DRP 012V Series 15W - 100W AC / DC DIN RAIL FEATURES • • • • • • • • 12VDC 15W - 100W 1Ph AC/DC Power Supply DIN Rail Mountable Power will not de-rate for the entire input voltage range Power Boost of 150% for 3 seconds Conformal coating on PCBAs Protected against common dust and chemical pollutants 60W-100W Hazardous Locations approval to ATEX Class I Div 2 Overvoltage/Overcurrent/Over Temperature Protection SPECIFICATIONS OUTPUT ENVIRONMENTAL Output Voltage 12Vdc Output Voltage Range 11 - 14Vdc Output Current See Selection Table Output Power 15W to 100W Line Regulation < 0.5% typ. (@ 85-264Vac input, 100% load) Load Regulation < 1% typ. (@ 85-264Vac input, 0-100% load) PARD (20MHz) < 100mVpp Parameters Rise Time <20ms (100% load) PROTECTIONS Hold-up Time > 110ms @ 230Vac Overvoltage Operating Temperature Storage Temperature Power De-rating Operating Humidity Operating Altitude Shock Test INPUT Overload/Overcurrent Input Voltage 85-264Vac (DC input range 120-375Vdc) Input Frequency 47-63Hz DRP15: <0.22A @ 230Vac DRP30: < 0.42A @ 230Vac DRP60: < 0.8A @ 230Vac DRP100: <1.5A @ 230Vac Over Temperature Efficiency > 84.0% at 100% load, vertical mounting MTBF Leakage Current < 1mA @ 230Vac Expected Life Time Input Current MECHANICAL Indicator Cooling System Convection Input Terminal 3 Pins (Rated 300V/20A) Output Terminal 2 Pins (Rated 300V/20A) DRP15: AWG 22-14 DRP30: AWG 22-14 DRP60: AWG 22-14 DRP100: AWG 18-14 Input / Output Wire Mounting Rail Protection against Shock 16V, +10% / -5% SELV Ouput, Hiccup Mode, Non-Latching (Auto-Recovery) > 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) > 80C Surrounding Air Temperature @ 100% load, Latch-off Mode Hiccup Mode, Non-Latching (Auto-Recovery) when the fault is removed) Class 1 with PE connection > 500,000 hrs as per Telcordia SR-332 I/P: 115Vac, O/P: 100% load, Ta 25C 10 years (230Vac 50% load @ 40C) STANDARDS & APPROVALS DRP15 & DRP30: Plastic DRP60 & DRP100: Aluminium Dimensions / Weight DRP15: 100 x 32 x 100.6mm, 0.18Kg DRP30: 100 x 32 x 100.6mm, 0.20kg DRP60: 121 x 32 x 120mm, 0.33kg DRP100: 121 x 50 x 118.7mm, 0.64kg Green LED (DC OK) Case Cover Short Circuit -20°C to +80°C -25°C to +85°C > 50°C (2.5% / °C) Vertical Mounting 5 to 95% RH (Non-Condensing) 0 to 2,000 Meters IEC60068-2-27, 30G (300m/s) for a duration of 18ms, 3 times per direction All Parameters are specified at 25C ambient TS35 DIN Rail in accordance with EN60715 Electronic Equipment Electrical Safety Industrial Control CE Materials & Parts EN50718 / IEC62103 In power installations TUV Bauart to EN60950-1 UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1 UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564) In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC RoHS Directive 2011/65/EU Compliant Hazardous Location / ATEX For DRP60 & DRP100 models, CSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 CLass 1, Division 2, Group A,B,C,D,T4, EN60079-0:2009, EN6007915:2010, Certificate No. EPS 12 ATEX 1 491.X Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC Doc. No. DRP012V Series Rev.C 16-9-15 DRP 012V Series 15W - 100W AC / DC DIN RAIL SELECTION TABLE MODEL NUMBER OUTPUT VOLTAGE OUTPUT CURRENT POWER BOOST (3 SECS) OUTPUT POWER DRP012V015W1AZ 12Vdc 1.25A 1.87A 15W DRP012V030W1AZ 12Vdc 2.5A 3.75A 30W DRP012V060W1AA 12Vdc 5A 7.5A 60W DRP012V100W1AA 12Vdc 8.33A 12.5A 100W TECHNICAL ILLUSTRATIONS Doc. No. DRP012V Series Rev.C 16-9-15 www.powerbox.com.au