FUJI EDS11-165A

PUM Series
Multi-loop module type
Temperature controller
Control Module [PUMA/B]
DATA SHEET
PUMA/B
PUMA/B is a control module, which forms the core of PUM
series. Each control module, 30mm wide, is equipped with
PID control function for maximum 4 channels, 8 points of
CT input/output, and high-speed RS-485 port. By connecting
with PUM event input/output modules, it realizes a compact
and high-performance system.
FEATURES
I. High-level control functions for various applications
1. Process value input, control output:
max. 4 points (4 channels independent control)
(Process value input: Insulation between channlel,
All input/output and power supply: Insulation)
2. CT input: max. 8 points
One unit can detect three phase heater break for 4
channels
3. High-speed sampling: 200ms
4. Input measurement accuracy: ±0.3%FS
5. Types of control output can be selected by 2 channels
(Relay contact / SSR drive / current linear output)
6. Analog re-transmission output function can be assigned
to current output
7. ON/OFF control, PID control Fuzzy PID control, and
Heat/Cool control
II.User-friendly structure and functions
1. Lateral connection : Max.16 units (64 channels) + event
input/output module 16 units = total 32 units
Simple wiring for power supply and communication
2. Detachable structure: Terminal block, main unit, and
the base part
→ Easy wiring with detachable terminal blcok
→ Main units exchangeable without re-wiring
3. Status LED for each control channel
→ Easy to detect error channel
4. Smart loader communication: Connect one module
and all connected modules are able to communicate
using a loader software.
III.Large scale system using high speed RS-485
1. Modbus RTU protocol for large volume communication
2. High-speed communication: Maximum 115.2kbps
3. Highly-efficient communication: Parameters dispersed
on the address map are re-allocated to contiguous
address
IV.Various functions to realize high-performance system
1. Alarm function (output from event I/O module)
2. Power distribution function (with event I/O module):
Power ratio can be set to multiple point output by
input/control calculation value of one channel
3. Operation mode control by digital input (with event
I/O module): Run/Standby, etc.
4. Remote operation using input, and re-transmission
output using output of connected alalog input/output
module (other stations)
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2.Module type
1)Analog module: Total maximum 16 units
a)Control module (4 loop/unit)
b)Extended input/output (analog) module
-Analog input/output module
(Input/output 4 points/unit)
-Analog input module (Input 4 points/unit)
-Analog output module (output 4 points/unit)
2)Extended input/output (digital) module:
Maximum 16 units
-Event input/output module
(Input/output ; 8 points/unit)
3)Enhanced communication module: 1 unit
3.Connecting method:
Lateral connecting with connectors
-For power supply and RS-485 communication,
any one of connected modules is required to be
connected.
4.No. of loop, input/output
1)Control loop:
Max. 64
2)No.of input / output: DI 128 points / DO 128 points
Control module specification
1. General specification
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
[when 24V DC is applied]
(3) Insulation resistance: 20MW or more (500V DC)
(4) Withstand voltage:
Power supply ↔ all terminals
1000V AC 1 min.
Relay contact ↔ all terminals
1500V AC 1 min.
Others
500V AC 1 min.
(5) Applied standards:
UL, C-UL, CE marking, RoHS directive
[Pending for UL, C-UL marking]
EDS11-165a
Date
Apr. 1, 2011
PUMA/B
2. Input
2.1 Process value input
(1) No. of input: 2 or 4 points (1 point/channel)
(2) Input setting: Input code selection
(3) Input signal: See table 1
Select from group I or II depending on the model
code.
(setting can be done by channel within group)
[Group I] a) Thermocouple
b) Resistance bulb (3 wire)
[Group II] c) DC voltage, current
(4) Measurement range and input type: See table 1
(5) Measurement accuracy (Ta = 23°C)
a) Thermocouple: ±0.3%FS ±1digit ±1°C
or ±3°C whichever is greater
*Unless;
B thermocouple 0 to 500°C: ±5%FS ±1digit ±1°C
R thermocouple 0 to 500°C: ±1%FS ±1digit ±1°C
T thermocouple -200 to 0°C: ±0.5%FS ±1digit ±1°C
b) Resistance bulb input: ±0.3%FS ±1digit or ±1°C
whichever is greater
c) Voltage / Current input: ±0.3%FS ±1digit
(6) Resolution: See table 1
(7) Temperature fluctuation: ±0.3%FS/10°C
(8) Input sampling cycle: 200ms
(9) Input impedance
Thermocouple: 1MΩ or more
Current input: 250Ω
Voltage input: approx. 1MΩ
(10) Influence of signal source resistance
Thermocouple: ±0.3%FS±1digit / 100Ω
Voltage input: ±0.3%FS±1digit / 500Ω
(11) Allowable wiring resistance
Resistance bulb: 10Ω or less (per wire)
(12) Allowable input voltage
DC voltage input: within ±15V
Current input: within ±25mA
Thermocouple/resistance bulb: within ±5V
(13) Noise rejection ratio
Normal mode: 30dB or more (50/60Hz)
Common mode: 120dB or more (50/60Hz)
between process value input and earth, power supply, output 220V AC, 50/60Hz
(14) Input compensation
a) User adjustment: zero point, span point ±50%FS
b) PV shift: ±10%FS
c) First order lag filter: 0.0 to 120.0 sec.
(15) Overrange, underrange:
Out of range of -5 to 105%FS
(Accuracy cannot be ensured for -5 to 0,
100 to 105%FS)
(16) Insulation: Functional insulation between channels,
and with any other input/output
2.2 Heater break detector (CT) input
(1) No. of input: 4 or 8 points (2 points/loop)
(2) Input type:
Single-phase type CT /point
1 to 30A: CTL-6-S-H
20 to 50A: CTL-12-S36-8
(3) Current detection accuracy:
Input value ±10% or ±2A, whichever is
greater
(4) Time required for detection
- ON detection: 800ms or more
- OFF detection: 2 sec. or more
2
(5) Connection method:
Connector for heater break detector
[on the front of module]
(6) Insulation:
No insulation between channels
No insulation with communication port
(RS-485, loader)
Functional insulation with any other input / output
3. Output
3.1 Control output
(1) No. of output:
2 points (1 point/loop) or 4 points (2
points/loop)
(2) Control output behaviour:
Heat (reverse action) or cool (direct action), or heat/cool (control output 2 points/
loop required)
(3) Output type: Selected from a) to d) (by 2 channels)
a) Relay contact output
- Proportional cycle: 1 to 150 sec.
- Contact structure: SPST contact
- Contact capacity: 220V AC / 30V DC, 3A (resistance load) 220V AC / 30V DC,
1A (inductive load)
- Min. switching current: 100mA (24V DC)
- Mechanical life:
20,000,000 switching or more
(100/min.)
- Electric life:
100,000 switching or more (rated
load)
- Insulation:
Basic insulation with any other
input/output
b) SSR/SSC drive output
- Proportional cycle: 1 to 150 sec.
- Minimum resolution: 5ms
- ON voltage:
10V DC (8 to 12V DC)
- OFF voltage:
0.5V DC or less
- Max. current:
20mA DC (per point)
- Load resistance: 500Ω or more
- Insulation:
No insulation with any other output (excluding relay output)
Functional insulation with others
than those above
c) Current output (4 to 20mA DC, 0 to 20mA DC)
- Actual output range: 0mA to 20.6mA DC
- Accuracy:
±0.3%FS
(less than 1mA : ±5%FS)
- Linearity:
±0.3%FS
(less than 1mA : ±5%FS)
- Resolution:
5,000 or more
- Ripple current:
P-P 0.3mA or less
- Load resistance: 300Ω or less
- Insulation:
No insulation with any other output (excluding relay output)
Functional insulation with others
than those above
(4) Optional functions:
Output limit, Soft start, power distribution, Output shutdown, output scaling
(for current output only)
3.2 Analog re-transmission output
(1) No. of output: 2 points (OUT3, OUT4 applied)
(2) Output type: Current output (4 to 20mA DC,0 to 20mA
DC)
(3) Option:
Output scaling
4. Communication function
4.1 RS-485 interface
(1) Communication standards: RS-485 compatible
(2) No. of port: 1 port
(3) Communication, synchro method:
Two-wire, half-duplex, asynchronous
cycle
(4) Communication speed: 9.6k, 19.2k, 38.4k, 115.2kbps
(5) Communication distance: 1km (38.4kbps or less),
250m (115.2kbps)
(6) Recommended cable: KPEV-SB 0.5sq-equivalent
(7) No. of connectable units:
33 units (master and slave)
(32 units if any modules other than PUM
series are included in slaves.)
(8) Data format: Data bit; 8, parity; even / odd / none
(9) Protocol:
Modbus RTU compatible
(10) Insulation: No insulation with loader communication
port, CT input
Functional insulation with any other input / output
5.4 Digital input function
(1) Operation control by digital input:
Run/Standby switch, Auto/Manual switch,
Local / Remote switch, Start auto tuning,
Ramp SV ON / OFF, Ramp SV HOLD, DO
latch release, Start timer, Output shutdown
(2) Input method: Input using event input/output module
6. Alarm function
6.1 Alarm function
(1) No. of alarm set- points: 5 points / control channel
(2) Alarm type: PV value(Lower/upper limit, absolute/deviation value, range)
Loop burnout alarm, Error alarm, etc.
(Non-excitation, delay, latch, timer function also available)
(3) Alarm output: Data output via communication or output
from event input / output module
6.2 Heater break alarm
4.2 Loader communication (RS-232C) interface
(1) Communication standards: RS-232C compatible
(2) No. of port: 1 port
(3) Communication, synchro method:
Half-duplex, asynchronous cycle
(4) Communication speed: 19.2kbps (fixed)
(5) Data format: Data bit 8, no parity
(6) Protocol:
Modbus RTU compatible
(7) Connection method:
2.5 diameter mini-plug / jack
[on the front of the module]
(Common cable with PXG, PXH)
(8) Insulation:
No insulation with RS-485, CT input
Functional insulation with any other input / output
(1) No. of alarm set-points:
4 or 8 points (2 points/control channel)
(2) Alarm type: Detect when output ON (break detection)
Detect when output OFF (leakage current
detection)
(setting can be done separately by point)
(3) Heater current alarm
Detectable current range:
2A to 50A
Detected current resolution: 0.1A
Setting resolution:
0.1A
Operation dead band:
0.0 to 50.0A
(4) Alarm output: Data output via communication or output
from event input/output module
7 Display, configuration
5. Control functions
5.1 Control methods
(1) PID control (including FUZZY PID control)
- PID constant: Set by auto tuning
(2) PID 2 (Heat/cool) control (including FUZZY PID control)
- PID constant: Set by auto tuning
7.1 Display
(1) Display:
Status display LED
(2 colors × 6 points)
(2) Display contents:
RUN/FAULT, RS-485 TX/RX, OUT/ERR by
loop (4 loops) (Functions are assigned to
LED of each channel)
5.2 Control parameter
- Proportional band (P):
0.0 to 999.9%, P=0: 2 position control
ON
- Integration time (I):
0 sec to 3200 sec. I=0: Integration OFF
- Derivation time (D):
0.0 to 999.9 sec. D=0: Derivation OFF
- Control cycle: 200ms
5.3 Control mode
(1) Mode type: Auto / Manual / Remote
(2) Mode switching:
Auto ↔ Manual: balanceless / bumpless transfer
Auto/Manual ↔ Remote: balance/bumpless transfer
Auto/Manual ↔ Remote: balance/bumpless transfer
7.2 Setting device
(1) Setting device: Rotary SW × 1
(2) Set contents: RS-485 Station No.
(Station No.= setting value + 1)
8. Power outage
(1) Impact of power outage:
Outage of 2ms or less ; no impact
(2) Operation after power outage:
Start from the first step (cold start)
(3) Memory backup:
Nonvolatile memory (EEPROM)
No. of update ; 100,000
9. Self diagnosis
Diagnosis method:
Program error monitoring by watch dog
timer
3
PUMA/B
4
10. Structure
11. Normal operating condition
(1) Installation method:
DIN rail mounting or mounting with M3
screws inside a cabinet
(2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm
(excluding terminal cover and projected
part)
(3) Weight:
Approx. 200 g
(4) Extrenal terminal
- Process value input/control output:
Detachable terminal block
(M3 screw × 20 terminals)
- Power supply connection:
Terminal block on the base part
(M3 screw × 2 terminals)
Power is supplied via side connectors
in case of lateral connecting. (Max. 33
units)
- RS-485 communication connection:
Terminal block on the base part
(M3 screw × 3 terminals)
RS-485 communication is connected via
side connectors in case of lateral connecting.
- CT input: Special connectors (8 pin × 2 pcs.)
[on the front of the module]
- Loader communication port:
2.5 diameter mini-plug / jack
[on the front of the module]
(5) Case material: Polyphenylene oxide
(flame retardant grade : UL94V-0 equivalent)
(6) Case color: Case ; red
Terminal, base part ; black
(7) Protection
- Body:
IP20 grade protection
(ventilation slits on the top and the bottom of the body)
- Terminal:
IP00 grade protection, terminal cover is
available as an option
(1) Ambient temperature*: -10 to 50°C
* “Ambient temperature” is the temperature underneath the controller inside
the equpiment or the cabinet where
the controller is installed.
(2) Ambient humidity:
90% RH or less (non condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
(4) Warmup time: 30 min. or more
12. Transporting, storage condition (packing condition)
(1) Storage temperature: -20 to 60°C
(2) Ambient humidity: 90%RH or less (no condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
(4) Shock:
294m/s2 (30G) or less
13. Packing list
Temperature controller: 1unit
Instruction manual:
1 copy
250Ω resistance:
0 or 2 or 4 pcs.
(For no. points of voltage /
current input selected)
14. Loader software
(1) Distribution medium:
Free download from Fuji Electric Systems HP (http://www.fic-net.jp/eng/index.
html)
(2) Recommended operating environment
PC:
DOS/V (PC-AT compatible)
OS:
Windows XP (operation confirmed in
Japanese / English)
RAM:
256M bytes or more
Free space on the hardware: 500M bytes or more
Display resolution: 1024 × 768 or over
Serial interface: RS-232C 1 port
(without RS-232C, USB serial converter
cable required)
(3) Connection with PUM
Via loader interface on the front face of the module
(special cable available from Fuji is required) or via
RS-485
CODE SYMBOLS
[Control module (4 channels)]
1 2 3 4 5 6 7 8
9 10 11 12 13
P UM
0
Digit
Description
4 < Module type >
4ch control module
5 < Input type >
Thermocouple / resistance bulb [all channels]
Voltage / current [all channels]
Thermocouple / resistance bulb [ch 1, 2], voltage / current [ch3, 4]
6 < OUT1, 2 output type >
Relay output
SSR drive output
Current output
7 < OUT3, 4 output type >
Relay output
SSR drive output
Current output
10 < Operation Manual >
Japanese
English
11 < Option 1 >
Not fitted
CT input (8 points)
[Control module (2 channels)]
Digit
Description
4 < Module type >
2ch control module
5 < Input type >
Thermocouple / resistance bulb [all channels]
Voltage / current [all channels]
6 < OUT1, 2 output type >
Relay output
SSR drive output
Current output
7 < OUT3, 4 output type >
Not fitted
Relay output
SSR drive output
Current output
10 < Operation Manual >
Japanese
English
11 < Option 1 >
Not fitted
CT input (4 points)
1
A
T
A
C
A
C
E
A
C
E
A
B
Y
C
1 2 3 4 5 6 7 8
9 10 11 12 13
P UM
0
1
Digit
Description
6 RS-485 terminating resistance
7 DIN rail mounting end plate
8 Side conneting terminal cover (right & left 1 set)
Front face screw terminal cover
Loader connecting cable (RS-232C)
CT input terminal cable (for 4 points) [l=1m]
CT input terminal cable (for 4 points) [l=3m]
CT input terminal cable (for 4 points) [l=5m]
CT for 1 to 30A (CTL-6-S-H)
CT for 2 to 50A (CTL-12-S36-8)
Digit
00
B
T
A
A
C
E
Y
A
C
E
A
B
Y
C
1 2 3 4 5 6 7 8
[Accessories]
Digit
00
Digit
P UM Z *
A
A
A
A
L
C
C
C
C
C
0
0
0
0
0
0
0
0
T
T
1
2
3
4
1
1
3
5
1
2
5
PUMA/B
[Table 1] Input type and standard nput range
Input type
Input
code
Resistance bulb Pt100Ω
(IEC)
Thermocouple
J
K
DC voltage *
Measurement range
[°C]
[°F]
Min. measurement unit
[°C]
[°F]
2
0 to 150
32 to 302
0.1
0.1
3
-150 to 300
-238 to 572
0.1
0.1
4
-150 to 850
-238 to 1562
0.1
1
5
0 to 400
32 to 752
0.1
0.1
6
0 to 800
32 to 1472
0.1
1
7
0 to 400
32 to 752
0.1
0.1
8
0 to 800
32 to 1472
0.1
1
9
0 to 1200
32 to 2192
1
1
1
R
10
0 to 1600
32 to 2912
1
B
11
0 to 1800
32 to 3272
1
1
S
12
0 to 1600
32 to 2912
1
1
T
13
-199 to 400
-326 to 752
0.1
1
E
14
-199 to 800
-326 to 1472
0.1
1
N
18
0 to 1300
32 to 2372
1
1
PL-II
19
0 to 1300
32 to 2372
1
1
DC0-5V
21
DC1-5V
22
DC0-10V
23
DC2-10V
24
-1999 to 9999
(scaling range)
-
-
* In case of currenet input, attach I / V unit which comes with the controller to the voltage input terminal.
[Table 2] Insulation block diagram
Power
PV1
Loader communication port
PV2
RS-485 communication port
PV3
CT Input (CT1A, B - CT4A,B)
PV4
OUT1 (relay contact output)
OUT1 (SSR drive, current)
OUT2 (relay contact output)
OUT2 (SSR drive, current)
OUT3 (relay contact output)
OUT3 (SSR drive, current)
OUT4 (relay contact output)
OUT4 (SSR drive, current)
Basic insulation (1500V AC)
Functional insulation (1000V AC)
Functional insulation (500V AC)
6
OUTLINE DIAGRAM (Unit : mm)
Front terminal cover (Option)
(10)
CT-input connectors
Base part
(Main unit is detached)
Terminal block
(at attach/detach)
30
85
Hole for screw mounting
LOADER
1.5
50
STATION
100
6
DIN rail
6.1
Terminal screw
M3
5
Terminal
screw M3
(8)
(30)
Hole for screw
mounting
Main unit (at attach/detach)
At mounting to the DIN rail
Dimensions for screw mounting
(30)
9±0.2
Notice at the installation
Please keep the distance of 30mm from this instrument to radiate.
[50mm is recommended]
30 or more
(3)
(100)
88.5±0.2
30 or more
2-M3
Locking tab
30 +0.7
+0.2
7
PUMA/B
Heater current detector (CT)
Specification : 20 to 50 A
Type
: CTL-12-S36-8
Specification : 1 to 30 A
Type
: CTL-6-S-H
21
φ2.36
30
2.8
7
9
15
40
2.5
10.5
25
φ5.8
10
φ12
φ3.5
M3, depth 4
30
40
8
7.5
40
15
30
TERMINAL CONNECTION DIAGRAM
CT input connector
CN1
CT1A
CT1B
CT2A
CT2B
2 1
4 3
6 5
8 7
CN2
Loader interface plug (RS-232C)
CT3A
CT3B
CT4A
CT4B
2 1
4 3
6 5
3 TX
2 RX
1 GND
CT input cable connection table
8 7
Cable distinction color
Pin No.
Cover color
1
Dot color
Red
Yellow
* No. 2, 4, 6 and 8 pins of CN1 and CN2
are connected in the instruments.
Black
2
Red
3
White
Black
4
φ2.5 3-pole miniature plug
* CN2 is not available for model PUMB.
Red
5
Light-glay
Black
6
Red
7
LOADER
Orange
Black
8
* Input 3 and Input 4 are not available for
model PUMB.
29
SSR-drive + 30
28
29
Relay
30
Output 4
16
27
17
28
18
29
19
Output 2
Relay
Input 2
* In case of current input, attach I / V unit
which comes with the controller to the
voltage input terminal.
B 15
SSR-drive
16
Thermocouple
20
30
15
17
16
18
19
B 19
20
B 20
12
Voltage/
Current*
Current
17
A
RTD
18
-
Thermocouple
27
26
B 14
11
13
14
15
16
17
Voltage/
Current*
18
-
+
15
13
14
+
+
30
28
25
12
A
RTD
13
Current
+
+
29
-
27
Input 4
14
Thermocouple
-
A
26
24
Input 1
11
-
28
-
26
13
12
+
B
23
SSR-drive
11
+
B
Output 3
25
Relay
12
Relay
-
26
27
24
22
Output 1
-
+
-
24
SSR-drive + 25
RTD
23
Thermocouple
11
+
-
25
22
21
+
-
24
+
Input 3
-
A 23
21
-
B 22
23
-
21
+
+
Voltage/
Current*
Current
22
RTD
Current
B
+
Voltage/
Current*
21
STATION
19
20
* In case of current input, attach I/V unit
which comes with the controller to the
voltage input terminal.
Base part
Power
3
2
4
1
2
+
1
-
DC24V
5
Communication
RS485
3
4
A(+) B(-)
5
SG
9
PUMA/B
Operation parameter
Parameter (name)
SV value
MV value
Manual mode switch
Run/Standby switch
Remote mode switch
Auto-tuning RUN command
Digital output latch release command
ALM1
ALM1
ALM2
ALM2
ALM3
ALM3
ALM4
ALM4
ALM5
ALM5
set
set
set
set
set
set
set
set
set
set
value
value
value
value
value
value
value
value
value
value
1
2
1
2
1
2
1
2
1
2
Read/write date setting range
0 to 100%FS
-3.0 to 103.0%
0: Auto
1: Manual
0: Run
1: Standby
0: Local
1: Remote
0: Stop/End
1: Normal type
2: Low PV type
0: OFF
1: Release latch
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
-100 to 100%FS
Depends on
Factory default
input range
yes
0
0 (Auto)
Ch 1
40001
40005
40013
Registor No.
Ch 2 Ch 3
40002 40003
40006 40007
40014 40015
Ch 4
40004
40008
40016
0 (Run)
40017 40018 40019 40020
0 (Local)
40009 40010 40011 40012
0 (End)
41005 42005 43005 44005
0 (OFF)
41031 42031 43031 44031
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
2.5%FS
41033
41034
41041
41042
41049
41050
41057
41058
41065
41066
42033
42034
42041
42042
42049
42050
42057
42058
42065
42066
43033
43034
43041
43042
43049
43050
43057
43058
43065
43066
44033
44034
44041
44042
44049
44050
44057
44058
44065
44066
5.0
240
60.0
1°C
1.0
0.0
0.0
100%FS
0 (Reverse/None)
Ch 1
41102
41103
41104
41105
41106
41107
41108
41109
41110
Registor No.
Ch 2 Ch 3
42102 43102
42103 43103
42104 43104
42105 43105
42106 43106
42107 43107
42108 43108
42109 43109
42110 43110
Ch 4
44102
44103
44104
44105
44106
44107
44108
44109
44110
0%FS
100%FS
-3.0
103.0
-3.0
103.0
0
41218
41219
41255
41256
41257
41258
41259
42218
42219
42255
42256
42257
42258
42259
44218
44219
44255
44256
44257
44258
44259
Control (PID) parameter
Parameter (name)
Proportional band [P]
Integration time [ I ]
Derivation time [D]
ON/OFF control hysteresis
Cooling proportional band coefficient [cool]
Dead band
Output convergence value
Anti-reset windup [ARW]
Direct/Reverse action setting [MV1/MV2]
SV Lower Limits
SV Upper Limits
MV1 Lower Limits
MV1 Upper Limits
MV2 Lower Limits
MV2 Upper Limits
Output limiter type setting
10
Read/write date setting range
0.0 to 999.9%
0 to 3200sec
0.0 to 999.9sec
0 to 50%FS
0.0 to 100.0
-50.0 to 50.0%
-100.0 to 100.0%
0 to 100%FS
0: Reverse/None
1: Direct/None
2: Reverse/Direct
3: Direct/Reverse
4: Reverse/Reverse
5: Direct/Direct
0 to 100%FS
0 to 100%FS
-3.0 to 103.0%
-3.0 to 103.0%
-3.0 to 103.0%
-3.0 to 103.0%
0 to 15 [See appendix A]
Depends on
input range
yes
yes
yes
yes
Factory default
43218
43219
43255
43256
43257
43258
43259
Setup parameter
Parameter (name)
PV input type
Read/write date setting range
PV input scale lower
0: Not selectable
1: Not selectable
2: Pt100 (0 to 150°C)
3: Pt100 (-150 to 300°C)
4: Pt100 (-150 to 850°C)
5: J (0 to 400°C)
6: J (0 to 800°C)
7: K (0 to 400°C)
8: K (0 to 800°C)
9: K (0 to 1200°C)
10: R (0 to 1600°C)
11: B (0 to 1800°C)
12: S (0 to 1600°C)
13: T (-199 to 400°C)
14: E (-199 to 800°C)
18: N (0 to 1300°C)
19: PL-2 (0 to 1300°C)
21: Voltage (0 to 5V DC)
22: Voltage (1 to 5V DC)
23: Voltage (0 to 10V DC)
24: Voltage (2 to 10V DC)
-1999 to 9999
PV input scale upper
-1999 to 9999
Decimal place
0: No decimal point
1: One decimal point
2: Two decimal point
0: °C
1: °F
-10 to 10%FS
-50 to 50%FS
0.0 to 120.0sec
-50 to 50%FS
-50 to 50%FS
0: OFF
1: ON
-50 to 50%FS
-50 to 50%FS
0 to 255
1 to 4
-3.0 to 103.0%
-3.0 to 103.0%
-3.0 to 103.0%
-3.0 to 103.0%
0 to 99hr.59min.
-3.0 to 103.0%
-3.0 to 103.0%
0: ALM=OFF
1: ALM=ON
0 to 255
1 to 4
Temperature Unit
PV input shift
SV value shift
PV input filter
PV display zero adjustment
PV display span adjustment
Cold junction compensation
RSV zero adjustment
RSV span adjustment
RSV input master Station No.
RSV input master Ch. No.
FAULT MV1 set value
FAULT MV2 set value
Softstart MV1 value
Softstart MV2 value
Softstart time
Standby MV1 value
Standby MV2 value
Standby mode setting
Linkage operation master Station No.
Linkage operation master Ch. No.
Depends on
input range
Factory default
7 (TC/Pt input)
22 (Voltage input)
0 (TC/Pt input)
0.0 (Voltage input)
400 (TC/Pt input)
100.0 (Voltage input)
0 (TC/Pt input)
1 (Voltage input)
yes
yes
yes
yes
yes
yes
Registor No.
Ch 1 Ch 2 Ch 3 Ch 4
40151 40152 40153 40154
41212 42212 43212 44212
41213 42213 43213 44213
41214 42214 43214 44214
0 (°C)
41215 42215 43215 44215
0
0
0
0
0
1 (ON)
41216
41217
41220
41221
41222
41223
42216
42217
42220
42221
42222
42223
43216
43217
43220
43221
43222
43223
44216
44217
44220
44221
44222
44223
0
0
0
(each Ch. No. )
-3.0
-3.0
103.0
103.0
0
-3.0
-3.0
0
41225
41226
41532
41533
41260
41261
41262
41263
41264
41268
41269
41270
42225
42226
42532
42533
42260
42261
42262
42263
42264
42268
42269
42270
43225
43226
43532
43533
43260
43261
43262
43263
43264
43268
43269
43270
44225
44226
44532
44533
44260
44261
44262
44263
44264
44268
44269
44270
0
(each Ch. No. )
41536 42536 43536 44536
41537 42537 43537 44537
11
PUMA/B
System parameter
Parameter (name)
Current output range
Output type
Outout
Output
Output
Output
Output
Output
proportion cycle
master Station No.
master Ch. No.
scaling span
scaling base
shutdown
DI-1 function select
DI-2 function select
DI-3 function select
DI-4 function select
DI-5 function select
DI-6 function select
DI-7 function select
DI-8 function select
DI-9 function select
DI-10 function select
DI-11 function select
DI-12 function select
DI-13 function select
DI-14 function select
DI-15 function select
DI-16 function select
DI master Station No. setting
DO1 output event type setting
DO1 option function setting
DO2 output event type setting
DO2 option function setting
DO3 output event type setting
12
Read/write date setting range
4: 0 - 20mA DC
5: 4 - 20mA DC
0: PV of own station
1: SV of own station
2: DV of own station
3: MV1 of own station
4: MV2 of own station
5: PV of other stations
6: SV of other stations
7: MV of other stations
1 to 120sec.
0 to 255
1 to 4
-100.0 to 100.0%
-100.0 to 100.0%
0 to 15 (bit data : 0000 to 1111)
bit 0: Output 1 shutdown
bit 1: Output 2 shutdown
bit 2: Output 3 shutdown
bit 3: Output 4 shutdown
0: No function
1: Run/Standby switch
2: Auto/Manual switch
3: Local/Remote switch
4, 5: No function
6: Start AT (Normal type)
7: Start AT (Low PV type)
8, 9: No function
10: Ramp SV ON/OFF
11: Ramp SV HOLD
12-16: No function
17: Latch release (all)
18: Latch release (DO1)
19: Latch release (DO2)
20: Latch release (DO3)
21: Latch release (DO4)
22: Latch release (DO5)
23-25: No function
26: Start timer (DO1)
27: Start timer (DO2)
28: Start timer (DO3)
29: Start timer (DO4)
30: Start timer (DO5)
31-48: No function
49: Output 1 shutdown
50: Output 2 shutdown
51: Output 3 shutdown
52: Output 4 shutdown
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 52
0 to 255
0 to 102 [See appendix B]
0 to 15 (bit data : 0000 to 1111)
bit 0: Alarm latch function
bit 1: Error input alarm function
bit 2: Non-excitation output function
bit 3: Hold reset function
0 to 102 [See appendix B]
0 to 15 (bit data : 0000 to 1111)
bit 0: Alarm latch function
bit 1: Error input alarm function
bit 2: Non-excitation output function
bit 3: Hold reset function
0 to 102 [See appendix B]
Depends on
input range
Factory default
5 (4-20mA DC)
Registor No.
Ch 1 Ch 2 Ch 3 Ch 4
40166 40167 40168 40169
3 (MV1 of own Station) 40171 40177 40183 40190
2(SSR)/30(Relay)
0
(each Ch. No. )
100.0
0.0
0 (bit data 0000)
40176
40172
40173
40174
40175
40182 40188
40178 40184
40179 40185
40180 40186
40181 40187
40201
0
41013 42013 43013 44013
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (bit data 0000)
41014
41015
41016
41017
41018
41019
41020
41021
41022
41023
41024
41025
41026
41027
41028
41011
41032
41036
0
0 (bit data 0000)
41040 42040 43040 44040
41044 42044 43044 44044
0
41048 42048 43048 44048
42014
42015
42016
42017
42018
42019
42020
42021
42022
42023
42024
42025
42026
42027
42028
42011
42032
42036
43014
43015
43016
43017
43018
43019
43020
43021
43022
43023
43024
43025
43026
43027
43028
43011
43032
43036
40194
40190
40191
40192
40193
44014
44015
44016
44017
44018
44019
44020
44021
44022
44023
44024
44025
44026
44027
44028
44011
44032
44036
System parameter
Parameter (name)
DO3 option function setting
DO4 output event type setting
DO4 option function setting
DO5 output event type setting
DO5 option function setting
Ramp SV ON/OFF
Ramp SV - decline
Ramp SV - incline
Ramp SV - slope time units
Control algorithm
ON/OFF hysteresis setting
Mode at startup
Read/write date setting range
0 to 15 (bit data : 0000 to 1111)
bit 0: Alarm latch function
bit 1: Error input alarm function
bit 2: Non-excitation output function
bit 3: Hold reset function
0 to 102 [See appendix B]
0 to 15 (bit data : 0000 to 1111)
bit 0: Alarm latch function
bit 1: Error input alarm function
bit 2: Non-excitation output function
bit 3: Hold reset function
0 to 102 [See appendix B]
0 to 15 (bit data : 0000 to 1111)
bit 0: Alarm latch function
bit 1: Error input alarm function
bit 2: Non-excitation output function
bit 3: Hold reset function
0: OFF
1: ON
0 to 100%FS
0 to 100%FS
0: Slope deg/hr.
1: Slope deg/min.
0: PID
1: FUZZY PID
2: PID against open-loop
0: OFF
1: ON
0: Auto mode
1: Manual mode
2: Remote mode
3: Standby mode
Depends on
input range
yes
yes
0 (bit data 0000)
Registor No.
Ch 1 Ch 2 Ch 3 Ch 4
41052 42052 43052 44052
0
0 (bit data 0000)
41056 42056 43056 44056
41060 42060 43060 44060
0
0 (bit data 0000)
41064 42064 43064 44064
41068 42068 43068 44068
0 (OFF)
41299 42299 43299 44299
0
0
0 (Slope deg/hr.)
41300 42300 43300 44300
41301 42301 43301 44301
41302 42302 43302 44302
0 (PID)
41291 42291 43291 44291
1 (ON)
41292 42292 43292 44292
0 (Auto mode)
41304 42304 43304 44304
Factory default
Alarm parameter
Parameter (name)
ALM1 hysteresis
ALM1 delay time
ALM1 delay time units
ALM2 hysteresis
ALM2 delay time
ALM2 delay time units
ALM3 hysteresis
ALM3 delay time
ALM3 delay time units
ALM4 hysteresis
ALM4 delay time
ALM4 delay time units
ALM5 hysteresis
ALM5 delay time
ALM5 delay time units
Object Ch. No. for interchannel ALM1
Object Ch. No. for interchannel ALM2
Object Ch. No. for interchannel ALM3
Object Ch. No. for interchannel ALM4
Object Ch. No. for interchannel ALM5
CT[A] HB alarm set value
CT[A] HB alarm hysteresis
CT[A] Load short-circuit alarm set value
CT[A] Load short-circuit alarm hysteresis
CT[B] HB alarm set value
CT[B] HB alarm hysteresis
CT[B] Load short-circuit alarm set value
CT[B] Load short-circuit alarm hysteresis
Loop break detection time
Loop break detection band
Depends on
Factory default
input range
0 to 50%FS
yes
0.25%FS
0 to 99min.59sec. or 0 to 99hr.59 min.
0
0: sec.
0 (sec.)
1: min.
0 to 50%FS
yes
0.25%FS
0 to 99min.59sec. or 0 to 99hr.59min.
0
0: sec.
0 (sec.)
1: min.
0 to 50%FS
yes
0.25%FS
0 to 99min.59sec. or 0 to 99hr.59min.
0
0: sec.
0 (sec.)
1: min.
0 to 50%FS
yes
0.25%FS
0 to 99min.59sec. or 0 to 99hr.59min.
0
0: sec.
0 (sec.)
1: min.
0 to 50%FS
yes
0.25%FS
0 to 99min.59sec. or 0 to 99hr.59min.
0
0: sec.
0 (sec.)
1: min.
1 to 4
(each Ch. No. )
1 to 4
(each Ch. No. )
1 to 4
(each Ch. No. )
1 to 4
(each Ch. No. )
1 to 4
(each Ch. No. )
0.0 to 50.0A
0
0.0 to 50.0A
0.5
0.0 to 50.0A
0
0.0 to 50.0A
0.5
0.0 to 50.0A
0
0.0 to 50.0A
0.5
0.0 to 50.0A
0
0.0 to 50.0A
0.5
0 to 9999sec
0 (detection OFF)
0 to 100%FS
yes
10°C
Read/write date setting range
Ch 1
41035
41037
41038
Registor No.
Ch 2 Ch 3
42035 43035
42037 43037
42038 43038
Ch 4
44035
44037
44038
41043 42043 43043 44043
41045 42045 43045 44045
41046 42046 43046 44046
41051 42051 43051 44051
41053 42053 43053 44053
41054 42054 43054 44054
41059 42059 43059 44059
41061 42061 43061 44061
41062 42062 43062 44062
41067 42067 43067 44067
41069 42069 43069 44069
41070 42070 43070 44070
41039
41047
41055
41063
41071
41072
41073
41074
41075
41076
41077
41078
41079
41080
41081
42039
42047
42055
42063
42071
42072
42073
42074
42075
42076
42077
42078
42079
42080
42081
43039
43047
43055
43063
43071
43072
43073
43074
43075
43076
43077
43078
43079
43080
43081
44039
44047
44055
44063
44071
44072
44073
44074
44075
44076
44077
44078
44079
44080
44081
13
PUMA/B
Communication parameter
Parameter (name)
RS-485 Parity setting
Read/write date setting range
0: NONE
1: ODD
2: EVEN
RS-485 Communication speed
0: 9.6kbps
1: 19.2kbps
2: 38.4kbps
3: Forbidden
4: 115.2kbps
RS-485 Communication permission
0: Read only
1: Read/Write
RS-485 Response interval time
0 to 25 (x20ms)
Enhanced communication module (PUMC) 0: PUMC not connected (RS485 Enable)
connection
1: PUMC connected (RS485 Disable)
Master/slave setting in connected
0: Master
modules
1: Slave
User address 01
30000 to 49999
User address 02
30000 to 49999
User address 03
30000 to 49999
User address 04
30000 to 49999
User address 05
30000 to 49999
User address 06
30000 to 49999
User address 07
30000 to 49999
User address 08
30000 to 49999
User address 09
30000 to 49999
User address 10
30000 to 49999
User address 11
30000 to 49999
User address 12
30000 to 49999
User address 13
30000 to 49999
User address 14
30000 to 49999
User address 15
30000 to 49999
User address 16
30000 to 49999
User address 17
30000 to 49999
User address 18
30000 to 49999
User address 19
30000 to 49999
User address 20
30000 to 49999
User address 21
30000 to 49999
User address 22
30000 to 49999
User address 23
30000 to 49999
User address 24
30000 to 49999
User address 25
30000 to 49999
User address 26
30000 to 49999
User address 27
30000 to 49999
User address 28
30000 to 49999
User address 29
30000 to 49999
User address 30
30000 to 49999
User address 31
30000 to 49999
User address 32
30000 to 49999
User data 01
Depends on "User address 01"
User data 02
Depends on "User address 02"
User data 03
Depends on "User address 03"
User data 04
Depends on "User address 04"
User data 05
Depends on "User address 05"
User data 06
Depends on "User address 06"
User data 07
Depends on "User address 07"
User data 08
Depends on "User address 08"
User data 09
Depends on "User address 09"
User data 10
Depends on "User address 10"
User data 11
Depends on "User address 11"
User data 12
Depends on "User address 12"
User data 13
Depends on "User address 13"
User data 14
Depends on "User address 14"
User data 15
Depends on "User address 15"
User data 16
Depends on "User address 16"
User data 17
Depends on "User address 17"
User data 18
Depends on "User address 18"
User data 19
Depends on "User address 19"
User data 20
Depends on "User address 20"
User data 21
Depends on "User address 21"
User data 22
Depends on "User address 22"
User data 23
Depends on "User address 23"
User data 24
Depends on "User address 24"
User data 25
Depends on "User address 25"
User data 26
Depends on "User address 26"
User data 27
Depends on "User address 27"
User data 28
Depends on "User address 28"
User data 29
Depends on "User address 29"
User data 30
Depends on "User address 30"
User data 31
Depends on "User address 31"
User data 32
Depends on "User address 32"
14
Depends on
input range
Factory default
0 (NONE)
Ch 1
Registor No.
Ch 2 Ch 3 Ch 4
40111
1 (9.6kbps)
40115
1 (R/W)
40114
0
0
(PUMC not connected)
1 (Slave)
40113
40116
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
30002
-
40301
40302
40303
40304
40305
40306
40307
40308
40309
40310
40311
40312
40313
40314
40315
40316
40317
40318
40319
40320
40321
40322
40323
40324
40325
40326
40327
40328
40329
40330
40331
40332
45001
45002
45003
45004
45005
45006
45007
45008
45009
45010
45011
45012
45013
45014
45015
45016
45017
45018
45019
45020
45021
45022
45023
45024
45025
45026
45027
45028
45029
45030
45031
45032
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
(PV1)
40117
Configuration parameter
Parameter (name)
Control when input burnout is detected
LED2 Lamp Allocation
LED3 Lamp Allocation
LED4 Lamp Allocation
LED5 Lamp Allocation
LED6 Lamp Allocation
Reset main unit
Read/write date setting range
Depends on
input range
0: Stop control
1: Continue control
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
0: RUN
1: Reset main unit
Factory default
0 (Stop Control)
Registor No.
Ch 1 Ch 2 Ch 3 Ch 4
41407 42407 43407 44407
1
12
13
14
15
0 (RUN)
40222
40223
40224
40225
40226
40101
Monitor parameter
Parameter (name)
System time
Measurement value (PV)
Set value (SV)
DV
Output value (MV1)
Output value (MV2)
Remote SV (RSV)
Remote mode switch
Heater current[A]
Heater current[B]
Leak current[A]
Leak current[B]
Error source display
Alarm 1-5 status
Event input status
Remaining time on timer 1
Remaining time on timer 2
Remaining time on timer 3
Remaining time on timer 4
Remaining time on timer 5
Output value
Communication permission
Read/write date setting range
0 to 65535
-5 to 105%FS
0 to 100%FS
-105 to 105%FS
-3.0 to 103.0%
-3.0 to 103.0%
0 to 100%FS
0: Local
1: Remote
0.0 to 50.0A
0.0 to 50.0A
0.0 to 50.0A
0.0 to 50.0A
0000 to FFFF
0000 to 001F
0000 to FFFF
0 to 99min.59sec.
0 to 99min.59sec.
0 to 99min.59sec.
0 to 99min.59sec.
0 to 99min.59sec.
0 to 99min.59sec.
0: Read only
1: Read/Write
Depends on
input range
Factory default
-
or
or
or
or
or
or
0
0
0
0
0
0
to
to
to
to
to
to
99hr.59min.
99hr.59min.
99hr.59min.
99hr.59min.
99hr.59min.
99hr.59min.
-
Ch 1
30002
30006
30010
30014
30015
30022
30030
30071
30072
30081
30082
31008
31007
31061
31011
31012
31013
31014
31015
30120
Registor No.
Ch 2 Ch 3
30001
30003 30004
30007 30008
30011 30012
30016 30018
30017 30019
30023 30024
30031 30032
30073 30075
30074 30076
30083 30085
30084 30086
32008 33008
32007 33007
32061 33061
32011 33011
32012 33012
32013 33013
32014 33014
32015 33015
30121 30122
30062
Ch 4
30005
30009
30013
30020
30021
30025
30033
30077
30078
30087
30088
34008
34007
34061
34011
34012
34013
34014
34015
30123
15
PUMA/B
[Appendix A] Output limiter type setting
Read/write date setting range
0: 103% / -3% , 103% / -3%
1: Limit / -3% , 103% / -3%
2: 103% / Limit , 103% / -3%
3: Limit / Limit , 103% / -3%
4: 103% / -3% , Limit / -3%
5: Limit / -3% , Limit / -3%
6: 103% / Limit , Limit / -3%
7: Limit / Limit , Limit / -3%
8: 103% / -3% , 103% / Limit
9: Limit / -3% , 103% / Limit
10: 103% / Limit , 103% / Limit
11: Limit / Limit , 103% / Limit
12: 103% / -3% , Limit / Limit
13: Limit / -3% , Limit / Limit
14: 103% / Limit , Limit / Limit
15: Limit / Limit , Limit / Limit
[Appendix B] DO output event type setting
0: None
1: Upper limit absolute
2: Lower limit absolute
3: Upper limit absolute(w/ hold)
4: Lower limit absolute(w/ hold)
5: Upper limit deviation
6: Lower limit deviation
7: Upper/lower limit deviation
8: Upper limit deviation(w/ hold)
9: Lower limit deviation(w/ hold)
10: Upper/lower limit deviation(w/ hold)
11: Range upper/lower limit deviation
12: No function
13: No function
14: No function
15: No function
16: Upper/lower limit absolute
17: Upper/lower limit deviation
18: Upper limit absolute, lower limit deviation
19: Upper limit deviation, lower limit absolute
20: Upper/lower limit absolute(w/ hold)
21: Upper/lower limit deviation(w/ hold)
22: Upper limit absolute, lower limit deviation(w/ hold)
23: Upper limit deviation, lower limit absolute(w/ hold)
24: Range upper/lower limit absolute
25: Range upper/lower limit deviation
26: Range upper limit absolute, lower limit deviation
27: Range upper limit deviation, lower limit absolute
28: Range upper/lower limit absolute(w/ hold)
29: Range upper/lower limit deviation(w/ hold)
30: Range upper limit absolute, lower limit deviation
31: Range upper limit deviation, lower limit absolute
32: SV upper limit
33: SV lower limit
34: SV upper/lower limit
35:
36:
37:
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
48:
49:
50:
51:
52:
53:
54:
55:
56:
57:
58:
59:
60:
61:
62:
63:
64:
65:
66:
67:
68:
69:
Read/write date setting range
MV1 (heat) upper limit
MV1(heat) lower limit
MV1(heat) upper/lower limit
MV2(cool) upper limit
MV2(cool) lower limit
MV2(cool) upper/lower limit
Interchannel upper limit deviation
Interchannel lower limit deviation
Interchannel upper/lower limit deviation
Interchannel upper limit deviation(w/ hold)
Interchannel lower limit deviation(w/ hold)
Interchannel upper/lower limit deviation(w/ hold)
No function
No function
No function
No function
No function
Delay ON timer
Delay OFF timer
Delay ON/OFF timer
No function
No function
No function
No function
No function
No function
Loop break alarm
No function
No function
HB alarm1
HB alarm2
HB alarm 1 OR 2
Load short-circuit alarm1
Load short-circuit alarm2
Load short-circuit alarm 1 OR 2
70: No function
71: During Auto-tuning
72: Direct Operation
73: Standby mode operating
74: Manual mode operating
75: Remote SV operating
76: During ramp SV
77: No function
78: No function
79: No function
80: No function
81: No function
82: No function
83: No function
84: No function
85: No function
86: No function
87: No function
88: No function
89: No function
90: No function
91: No function
92: No function
93: No function
94: No function
95: No function
96: No function
97: No function
98: No function
99: No function
100: No function
101: No function
102: No function
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan