PhMKDg..., Triangular, LVAC Datasheet

PhMKDg..., Triangular, LVAC
www.vishay.com
Vishay ESTA
ESTAdry D-Type, LVAC Power Capacitors
FEATURES
• Self-healing technology
• Over pressure tear-off fuse
• Smallest available height for 50 kvar units: 210 mm
(+ 68 mm for terminals)
• Excellent heat dissipation
• Screw-on terminal with M10 bolts
• Resin filling provides thermal conductivity similar to that of
oil-filled capacitors
• Aluminum case is welded and hermetically sealed
• No paint required for OUTDOOR applications
• UL and cUL approved
APPLICATIONS
• Areas with dust and moisture, which require a high degree
of protection and high creepage distances. Also for
OUTDOOR applications
• Free-standing, fixed individual PFC (e.g. motors, lighting,
transformers)
• Automatic central PFC (e.g. group of loads)
• Harmonic trap (e.g. UPS, frequency drives, converter)
• Pole-mounted PFC
QUICK REFERENCE DATA
Series
PhMKDg…, triangular
PhMKDgF…, triangular
ESTAdry D-type, LVAC power capacitors dry - INDOOR, IP00
ESTAdry D-type, LVAC power capacitors dry - OUTDOOR, IP00
Capacitors, fixed, low voltage
Capacitors, fixed, low voltage
MKP, metallized polypropylene film
MKP, metallized polypropylene film
1000
1000
Capacitance min. (μF)
3-phase D: 3 x 115.5, 3-phase Y: 3 x 140.1
3-phase D: 3 x 115.5, 3-phase Y: 3 x 140.1
Capacitance max. (μF)
3-phase D: 3 x 331.6, 3-phase Y: 3 x 334.3
3-phase D: 3 x 331.6, 3-phase Y: 3 x 334.3
Output min. (kvar)
30
30
Output max. (kvar)
56.2
56.2
Description
Type
Technology
Voltage max. (V)
Revision: 04-Feb-16
Document Number: 13007
1
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
PhMKDg..., Triangular, LVAC
www.vishay.com
CAPACITORS IN TRAINGULAR CASING
Vishay ESTA
3-PHASE CAPACITOR, INDOOR
DESCRIPTION
The PhMKDg series capacitor in a triangular aluminum case
with a standard rating of 50 kvar, augments Vishay ESTA
broad line of reliable three-phase power capacitors. The
PhMKDg series is preceded by our PhMKP and the ESTAdry
PhMKPg series in aluminum tubular casings, with outputs
up to 37 kvar, depending on their rated voltage.
The standard PhMKDg series capacitor is designed for
indoor application, with externally arranged discharge
resistors (U  50 V/60 s). For outdoor application, the
discharge resistors can be incorporated internally
(U  75 V/180 s). Also, the pure aluminum welded cases
render these capacitors perfectly suitable for outdoor use.
The PhMKDg capacitor can be used for both controlled
equipment and for stationary or mobile fixed compensation,
e.g. for induction-motor-operated conveyor belts in the
mining industry.
The indoor capacitor can be supplied with the option of a
small protective cover for each individual connection or with
an IP53-type overall protective cover.
The triangular case and corresponding triangular
arrangement of the winding elements allows for simple
connection in parallel of several units (IN-LINE). The joint
insulation created by means of a solid ceramic terminal base
with high surface-creepage resistance and very long
tracking paths establishes an additionally superior
mechanical stability for the three solid connector bolts.
With a resin filled pure aluminum case offering superior
mechanical stability, low profile design, excellent thermal
conductance, easy paralleling and a complete three-phase
tear-off fuse system incorporated into the PhMKDg design,
this series is the ideal first choice for new designs and
applicable retrofit requirements.
Revision: 04-Feb-16
Single bolt protection
IP53
3-PHASE CAPACITOR, OUTDOOR
Document Number: 13007
2
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
PhMKDg..., Triangular, LVAC
www.vishay.com
Vishay ESTA
ESTAdry D-TYPE PhMKDg, INDOOR
TECHNICAL DATA
STANDARDS
IEC 60831-1 + 2, EN 60831-1 + 2, UL810 LATEST EDITION
UL / ULC FILE # E97723
Overvoltages
(in accordance with the above standards)
Ucn + 10 % (up to 8 h daily)
Ucn + 15 % (up to 30 min daily)
Ucn + 20 % (up to 5 min, only 200 times in the life of the capacitor)
Ucn + 30 % (up to 1 min, only 200 times in the life of the capacitor)
Please also refer to “Terms and Definitions”.
Overcurrent
(in accordance with the above standards)
1.3 x In,
1.43 x In with 10 % overvoltages, 10 % over capacitance and harmonics included,
continuous operation
Please also refer to “Terms and Definitions”.
Tolerance on capacitance
- 5 % / + 10 % in accordance with the standards
± 5 % as Vishay ESTA standard
Test voltage, terminal / terminal
2.15 x Ucn, VAC, 2 s (routine test)
Test voltage, terminal / casing
6000 VAC, 2 s (routine test)
Inrush current
300 times rated current In
Losses
0.4 W/kvar to 0.5 W/kvar (without discharge resistors)
Statistical life expectancy (2)
> 130 000 operating h (ESTAdry)
Degree of protection
IP00 (terminal cover for higher protection class upon request), indoor
Ambient temperature category
-25 / D (max. 55 °C), (-40 / D on request)
Permitted casing temperature
Max. 65 °C (measured on top of the can)
Cooling
Naturally air-cooled
Permissible relative humidity
Maximum 95 %
Maximum allowed altitude
2000 m above sea level
Mounting position
Vertical and horizontal
Mounting and grounding
Threaded M12 stud at the bottom of the container
Safety features
All-phase overpressure tear-off fuse, self-healing
Casing
Aluminum can, welded top
Dielectric
Polypropylene film, self-healing
Filling agent
Resin-filled (ESTAdry), non-PCB, non-toxic
Terminals
Threaded studs M10
3-PHASE CAPACITORS IN TRAINGULAR CASING, INDOOR
ARTICLE NO. (1)
RATED
VOLTAGE
V
RATED
OUTPUT
kvar
CAPACITANCE
μF
CURRENT
A
(50 Hz)
WEIGHT
kg
HEIGHT
H
mm
PhMKDg400.3.50,00-K
5345-44814-xx
400
50
3 x 331.6 
72.2
4.0
210
PhMKDg440.3.50,00-K
5345-44804-xx
440
50
3 x 274.0 
65.6
4.0
210
PhMKDg440.3.56,20-K
5345-44805-xx
440 / 415
56.2 / 50
3 x 308.0 
73.7 / 69.6
4.0
210
PhMKDg460.3.50,00-K
5345-44803-xx
460
50
3 x 250.7 
62.8
4.0
210
PhMKDg525.3.50,00-K
5345-44824-xx
525
50
3 x 192.5 
55.0
4.0
210
PhMKDg690.2.50,00-K
5345-44807-xx
690
50
3 x 334.3 Y
41.8
4.0
210
PhMKDg760.2.50,00-K
5345-44808-xx
760
50
3 x 275.5 Y
38.0
4.0
210
TYPE
ORDERING INFORMATION
Packing units
1 piece per carton
Notes
• Other voltage ratings, outputs, and frequencies on request.
(1) Version no. xx may differ as it respects small changes, e.g. on the label
(2) Statements about product lifetime are based on calculations and internal testing. They should only be interpreted as estimations. Also due
to external factors, the lifetime in the field application may deviate from the calculated lifetime. In general, nothing stated herein shall be
construed as a guarantee of quality or durability.
Revision: 04-Feb-16
Document Number: 13007
3
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
PhMKDg..., Triangular, LVAC
www.vishay.com
Vishay ESTA
DIMENSIONS, INDOOR
M10
Screw bolt M10 brass blank
Hexagonal nut M10 DIN 934 steel hot dip galvaniced
Spring washer wave B10 DIN 137 steel hot dip galvaniced
Hexagonal nut M10 DIN 934 steel hot dip galvaniced
Hexagon thin nut M10 DIN 439 A2
35 + 1
51 ± 2
68 ± 2
25
Required space for bulging
15.8 + 1
H±1
Screw bolt M8x15 steel hot dip galvaniced
Toothed lock washer
Hexagonal nut M12
M12
172
78
160
70
Drawing 6
DISCHARGE RESISTORS
Δ
Y
RECOMMENDED TORQUES
STYLE
RECOMMENDED TORQUE
Terminals M8
6 Nm
Terminals M10 (new K-type PhMKDg...-K)
20 Nm
M12 mounting stud
10 Nm
Revision: 04-Feb-16
Document Number: 13007
4
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
PhMKDg..., Triangular, LVAC
www.vishay.com
Vishay ESTA
ESTAdry D-TYPE PhMKDgF, LVAC POWER CAPACITORS, OUTDOOR
TECHNICAL DATA
STANDARDS
Overvoltages
(in accordance with the above standards)
Overcurrent
(in accordance with the above standards)
Tolerance on capacitance
Test voltage, terminal / terminal
Test voltage, terminal / casing
Inrush current
Losses
Statistical life expectancy (1)
Degree of protection
Ambient temperature category
Permitted casing temperature
Cooling
Permissible relative humidity
Maximum allowed altitude
Mounting position
Mounting and grounding
Safety features
Casing
Dielectric
Filling agent
Terminals
IEC 60831-1 + 2, EN 60831-1 + 2, LATEST EDITION
Ucn + 10 % (up to 8 h daily)
Ucn + 15 % (up to 30 min daily)
Ucn + 20 % (up to 5 min, only 200 times in the life of the capacitor)
Ucn + 30 % (up to 1 min, only 200 times in the life of the capacitor)
Please also refer to “Terms and Definitions”.
1.3 x In,
1.43 x In with 10 % overvoltages, 10 % over capacitance and harmonics included,
continuous operation
Please also refer to “Terms and Definitions”.
- 5 % / + 10 % in accordance with the standards
± 5 % as Vishay ESTA standard
2.15 x Ucn, VAC, 2 s (routine test)
6000 VAC, 2 s (routine test)
300 times rated current In
 0.4 W/kvar to 0.5 W/kvar (without discharge resistors)
> 130 000 operating h (ESTAdry)
IP00 outdoor
-25 / D (max. 55 °C), (-40 / D on request)
Max. 65 °C (measured on top of the can)
Naturally air-cooled
Maximum 95 %
2000 m above sea level
Vertical and horizontal
Threaded M12 stud at the bottom of the container
All-phase overpressure tear-off fuse, self-healing
Aluminum can, welded top
Polypropylene film, self-healing
Resin-filled (ESTAdry), non-PCB, non-toxic
Threaded studs M10
Available types same as for indoor use, different type designation “F”.
For example:
TYPE
PhMKDgF460.3.50
RATED VOLTAGE
V
RATED OUTPUT
kvar
CAPACITANCE
μF
460
50
3 x 250.7 
CURRENT
A
(50 Hz)
62.8
WEIGHT
kg
4.0
HEIGHT
H
mm
210
ORDERING INFORMATION
Packing units
1 piece per carton
RECOMMENDED TORQUES
STYLE
Terminals M8
Terminals M10
M12 mounting stud
RECOMMENDED TORQUE
6 Nm
10 Nm
10 Nm
Notes
• Other voltage ratings, output, and frequencies upon request
(1) Statements about product lifetime are based on calculations and internal testing. They should only be interpreted as estimations. Also due
to external factors, the lifetime in the field application may deviate from the calculated lifetime. In general, nothing stated herein shall be
construed as a guarantee of quality or durability.
Revision: 04-Feb-16
Document Number: 13007
5
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
PhMKDg..., Triangular, LVAC
www.vishay.com
Vishay ESTA
+1
DIMENSIONS, OUTDOOR
Hexagonal nut M12
Toothed lock washer
+2
44 - 2
+2
68 - 2
H ±1
15.8
M12
Screw bolt M8 X 10
Slotted nut M10
Spring washer wave
Hexagonal-nut M10
Screw bolt M10
M10
X
172
70
78
160
X:
Drawing 7
ACCESSORIES: SUPPORT FOR POLE AND WALL MOUNTING
A-A
200
A
M16
A
Revision: 04-Feb-16
Document Number: 13007
6
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
Legal Disclaimer Notice
www.vishay.com
Vishay
Disclaimer
ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE
RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.
Vishay Intertechnology, Inc., its affiliates, agents, and employees, and all persons acting on its or their behalf (collectively,
“Vishay”), disclaim any and all liability for any errors, inaccuracies or incompleteness contained in any datasheet or in any other
disclosure relating to any product.
Vishay makes no warranty, representation or guarantee regarding the suitability of the products for any particular purpose or
the continuing production of any product. To the maximum extent permitted by applicable law, Vishay disclaims (i) any and all
liability arising out of the application or use of any product, (ii) any and all liability, including without limitation special,
consequential or incidental damages, and (iii) any and all implied warranties, including warranties of fitness for particular
purpose, non-infringement and merchantability.
Statements regarding the suitability of products for certain types of applications are based on Vishay’s knowledge of typical
requirements that are often placed on Vishay products in generic applications. Such statements are not binding statements
about the suitability of products for a particular application. It is the customer’s responsibility to validate that a particular
product with the properties described in the product specification is suitable for use in a particular application. Parameters
provided in datasheets and/or specifications may vary in different applications and performance may vary over time. All
operating parameters, including typical parameters, must be validated for each customer application by the customer’s
technical experts. Product specifications do not expand or otherwise modify Vishay’s terms and conditions of purchase,
including but not limited to the warranty expressed therein.
Except as expressly indicated in writing, Vishay products are not designed for use in medical, life-saving, or life-sustaining
applications or for any other application in which the failure of the Vishay product could result in personal injury or death.
Customers using or selling Vishay products not expressly indicated for use in such applications do so at their own risk. Please
contact authorized Vishay personnel to obtain written terms and conditions regarding products designed for such applications.
No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted by this document or by
any conduct of Vishay. Product names and markings noted herein may be trademarks of their respective owners.
Material Category Policy
Vishay Intertechnology, Inc. hereby certifies that all its products that are identified as RoHS-Compliant fulfill the
definitions and restrictions defined under Directive 2011/65/EU of The European Parliament and of the Council
of June 8, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment
(EEE) - recast, unless otherwise specified as non-compliant.
Please note that some Vishay documentation may still make reference to RoHS Directive 2002/95/EC. We confirm that
all the products identified as being compliant to Directive 2002/95/EC conform to Directive 2011/65/EU.
Vishay Intertechnology, Inc. hereby certifies that all its products that are identified as Halogen-Free follow Halogen-Free
requirements as per JEDEC JS709A standards. Please note that some Vishay documentation may still make reference
to the IEC 61249-2-21 definition. We confirm that all the products identified as being compliant to IEC 61249-2-21
conform to JEDEC JS709A standards.
Revision: 02-Oct-12
1
Document Number: 91000