FPS DeviceNet Manual

3714 Kinnear Place
Saskatoon, SK
Canada
S7P 0A6
Ph: (306) 373-5505
Fx: (306) 374-2245 www.littelfuse.com/relayscontrols
FPS DEVICENET INTERFACE
REVISION 0-A-041114
QUICK SETUP
 Use the OPI to access the Setup | Hardware | Network Comms menu. Set the
Network ID for the device (63 maximum). Set the Baud Rate as DN 125K, DN
250K,
or
DN 500K. Select the DeviceNet producing assembly (input) from the DeviceNet
Produce menu and the DeviceNet consuming assembly (output) from the
DeviceNet Consume menu. Select DeviceNet from the Network Type menu.
The assembly types can also be set using parameter 10 and 11 via configuration
software.
 Configure the scanner’s polled connections for the selected assembly sizes.
The scanner may issue a configuration warning if an I/O size other than the
default is used. Disregard the warning. See Section 3.5 for byte sizes.
Copyright  2014 Littelfuse Startco
All rights reserved.
Document Number: PM-1151-EN
Printed in Canada
FPS DeviceNet Interface
Page i
Rev. 0-A-041114
Page ii
Rev. 0-A-041114
FPS DeviceNet Interface
DISCLAIMER
TABLE OF CONTENTS
SECTION
PAGE
1
2
General ................................................................. 1
DeviceNet Interface ............................................. 1
2.1 Network Settings ................................................... 1
2.2 Product Manual Notes ........................................... 1
2.3 Communication Status Display ............................. 2
2.4 DeviceNet LED Indication.................................... 2
2.5 Network Errors...................................................... 2
2.6 Configuration Using RSNetWorx ......................... 2
3
DeviceNet Objects ............................................... 2
3.1 Identity Object ...................................................... 3
3.2 Message Router ..................................................... 3
3.3 DeviceNet Object .................................................. 4
3.4 DeviceNet Connection Object............................... 5
3.5 Assembly Object ................................................... 7
3.6 Control Supervisor Object..................................... 9
3.7 Overload Class 0x2C .......................................... 15
3.8 Set Point Class 0x64 ........................................... 17
3.9 Inverse Curve Class 0x65.................................... 22
3.10 Digital Input Class 0x66 ..................................... 23
3.11 Analog I/O Class 0x67 ........................................ 25
3.12 RTD Module Class 0x68..................................... 27
3.13 RTC Class 0x69 .................................................. 30
3.14 User Register Class 0x6A ................................... 31
3.15 Data Logging Class 0x6B ................................... 32
Appendix A FPS DeviceNet EDS Files ....................... 35
Appendix B FPS DeviceNet Interface Revision
History ........................................................................... 36
LIST OF FIGURES
FIGURE
1
PAGE
Outline Drawing ...................................................... 1
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a result
of incorrect application, incorrect adjustment, or a
malfunction.
FPS DeviceNet Interface
This page intentionally left blank.
Page iii
Rev. 0-A-041114
Page 1
Rev. 0-A-041114
FPS DeviceNet Interface
1. GENERAL
Network Type to None. Set Network ID to the slave
number. Set the Baud Rate to DN 125K, DN 250K or
DN 500K. Select the producing assembly instance using
the DeviceNet Produce menu and the consuming
assembly instance using the DeviceNet Consume menu.
See Section 3.5 for assembly details. Once the changes
have been made, select DeviceNet from the Network Type
menu.
This document describes the DeviceNet features
supported by the FPS. The FPS supports Explicit and
Polled I/O. It does not support the Unconnected Message
Manager (UCMM).
The FPS requires supply voltage connected to L1 and
L2 to power the control unit and 24-Vdc supply voltage to
power the isolated DeviceNet transceiver circuit. The
DeviceNet transceiver circuit requires 70 mA @ 24-Vdc
from the DeviceNet power supply.
2.2 PRODUCT MANUAL NOTES
Appendix E, Register 661: Baud rate selections (Type
T17 in Appendix F) includes DeviceNet selections
5:125 kb, 6:250 kb, and 7: 500 kb.
Appendix E, Register 663: Network ID range is 0 to 63.
Values greater than 63 will be forced to 63.
2. DEVICENET INTERFACE
2.1 NETWORK SETTINGS
DeviceNet settings are located in the Setup  Hardware
 Network Comms menu. Prior to making changes to
network settings via the OPI, it is recommended to set the
33 32
31
5A
1A
A
30 29
28 27 26
5A
1A
B
PHASE CURRENT
24 23 22
25
5A
1A
C
20
V
N
21
5A
1A
EFCT
EARTH
LEAKAGE
19
V
A
18
V
B
17
V
C
VOLTAGE
DeviceNet
C D C
V A R A V
+ N AI N H N L
5
4
3
2
1
I/O MODULE
AN
IN
IRIG 2 COMM
4
PTC
+ - V+ + HS - V0
+ 62 61 60 59 58 57 56 55 54 53 52
62 61 60 59 58 57 56 55 54 53 52
S
0
2
H
V
PTC
4
IRIG
AN IN
V
COMM
I/O MODULE
FEEDER PROTECTION SYSTEM
CONTROL UNIT
FPS-CTU
POWER
TRIP
ALARM
ERROR
OPERATOR
INTERFACE
RESET
AN
OUT
COMM
S
H
35 36 37 39 40
+ +
FIGURE 1. Outline Drawing.
24 VDC
SOURCE
41 42
DIGITAL INPUTS
C
I
I
I
I
I
I
I
H
O N N N N N N N S
M 1
2 3
4
5 6
7
I
43 44 45 46 47 48 49 50 51
Page 2
Rev. 0-A-041114
FPS DeviceNet Interface
2.3 COMMUNICATION STATUS DISPLAY
The DeviceNet communication status can be viewed
using the Metering  Comm State menu.
This menu indicates the connection state as ONLINE or
OFFLINE.
The last communication error is also
displayed. The FPS can be programmed to trip if the
connection is OFFLINE. The FPS is OFFLINE when
there are no connections established and ONLINE when
at least one connection is established.
2.4 DEVICENET LED INDICATION
Two LED’s labeled MODULE STATUS (MS) and
NETWORK STATUS (NS) are located on the left side of
the control unit as shown in Fig. 1. The MS LED is green
when the DeviceNet driver is operational. If this LED is
off, verify that DeviceNet is selected from the Setup 
Hardware  Network Comms  Network Type menu.
The NS LED is off when the FPS is the only device on
the network. It flashes green when the FPS is physically
connected to a network containing other devices but has
no established communication connections. It is solid
green when a Polling or Explicit Messaging connection is
established. It flashes red when one or more connections
have timed out. It is solid red if a Duplicate MAC ID or
Bus-off error has occurred. Red LED indication requires
a restart of the DeviceNet driver. This is done by,
unplugging and re-connecting the DeviceNet connector,
cycling supply voltage or by using the Setup  Hardware 
Network Comms  Network Type menu. Select None to
shut down the driver and then select DeviceNet to restart.
2.5 NETWORK ERRORS
The FPS can be configured to trip or alarm on a
network error using the Setup  Hardware  Network
Comms  Network Error menu, or by using attribute 0x64
of the DeviceNet object.
The Network Error set point sets the action to be taken
when the module is off line. Selections are Trip, Alarm,
Trip and Alarm, or No Trip or Alarm. Network errors can
originate from network watchdog timeouts or the network
hardware in the FPS.
The last error code is displayed in the Metering  Comm
State menu. The error codes are listed in the following
table.
ERROR
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
DEVICENET ERROR CODES
DESCRIPTION
Receive Overrun
Transmit Overrun
CAN Overrun
IO Send
Duplicate MAC
Bus Sense
MAC Was Set
ID Reset 0
ID Reset 1
Bus Off
CAN ESET
CAN ERESET
Explicit Timeout
IO Timeout
IO Delete
No CAN Interface
2.6 CONFIGURATION USING RSNETWORX
Use the EDS Wizard to register the eds file. The
device will register as a Motor Starter named FPS. Select
device properties to view Device Parameters. When there
is a request to upload from device, select this option. This
will load the present configuration from the FPS.
3. DEVICENET OBJECTS (In Order of Class Number)
The module supports the following objects:
CLASS
0x01
0x02
0x03
0x04
0x05
0x29
0x2C
0x64
0x65
0x66
0x67
0x68
0x69
0x6A
0x6B
DESCRIPTION
Identity
Message Router
DeviceNet
Assembly
Connection
Control Supervisor
Overload
Set Point
Inverse Curve
Digital Input
Analog I/O
RTD Module
RTC Clock
User Registers
Data Logging
Page 3
Rev. 0-A-041114
FPS DeviceNet Interface
3.1 IDENTITY OBJECT
Identity Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Identity Class (1), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DESCRIPTION
Revision of this object.
Maximum number of instances.
DATA
TYPE
UINT
UINT
Identity Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify the specified attribute.
Reset: Performs reset services based on the parameter.
No Parameter or Parameter = 0: The DeviceNet driver
is reset with the existing MAC ID and baud rate.
Parameter = 1: The MAC ID is set to 63 and the baud
rate is set to 125 kb. The FPS will then perform a reset
that emulates cycling control power.
Identity Class (1), Instance (1) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
Vendor ID
Get
2
3
4
Device Type
Product Code
Revision
Get
Get
Get
5
Status
Get
Serial Number
Get
Product Name
Get
6
PARAM
1
7
100 (0x64)
2
Revision
Get
101 (0x65)
3
System Name
Get/Set
102 (0x66)
4
Password
Get/Set
103 (0x67)
5
Password Timeout
Get/Set
3.2 MESSAGE ROUTER
No attributes supported for this object.
DESCRIPTION
Identification of each vendor
by number.
Motor Starter
Platform Type
Major revision must match
the EDS value.
Summary Status of the
device.
Serial Number
Human Readable
Identification
Revision of Firmware
100 = 1.00
22 characters. Only 20
significant.
22 characters. Only 4
significant.
Sets password timeout in
minutes.
DEFAULT,
MINIMUM,
MAXIMUM
691
22
205
1.001
0, 0, 255
N/A, 0,
999999999
“Startco FPS”
N/A, 100, N/A
“Startco FPS”
“1111”
10, 1, 60
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
A2 02 C6
C6
WORD
0
UDINT
2
SHORT_
STRING
UINT
1
SHORT_
STRING
SHORT_
STRING
REAL
750
740
506/507
Page 4
Rev. 0-A-041114
FPS DeviceNet Interface
3.3 DEVICENET OBJECT
DeviceNet Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
DeviceNet Class (3), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
Revision
Get
DESCRIPTION
Revision of the DeviceNet object class.
Definition upon which the implementation
is based.
DEFAULT,
MINIMUM,
MAXIMUM
1
DATA
TYPE
UINT
DeviceNet Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify specified attribute.
Allocate_Master/Slave_Connection_Set:
Release_Master/Slave_Connection_Set:
DeviceNet Class (3), Instance (1) Attributes
ATTRIBUTE
NAME
SERVICES
1
2
MAC ID
Baud Rate
Get/Set
Get/Set
3
Buss-Off
Interrupt
Get/Set
4
Buss-Off
Counter
Get/Set
5
Allocation
Information
Net Trip
Action
Get
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
100 (0x64)
6
101 (0x65)
7
Net Alarm
Action
Get/Set
Get/Set
DESCRIPTION
Node Address
The baud rate of the device:
0 = 125 kb
1 = 250 kb
2 = 500 kb
Define Processing of BOI
0 = Hold CAN in Reset
1 = Automatic CAN Reset
Set to 0 on powerup or when
ID Reset is used. In both cases
existing connections are lost.
Number of times CAN went to
the bus-off state.
Writing any value clears the
counter.
Count held at 255.
Master/Slave Allocation
Indication
Trip Action taken on
communication error:
0 = Disable
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
Action taken on communication
error:
0 = Disable
1 = Alarm1
2 = Alarm2
3 = Alarm3
4 = Alarm1 & Alarm2
5 = Alarm1 & Alarm3
6 = Alarm1 & Alarm2 & Alarm3
7 = Alarm2 & Alarm3
DEFAULT,
MINIMUM,
MAXIMUM
63, 0, 63
0, 0, 2
USINT
USINT
0, 1, 0
BOOL
0, 0, 255
USINT
Array
0, 0, 7
BYTE,
USINT
UINT
665
0, 0, 7
UINT
666
DATA
TYPE
COMM
REGISTER
Page 5
Rev. 0-A-041114
FPS DeviceNet Interface
3.4 DEVICENET CONNECTION OBJECT
Connection Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify specified attribute.
DeviceNet Connection Class (5), Instance (0) Attributes
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
1
ATTRIBUTE
NAME
SERVICES
Revision
Get
100 (0x64)
10
Polled Cons ID
Get/Set
101 (0x65)
11
Polled Prod ID
Get/Set
(1)
(2)
DESCRIPTION
Revision of this Connection Object
Class.
Specifies output assembly ID.(1)
0 = None (Default)
1 = Basic Overload (0x02)
2 = Basic Motor Starter (0x03)
Specifies Input assembly ID. (2)
0 = None (Empty EPATH)
1 = Basic Overload (0x32)
2 = Extended Overload (0x33)
3 = Basic Motor Starter (0x34)
4 = Extended Motor Starter 1 (0x35)
5 = User Registers (0x64)
DEFAULT,
MINIMUM,
MAXIMUM
1
UINT
0, 0, 2
UINT
5, 0, 5
UINT
DATA
TYPE
Can also be set using Class 5, Instance 2, Attribute 16 path. See 3.5 for byte sizes. ID1 and ID2 are 1 byte.
Can also be set using Class 5, Instance 2, Attribute 14 path. See 3.5 for byte sizes. ID3 and ID4 are 1 byte, ID5 is 64
bytes.
Connection Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify specified attribute.
Delete: Delete specified connection instance.
Reset: Reset the connection instance.
DeviceNet Connection Class (5), Explicit Connection Instance (1) Attributes
ATTRIBUTE
NAME
SERVICES
1
State
Get
2
Instance Type
Get
3
Get
4
Transport Class
Trigger
Produced Cnxn ID
5
Consumed Cnxn ID
Get
6
Initial Comm
Characteristics
Get
7
Produced
Connection Size
Consumed
Connection Size
Get
ATTRIBUTE
NUMBER
8
DEVICENET
PARAMETER
Get
Get
DESCRIPTION
State of the object:
0 = Nonexistent
1 = Configuring
3 = Established
4 = Timed Out
5 = Deferred Delete
Indicates either IO or messaging
connection.
Defines behavior of the connection.
Placed in CAN Identifier field when
the connection transmits.
CAN Identifier Field value that
denotes message to be received.
Defines the Message Group(s) across
which productions and consumptions
associated with this Connection occur.
Maximum number of bytes
transmitted across this connection.
Maximum number of bytes received
across this connection.
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 5
USINT
0, 0, 0
USINT
0x83
BYTE
DATA
TYPE
UINT
UINT
BYTE
254
UINT
254
UINT
Page 6
Rev. 0-A-041114
FPS DeviceNet Interface
DeviceNet Connection Class (5), Explicit Connection Instance (1) Attributes (Continued)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
9
12 (0x0C)
13 (0x0D)
14 (0x0E)
15 (0x0F)
16 (0x10)
17 (0x11)
ATTRIBUTE
NAME
SERVICES
Expected Packet
Rate
Watchdog Timeout
Action
Get/Set
Produced
Connection Path
Length
Produced
Connection Path
Consumed
Connection
Path Length
Consumed
Connection Path
Get
Production Inhibit
Time
Get/Set
Get/Set
Get
Get
Get
DESCRIPTION
Defines timing (ms) associated with
this Connection. Resolution is 10 ms.
Defines how to handle
inactivity/watchdog timeouts.
1 = Auto Delete
3 = Deferred Delete
Number of bytes in the
produced_connection_path length
attribute.
Application Object producing data on
this connection.
Number of bytes in the
consumed_connection_path length
attribute.
Specifies the Application Object(s)
that are to receive the data consumed
by this connection object.
Defines minimum time (ms) between
new data production.
DEFAULT,
MINIMUM,
MAXIMUM
2500, 0,
65535
1, 1, 3
Set to 1 or 3
DATA
TYPE
UINT
USINT
0
UINT
{}
EPATH
0
UINT
{}
EPATH
0
UINT
DeviceNet Connection Class (5), Polled I/O Connection Instance (2) Attributes
ATTRIBUTE
NAME
SERVICES
1
State
Get
2
Instance Type
Get
3
Get
4
Transport Class
Trigger
Produced Cnxn ID
5
Consumed Cnxn ID
Get
6
Initial Comm
Characteristics
Get
7
Produced
Connection Size
Get
8
Consumed
Connection Size
Get
Maximum number of bytes received
across this connection.
9
Expected Packet
Rate
Watchdog Timeout
Action
Get/Set
Defines timing (ms) associated with
this connection.
Defines how to handle
inactivity/watchdog timeouts.
0 = Transition to Time Out
1 = Auto Delete
2 = Auto Reset
ATTRIBUTE
NUMBER
12 (0x0C)
DEVICENET
PARAMETER
Get
Get
DESCRIPTION
State of the object:
0 = Nonexistent
1 = Configuring
3 = Established
4 = Timed Out
Indicates either IO or messaging
connection.
0 = Explicit Message
1 = I/O Message
Defines behavior of the connection.
Placed in CAN Identifier field when
the connection transmits.
CAN Identifier Field value that
denotes message to be received.
Defines the Message Group(s) across
which productions and consumptions
associated with this Connection occur.
Maximum number of bytes
transmitted across this connection.
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 4
USINT
1, 0, 1
USINT
0x83
BYTE
DATA
TYPE
UINT
UINT
BYTE
Defined by
Assembly
Instance
Defined by
Assembly
Instance
0, 0, 65535,
N/A, N/A
0, 0, 0
UINT
UINT
UINT
USINT
Page 7
Rev. 0-A-041114
FPS DeviceNet Interface
DeviceNet Connection Class (5), Polled I/O Connection Instance (2) Attributes (Continued)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
13 (0x0D)
ATTRIBUTE
NAME
SERVICES
Produced
Connection Path
Length
Produced
Connection Path
Consumed
Connection
Path Length
Consumed
Connection Path
14 (0x0E)
15 (0x0F)
16 (0x10)
17 (0x11)
Production Inhibit
Time
Get
Get/Set
Get
Get/Set
Get/Set
DESCRIPTION
Number of bytes in the
produced_connection_path length
attribute. Symbolic notation.
Application Object producing data on
this connection.
Number of bytes in the
consumed_connection_path length
attribute. Symbolic notation.
Specifies the Application Object(s)
that are to receive the data consumed
by this Connection Object.
Defines minimum time (ms) between
new data production.
DEFAULT,
MINIMUM,
MAXIMUM
3, 3, 3
UINT
62 33 36
EPATH
3
UINT
{}
EPATH
0
UINT
DATA
TYPE
3.5 ASSEMBLY OBJECT
Assembly Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Assembly Class (4), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DEFAULT,
MINIMUM,
MAXIMUM
1
0x64
DESCRIPTION
Revision of this object.
Maximum instance of assembly.
DATA
TYPE
UINT
UINT
Assembly Object Instance Services
Get_Attribute_Single: Returns
assembly-instance
data. Applies to both output and input instances.
Set_Attribute_Single: Set assembly instance data.
Applies to output instances only. Service not supported
for input instances.
The following static input instances are supported and can be selected by setting parameter 473 to the desired ID:
DATA SIZE IN
PRODUCING
SYMBOLIC IO
DESCRIPTION
INSTANCE
ASSEMBLY ID
BYTES
CONNECTION PATH
1
2
3
4
5
(1)
50 (0x32)
51 (0x33)
52 (0x34)
53 (0x35)
103 (0x67)
Basic Overload
Extended Overload
Basic Motor Starter
Extended Motor Starter 1
User Registers (1) (Default)
1
1
1
1
64
62 33 32
62 33 33
62 33 34
62 33 35
62 36 34
Requires configuration of the User Defined Registers defined by parameters 451 to 466 and set via RSNetWorx or the
User Registers menu. SIZE IS FIXED AT 64 BYTES. See Assembly Class 4, Instance 0x67, Attribute 3.
The following static output instance are supported and can be selected by setting parameter 472 to the desired ID:
DATA SIZE IN
CONSUMING
SYMBOLIC IO
INSTANCE (1) DESCRIPTION
BYTES
CONNECTION PATH
ASSEMBLY ID
1
2
(1)
Default is None.
2 (0x02)
3 (0x03)
Basic Overload
Basic Motor Starter (Default)
1
1
62 30 32
62 30 33
Page 8
Rev. 0-A-041114
FPS DeviceNet Interface
Assemblies are configured using attributes 0x64 and
0x65 of Class 5, or selected by setting the Produced and
Consumed connection path attribute in the Polled I/O
connection instance. Setting the path to empty (no data),
will disable production or consumption and the
corresponding connection size will be zero.
Assemblies are accessed using Polled I/O or can be
read using Explicit Messaging. For explicit messaging,
the Class is 4, the Attribute is 3, and the Instance is the
assembly instance number.
Assembly Class (4), Instance (0x64), Attribute (3)
Produced Connection Path = “62 36 34”
This assembly is used to access any combination of
sixteen user-defined registers. Assembly size is fixed at
64 bytes. User defined registers are programmed using
the Setup  Hardware  Network Comms  User
Registers menu, or by explicit messaging to Class 0x6A
via the configuration tool. Register values are defined in
Appendix E of the FPS manual. Each comm register in
Appendix E defines a 16-bit value. For 32-bit float type
(DeviceNet REAL), only the first register of the pair
needs too be entered. For example, to configure an
ASSEMBLY
BIT
Bit 0
Bit 1
Bit 2
Bit 4
Bit 5
INSTANCE
SERVICES
CLASS_INSTANCE_
ATTRIBUTE
0x02
0x03
0x32
0x33
0x34
0x35
0x64
Get/Set
Get/Set
Get
Get
Get
Get
Get
04_02_03
04_03_03
04_32_03
04_33_03
04_34_03
04_35_03
04_64_03
assembly to read the first four RTD temperatures in RTD
Module 1, enter register numbers 902, 904, 906, 908 in
sequence. The first 16 bytes of the assembly will contain
the RTD data and the other 16 bytes do not contain any
valid data. Register definitions resulting in more than 64
bytes of data will be ignored.
Scanner byte size must be set to 64 bytes in all cases.
Overload/Starter Instances
Instances 2 to 5 and 0x32 to 0x36 are assemblies
containing attribute values from the Control Supervisor.
NAME
CLASS NAME
Faulted/Trip
Warning
Running 1
Ready
Control From Net
Control Supervisor
Control Supervisor
Control Supervisor
Control Supervisor
Control Supervisor
Assembly Class (4), Instance (0x32), Attribute (3) – Input – Basic Overload
Produced Connection Path = “62 33 32”
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BYTE
0
Reserved
Reserved
Reserved
Reserved
Reserved
Assembly Class (4), Instance (0x33), Attribute (3) – Input – Extended Overload
Produced Connection Path = “62 33 33”
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
0
Reserved
Reserved
Reserved
Reserved
Reserved
CLASS
INSTANCE
ATTRIBUTE
0x29
0x29
0x29
0x29
0x29
1
1
1
1
1
10
11
7
9
15
BIT 2
BIT 1
BIT 0
Reserved
Reserved
Faulted/
Trip
BIT 2
BIT 1
BIT 0
Reserved
Warning
Faulted/
Trip
Page 9
Rev. 0-A-041114
FPS DeviceNet Interface
Assembly Class (4), Instance (0x34), Attribute (3) – Input – Basic Starter
Produced Connection Path = “62 33 34”
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
0
Reserved
Reserved
Reserved
Reserved
Reserved
Assembly Class (4), Instance (0x35), Attribute (3) – Input – Extended Starter
Produced Connection Path = “62 33 35”
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
0
(1)
(2)
Reserved
Reserved
CntrlfrmNet
Ready
(2)
(1)
Reserved
BIT 1
BIT 0
Reserved
Faulted/
Trip
BIT 2
BIT 1
BIT 0
Running1
Warning
Faulted/
Trip
No trips, all interlocks valid, all perrmissives valid, CB open. Alarms allowed.
Must be in Remote Control, Remote Group must have Net Control enabled, Control Type other than None.
Assembly Class (4), Instance (0x02), Attribute (3) – Output – Basic Overload
Consumed Connection Path = “62 30 32”
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
0
Reserved
Reserved
Reserved
Reserved
Reserved
Assembly Class (4), Instance (0x03), Attribute (3) – Output – Basic Starter
Consumed Connection Path = “62 30 33”
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
0
(3)
BIT 2
Running1
Reserved
Reserved
Reserved
Reserved
Reserved
BIT 2
BIT 1
BIT 0
FaultReset
Reserved
Reserved
BIT 2
BIT 1
BIT 0
FaultReset
Reserved
Run1(3)
Run1 generates a CLOSE provided that conditions outlined in notes (1) and (2) are satisfied.
3.6 CONTROL SUPERVISOR OBJECT
State Transition Diagram
Close/open control can be performed using the control
supervisor class attributes. The control supervisor issues
commands to the FPS as shown in the state diagram.
Power Up
Idle State
0->1 on Run1
"Issue CB Close"
CB Open
Wait For
CB Open
Run1 State
Run1 = 0
"Issue CB Open"
Page 10
Rev. 0-A-041114
FPS DeviceNet Interface
NOTES:
Commands issued are only processed if the CtrlFromNet
(Attribute 15) is 1. For this bit to be set, the following
conditions must be met:
1) A starter type other than NONE must be selected
(Attribute 0x73).
2) FPS must be in REMOTE CONTROL.
3) Network control must be in the remote group (Attribute
0x72) - Default setting.
The user is responsible for setting Run1 bit
(Attributes 3) to zero when an open or trip condition
occurs.
Control Supervisor Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Control Supervisor Class (0x29), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DESCRIPTION
Revision of this object.
Maximum number of instances.
DATA
TYPE
UINT
UINT
Supervisor Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
Reset: Issues a STOP and transition to idle state.
Supervisor Class (0x29), Instance (1) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
3
7
9
10 (0x0A)
11 (0x0B)
12 (0x0C)
15 (0x0F)
Run 1 (1)
Running 1 (1)
Ready
Faulted
Warning
Fault Rst
Ctrl From Net
Get/Set
Get
Get
Get
Get
Get/Set
Get
(1)
Not applicable in Protection Only mode.
DESCRIPTION
Run 1 input from master.
Close Indication
Ready (No Trips)
One or more trips present.
One or more alarms present.
Reset issued on 0  1 transition.
1 = Network Control Enabled
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 1
0, 0, 1
0, 0, 1
0, 0, 1
0, 0, 1
0, 0, 1
N/A
DATA
TYPE
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
COMM
REGISTER
Page 11
Rev. 0-A-041114
FPS DeviceNet Interface
Supervisor Class (0x29), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
DESCRIPTION
100 (0x64)
15
Command
Get/Set
A command “Set” will cause the
requested command to be issued.
A “Get” will read the last
command.
0 = None
1 = Open
2 = Close
3 = Reset Trips
4 = Set RTC
5 = Clear Data Logging Records
6 = Clear Trips Counters
7 = Clear Energy Totals
8 = Clear Running Time
9 = Emergency I²t Reset
10 = Select Local-Input Ctrl
11 = Release Local-Input Ctrl
12 = Re-enable Temperature
Protection
13= Remote Trip Set
14= Remote Trip Clear
15= Remote Alarm Set
16= Remote Alarm Clear
17= Net Relay Set
18= Net Relay Clear
101 (0x65)
102 (0x66)
103 (0x67)
104 (0x68)
105(0x69)
106 (0x6A)
16
17
18
19
20
21
Reserved
Reserved
Reserved
Reserved
Reserved
Trip Action
Get/Set
107 (0x6B)
22
# of OPI's
Get/Set
OPI Loss Trip Action
0 = Disable
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
Selects the number of OPI's
connected to the control unit.
0 = 1 OPI
1= 2 OPI’s
2 = 3 OPI’s
108 (0x6C)
109 (0x6D)
110 (0x6E)
111 (0x6F)
112 (0x70)
23
24
25
26
27
Reserved
Reserved
Reserved
OPI Trips
RemGrpDig
Get
Get/ Set
113 (0x71)
28
RemGrpNet
Get/Set
114 (0x72)
29
RemGrpOPI
Get/Set
Number of OPI Comm Trips
Bind digital start sources to the
REMOTE group.
0 = Include in Group
1 = Do Not Include in Group
Bind OPI start sources to the
REMOTE group.
0 = Include in Group
1 = Not in Group
Bind Net start sources to the
REMOTE group.
0 = Include in Group
1 = Not in Group
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 12
DATA
TYPE
COMM
REGISTER
USINT
6
0, 0, 7
UINT
504
0, 0, 2
UINT
505
0, 0, 1
UINT
UINT
1182
524
0, 0, 1
UINT
525
0, 0, 1
UINT
526
Page 12
Rev. 0-A-041114
FPS DeviceNet Interface
Supervisor Class (0x29), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
DESCRIPTION
115 (0x73)
30
CB Control Type
Get/Set
116 (0x74)
31
CB Trip Source
Get/Set
117 (0x75)
32
CB Trip Sense
Get/Set
118 (0x76)
33
CB Close Sense
Get/Set
119 (0x77)
34
CB Close Pulse
Get/Set
120 (0x78)
35
CB Open Pulse
Get/Set
121 (0x79)
36
OPI Local Control
Get/Set
122 (0x7A)
123 (0x7B)
37
38
Open Retry
Open Count
Get/Set
Get
124 (0x7C)
39
RY Status Trips
Get
125 (0x7D)
40
TC Supervisor Trips
Get
126 (0x7E)
41
CC Supervisor Trips
Get
Selects the Device Control Type
0 = None
1 = Contractor
2 = 2-Coil Device
Defines which trip sources cause
the breaker or contractor to open.
0= Disabled
1= Trip1
2= Trip2
3= Trip3
4= Trip1 or Trip2
5= Trip1 or Trip3
6= Trip1 or Trip2 or Trip3
7= Trip2 or Trip3
Coil Supervisor Sense Location
0= None
1= CB Contact
2= CB Coil
Coil Supervisor Sense Location
0= None
1= CB Contact
2= CB Coil
Circuit Breaker Close Pulse
Width
Circuit Breaker Open Pulse
Width
0: Enable OPI Control
1: Disable OPI Control
Breaker Open Retry Count
Number of trips caused by an open
key press when control type is set
to None.
Number of Contactor Status
Trips
Number of Trip-Coil Supervisor
Trips
Number
of
Close-Coil
Supervisor Trips
127(0x7f)
128 (0x80)
42
43
Reserved
RY1 Function
Get/Set
129 (0x81)
44
RY1 Mode
Get/Set
Function Assigned to Relay 1
0 = None
1 = Trip1
2 = Trip2
3 = Trip3
4 = Alarm1
5 = Alarm2
6 = Alarm3
7 = CB Close
8 = CB-Open
9 = Contractor
10 = Trip1 Pulse
11 = Local
12 = Interlock
13 = Current
14 = Network Run1
15 = Group2 Selected
16 = Watchdog
0 = Fail Safe, 1 = Non Fail Safe
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 2
DATA
TYPE
COMM
REGISTER
UINT
520
0, 0, 7
UINT
521
0, 0, 2
UINT
522
0, 0, 2
UINT
523
0.3, 0.1, 5
REAL
527/528
0.3, 0.1, 5
REAL
529/530
0, 0, 1
UINT
531
0, 0, 5
UINT
UINT
532
1176
UINT
1177
UINT
1178
UINT
1179
0, 0, 16
UINT
610
0, 0, 1
UINT
611
Page 13
Rev. 0-A-041114
FPS DeviceNet Interface
Supervisor Class (0x29), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
DESCRIPTION
130 (0x82)
131 (0x83)
132 (0x84)
133 (0x85)
134 (0x86)
135 (0x87)
136 (0x88)
137 (0x89)
138 (0x8A)
45
46
47
48
49
50
51
52
53
RY2 Function
RY2 Mode
RY3 Function
RY3 Mode
RY4Function
RY4 Mode
RY5 Function
RY5 Mode
RY Pulse Time
Get/Set
Get/Set
Get/ Set
Get/Set
Get/ Set
Get/Set
Get/ Set
Get/Set
Get/Set
144 (0x90)
54
TA Summary
Get
145 (0x91)
55
IO Status
Get
146 (0x92)
56
Trip/Alarm Msg 0
Get
147 (0x93)
57
Trip/Alarm Msg 1
Get
148 (0x94)
58
Trip/Alarm Msg 2
Get
149 (0x95)
59
Trip/Alarm Msg 3
Get
150 (0x96)
60
Trip/Alarm Msg 4
Get
See Attribute 0x80
0 = Fail Safe, 1 = Non Fail Safe
See Attribute 0x80
0 = Fail Safe, 1 = Non Fail Safe
See Attribute 0x80
0 = Fail Safe, 1 = Non Fail Safe
See Attribute 0x80
0 = Fail Safe, 1 = Non Fail Safe
Specifies the duration of the trip
pulse when the RY function is
set to “Trip1 Pulse”.
FPS Status
Bit0: 1= Current > Threshold
Bit1: 1= 3IO Picked Up
Bit2: 1= Ph Picked Up
Bit3: Reserved
Bit4: 1= Trip1
Bit5: 1= Trip2
Bit6: 1= Trip3
Bit7: 1= Alarm1
Bit8: 1= Alarm2
Bit9: 1= Alarm3
Bit10: 1= ETR is ON
Bit11: 1= PTC is Open
Bit12: 1= Interdock Valid
Bit13: 1= Permissive Valid
Bit14: 1= Breaker Closed
Bit 0: IN1 Voltage Detected
Bit 1: IN2 Voltage Detected
Bit 2: IN3 Voltage Detected
Bit 3: IN4 Voltage Detected
Bit 4: IN5 Voltage Detected
Bit 5: IN6 Voltage Detected
Bit 6: IN7 Voltage Detected
Bit 7: Spare
Bit 8: Relay 1 Energized
Bit 9: Relay 2 Energized
Bit 10: Relay 3 Energized
Bit 11: Relay 4 Energized
Bit 12: Relay 5 Energized
Trip and Alarm FIFO. See Main
Product Manual Appendix F
T90. 255= No trip or alarm.
Trip and Alarm FIFO. See Main
Product Manual Appendix F
T90. 255= No trip or alarm.
Trip and Alarm FIFO. See Main
Product Manual Appendix F
T90. 255= No trip or alarm.
Trip and Alarm FIFO. See Main
Product Manual Appendix F
T90. 255= No trip or alarm.
Trip and Alarm FIFO. See Main
Product Manual Appendix F
T90. 255= No trip or alarm.
151 (0x97)
152 (0x98)
61
62
Reserved
Reserved
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 16
0, 0, 1
0, 0, 16
0, 0, 1
0, 0, 16
0, 0, 1
0, 0, 16
0, 0, 1
0.25, 0.05,
10
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
REAL
612
613
614
615
616
617
618
619
620
WORD
1110
WORD
1111
UINT
1112
UINT
1113
UINT
1114
UINT
1115
UINT
1116
Page 14
Rev. 0-A-041114
FPS DeviceNet Interface
Supervisor Class (0x29), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
153 (0x99)
154 (0x9A)
155 (0x9B)
156 (0x9C)
63
64
65
66
Reserved
Reserved
Reserved
CT Primary
Get/Set
CT Primary Rating (A)
157 (0x9D)
158 (0x9E)
67
68
EFCT Primary
System Voltage
Get/Set
Get/Set
EFCT Primary Rating (A)
Line-to-Line Voltage (kV)
159 (0x9F)
69
Vin Rating
Get/Set
160 (0xA0)
70
V Connection
Get/Set
161 (0xA1)
71
Frequency
Get/Set
162 (0xA2)
72
Set-Point Group
Get/Set
163 (0xA3)
73
I2/I1 Threshold
Get/Set
Input Voltage at Rated System
Voltage (kV)
Voltage Input Connection
0= None
1= 1PT
2= 2PT
3= 3PT / DIRECT
System Frequency
0 – 50, 1= 60 Hz
Selects Set Point Group
0= Group1
1= Group2
Unbalance Threshold
164 (0xA4)
165 (0xA5)
166 (0xA6)
167 (0xA7)
168 (0xA8)
169 (0xA9)
170 (0xAA)
171 (0xAB)
172 (0xAC)
173 (0xAD)
174 (0xAE)
175 (0xAF)
176 (0xB0)
177 (0xB1)
178 (0xB2)
179 (0xB3)
180 (0xB4)
181 (0xB5)
182 (0xB6)
183 (0xB7)
184 (0xB8)
185 (0xB9)
186 (0xBA)
187 (0xBB)
188 (0xBC)
189 (0xBD)
190 (0xBE)
191 (0xBF)
192 (0xC0)
193 (0xC1)
194 (0xC2)
195 (0xC3)
196 (0xC4)
197 (0xC5)
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Ia
Ib
Ic
Iave
ICT
3IO
Vab
Vbc
Vca
Va
Vb
Vc
S
Q
P
PF
Used I2T
Thermal Trend
Overload Time
+SeqI
–SeqI
Unbalance I
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
SERVICES
DESCRIPTION
Phase A Current (A)
Phase B Current (A)
Phase C Current (A)
Average Current (A)
EF CT Current (A)
Calculated 3IO (A)
Line–Line Voltage (KV)
Line–Line Voltage (KV)
Line–Line Voltage (KV)
Line–Line Voltage (KV)
Line–Line Voltage (KV)
Line–Line Voltage (KV)
Apparent Power (KVA)
Reactive Power (KVAR)
Real Power (KW)
Power Factor
Used Thermal Capacity (0/0)
Thermal Trend (0/0)
Overload Trip/ Reset Time (m)
Positive Sequence Current (pu)
Negative Sequence Current (pu)
Current Unbalance (pu)
DEFAULT,
MINIMUM,
MAXIMUM
DATA
TYPE
COMM
REGISTER
REAL
480/481
REAL
REAL
482/483
484/485
REAL
486/487
UINT
488/489
1, 0, 1
UINT
489
0, 0, 1
UINT
490
0.25, 0.10,
0.50
REAL
491/ 492
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
860/861
862/863
864/865
866/867
868/869
870/871
872/873
874/875
876/877
878/879
880/881
882/883
884/885
886/887
888/889
890/891
892/893
894/895
896/897
898/899
900/901
902/903
100, 1,
5000
5, 1, 5000
0.6, 0.12,
75
0.12, 0.03,
0.6
0,0,3
Page 15
Rev. 0-A-041114
FPS DeviceNet Interface
Supervisor Class (0x29), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
198 (0xC6)
199 (0xC7)
108
109
+SeqV
–SeqV
Get
Get
200 (0xC8)
201 (0xC9)
202 (0xCA)
203 (0xCB)
204 (0xCC)
205 (0xCD)
206 (0xCE)
207 (0xCF)
110
111
112
113
114
115
116
117
Unbalance V
Analog In
Frequency
Run Time
HS Frequency
KWs
KVAs
KVARs
Get
Get
Get
Get
Get
Get
Get
Get
DESCRIPTION
DEFAULT,
MINIMUM,
MAXIMUM
Positive Sequence Voltage (KV)
Negative Sequence Voltage
(KV)
Voltage Unbalance (pu)
Analog Input (nA)
Frequency of Voltage
Running Time (s)
High-Speed Input Frequency
KW seconds
KVA seconds
KVAR seconds
DATA
TYPE
COMM
REGISTER
REAL
REAL
904/905
906/907
REAL
REAL
REAL
UDINT
REAL
REAL
REAL
REAL
908/909
910/911
912/913
914/915
916/917
950/953
954/957
958/961
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
44
REAL
45/46
DATA
TYPE
COMM
REGISTER
UINT
8
3.7 OVERLOAD CLASS 0x2C
Overload Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify specified attribute.
Overload Class (0x2C), Instance (0) Attributes
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
100 (0x64)
121
Revision
Max Instance
Reset Type
Get
Get
Get/Set
100 (0x65)
122
Reset Level
Get/Set
ATTRIBUTE
NUMBER
DESCRIPTION
Revision of this object.
Maximum number of instances.
Specifies Type of Reset:
0= Normal
1= Autoreset
2= Rapid
Specifies Reset Level
DEFAULT,
MINIMUM,
MAXIMUM
1
1
0, 0, 2
0.3, 0.1,
0.9
Overload Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modify specified attribute.
Overload Class 0x2C, Instance 1 Attributes - Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
100 (0x64)
123
Trip Action
Get/Set
DESCRIPTION
0 = Disable
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
Page 16
Rev. 0-A-041114
FPS DeviceNet Interface
Overload Class 0x2C, Instance 1 Attributes - Group 1 (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
101 (0x65)
124
Alarm Action
Get/Set
0 = Disable
1 = Alarm1
2 = Alarm2
3 = Alarm3
4 = Alarm1 & Alarm2
5 = Alarm1 & Alarm3
6 = Alarm1 & Alarm2 & Alarm3
7 = Alarm2 & Alarm3
102 (0x66)
103 (0x67)
125
126
Reserved
Pickup
Get/Set
O/L Curve Pickup Level
104 (0x68)
105 (0x69)
127
128
Reserved
H-Factor
Get/Set
106 (0x6A)
129
C-Factor
Get/Set
107 (0x6B)
130
Get/Set
108 (0x6C)
131
Time
Constant
Alarm Level
Get/Set
Hot Factor Multiplier
For I < 100%
Time-Constant Multiplier
When Cooling
Thermal Time Constant
in Minutes
Level Where Alarm Occurs
109 (0x6D)
132
Trip Count
Get
DESCRIPTION
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
DATA
TYPE
COMM
REGISTER
UINT
9
1, 0.1,
1.25
REAL
11/12
0.5, 0.1,
1.0
2, 1, 10
REAL
15/16
REAL
17/18
10, 1, 60
REAL
19/20
1.0, 0.5,
1.0
REAL
21/22
UINT
1130
Counts Number of Trips
Overload Class 0x2C, Instance 2 Attributes – Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
100 (0x64)
133
Trip Action
Get/Set
101 (0x65)
134
Alarm Action
Get/Set
102 (0x66)
103 (0x67)
135
136
Reserved
Pickup
Get/Set
O/L Curve Pickup Level
104 (0x68)
105 (0x69)
137
138
Reserved
H-Factor
Get/Set
106 (0x6A)
139
C-Factor
Get/Set
107 (0x6B)
140
Get/Set
108 (0x6C)
141
Time
Constant
Alarm Level
Get/Set
Hot Factor Multiplier
For I < 100%
Time-Constant Multiplier
When Cooling
Thermal Time Constant
in Minutes
Level Where Alarm Occurs
109 (0x6D)
142
Trip Count
Get
DESCRIPTION
0 = Disable
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
0 = Disable
1 = Alarm1
2 = Alarm2
3 = Alarm3
4 = Alarm1 & Alarm2
5 = Alarm1 & Alarm3
6 = Alarm1 & Alarm2 & Alarm3
7 = Alarm2 & Alarm3
Counts Number of Trips
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
DATA
TYPE
COMM
REGISTER
UINT
26
1, 0, 7
UINT
27
1, 0.1,
1.25
REAL
29/30
0.5, 0.1,
1.0
2, 1, 10
REAL
33/34
REAL
35/36
10, 1, 60
REAL
37/38
1.0, 0.5,
1.0
REAL
39/40
UINT
1131
Page 17
Rev. 0-A-041114
FPS DeviceNet Interface
3.8 SET POINT CLASS 0x64
Set Point Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set Point Class 0x64, Instance 0 Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Number of last instance.
Set Point Object Instances
Set Point Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
The set point class consists of seven attributes. Each
set-point instance may use some or all of these attributes.
Attribute 1 - Trip Action
Specifies the action to take on a trip.
0 = Disable
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
DEFAULT,
MINIMUM,
MAXIMUM
5
20
Attribute 2 - Alarm Action
Specifies the action to take on an alarm.
0 = Disable
1 = Alarm1
2 = Alarm2
3 = Alarm3
4 = Alarm1 & Alarm2
5 = Alarm1 & Alarm3
6 = Alarm1 & Alarm2 & Alarm3
7 = Alarm2 & Alarm3
Attribute 3 - Trip Level
Attribute 4 - Trip Delay
Attribute 5 - Alarm Level
Attribute 6 - Alarm Delay
Attribute 7 - Trip Counter for the set point
DATA
TYPE
UINT
UINT
Page 18
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x64, Instance 1 - Definite-Time Overcurrent, Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
150
151
152
153
154
155
156
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
10, 1, 15
0.05, 0, 10
10, 0.1, 15
0.05, 0, 10
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
70
71
72/73
74/75
76/77
78/79
1134
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
84
85
86/87
88/89
90/91
92/93
1135
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
120
121
122/123
124/125
126/127
128/129
1138
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
136
137
138/139
140,141
142/143
144/145
1139
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
150
151
152/153
154/155
156/157
158/159
1140
Class 0x64, Instance 2 - Definite-Time Overcurrent, Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
157
158
159
160
161
162
163
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
10, 1, 15
0.05, 0, 10
10, 0.1, 15
0.05, 0, 10
Class 0x64, Instance 3 – 3I0 Definite-Time Earth Fault, Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
164
165
166
167
168
169
170
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
10, 0.1, 15
0.05, 0, 10
10, 0.1, 15
0.05, 0, 10
Class 0x64, Instance 4 – 3I0 Definite-Time Earth Fault, Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
171
172
173
174
175
176
177
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
10, 0.1, 15
0.05, 0, 10
10, 0.1, 15
0.05, 0, 10
Class 0x64, Instance 5 – EFCT Definite-Time, Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
178
179
180
181
182
183
184
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.4, 0.01, 1
0.25, 0, 100
0.2, 0.01, 1
1, 0, 100
Page 19
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x64, Instance 6 - EFCT Definite-Time, Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
185
186
187
188
189
190
191
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.4, 0.01, 1
0.25, 0, 100
0.2, 0.01, 1
1, 0, 100
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
166
167
168/169
170/171
172/173
174/175
1141
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
180
181
182/183
184/185
186/187
188/189
1142
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
192
193
194/195
196/197
1143
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
198
199
200/201
202/203
1144
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
214
215
216/217
218/219
220/221
222/223
1145
Class 0x64, Instance 7 – Unbalance (I)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
192
193
194
195
196
197
198
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
1, 0, 7
0.25, 0.05, 1
15, 1, 100
0.10, 0.05, 1
10, 1, 100
Class 0x64, Instance 8 – Phase Loss (I)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
4
6
7
199
200
201
202
203
Trip Action
Alarm Action
Trip Delay
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
5, 1, 100
2, 1, 100
Class 0x64, Instance 9 – Phase Reverse (I)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
4
6
7
204
205
206
207
208
Trip Action
Alarm Action
Trip Delay
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
5, 1, 100
2, 1, 100
Class 0x64, Instance 0x0A – Unbalance (V)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
209
210
211
212
213
214
215
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
1, 0, 7
0.25, 0.05, 1
15, 1, 100
0.10, 0.05, 1
10, 1, 100
Page 20
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x64, Instance 0x0B – Phase Loss (V)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
4
6
7
216
217
218
219
220
Trip Action
Alarm Action
Trip Delay
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
5, 1, 100
2, 1, 100
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
224
225
226/227
228/229
1146
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
234
235
236/237
238/239
1147
Class 0x64, Instance 0x0C – Phase Reverse (V)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
4
6
7
221
222
223
224
225
Trip Action
Alarm Action
Trip Delay
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
5, 1, 100
2, 1, 100
Class 0x64, Instance 0x0D - Undervoltage
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
226
227
228
229
230
231
232
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.7, 0.5, 1
5, 1, 500
0.8, 0.5, 1
5, 1, 500
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
242
243
244/245
246/247
248/249
250/251
1149
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
254
255
256/257
258/259
260/261
262/263
1148
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
270
271
272/273
274/275
276/277
278/279
1150
Class 0x64, Instance 0x0E - Overvoltage
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
233
234
235
236
237
238
239
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
1, 0, 7
1.2, 1, 1.4
5, 1, 500
1.1, 1, 1.4
5, 1, 500
Class 0x64, Instance 0x0F - Underfrequency
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
240
241
242
243
244
245
246
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
45, 30, 80
5, 1, 500
48, 30, 80
1, 1, 500
Page 21
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x64, Instance 0x10 - Overfrequency
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
247
248
249
250
251
252
253
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
65, 30, 80
5, 1, 500
62, 30, 80
1, 1, 500
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
280
281
282/283
284/285
286/287
288/289
1151
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
294
295
296/297
298/299
300/301
302/303
1152
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
304
305
306/307
308/309
310/311
312/313
1153
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
324
325
1157
Class 0x64, Instance 0x11 - Power Factor Lag
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
254
255
256
257
258
259
260
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.8, 0.5, 1
5, 1, 500
0.9, 0.5, 1
10, 1, 500
Class 0x64, Instance 0x12 - Power Factor Lead
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
261
262
263
264
265
266
267
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.8, 0.5, 1
5, 1, 500
0.9, 0.5, 1
10, 1, 500
Class 0x64, Instance 0x13 – PTC Temperature
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
7
268
269
270
Trip Action
Alarm Action
Trip Count
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
Page 22
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x64, Instance 0x14 - Reversepower
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
271
272
273
274
275
276
277
Trip Action
Alarm Action
Trip Level
Trip Delay
Alarm Level
Alarm Delay
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 7
0, 0, 7
0.1, 0.1, 1
5, 0.5, 500
0.1, 0.1, 1
1, 0.5, 500
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
REAL
REAL
UINT
204
205
206/207
208/209
210/211
212/213
1190
3.9 INVERSE CURVE CLASS 0x65
Inverse Curve Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Inverse Curve Class 0x65, Instance 0 Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DEFAULT,
MINIMUM,
MAXIMUM
1
4
DESCRIPTION
Revision of this object.
Maximum number of instances.
DATA
TYPE
UINT
UINT
Inverse Curve Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute
The inverse curve class consists of five attributes.
Attribute 1 - Trip Action
Specifies the action to take on a trip.
0 = Disable Trip
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
3 = IEC Short Inverse A
4 = IEC Long Inverse B
5 = IEEE Moderate Inverse
6 = IEEE Very Inverse
7 = IEEE Extreme Inverse
Attribute 3 – Multiplier
Adjusts the trip time for the selected curve type.
Attribute 4 – Pickup
Sets the threshold current in multiples of CT rating.
Attribute 5 – Trip Count
Trip counter for the set point.
Attribute 2 – Curve
0 = IEC Normal Inverse A
1 = IEC Very Inverse B
2 = IEC Extreme Inverse C
For curve formulas, see the FPS product manual.
Class 0x65, Instance 1 – Phase Inverse, Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
285
286
287
288
289
Trip Action
Curve
Multiplier
Pickup
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
0, 0, 7
0.2, 0.05, 1
2, 0.1, 10
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
50
51
52/53
54/55
1132
Page 23
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x65, Instance 2 – Phase Inverse, Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
290
291
292
293
294
Trip Action
Curve
Multiplier
Pickup
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
0, 0, 7
0.2, 0.05, 1
2, 0.1, 10
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
60
61
62/63
64/65
1133
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
100
101
102/103
104/105
1136
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
110
111
112/113
114/115
1137
Class 0x65, Instance 3 – 3I0 Inverse, Group 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
295
296
297
298
299
Trip Action
Curve
Multiplier
Pickup
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
0, 0, 7
0.2, 0.05, 1
2, 0.1, 10
Class 0x65, Instance 4 – 3I0 Inverse, Group 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
300
301
302
303
304
Trip Action
Curve
Multiplier
Pickup
Trip Count
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
1, 0, 7
0, 0, 7
0.2, 0.05, 1
2, 0.1, 10
3.10 DIGITAL INPUT CLASS 0x66
Digital Input Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Digital Input Class (0x66), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Maximum number of instances.
Digital Input Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
DEFAULT,
MINIMUM,
MAXIMUM
1
7
DATA
TYPE
UINT
UINT
Page 24
Rev. 0-A-041114
FPS DeviceNet Interface
The digital-input class consists of 5 attributes.
Attribute 1 - Function
Selects the function of the digital input.
0 = None
1 = Group 2 Select
2 = Local Control Select
3 = Permissive
4 = 3-Wire Close
5 = 2-Wire Close
6 = 3-Wire Close Local
7 = 2-Wire Close Local
8 = 52a Close Status
9 = 52b Open Status
10 = Reserved 10
11 = Reserved 11
12 = Reserved 12
13 = Interlock
14 = Trip1
15 = Reset
16 = Positive-Edge Trigger
17 = Negative-Edge Trigger
18 = Transition Trigger
Attribute 2 - Bypass Enable/Disable
Attribute applies when the input function is trip. When
enabled, the input is bypassed for the time defined by the
Bypass Delay when a breaker or contactor is closed.0 =
Enable, 1 = Disable
Attribute 3 - Bypass Delay
Defines the Trip bypass time duration on close.
Attribute 4 - Trip Delay
Applies only to the trip function.
Attribute 5 - Trip Count
The trip counter only applies to the trip function.
Class 0x66, Instance 1 - Input 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
315
316
317
318
319
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
540
541
542/543
544/545
1158
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
550
551
552/553
554/555
1159
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
560
561
562/563
564/565
1160
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
570
571
572/573
574/575
1161
Class 0x66, Instance 2 - Input 2
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
320
321
322
323
324
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
Class 0x66, Instance 3 - Input 3
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
325
326
327
328
329
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
Class 0x66, Instance 4 - Input 4
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
330
331
332
333
334
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
Page 25
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x66, Instance 5 - Input 5
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
335
336
337
338
339
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
580
581
582/583
584/585
1162
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
590
591
592/593
594/595
1163
DATA
TYPE
COMM
REGISTER
UINT
UINT
REAL
REAL
UINT
600
601
602/603
604/605
1164
Class 0x66, Instance 6 - Input 6
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
340
341
342
343
344
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
Class 0x66, Instance 7 - Input 7
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
345
346
347
348
349
Function
Bypass Enable/Disable
Bypass Delay
Trip Delay
Trip Counter
Get/Set
Get/Set
Get/Set
Get/Set
Get
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 18
1, 0, 1
5, 0.5, 100
0.1, 0.01, 100
3.11 ANALOG I/O CLASS 0x67
Analog I/O Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Analog I/O Class (0x67), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Maximum number of instances.
Analog I/O Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DATA
TYPE
UINT
UINT
Page 26
Rev. 0-A-041114
FPS DeviceNet Interface
Analog I/O Class (0x67), Instance (1) Attributes
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
1
350
Analog In Type
Get/Set
2
351
Trip Action
Get/Set
3
352
Alarm Action
Get/Set
4
353
High Trip
Get/Set
5
354
Low Trip
Get Set
6
7
355
356
Trip Delay
High Alarm
Get/Set
Get/Set
8
357
Low Alarm
Get/Set
DESCRIPTION
Defines the analog-input type:
0 = Metering
1 = Protection (Trip1, Alarm1
Enabled)
Sets trip action for High and
Low Trips.
Sets alarm actions for High and
Low Alarms.
Sets high trip level for generic
input type. (mA)
Sets low trip level for generic
input type. (mA)
Applies to generic type. (s)
Sets high alarm level for generic
input type. (mA)
Sets low alarm level for generic
input type. (mA)
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 3
DATA
TYPE
COMM
REGISTER
UINT
630
0, 0, 7
UINT
631
0, 0, 7
UINT
632
16, 0.1, 20
REAL
633/634
7, 0.1, 20
REAL
635/636
5, 0.01, 100
14, 0.1, 20
REAL
REAL
637/638
639/640
9, 0.1, 20
REAL
641/642
Analog I/O Class (0x67), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
9
10 (0x0A)
358
359
Alarm Delay
Out Param
Get/Set
Get/Set
11 (0x0B)
12 (0x0C)
360
361
High Trips
Low Trips
Get
Get
DESCRIPTION
Applies to generic type (s)
Specifies the analog output
parameter:
0 = Phase Current
1 = Earth Leakage
2 = Thermal Capacity
3 = Max Group A RTD
4 = Max Group B RTD
5 = Max Group C RTD
6 = Max Ambient RTD
7 = Voltage
8 = Unbalance (I)
9 = Power Factor
10 = Real Power
11 = Reactive Power
12 = Apparent Power
13 = Zero (4 mA)
14 = Full Scale (20 mA)
Input-High Trip Count
Input-Low Trip Count
DEFAULT,
MINIMUM,
MAXIMUM
1, 0.01, 100
0, 0, 14
DATA
TYPE
COMM
REGISTER
REAL
UINT
643/644
650
UINT
UINT
1155
1156
Page 27
Rev. 0-A-041114
FPS DeviceNet Interface
3.12 RTD MODULE CLASS 0x68
RTD Module Object Class Services
Get_Attribute_Single: Returns contents of specified attribute.
Set_Attribute_Single: Modifies specified attribute.
Class 0x68, Instance 0, Attributes
ATTRIBUTE
NUMBER
PARAM
1
2
ATTRIBUTE
NAME
SERVICES
Revision Number
Max Instance
Get
Get
100 (0x64)
365
Modules Used
Get/Set
101 (0x65)
366
Sensor Trip Action
Get/Set
102 (0x66)
367
Sensor Alarm
Action
Get/Set
103 (0x67)
368
Module Error Trip
Action
Get/Set
104 (0x68)
369
Module Error Alarm
Action
Get/Set
105 (0x69)
370
Get
106 (0x6A)
107 (0x6B)
108 (0x6C)
109 (0x6D)
110 (0x6E)
111 (0x6F)
112 (0x70)
113 (0x71)
114 (0x72)
115 (0x73)
116 (0x74)
117 (0x75)
118 (0x76)
119 (0x77)
371
372
373
374
375
376
377
378
379
380
381
382
383
384
Module1 Comm
Trip Count
Reserved
Reserved
Sensor Trip Count
Reserved
Reserved
Reserved
Max GrpA Temp
Max GrpB Temp
Max GrpC Temp
Max Amb Temp
Min GrpA Temp
Min GrpB Temp
Min GrpC Temp
Min Ambient Temp
DESCRIPTION
Revision number of this class.
Maximum Number of RTD
Modules
Specifies the Number of RTD
Modules Used
Specifies trip action to take on a
sensor error.
0 = Disable Trips
1 = Trip1
2 = Trip2
3 = Trip3
4 = Trip1 & Trip2
5 = Trip1 & Trip3
6 = Trip1 & Trip2 & Trip3
7 = Trip2 & Trip3
A Trip initiates an OPEN when a
CB Control is enabled.
Specifies alarm action to take on
a sensor error.
0 = Disable Alarms
1 = Alarm1
2 = Alarm2
3 = Alarm3
4 = Alarm1 & Alarm2
5 = Alarm1 & Alarm3
6 = Alarm1 & Alarm2 & Alarm3
7 = Alarm2 & Alarm3
Specifies trip action to take on a
module error. Action list is the
same as Attribute 9.
Specifies alarm action to take on
a module error. Action list is the
same as Attribute A.
Number of module1
communication-error trips.
DEFAULT,
MINIMUM,
MAXIMUM
1
3
UINT
UINT
0, 0, 1
UINT
328
0, 0, 7
UINT
331
1, 0, 7
UINT
332
0, 0, 7
UINT
329
1, 0, 7
UINT
330
UINT
1173
DATA
TYPE
COMM
REGISTER
Get
Number of RTD sensor trips.
UINT
1174
Get
Get
Get
Get
Get
Get
Get
Get
Max Group A Temperature (°C)
Max Group B Temperature (°C)
Max Group C Temperature (°C)
Max Ambient Temperature (°C)
Min Group A Temperature (°C)
Min Group B Temperature (°C)
Min Group C Temperature (°C)
Min Ambient Temperature (°C)
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
934/935
936/937
938/939
940/941
942/943
944/945
946/947
948/949
Page 28
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x68, Instance 0, Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
120 (0x78)
121 (0x79)
122 (0x7A)
123 (0x7B)
385
386
387
388
124 (0x7C)
389
ATTRIBUTE
NAME
UTemp Trip
UTemp Alarm
UTemp Trip Action
UTemp Alarm
Action
UTemp Trip Count
SERVICES
Get/Set
Get/Set
Get/Set
Get/Set
Get
DESCRIPTION
Trip Level Selection
Alarm Level Selection
Trip Action
Trip Action
DEFAULT,
MINIMUM,
MAXIMUM
4, 0, 8
4, 0, 8
0, 0, 7
0, 0, 7
Undertemperature Trip Count
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
UINT
314
315
316
317
UINT
1191
RTD Module Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
Object Instance Attributes 1 to 8 define the RTD type.
Selecting an RTD will enable trip and alarm set points.
The trip action is fixed as Trip1 and the alarm action is
fixed as Alarm1.
0 = RTD Disabled
1 = Platinum 100 ohm
2 = Nickel 100 ohm
3 = Nickel 120 ohm
4 = Copper 10 ohm
Object Instance Attributes 0x11 to 0x20 define the trip
and alarm settings in degrees C. The trip action is fixed
as Trip1 and the alarm action is fixed as Alarm1.
Object Instance Attributes 0x09 to 0x10 define the
RTD function.
0 = Stator
1 = Bearing
2 = Load
3 = Ambient
Object Instance Attributes 0x31 to 0x38 are the trip
counters for each of the RTD's
Object Instance Attributes 0x21 to 0x28 define an 18character name.
Object Instance Attributes
temperature readings.
0x29
to
0x30
are
Page 29
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x68, Instance 1
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
8
9
10 (0x0A)
11 (0x0B)
12 (0x0C)
13 (0x0D)
14 (0x0E)
15 (0x0F)
16 (0x10)
17 (0x11)
18 (0x12)
19 (0x13)
20 (0x14)
21 (0x15)
22 (0x16)
23 (0x17)
24 (0x18)
25 (0x19)
26 (0x1A)
27 (0x1B)
28 (0x1C)
29 (0x1D)
30 (0x1E)
31 (0x1F)
32 (0x20)
33 (0x21)
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
RTD #1 Type
RTD #2 Type
RTD #3 Type
RTD #4 Type
RTD #5 Type
RTD #6 Type
RTD #7 Type
RTD #8 Type
RTD #1 Function
RTD #2 Function
RTD #3 Function
RTD #4 Function
RTD #5 Function
RTD #6 Function
RTD #7 Function
RTD #8 Function
RTD #1 Trip Level
RTD #1 Alarm Level
RTD #2 Trip Level
RTD #2 Alarm Level
RTD #3 Trip Level
RTD #3 Alarm Level
RTD #4 Trip Level
RTD #4 Alarm Level
RTD #5 Trip Level
RTD #5 Alarm Level
RTD #6 Trip Level
RTD #6 Alarm Level
RTD #7 Trip Level
RTD #7 Alarm Level
RTD #8 Trip Level
RTD #8 Alarm Level
RTD #1 Name
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 4
0, 0, 3
0, 0, 3
0, 0, 3
0, 0, 3
0, 0, 3
0, 0, 3
0, 0, 3
0, 0, 3
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
130, 40, 200
110, 40, 200
RTD M1 #1
34 (0x22)
423
RTD #2 Name
Get/Set
RTD M1 #2
35 (0x23)
424
RTD #3 Name
Get/Set
RTD M1 #3
36 (0x24)
425
RTD #4Name
Get/Set
RTD M1 #4
37 (0x25)
426
RTD #5 Name
Get/Set
RTD M1 #5
38 (0x26)
427
RTD #6 Name
Get/Set
RTD M1 #6
39 (0x27)
428
RTD #7 Name
Get/Set
RTD M1 #7
40 (0x28)
429
RTD #8 Name
Get/Set
RTD M1 #8
41 (0x29)
42 (0x2A)
43 (0x2B)
44 (0x2C)
45 (0x2D)
46 (0x2E)
47 (0x2F)
48 (0x30)
430
431
432
433
434
435
436
437
RTD #1 Temp RDG
RTD #2 Temp RDG
RTD #3 Temp RDG
RTD #4 Temp RDG
RTD #5 Temp RDG
RTD #6 Temp RDG
RTD #7 Temp RDG
RTD #8 Temp RDG
Get
Get
Get
Get
Get
Get
Get
Get
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352/353
354/355
356/357
358/359
360/361
362/363
364/365
366/367
368/369
370/371
372/373
374/375
376/377
378/379
380/381
382/383
384..393
394..403
404..413
414..423
424..433
434..443
444..453
454..463
918/919
920/921
922/923
924/925
926/927
928/929
930/931
932/933
Page 30
Rev. 0-A-041114
FPS DeviceNet Interface
Class 0x68, Instance 1 (continued)
ATTRIBUTE
NUMBER
DEVICENET
PARAMETER
ATTRIBUTE
NAME
SERVICES
49 (0x31)
50 (0x32)
51 (0x33)
52 (0x34)
53 (0x35)
54 (0x36)
55 (0x37)
56 (0x38)
438
439
440
441
442
443
444
445
RTD #1 Trip Cntr
RTD #2 Trip Cntr
RTD #3 Trip Cntr
RTD #4 Trip Cntr
RTD #5 Trip Cntr
RTD #6 Trip Cntr
RTD #7 Trip Cntr
RTD #8 Trip Cntr
Get
Get
Get
Get
Get
Get
Get
Get
DEFAULT,
MINIMUM,
MAXIMUM
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
1165
1166
1167
1168
1169
1170
1171
1172
3.13 RTC CLASS 0x69
RTC Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
RTC Class (0x69), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Maximum number of instances.
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DATA
TYPE
UINT
UINT
RTC Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
RTC Class (0x69), Instance (1) Attributes
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
1
446
IRIG Hrs Offset
Get/Set
2
447
IRIG Min Offset
Get/Set
3
448
RTC Date
Get
4
449
RTC Time
Get
5
450
RTC Set
Get/Set
(1)
(1)
DESCRIPTION
RTC Hrs = IRIG Hrs + IRIG Hr
Offset
RTC Min = IRIG Min + IRIG
Min Offset
Number of Days Since 1972-0101
Number of Milliseconds Since
00:00:00:00.000
String Used to Set the Date and
Time YY/MM/DD-HH:MM:SS
Time value is not activated until a SET RTC command
is issued using Class 0x29, Instance 1, Attribute 0x64.
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 30
DATA
TYPE
COMM
REGISTER
REAL
726/727
0, 0, 23
REAL
724/725
DATE
720/721
TIME
OF DAY
SHORT_
STRING
722/723
0, 0,
86399999
728..737
FPS DeviceNet Interface
Page 31
Rev. 0-A-041114
3.14 USER REGISTER CLASS 0x6A
This object defines the communication registers that
generate the data for Assembly Class 4, Instance 0x67,
Attribute 3. Register values are defined in Appendix E of
the Main Product Manual. Each register in Appendix E
defines a 16-bit value. For 32-bit float type (DeviceNet
REAL), only the first register of the pair needs too be
entered. For example, to configure an assembly to read
the first four RTD temperatures in RTD Module 1, enter
register numbers 902, 904, 906, 908. The first 16 bytes of
the assembly will contain the RTD data and the remaining
bytes do not contain any valid data. Register definitions
resulting in more than 64 bytes of data will be ignored.
User Register Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
User Register Class (0x6A), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Maximum number of instances.
User Register Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DATA
TYPE
UINT
UINT
Page 32
Rev. 0-A-041114
FPS DeviceNet Interface
User Register Class (0x6A), Instance (1) Attributes
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
Register 0
Register 1
Register 2
Register 3
Register 4
Register 5
Register 6
Register 7
Register 8
Register 9
Register 10
Register 11
Register 12
Register 13
Register 14
Register 15
Register 16
Register 17
Register 18
Register 19
Register 20
Register 21
Register 22
Register 23
Register 24
Register 25
Register 26
Register 27
Register 28
Register 29
Register 30
Register 31
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
Get/Set
DESCRIPTION
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
User Register Value
3.15 DATA LOGGING CLASS 0x6B
This object is used to access one of 64 data-logging
records. The Record Selector value defines the record
that is displayed. Record Head indicates the record
number for the latest record.
Data Logging Object Class Services
Get_Attribute_Single: Returns contents of specified
attribute.
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
0, 0, 1189
DATA
TYPE
COMM
REGISTER
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
1400
1401
1402
1403
1404
1405
1406
1407
1408
1409
1410
1411
1412
1413
1414
1415
1416
1417
1418
1419
1420
1421
1422
1423
1424
1425
1426
1427
1428
1429
1430
1431
Page 33
Rev. 0-A-041114
FPS DeviceNet Interface
Data Logging Class (0x6B), Instance (0) Attributes
ATTRIBUTE
NUMBER
ATTRIBUTE
NAME
SERVICES
1
2
Revision
Max Instance
Get
Get
DESCRIPTION
Revision of this object.
Maximum number of instances.
DEFAULT,
MINIMUM,
MAXIMUM
1
1
DATA
TYPE
UINT
UINT
Data Logging Object Instance Services
Get_Attribute_Single: Returns contents of specified
attribute.
Set_Attribute_Single: Modifies specified attribute.
Data Logging Class (0x6B), Instance (1) Attributes
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
1
485
Record Count
Get
2
486
Record Head
Get
3
487
Record Selector
Get/Set
4
488
Record Date
Get
5
489
Record Time
Get
6
490
Record Type
Get
7
491
Trip Code
Get
8
9
10 (0x0A)
11 (0x0B)
492
493
494
495
IA
IB
IC
ICT
Get
Get
Get
Get
DESCRIPTION
Number of captured records
since the last time the event
records were cleared.
Points to next record. Latest
record at Record Head minus 1.
Selects the record for which the
data is displayed in this instance.
The date when the record was
captured.
Time-of-Day the record was
captured.
Specifies the trigger source.
0= Record Empty
1= Trip Record
2= + Edge Record
3= – Edge Record
4= +/– Edge Record
See Main Product Manual
Appendix F T27 for a list of trip
codes. 255 = No Trip or Alarm
Phase A Current (A)
Phase B Current (A)
Phase C Current (A)
Ground-Fault Current (A)
DEFAULT,
MINIMUM,
MAXIMUM
0, 0, 65535
DATA
TYPE
COMM
REGISTER
UINT
980
0, 0, 63
UINT
981
0, 0, 63
UINT
982
0, 0, 65535
DATE
983/984
0, 0,
86399999
0, 0, 4
TOD
985/986
UINT
987
0, 0, 255
UINT
988
REAL
REAL
REAL
REAL
989/990
991/992
993/994
995/996
Page 34
Rev. 0-A-041114
FPS DeviceNet Interface
Data Logging Class (0x6B), Instance (1) Attributes (continued)
ATTRIBUTE
NUMBER
PARAM
ATTRIBUTE
NAME
SERVICES
12 (0x0C)
13 (0x0D)
14 (0x0E)
15 (0x0F)
16 (0x10)
17 (0x11)
18 (0x12)
19 (0x13)
20 (0x14)
21 (0x15)
22 (0x16)
23 (0x17)
24 (0x18)
25 (0x19)
26 (0x1A)
27 (0x1B)
28 (0x1C)
29 (0x1D)
30 (0x1E)
31 (0x1F)
32 (0x2A)
33 (0x21)
34 (0x22)
35 (0x23)
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
3I0
Vab
Vbc
Vca
Va
Vb
Vc
Ain
Unbalance (I)
Unbalance (V)
I2T Used
Frequency
S
P
Q
PF
M1 RTD1
M1 RTD2
M1 RTD3
M1 RTD4
M1 RTD5
M1 RTD6
M1 RTD7
M1 RTD8
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
DESCRIPTION
Calculated Residual
Line-to-Line Voltage (kV)
Line-to-Line Voltage (kV)
Line-to-Line Voltage (kV)
Line-to-Ground Voltage (kV)
Line-to-Ground Voltage (kV)
Line-to-Ground Voltage (kV)
Analog Input
Current Unbalance (pu)
Current Unbalance (pu)
Used I2T Overload (pu)
Frequency in Hz
Apparent Power (kVA)
Real Power (kW)
Reactive Power (kVAR)
Power Factor (-1, +1)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
RTD Temperature Reading (ºC)
DEFAULT,
MINIMUM,
MAXIMUM
DATA
TYPE
COMM
REGISTER
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
997/998
999/1000
1001/1002
1003/1004
1005/1006
1007/1008
1009/1010
1011/1012
1013/1014
1015/1016
1017/1018
1019/1020
1021/1022
1023/1024
1025/1026
1027/1028
1029/1030
1031/1032
1033/1034
1035/1036
1037/1038
1039/1040
1041/1042
1043/1044
Page 35
Rev. 0-A-041114
FPS DeviceNet Interface
FPS FIRMWARE
APPENDIX A
FPS DEVICENET EDS FILES
EDS FILES
EDS FILE DATE
1.10
2.001
06-25-2013
0.01 to 1.05
1.002
04-20-2011
Page 36
Rev. 0-A-041114
FPS DeviceNet Interface
APPENDIX B
FPS DEVICENET INTERFACE REVISION HISTORY
MANUAL RELEASE DATE
MANUAL REVISION
April 11, 2014
May 11, 2011
MANUAL REVISION HISTORY
REVISION 0-A-041114
Open Retry added to Supervisor Class, Instance 1.
Set Point Class 0x64, Instance 0 Attributes updated.
PTC Temperature and Reversepower added to Class 0x64.
Undertemperature added to Class 0x68.
REVISION PRELIMINARY 1
Initial release.
0-A-041114
Preliminary 1