Pan-Way LD2P10 Surface Raceway System: SRSP29--WW-ENG

Pan-Way ® LD2P10
Surface Raceway System
S P E C I F I C AT I O N S H E E T
specifications
Type LD2P10 non-metallic two channel, one-piece tamper resistant
latch design, adhesive backed, hinged cover surface raceway shall
be used to route, protect and conceal low voltage data, voice, fiber
optic and power cabling. The raceway shall be listed as suitable for
use in applications having up to 600V between conductors by
Underwriters Laboratories, Inc. per Standard 5A and by Canadian
Standards Associations per C22.2 No. 62.1-03 when installed per
instructions. The raceway includes a full complement of bend
radius control (BRC) fittings consisting of, but not limited to: elbows,
(internal and external), couplings for joining raceway sections, blank
end fittings for closing open ends of the raceway, entrance end
fittings, reducer fittings, tee fittings, and an optional raceway
installation tool. The BRC fittings shall incorporate a minimum of 1"
bend radius as recommended for Category 6 UTP and fiber optic
cabling in TIA/EIA 569-B. This non-metallic surface raceway shall be
manufactured in two standard lengths from impact resistant material
with a flammability rating of UL94V-0. The non-metallic raceway
finish shall be pure color, resist scratches and dents and not peel
or corrode. The raceway shall be available in four standard colors
and shall be optimized for use with Panduit® Pan-Net ® Network
Cabling Systems.
technical information
Rigid PVC
Flammability:
UL94V-0; FT4
Voltage rating:
UL-5A 600VAC; CSA C22.2 No. 62.1-03 600V
Approvals:
UL Listed 95425 (raceway); UL Listed E116129 (fittings)
NEC: Article 388
Color: Off White (IW), Electrical Ivory (EI), International Gray (IG), White (WH)
CSI spec form: LP-CSISPEC-LD2P10-1
key features and benefits
Multi-channel system
Allows end user to purchase one raceway to route both data and power cabling
Available 1" bend radius
control fittings
Meets TIA/EIA standard and many warranty requirements
One-piece hinged design
Cables can be laid into the raceway, which prevents damage to cables during installation
Adhesive backing for temporary mounting
Installations are easier and faster, reducing the total installed cost
Highly tamper resistant
Provides maximum security for communication cabling and
maximum safety for power cabling
Non-metallic construction
Lightweight, which reduces installer fatigue and reduces labor required to install the raceway; solid color throughout will not chip, peel, rust or corrode; easy to cut with standard saws and saw blades, which reduces the need for special cutting devices
Available in four colors
Matches a wide variety of colors for various applications
applications
w w w. p a n d u it.c o m
Raceway:LD2P10IW**-A
LD2P10 Raceway Fittings
Coupler fitting:
CFX10IW-X
Inside corner
fitting:
ICFX10IW-X
Outside corner
fitting:
OCFX10IW-X
Right angle
fitting:
RAFX10IW-X
Tee fitting:
TFXD10IW-X
End cap fitting:
ECFX10IW-X
Entrance
end fitting:
EEFXIW
Raceway
installation tool:
LDW10-V
**Insert raceway length of 8' or 10'.
All parts listed in Off White (IW) color. To order
other colors substitute Electrical Ivory (EI),
International Gray (IG), and White (WH).
Material:
Pan-Way ® LD2P10 Profile Raceway is a
one-piece multi-channel channel raceway
which provides solutions for routing both
Pan-Way ® LD2P10 Raceway
power and data cabling along perimeter
walls. LD2P10 profile raceway is available
with multi-channel fittings.
Pan-Way ® LD2P10 Surface Raceway System
wire fill
Electrical Cables
Data Grade Cables
Coax Cables
14 AWG 12 AWG 10 AWG
24 AWG
24 AWG
24 AWG
24 AWG
THHN/THWN/T90
Cat 5e — Plenum
Cat 5e — Riser
Cat 6 and Cat 6A (SD)
Cat. 6A
DIA = 0.193
DIA = 0.225
DIA = 0.240
FILL
FILL
FILL
0.111
0.130
0.164
FILL
Raceway
Type and
Configuration
Fill
Area
(in²)
MAX
LD2P10 —
Left Channel
0.43
14
11
LD2P10 —
Right Channel
0.50
**
**
MAX
MAX
Fiber Optic Cable
RG6
RG59/u
2 Strand
DIA = 0.300
DIA = 0.275
DIA = 0.242
DIA = 0.175
FILL
FILL
FILL
FILL
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
SPEC
MAX
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
(40%)
(60%)
8
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
6
10
5
7
4
6
2
4
3
5
4
6
8
12
(UL Temp Rise Test)
LD2P raceway
A=
A=
0.43in2 0.50in2
0.86"
LD2P10
fittings
CFX
ICFX
OCFX
TFXD
ECFX
EEFX
RAFX
LDW10-V
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT CANADA
Markham, Ontario
[email protected]
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK
[email protected]
Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore
[email protected]
Phone: 65.6305.7575
PANDUIT JAPAN
Tokyo, Japan
[email protected]
Phone: 81.3.6863.6000
PANDUIT LATIN AMERICA
Guadalajara, Mexico
[email protected]
Phone: 52.33.3777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia
[email protected]
Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
For more information
Visit us at www.panduit.com
Contact Customer Service by email: [email protected]
or by phone: 800.777.3300
©2014 Panduit Corp.
ALL RIGHTS RESERVED.
SRSP29--WW-ENG
Replaces WW-SRSP07
11/2014