Pan-Way Cove Raceway System: SRSP26--WW-ENG

Pan-Way ® Cove Raceway System
S P E C I F I C AT I O N S H E E T
specifications
WCM35 non-metallic multi-channlel capable surface shall be used to
route, protect, and conceal data, voice, video, fiber optic, and power
cabling. The raceway shall be listed as suitable for use in applications up
to 600 volts between conductors by Underwriters Laboratories, Inc. per
standard 5A, and by Canadian Standards Association, Inc. per 22.2
no.62.1-03, when screw secured and installed per instructions. A full
complement of fittings with a 1" minimum bend radius compliant with
TIA/EIA-568-B, must be available. Divider walls must be available to form
separate channels in the multi-channel raceway. WCM35 raceway will be
manufactured from impact-resistant material with flammability rating of
V-0. WCM35 raceway must be tamper resistant yet allow access for
moves, adds and changes. WCM35 raceway finish shall be pure color
and will resist scratches and dents and will not peel or corrode. WCM35
Raceway shall be available in off-white as a standard color, shall be
paintable, and shall be optimized for use with the Panduit ® Pan-Net ®
Communication System.
technical information
Material:
Rigid PVC
Flammability:
UL94V-0; FT4
Voltage rating:
UL-5A 600VAC CSA C22.2 No.62-93 300VAC
Approvals:
UL Listed 95425 (Raceway); UL Listed E116129 (Fittings)
NEC:
Article 388
Color:
Off White
CSI spec form:
LP-CSISPEC-WCM-1
key features and benefits
1" bend radius control
Fittings conform to TIA/EIA bend radius control standards while
providing an aesthetic appearance; bend radius control ensures
maximum headroom of high performance copper and fiber cable
Can be used as
trunking raceway
Decorative appearance preserves original
architectural styling
Can be painted with
latex paint
Blends well with any décor creating a virtually invisible
premise raceway routing solution
Lightweight
Reduces install fatigue; allows for one-person installation
Non-metallic construction
Solid color throughout will not chip, peel, rust, or corrode;
masks scratches
High impact resistance
Extremely durable for a long life
Easy to cut with standard
saws and saw blades
Reduces installed cost and the need for special
cutting devices
Designer profile
Maintains aesthetically pleasing appearance
Synergy with complete
line of Pan-Way ® Raceway
Cove Raceway may be integrated with other Panduit
Raceway Systems
applications
Pan-Way ® Cove Raceway mounts in the
horizontal corner between ceiling and wall
and/or the vertical corner between walls
and maintains an aesthetically pleasing
design that discreetly conceals cabling.
Cove Raceway is tamper resistant yet allows
w w w. p a n d u it.c o m
access for moves, adds and changes and
includes a full complement of fittings,
accessories and termination options.
Cove Raceway is compatible with other
Pan-Way Raceway Systems.
Cove Raceway:
Base:
Cover:
Divider wall: WCM35BIW8*
WCM35CIW8*
WCM35DW8^
Cove Raceway Fittings:
Cover coupler:
Inside corner
fitting:
Outside corner
fitting:
Tee fitting: Tee fitting insert:
End cap fitting: Transition fitting: Transition fitting
LD/LDPH5 raceway:
Transition fitting
LD/LDPH10 raceway:
Transition fitting
T70 raceway: Device box and
faceplate adapter: Backfeed fitting: Wire retainer: WCM35CCIW-X
WCM35ICIW
WCM35OCIW
WCM35TIW
WCM35TI^
WCM35ECIW
WCM35TRIW
WCM35TR5IW
WCM35TR10IW
WCM35TR70IW
WCM35DBFIW
WCM35BFIW
WCM35WR-X^
*Supplied in eight foot lengths.
IW (Off White) in part number represents color
availability.
^ Available in International Gray only.
Pan-Way® Cove Raceway System
Electrical Cables
14
AWG
12
AWG
Data Grade Cables
10
AWG
THHN/THWN/T90
0.111
0.130
MAX
0.164
24
AWG
24
AWG
24
AWG
Cat. 5e – Plenum
Cat. 5e – Riser
Cat. 6 and
Cat. 6A (SD)
Cat. 6A
RG6
RG59/u
2 Strand
DIA = 0.193
DIA = 0.225
DIA = 0.240
DIA = 0.300
DIA = 0.275
DIA = 0.242
DIA = 0.175
Fill
Raceway
Type and
Configuration
Fill
Area
(in²)
MAX
WCM35:
No Devices
5.40
50
40
WCM35:
Using Wire
Retainer — No
Devices
5.00
50
2.40
WCM35:
Power and
Data Using
Wire Retainer
and Divider
Wall
WCM35:
Power and
Data Using
DBF
WCM35:
Power and
Data Using
Low Profile
Transition
Insert
Fill
Fill
24
AWG
Fill
Fill
Fill
Fill
Fill
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
30
73
110
54
81
47
71
30
45
36
54
46
70
89
134
40
30
68
102
50
75
44
66
28
42
33
50
43
65
83
124
—
—
—
32
49
24
36
21
31
13
20
16
24
20
31
39
59
2.40
30
25
20
—
—
—
—
—
—
—
—
—
—
—
—
—
—
160
—
—
—
21
32
16
24
14
21
9
13
10
16
13
20
26
39
140
25
25
20
—
—
—
—
—
—
—
—
—
—
—
—
—
—
180
25
25
20
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2.50
—
—
—
34
51
25
37
22
33
14
21
16
25
21
32
41
62
WCM35BIW8
MAX
Fiber Optic
Cable
Coax Cables
(UL Temp Rise Test)
WCM35CIW8
WCM35DW8
WCM35CCIW-X
WCM35ICIW
3.5"
(89mm)
WCM35OCIW
WCM35TR70IW
WCM35TI
WCM35TIW
WCM35DBFIW
WCM35ECIW
WCM35BFIW
WCM35WR-X
A=5.40in 2
(3484mm)
3.5"
(89mm)
WCM35TRIW
WCM35TR5IW
WCM35TR10IW
Dimensions are in inches. (Dimensions in parenthesis are metric).
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT CANADA
Markham, Ontario
[email protected]
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
[email protected]
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
[email protected]
Phone: 65.6305.7575
PANDUIT JAPAN
Tokyo, Japan
[email protected]
Phone: 81.3.6863.6000
PANDUIT LATIN AMERICA
Guadalajara, Mexico
[email protected]
Phone: 52.33.3777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
[email protected]
Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
For more information
Visit us at www.panduit.com
Contact Customer Service by email: [email protected]
or by phone: 800.777.3300
©2014 Panduit Corp.
ALL RIGHTS RESERVED.
SRSP26--WW-ENG
Replaces WW-SRSP05
12/2014