0x0D) 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) 18 (0x12) 19 (0x13) 20 (0x14) 21 (0x15) 22 (0x16) 23 (0x17) 24 (0x18) 25 (0x19) 26 (0x1A) 27 (0x1B) 28 (0x1C) 29 (0x1D) 30 (0x1E) 31 (0x1F) 32 (0x20) 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 RTD #1 Type RTD #2 Type RTD #3 Type RTD #4 Type RTD #5 Type RTD #6 Type RTD #7 Type RTD #8 Type RTD #1 Function RTD #2 Function RTD #3 Function RTD #4 Function RTD #5 Function RTD #6 Function RTD #7 Function RTD #8 Function RTD #1 Trip Level RTD #1 Alarm Level RTD #2 Trip Level RTD #2 Alarm Level RTD #3 Trip Level RTD #3 Alarm Level RTD #4 Trip Level RTD #4 Alarm Level RTD #5 Trip Level RTD #5 Alarm Level RTD #6 Trip Level RTD #6 Alarm Level RTD #7 Trip Level RTD #7 Alarm Level RTD #8 Trip Level RTD #8 Alarm Level Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 DATA TYPE COMM REGISTER UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL 391 392 393 394 395 396 397 398 415 416 417 418 419 420 421 422 446/447 448/449 450/451 452/453 454/455 456/457 458/459 460/461 462/463 464/465 466/467 468/469 470/471 472/473 474/475 476/477 Page 31 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 1 (Continued) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 33 (0x21) 310 RTD #1 Name Get/Set DEFAULT, MINIMUM, MAXIMUM RTD M1 #1 34 (0x22) 311 RTD #2 Name Get/Set RTD M1 #2 35 (0x23) 312 RTD #3 Name Get/Set RTD M1 #3 36 (0x24) 313 RTD #4Name Get/Set RTD M1 #4 37 (0x25) 314 RTD #5 Name Get/Set RTD M1 #5 38 (0x26) 315 RTD #6 Name Get/Set RTD M1 #6 39 (0x27) 316 RTD #7 Name Get/Set RTD M1 #7 40 (0x28) 317 RTD #8 Name Get/Set RTD M1 #8 41 (0x29) 42 (0x2A) 43 (0x2B) 44 (0x2C) 45 (0x2D) 46 (0x2E) 47 (0x2F) 48 (0x30) 49 (0x31) 50 (0x32) 51 (0x33) 52 (0x34) 53 (0x35) 54 (0x36) 55 (0x37) 56 (0x38) 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 RTD #1 Temp RDG RTD #2 Temp RDG RTD #3 Temp RDG RTD #4 Temp RDG RTD #5 Temp RDG RTD #6 Temp RDG RTD #7 Temp RDG RTD #8 Temp RDG RTD #1 Trip Cntr RTD #2 Trip Cntr RTD #3 Trip Cntr RTD #4 Trip Cntr RTD #5 Trip Cntr RTD #6 Trip Cntr RTD #7 Trip Cntr RTD #8 Trip Cntr Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get DATA TYPE COMM REGISTER SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING REAL REAL REAL REAL REAL REAL REAL REAL UINT UINT UINT UINT UINT UINT UINT UINT 610..619 DATA TYPE COMM REGISTER UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT REAL REAL 399 400 401 402 403 404 405 406 423 424 425 426 427 428 429 430 478 480 620..629 630..639 640..649 650..659 660..669 670..679 680..689 902/903 904/905 906/907 908/909 910/911 912/913 914/915 916/917 1156 1157 1158 1159 1160 1161 1162 1163 Class 0x68, Instance 2 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 8 9 10 (0x0A) 11 (0x0B) 12 (0x0C) 13 (0x0D) 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) 18 (0x12) 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 RTD #1 Type RTD #2 Type RTD #3 Type RTD #4 Type RTD #5 Type RTD #6 Type RTD #7 Type RTD #8 Type RTD #1 Function RTD #2 Function RTD #3 Function RTD #4 Function RTD #5 Function RTD #6 Function RTD #7 Function RTD #8 Function RTD #1 Trip Level RTD #1 Alarm Level Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 130, 40, 200 110, 40, 200 Page 32 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 2 (Continued) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 19 (0x13) 20 (0x14) 21 (0x15) 22 (0x16) 23 (0x17) 24 (0x18) 25 (0x19) 26 (0x1A) 27 (0x1B) 28 (0x1C) 29 (0x1D) 30 (0x1E) 31 (0x1F) 32 (0x20) 33 (0x21) 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 RTD #2 Trip Level RTD #2 Alarm Level RTD #3 Trip Level RTD #3 Alarm Level RTD #4 Trip Level RTD #4 Alarm Level RTD #5 Trip Level RTD #5 Alarm Level RTD #6 Trip Level RTD #6 Alarm Level RTD #7 Trip Level RTD #7 Alarm Level RTD #8 Trip Level RTD #8 Alarm Level RTD #1 Name Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 RTD M2 #1 34 (0x22) 367 RTD #2 Name Get/Set RTD M2 #2 35 (0x23) 368 RTD #3 Name Get/Set RTD M2 #3 36 (0x24) 369 RTD #4Name Get/Set RTD M2 #4 37 (0x25) 370 RTD #5 Name Get/Set RTD M2 #5 38 (0x26) 371 RTD #6 Name Get/Set RTD M2 #6 39 (0x27) 372 RTD #7 Name Get/Set RTD M2 #7 40 (0x28) 373 RTD #8 Name Get/Set RTD M2 #8 41 (0x29) 42 (0x2A) 43 (0x2B) 44 (0x2C) 45 (0x2D) 46 (0x2E) 47 (0x2F) 48 (0x30) 49 (0x31) 50 (0x32) 51 (0x33) 52 (0x34) 53 (0x35) 54 (0x36) 55 (0x37) 56 (0x38) 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 RTD #1 Temp RDG RTD #2 Temp RDG RTD #3 Temp RDG RTD #4 Temp RDG RTD #5 Temp RDG RTD #6 Temp RDG RTD #7 Temp RDG RTD #8 Temp RDG RTD #1 Trip Cntr RTD #2 Trip Cntr RTD #3 Trip Cntr RTD #4 Trip Cntr RTD #5 Trip Cntr RTD #6 Trip Cntr RTD #7 Trip Cntr RTD #8 Trip Cntr Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get DATA TYPE COMM REGISTER REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING REAL REAL REAL REAL REAL REAL REAL REAL UINT UINT UINT UINT UINT UINT UINT UINT 482/483 484/485 486/487 488/489 490/491 492/493 494/495 496/497 498/499 500/501 502/503 504/505 506/507 508/509 690..699 700..709 710..719 720..729 730..739 740..749 750..759 760..769 918/919 920/921 922/923 924/925 926/927 928/929 930/931 932/933 1164 1165 1166 1167 1168 1169 1170 1171 Page 33 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 3 ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 8 9 10 (0x0A) 11 (0x0B) 12 (0x0C) 13 (0x0D) 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) 18 (0x12) 19 (0x13) 20 (0x14) 21 (0x15) 22 (0x16) 23 (0x17) 24 (0x18) 25 (0x19) 26 (0x1A) 27 (0x1B) 28 (0x1C) 29 (0x1D) 30 (0x1E) 31 (0x1F) 32 (0x20) 33 (0x21) 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 RTD #1 Type RTD #2 Type RTD #3 Type RTD #4 Type RTD #5 Type RTD #6 Type RTD #7 Type RTD #8 Type RTD #1 Function RTD #2 Function RTD #3 Function RTD #4 Function RTD #5 Function RTD #6 Function RTD #7 Function RTD #8 Function RTD #1 Trip Level RTD #1 Alarm Level RTD #2 Trip Level RTD #2 Alarm Level RTD #3 Trip Level RTD #3 Alarm Level RTD #4 Trip Level RTD #4 Alarm Level RTD #5 Trip Level RTD #5 Alarm Level RTD #6 Trip Level RTD #6 Alarm Level RTD #7 Trip Level RTD #7 Alarm Level RTD #8 Trip Level RTD #8 Alarm Level RTD #1 Name Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DEFAULT, MINIMUM, MAXIMUM 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 4 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 0, 0, 7 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 130, 40, 200 110, 40, 200 RTD M3 #1 34 (0x22) 423 RTD #2 Name Get/Set RTD M3 #2 35 (0x23) 424 RTD #3 Name Get/Set RTD M3 #3 36 (0x24) 425 RTD #4Name Get/Set RTD M3 #4 37 (0x25) 426 RTD #5 Name Get/Set RTD M3 #5 38 (0x26) 427 RTD #6 Name Get/Set RTD M3 #6 39 (0x27) 428 RTD #7 Name Get/Set RTD M3 #7 40 (0x28) 429 RTD #8 Name Get/Set RTD M3 #8 41 (0x29) 42 (0x2A) 43 (0x2B) 44 (0x2C) 45 (0x2D) 46 (0x2E) 430 431 432 433 434 435 RTD #1 Temp RDG RTD #2 Temp RDG RTD #3 Temp RDG RTD #4 Temp RDG RTD #5 Temp RDG RTD #6 Temp RDG Get Get Get Get Get Get DATA TYPE COMM REGISTER UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING SHORT_ STRING REAL REAL REAL REAL REAL REAL 407 408 409 410 411 412 413 414 431 432 433 434 435 436 437 438 510/511 512/513 514/515 516/517 518/519 520/521 522/523 524/525 526/527 528/529 530/531 532/533 534/535 536/537 538/539 540/541 770..779 780..789 790..799 800..809 810..819 820..829 830..839 840..849 934..935 936..937 938..939 940..941 942..943 944..945 Page 34 Rev. 12-C-061015 MPS DeviceNet Interface Class 0x68, Instance 3 (Continued) ATTRIBUTE NUMBER DEVICENET PARAMETER ATTRIBUTE NAME SERVICES 47 (0x2F) 48 (0x30) 49 (0x31) 50 (0x32) 51 (0x33) 52 (0x34) 53 (0x35) 54 (0x36) 55 (0x37) 56 (0x38) 436 437 438 439 440 441 442 443 444 445 RTD #7 Temp RDG RTD #8 Temp RDG RTD #1 Trip Cntr RTD #2 Trip Cntr RTD #3 Trip Cntr RTD #4 Trip Cntr RTD #5 Trip Cntr RTD #6 Trip Cntr RTD #7 Trip Cntr RTD #8 Trip Cntr Get Get Get Get Get Get Get Get Get Get DEFAULT, MINIMUM, MAXIMUM DATA TYPE COMM REGISTER REAL REAL UINT UINT UINT UINT UINT UINT UINT UINT 946/947 948/949 1172 1173 1174 1175 1176 1177 1178 1179 3.13 RTC CLASS 0x69 RTC Object Class Services Get_Attribute_Single: Returns contents of specified attribute. RTC Class (0x69), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object Maximum number of instances DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT RTC Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. RTC Class (0x69), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 1 446 IRIG Hrs Offset Get/Set 2 447 IRIG Min Offset Get/Set 3 448 RTC Date Get 4 449 RTC Time Get 5 450 RTC Set Get/Set (1) (1) DESCRIPTION RTC Hrs = IRIG Hrs + IRIG Hr Offset RTC Min = IRIG Min + IRIG Min Offset Number of Days since 1972-0101 Number of Milliseconds since 00:00:00:00.000 String Used to Set the Date and Time YY/MM/DD-HH:MM:SS Time value is not activated until a SET RTC command is issued using Class 0x29, Instance 1, Attribute 0x64. DEFAULT, MINIMUM, MAXIMUM 0, 0, 30 DATA TYPE COMM REGISTER REAL 568/569 0, 0, 23 REAL 570/571 DATE 574/575 TIME OF DAY SHORT_ STRING 576/577 580/589 Page 35 Rev. 12-C-061015 MPS DeviceNet Interface 3.14 USER REGISTER CLASS 0x6A This object defines the communication registers that generate the data for Assembly Class 4, Instance 0x67, Attribute 3. Register values are defined in Appendix E of the Main Product Manual. Each register in Appendix E defines a 16-bit value. For 32-bit float type (DeviceNet REAL), only the first register of the pair needs too be entered. For example, to configure an assembly to read the first four RTD temperatures in RTD Module 1, enter register numbers 902, 904, 906, 908. The first 16 bytes of the assembly will contain the RTD data and the other 16 bytes do not contain any valid data. Register definitions resulting in more than 32 bytes of data will be ignored. User Register Object Class Services Get_Attribute_Single: Returns contents of specified attribute. User Register Class (0x6A), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT User Register Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. User Register Class (0x6A), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 Register 1 Register 2 Register 3 Register 4 Register 5 Register 6 Register 7 Register 8 Register 9 Register 10 Register 11 Register 12 Register 13 Register 14 Register 15 Register 16 Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set Get/Set DESCRIPTION User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value User Register value DEFAULT, MINIMUM, MAXIMUM 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 0, 0, 1246 DATA TYPE COMM REGISTER UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT 1400 1401 1402 1403 1404 1405 1406 1407 1408 1409 1410 1411 1412 1413 1414 1415 Page 36 Rev. 12-C-061015 MPS DeviceNet Interface 3.15 DATA LOGGING CLASS 0x6B This object is used to access one of 64 data-logging records. The Record Selector value defines the record that is displayed. Record Head indicates the record number for the latest record. Data Logging Object Class Services Get_Attribute_Single: Returns contents of specified attribute. Data Logging Class (0x6B), Instance (0) Attributes ATTRIBUTE NUMBER ATTRIBUTE NAME SERVICES 1 2 Revision Max Instance Get Get DESCRIPTION Revision of this object. Maximum number of instances. DEFAULT, MINIMUM, MAXIMUM 1 1 DATA TYPE UINT UINT Data Logging Object Instance Services Get_Attribute_Single: Returns contents of specified attribute. Set_Attribute_Single: Modifies specified attribute. Data Logging Class (0x6B), Instance (1) Attributes ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 1 475 Record Count Get 2 476 Record Head Get 3 477 Record Selector Get/Set 4 478 Record Date Get 5 479 Record Time Get 6 480 Record Type Get 7 481 Trip Code Get 8 9 10 (0x0A) 11 (0x0B) 12 (0x0C) 13 (0x0D) 14 (0x0E) 15 (0x0F) 16 (0x10) 17 (0x11) 18 (0x12) 19 (0x13) 20 (0x14) 21 (0x15) 22 (0x16) 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 IA IB IC 3IA Vab Vbc Vca Frequency S P Q PF Ain Unbalance I Unbalance V Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get DESCRIPTION Number of captured records since the last time the event records were cleared. Points to next record. Latest record at Record Head minus 1. Selects the record for which the data is displayed in this instance. The date when the record was captured. Time-of-Day the record was captured. Specifies the trigger source: 0 = Record Empty 1 = Triggered by start 2 = Triggered by trip See Main Product Manual Appendix F T27 for a list of trip codes. 255 = No Trip or Alarm. Phase A Current (A)(1) Phase B Current (A)(1) Phase C Current (A)(1) Ground-Fault Current (A)(1) Line-to-Line Voltage (kV)(1) Line-to-Line Voltage (kV)(1) Line-to-Line Voltage (kV)(1) Frequency in Hz Apparent Power (kVA) Real Power (kW) Reactive Power (kVAR) Power Factor (-1, +1) Analog Input (mA) Current Unbalance (pu)(1) Voltage Unbalance (pu)(1) DEFAULT, MINIMUM, MAXIMUM 0, 0, 65535 DATA TYPE COMM REGISTER UINT 973 0, 0, 63 UINT 974 0, 0, 63 UINT 975 0, 0, 65535 DATE 976/977 0, 0, 86399999 0, 0, 2 TOD 978/979 UINT 980 0, 0, 255 UINT 981 Real Real Real Real Real Real Real Real Real Real Real Real Real Real Real 982 984 986 988 990 992 994 1053/1054 1055/1056 1057/1058 1059/1060 1061/1062 996/997 998/999 1000/1001 Page 37 Rev. 12-C-061015 MPS DeviceNet Interface Data Logging Class (0x6B), Instance (1) Attributes (Continued) ATTRIBUTE NUMBER PARAM ATTRIBUTE NAME SERVICES 23 (0x17) 497 Start Time Get 24 (0x18) 498 I²t Used Get 32 (0x20) 33 (0x21) 34 (0x22) 35 (0x23) 36 (0x24) 37 (0x25) 38 (0x26) 39 (0x27) 40 (0x28) 41 (0x29) 42 (0x2A) 43 (0x2B) 44 (0x2C) 45 (0x2D) 46 (0x2E) 47 (0x2F) 48 (0x30) 49 (0x31) 50 (0x32) 51 (0x33) 52 (0x34) 53 (0x35) 54 (0x36) 55 (0x37) 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 M1 RTD1 M1 RTD2 M1 RTD3 M1 RTD4 M1 RTD5 M1 RTD6 M1 RTD7 M1 RTD8 M2 RTD1 M2 RTD2 M2 RTD3 M2 RTD4 M2 RTD5 M2 RTD6 M2 RTD7 M2 RTD8 M3 RTD1 (2) M3 RTD2 (3) M3 RTD3 (4) M3 RTD4 (5) M3 RTD5 (5) M3 RTD6 (5) M3 RTD7 (5) M3 RTD8 (5) Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get (1) (2) (3) (4) (5) DESCRIPTION Start time in seconds. Only valid for start-type records. For start records this is the I²t used during a start. RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) RTD Temperature Reading (ºC) DEFAULT, MINIMUM, MAXIMUM DATA TYPE COMM REGISTER UINT 1002 REAL 1003/1004 REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL 1005/1006 1007/1008 1009/1010 1011/1012 1013/1014 1015/1016 1017/1018 1019/1020 1021/1022 1023/1024 1025/1026 1027/1028 1029/1030 1031/1032 1033/1034 1035/1036 1037/1038 1039/1040 1041/1042 1043/1044 1045/1046 1047/1048 1049/1050 1051/1052 For start records, current and unbalance are maximum values recorded during the start. Voltages are the minimum values recorded during the start. Phase A differential current for firmware > 2.30 Phase B differential current for firmware > 2.30 Phase C differential current for firmware > 2.30 Ignore this value for firmware > 2.30 Page 38 Rev. 12-C-061015 MPS DeviceNet Interface MPS FIRMWARE APPENDIX A MPS DEVICENET EDS FILES EDS FILES EDS FILE DATE 3.11 to Present 4.400 03-19-2013 2.61 to 3.10 4.300 03-09-2009 2.42 to 2.60 4.200 08-28-2007 1.84 to 2.41 4.100 11-13-2004 Page 39 Rev. 12-C-061015 MPS DeviceNet Interface APPENDIX B MPS DEVICENET INTERFACE REVISION HISTORY MANUAL RELEASE DATE MANUAL REVISION June 10, 2015 12-C-061015 March 21, 2014 12-B-032114 August 20, 2013 12-A-082013 MANUAL REVISION HISTORY REVISION 12-C-061015 Added RTD Module Set Point Class, Instance 0, Attributes 120 and 121. REVISION 12-B-032114 Updated Set Point Class, Instance 0 default, minimum and maximum. Added Underpower and Reversepower instances. REVISION 12-A-082013 Updated Attribute 127 (0x7F) on page 14. Added Appendix A, Appendix B. MPS DeviceNet Interface This page intentionally left blank. Page 40 Rev. 12-C-061015