Specification Sheet

DRP 012V Series
15W - 100W AC / DC DIN RAIL
FEATURES
•
•
•
•
•
•
•
•
12VDC 15W - 100W
1Ph AC/DC Power Supply DIN Rail Mountable
Power will not de-rate for the entire input voltage range
Power Boost of 150% for 3 seconds
Conformal coating on PCBAs
Protected against common dust and chemical pollutants
60W-100W Hazardous Locations approval to ATEX Class I Div 2
Overvoltage/Overcurrent/Over Temperature Protection
SPECIFICATIONS
OUTPUT
ENVIRONMENTAL
Output Voltage
12Vdc
Output Voltage Range
11 - 14Vdc
Output Current
See Selection Table
Output Power
15W to 100W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% load)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% load)
PARD (20MHz)
< 100mVpp
Parameters
Rise Time
<20ms (100% load)
PROTECTIONS
Hold-up Time
> 110ms @ 230Vac
Overvoltage
Operating Temperature
Storage Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
INPUT
Overload/Overcurrent
Input Voltage
85-264Vac (DC input range 120-375Vdc)
Input Frequency
47-63Hz
DRP15: <0.22A @ 230Vac
DRP30: < 0.42A @ 230Vac
DRP60: < 0.8A @ 230Vac
DRP100: <1.5A @ 230Vac
Over Temperature
Efficiency
> 84.0% at 100% load, vertical mounting
MTBF
Leakage Current
< 1mA @ 230Vac
Expected Life Time
Input Current
MECHANICAL
Indicator
Cooling System
Convection
Input Terminal
3 Pins (Rated 300V/20A)
Output Terminal
2 Pins (Rated 300V/20A)
DRP15: AWG 22-14
DRP30: AWG 22-14
DRP60: AWG 22-14
DRP100: AWG 18-14
Input / Output Wire
Mounting Rail
Protection against Shock
16V, +10% / -5% SELV Ouput, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 80C Surrounding Air Temperature @ 100%
load, Latch-off Mode
Hiccup Mode, Non-Latching (Auto-Recovery)
when the fault is removed)
Class 1 with PE connection
> 500,000 hrs as per Telcordia SR-332 I/P:
115Vac, O/P: 100% load, Ta 25C
10 years (230Vac 50% load @ 40C)
STANDARDS & APPROVALS
DRP15 & DRP30: Plastic
DRP60 & DRP100: Aluminium
Dimensions / Weight
DRP15: 100 x 32 x 100.6mm, 0.18Kg
DRP30: 100 x 32 x 100.6mm, 0.20kg
DRP60: 121 x 32 x 120mm, 0.33kg
DRP100: 121 x 50 x 118.7mm, 0.64kg
Green LED (DC OK)
Case Cover
Short Circuit
-20°C to +80°C
-25°C to +85°C
> 50°C (2.5% / °C) Vertical Mounting
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters
IEC60068-2-27, 30G (300m/s) for a duration of
18ms, 3 times per direction
All Parameters are specified at 25C ambient
TS35 DIN Rail in accordance with EN60715
Electronic Equipment
Electrical Safety
Industrial Control
CE
Materials & Parts
EN50718 / IEC62103 In power installations
TUV Bauart to EN60950-1 UL/cUL recognized
to UL60950-1, CSA C22.2 No. 60950-1, CB
scheme to IEC60950-1
UL/cUL listed to UL508 and CSA C22.2 No.
107.1-01, CSA to CSA C22.2 No. 107.1-01 (File
No. 181564)
In conformance with EMC Directive
2004/108/EC and Low Voltage Directive
2006/95/EC
RoHS Directive 2011/65/EU Compliant
Hazardous Location / ATEX
For DRP60 & DRP100 models, CSAus to CSA
C22.2 No.213-M1987, ANSI / ISA
12.12.01:2007 CLass 1, Division 2, Group
A,B,C,D,T4, EN60079-0:2009, EN6007915:2010, Certificate No. EPS 12 ATEX 1 491.X
Galvanic Isolation
Input to Output: 4.0KVAC
Input to Ground: 1.5KVAC
Output to Ground: 1.5KVAC
Doc. No. DRP012V Series Rev.C 16-9-15
DRP 012V Series
15W - 100W AC / DC DIN RAIL
SELECTION TABLE
MODEL NUMBER
OUTPUT VOLTAGE
OUTPUT CURRENT
POWER BOOST (3 SECS)
OUTPUT POWER
DRP012V015W1AZ
12Vdc
1.25A
1.87A
15W
DRP012V030W1AZ
12Vdc
2.5A
3.75A
30W
DRP012V060W1AA
12Vdc
5A
7.5A
60W
DRP012V100W1AA
12Vdc
8.33A
12.5A
100W
TECHNICAL ILLUSTRATIONS
Doc. No. DRP012V Series Rev.C 16-9-15
www.powerbox.com.au