3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols FPS MANUAL FEEDER PROTECTION SYSTEM Revision 1-C-031615 MAIN MENU Metering Ñ ²Messages Ñ Setup Ñ Copyright 2015 by Littelfuse Startco All rights reserved. Document Number: PM-1150-EN Printed in Canada. Factory default password is 1111 New Password See Section 4.3.6. System Identification Table of Contents Page i Rev. 1-C-031615 FPS Feeder Protection System TABLE OF CONTENTS SECTION PAGE List of Figures......................................................................... ii List of Tables .......................................................................... ii 1 Introduction ..........................................................1-1 1.1 General.....................................................................1-1 1.2 FPS Features ............................................................1-1 1.2.1 Protection .....................................................1-1 1.2.2 Breaker Control ...........................................1-1 1.2.3 Metering.......................................................1-1 1.2.4 Data Logging ...............................................1-1 1.2.5 Inputs and Outputs ......................................1-1 1.2.6 FPS-OPI Operator Interface .......................1-1 1.2.7 MPS-RTD Module......................................1-1 1.2.8 Communications .........................................1-2 1.3 Ordering Information ..............................................1-2 2 Installation..............................................................2-1 2.1 General.....................................................................2-1 2.2 FPS-CTU Control Unit ...........................................2-1 2.3 FPS-OPI Operator Interface....................................2-1 2.4 MPS-RTD RTD Module ........................................2-1 2.5 Earth-Fault CT’s ......................................................2-1 3 System Wiring .......................................................3-1 3.1 General.....................................................................3-1 3.2 Wiring Connections ................................................3-1 3.2.1 FPS-CTU Connections ...............................3-1 3.2.1.1 Supply Voltage...............................3-1 3.2.1.2 Current Inputs ................................3-1 3.2.1.3 Voltage Inputs ................................3-1 3.2.1.3.1 Direct Connection .........3-3 3.2.1.3.2 1-PT Connection ...........3-3 3.2.1.3.3 2-PT Connection ...........3-3 3.2.1.3.4 3-PT Connection ...........3-3 3.2.1.4 Digital Inputs..................................3-3 3.2.1.4.1 DC Operation ................3-4 3.2.1.4.2 AC Operation ................3-4 3.2.1.4.3 Combined AC and DC Operation................3-4 3.2.1.5 Analog Input (AN IN) ...................3-4 3.2.1.6 Analog Output (AN OUT) ............3-4 3.2.1.7 PTC Input .......................................3-4 3.2.1.8 IRIG-B Input ..................................3-4 3.2.1.9 I/O Module Communication .........3-4 3.2.1.10 RS-485 Network Communications .........................................3-4 3.2.2 FPS-OPI Connections and Address Selection ........................................3-4 3.2.3 MPS-RTD Connections and Address Selection ........................................3-5 3.2.4 Dielectric-Strength Testing .........................3-5 SECTION PAGE 4 Operation and Setup ............................................ 4-1 4.1 General .................................................................... 4-1 4.2 FPS-CTU ................................................................. 4-1 4.2.1 LED Indication............................................ 4-1 4.2.2 Reset Switch ................................................ 4-1 4.2.3 Phase-CT Inputs .......................................... 4-1 4.2.4 Earth-Fault-CT Input .................................. 4-2 4.2.5 Voltage Inputs ............................................. 4-2 4.2.6 Frequency .................................................... 4-2 4.2.7 Set-Point Group .......................................... 4-2 4.2.8 Output Relay Assignment .......................... 4-2 4.2.9 Digital Inputs 1 to 7 .................................... 4-3 4.2.10 Analog Output............................................. 4-4 4.2.11 Analog Input ............................................... 4-4 4.2.11.1 Metering Only.............................. 4-4 4.2.11.2 Protection ..................................... 4-4 4.2.12 Breaker Control........................................... 4-5 4.2.13 Protection .................................................... 4-5 4.2.14 Miscellaneous Configuration ..................... 4-5 4.2.15 Network Communications.......................... 4-5 4.3 FPS-OPI .................................................................. 4-5 4.3.1 General ........................................................ 4-5 4.3.2 Configuring the FPS-CTU for OPI Operation ......................................................... 4-5 4.3.3 Breaker Control........................................... 4-5 4.3.3.1 Local Control ................................. 4-5 4.3.3.2 Remote Control.............................. 4-6 4.3.4 Metering ...................................................... 4-6 4.3.5 Messages ..................................................... 4-7 4.3.5.1 Trip Reset ....................................... 4-7 4.3.5.2 Status .............................................. 4-7 4.3.5.3 Data Logging ................................. 4-7 4.3.5.4 Statistical Data ............................... 4-7 4.3.5.5 Emergency Thermal Reset ............ 4-7 4.3.6 Password Entry and Programming............. 4-8 4.4 MPS-RTD ............................................................... 4-9 5 Protective Functions ........................................ 5-1 5.1 General............................................................... 5-1 5.2 Overload ............................................................ 5-1 5.2.1 I2t Protection ........................................... 5-1 5.2.2 Emergency Thermal Reset...................... 5-2 5.3 Inverse-Time Overcurrent.................................. 5-2 5.4 Definite-Time Overcurrent .............................. 5-12 5.5 Inverse-Time 3I0 Earth Fault ........................... 5-12 5.6 Definite-Time 3I0 Earth Fault .......................... 5-12 5.7 Definite-Time Earth Fault ................................ 5-13 5.8 Current Unbalance ........................................... 5-13 5.9 Phase Loss—Current ....................................... 5-13 5.10 Phase Reverse—Current .................................. 5-13 5.11 Overvoltage ..................................................... 5-13 Table of Contents Page ii Rev. 1-C-031615 FPS Feeder Protection System SECTION 5.12 5.13 5.14 5.15 5.16 5.17 5.18 5.19 5.20 5.21 5.22 5.23 5.24 PAGE Voltage Unbalance ........................................... 5-14 Phase Loss—Voltage ....................................... 5-14 Phase Reverse—Voltage .................................. 5-14 Undervoltage .................................................... 5-14 Reversepower ................................................... 5-14 Power Factor—Lag .......................................... 5-14 Power Factor—Lead ........................................ 5-14 Underfrequency................................................ 5-15 Overfrequency.................................................. 5-15 PTC Temperature ............................................. 5-15 RTD Temperature ............................................ 5-15 RTD Undertemperature.................................... 5-15 Analog Input .................................................... 5-16 6 Control Method ................................................ 6-1 6.1 General ............................................................... 6-1 6.2 OPEN/CLOSE Control ...................................... 6-2 6.2.1 Contact Status Monitor ........................... 6-3 7 Theory of Operation ........................................ 7-1 7.1 Signal-Processing Algorithms ............................ 7-1 7.2 Power Algorithm ................................................ 7-1 7.3 Operator Interface (FPS-OPI) ............................ 7-1 7.4 RTD Module (MPS-RTD) ................................. 7-1 7.5 Firmware Diagnostics ........................................ 7-1 8 Communications............................................... 8-1 8.1 Personal Computer Interface .............................. 8-1 8.1.1 Firmware Upgrade .................................. 8-1 8.1.2 SE-Comm-RIS ........................................ 8-1 8.2 Network Interface .............................................. 8-1 8.2.1 RS-485 Communications ........................ 8-1 8.2.2 DeviceNet Communications ................... 8-1 8.2.3 Ethernet Communications....................... 8-1 8.2.4 Profibus DP Communications................. 8-1 9 Technical Specifications................................... 9-1 9.1 Control Unit (FPS-CTU) .................................... 9-1 9.2 Operator Interface (FPS-OPI) ............................ 9-3 9.3 RTD Module (MPS-RTD) ................................. 9-3 10 Warranty .......................................................... 9-4 Appendix A FPS-OPI Menu Level ........................... A-1 Appendix B FPS Set-Up Record .............................. B-1 Appendix C FPS Modbus Protocol .......................... C-1 Appendix D FPS A-B DF1 Protocol ......................... D-1 Appendix E Communications Database Table ....... E-1 Appendix F Register Formats ................................... F-1 Appendix G FPS Revision History ........................... G-1 LIST OF FIGURES FIGURE 1.1 1.2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4.1 4.2 4.3 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 6.1 6.2 6.3 6.4 PAGE Feeder Protection System Block Diagram............. 1-3 FPS Ordering Information ...................................... 1-4 FPS-CTU Outline and Mounting Details .............. 2-2 FPS-OPI Outline and Mounting Details ................ 2-3 FPS-CTU with OPI Outline and Mounting Details .................................................... 2-4 MPS-RTD Outline and Mounting Details ............. 2-5 EFCT-1 Outline and Mounting Details ................. 2-6 EFCT-2 Outline and Mounting Details ................. 2-7 EFCT-26 Outline and Mounting Details ............... 2-8 Typical FPS Connection Diagram ......................... 3-2 Direct Connection ................................................... 3-3 1-PT Connection ..................................................... 3-3 2-PT Connection ..................................................... 3-3 3-PT Connection ..................................................... 3-3 Address Selection Switch Detail ............................ 3-4 Two Examples of I/O Module Connections .......... 3-5 FPS-CTU to MPS-RTD Connection Diagram ...... 3-6 Menu Example ........................................................ 4-1 Menu Symbols ........................................................ 4-1 FPS-OPI Interface ................................................... 4-6 Class-20 Overload Curve........................................ 5-3 IEC Normal Inverse, Curve Type A ...................... 5-4 IEC Very Inverse, Curve Type B ........................... 5-5 IEC Extreme Inverse, Curve Type C ..................... 5-6 IEC Short Inverse, Curve Type A .......................... 5-7 IEC Long Inverse, Curve Type B .......................... 5-8 IEEE Moderate Inverse Curves .............................. 5-9 IEEE Very Inverse Curves ................................... 5-10 IEEE Extremely Inverse Curves .......................... 5-11 Asymmetrical-Current Multipliers ....................... 5-12 Typical Three-Wire Control ................................... 6-1 Typical Two-Wire Control ..................................... 6-2 Breaker with Close and Open Coils ....................... 6-3 Breaker with Close and UV Coils .......................... 6-3 LIST OF TABLES TABLE 3.1 3.2 4.1 4.2 4.3 4.4 4.5 5.1 5.2 6.1 PAGE FPS-OPI Address Selection.................................... 3-4 MPS-RTD Address Selection ................................ 3-5 Output-Relay Functions.......................................... 4-2 Digital-Input Functions........................................... 4-3 Analog-Output Parameters ..................................... 4-4 Metering Display .................................................... 4-8 Status Messages ...................................................... 4-8 Curve Types ............................................................ 5-2 Fault Duration Required for Trip ......................... 5-12 Close-Source Summary .......................................... 6-1 Table of Contents FPS Feeder Protection System Page iii Rev. 1-C-031615 DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. Table of Contents FPS Feeder Protection System Page iv Rev. 1-C-031615 This page intentionally left blank. Table of Contents Page 1-1 Rev. 1-C-031615 FPS Feeder Protection System 1. INTRODUCTION 1.1 GENERAL The Feeder Protection System (FPS) is a modular system with integrated protection, control, metering, and data-logging functions. The Control Unit (FPS-CTU) is the core module. It can operate as a stand-alone unit or with the Operator Interface (FPS-OPI), and an RTD Module (MPS-RTD). The CTU can be programmed using the OPI or the communications network. Programmable inputs and outputs provide a flexible hardware platform and custom software can be easily loaded from a PC to the CTU’s flash memory. The FPS block diagram is shown in Fig. 1.1. 1.2 FPS FEATURES 1.2.1 PROTECTION Overload (49, 51) Definite-time overcurrent (50, 51) Inverse-time overcurrent (50, 51, IEC, IEEE) Definite-time earth fault (50G/N, 51G/N) Inverse-time earth fault (50G/N, 51G/N, IEC, IEEE) Unbalance (voltage and current) (46, 47) Phase loss (voltage and current) (46, 47) Phase reverse (voltage and current) (46, 47) Overvoltage (59) Undervoltage (27) Power factor (55) Reversepower (32) Overfrequency (81) Underfrequency (81) PTC overtemperature (49) RTD overtemperature (49) RTD undertemperature (49) Two setting groups 1.2.2 BREAKER CONTROL Open and close control Local, remote, or network control Status verification and indication 1.2.3 METERING Line currents Current unbalance Positive-sequence current Negative-sequence current Earth-leakage current Line to line voltages Line frequency Voltage unbalance Positive-sequence voltage Negative-sequence voltage Power Apparent, reactive, real, and power factor Energy kWh, kVAh, and kVARh Used thermal capacity Thermal trend RTD temperature Analog input and output 1.2.4 DATA LOGGING Sixty-four records Date and time of event Event type Line currents Current unbalance Earth-leakage current Line-to-line voltages Voltage unbalance Thermal capacity Analog-input value RTD temperatures Trip counters Running hours Frequency Power (P, S, Q, PF) 1.2.5 INPUTS AND OUTPUTS Three ac-current inputs Three ac-voltage inputs Earth-leakage-current input Seven programmable digital (ac/dc) inputs 24-Vdc source for digital input 4-20-mA analog input and output PTC thermistor temperature input Up to eight RTD inputs Five programmable output relays Network communications IRIG-B time-code input 1.2.6 FPS-OPI OPERATOR INTERFACE 4 x 20 vacuum-fluorescent display Control keys Display-control and programming keys LED status indication Remote operation up to 1.2 km (4,000’) Powered by FPS-CTU 1.2.7 MPS-RTD MODULE One eight-input module Individually selectable RTD types Solid-state multiplexing Remote operation up to 1.2 km (4,000’) Powered by FPS-CTU Introduction FPS Feeder Protection System Page 1-2 Rev. 1-C-031615 1.2.8 COMMUNICATIONS The standard network communications interface is an RS-485 port with Modbus RTU and A-B DF1 protocol support. In addition to the standard interface, network communications options include DeviceNetTM, Profibus, Modbus TCP, and Ethernet/IP.. 1.3 ORDERING INFORMATION See Fig. 1.2 for FPS-CTU, FPS-OPI, and MPS-RTD model numbers. Earth-Fault Current Sensors: EFCT-1 ......................... Earth-Fault CT, 5-A-primary rating, 82-mm (3.2”) window EFCT-1FC .................... Flux Conditioner for EFCT-1, 70-mm (2.7”) window EFCT-2 ......................... Earth-Fault CT with Flux Conditioner, 5-A-primary rating, 139-mm (5.5”) window EFCT-26 ....................... Earth-Fault CT, 5-A-primary rating, 26-mm (1”) window (All EFCT’s include 6 m (19.5’) of 22 AWG (0.33 mm2) shielded cable). Other Earth-Fault CT’s .. Contact factory Phase CT’s ....................... Protection-class CT’s, contact factory Accessories: SE-IP65CVR-M ........... Hinged Transparent OPI Cover SE-485-PP .................... Port-Powered Serial Converter SE-485-DIN .................. Serial Converter, Industrial, 24 Vdc Software: SE-Comm-RIS .............. PC Communication Software(1) SE-Flash ....................... Firmware Upgrade Software(1) (1) Available at www.littelfuse.com/relayscontrols. Introduction Page 1-3 Rev. 1-C-031615 FPS Feeder Protection System FPS-CTU FPS-OPI 5 CONTROL UNIT 6 7 L1 1 L2 2 8 3 9 SUPPLY SPG 4 SPGA OUTPUT RELAY 1 10 4A OUTPUT RELAY 2 OPERATOR INTERFACE OUTPUT RELAY CONTACTS SHOWN WITH FPS-CTU DE-ENERGIZED. 4 x 20 ALPHANUMERIC DISPLAY LED INDICATORS: TRIP ALARM REMOTE LOCAL OUTPUT RELAY 3 11 12 VA 19 VB 18 VC 17 VN 20 PHASE A CURRENT INPUT 1A 33 5A 32 C 31 PHASE B CURRENT INPUT 1A 30 5A 29 C 28 PHASE C CURRENT INPUT 1A 27 5A 26 C 25 S 24 PHASE VOLTAGE INPUT EARTH LEAKAGE CURRENT INPUT 1A 23 5A 22 C 21 13 OUTPUT RELAY 4 KEYPAD: 14 STOP 15 16 RESET ESC OUTPUT RELAY 5 ENTER LED INDICATORS: POWER TRIP ALARM ERROR CLOSE OPEN CLOSE +24V 60 5 0V 56 + + 59 I/O COMMUNICATIONS - 57 - 58 1 4 2 ADDRESS SWITCHES 3 RESET PUSHBUTTON 55 PTC INPUT 54 4-20 mA ANALOG INPUT + 53 - 52 24 V DC OUTPUT + 41 - 42 COM 43 IN1 44 IN2 45 IN3 46 IN4 47 IN5 48 +24V IN6 49 0V IN7 50 HSI 51 24-120 Vac/Vdc DIGITAL INPUTS + - I/O COMMUNICATIONS 18 15 17 16 39 40 62 61 + 4-20 mA - ANALOG OUTPUT RTD 4 IRIG RTD 3 OPTIONAL NETWORK COMMUNICATIONS RTD 2 37 36 RS-485 NETWORK COMMUNICATIONS 35 RTD 1 C D R SHIELD C D R C D R SHIELD C D R 14 13 12 11 10 9 8 7 6 5 4 3 2 1 MPS-RTD RTD MODULE LED INDICATORS: PWR COMM 21 22 23 24 25 26 27 28 29 30 31 32 33 34 R D C SHIELD R D C R D C SHIELD R D C RTD 5 RTD 6 RTD 7 RTD 8 ADDRESS SWITCHES 20 19 SPG FIGURE 1.1 Feeder Protection System Block Diagram. Introduction Page 1-4 Rev. 1-C-031615 FPS Feeder Protection System 33 32 31 5 A 1 A A 30 29 28 27 5 A 1 A B PH AS E CURRENT 26 25 24 23 5 A 1 A C 22 20 V N 21 5 A 1 A EFCT EARTH LEAKAGE 19 V A 18 V B FPS-CTU 17 V C I/O MODULE AN COMM IRIG IN 2 4 PTC - V - 0 V H + + + S + 62 61 60 59 58 57 56 55 54 53 52 62 61 60 59 58 57 56 55 54 53 52 S 0 2 H V PTC 4 AN IN IRIG V COMM FPS-CTU FEEDER PROTECTION SYSTEM CONTROL UNIT I/O MODULE P O W ER TRIP ALARM ERROR INTERFACE R E S ET 24 VDC SOURCE AN OUT COMM S H 35 36 37 39 40 + + 41 42 - VOLTAG E DIGITAL INPUTS C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I 43 44 45 46 47 48 49 50 51 Future Options: 00 No Options LITTELFUSE STARTCO FEEDER PROTECTION SYSTEM Communications: 01 Standard RS-485. ® & Includes A-BÆ ModbusÆ® Protocols 02 DeviceNetTMand standard RS-485 03 ProfibusÆ® and standard RS-485 04 Ethernet and standard RS-485 FPS-OPI FPS-OPI - TRIP ALARM REMOTE LOCAL Display: 01 Vacuum Fluorecent MAIN MA I N MENU ME N U Metering Me t e r i nÑg — ²Messages ≤ Me s s a g eÑ s — Setup S e t uÑ p — CLOSE CLOSE OPEN OPEN ESC Future Options: 00 No Options ENTER RESET MPS-RTD Configuration: 01 8 RTD 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 C D R S C D R C D R S C D R S H H P INP 8 INP 7 INP 6 INP 5 G PWR INPUT MODULE COMM INP 1 - MPS-RTD CTU/ MPU INP 2 INP 3 INP 4 COMM S S 0 R D C H R D C R D C H R D C V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 2 4 V 18 Future Options: 00 No Options Supplied Interconnect Cable: 3124A . . . . . I/O Module to MPS-CTU Interconnect Cable, 4 m (13’) included with FPS-OPI, MPS-RTD. FIGURE 1.2 FPS Ordering Information. Introduction FPS Feeder Protection System Page 2-1 Rev. 1-C-031615 2. INSTALLATION 2.1 GENERAL A basic Feeder Protection System (FPS) consists of an FPS-CTU and three customer-supplied current transformers (CT's) for measuring phase current. For core-balance earth-fault detection, a 1-A, 5-A, EFCT-1, or EFCT-2 CT is required. The residual phase-CT connection can also be used for earth-fault detection. Voltage inputs do not require potential transformers (PT’s) for system voltages up to 600 Vac. For RTDtemperature measurement an MPS-RTD module can be connected to the FPS-CTU. The FPS-OPI provides an operator interface for the FPS. The FPS power-factor corrected switch-mode power supply is rated 65 to 265 Vac and 80 to 275 Vdc. All modules can be mounted in any orientation. 2.2 FPS-CTU CONTROL UNIT The Control Unit is configured for surface mounting. Outline and mounting details for the FPS-CTU are shown in Fig. 2.1. 2.3 FPS-OPI OPERATOR INTERFACE Outline and mounting details for the FPS-OPI are shown in Fig. 2.2. It is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The Operator Interface is configured for panel mounting or it can be mounted on the FPS-CTU as shown in Fig. 2.3. 2.4 MPS-RTD RTD MODULE Outline and mounting details for the MPS-RTD are shown in Fig. 2.4. The MPS-RTD is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The MPS-RTD can be surface or DIN-rail mounted. 2.5 EARTH-FAULT CT’S Outline and mounting details for the EFCT-1, EFCT-2, and EFCT-26 are shown in Figs. 2.5, 2.6, and 2.7. Installation Page 2-2 Rev. 1-C-031615 FPS Feeder Protection System 33 32 31 5A 1A A 30 29 28 27 5A 1A B PHASE CURRENT 26 25 24 23 22 20 V N 21 5A 1A EFCT EARTH LEAKAGE 5A 1A C 19 V A 18 V B NOTES: 17 V C VOLTA GE 1. ALL DIMENSIONS IN MILLIMETERS (INCHES). 2. SHOWN WITH PLUG-IN TERMINAL BLOCKS INSTALLED. 3. MOUNTING SCREWS M4 OR 8-32 PAN HEAD. I/O MODULE COMM AN IN S 0 PTC H - V + 62 61 60 59 58 57 56 55 54 53 52 IRIG 2 4 + - V+ + 190.0 127.0 (5.00) 118.0 (4.65) 12.5 (0.49) (0.20) 62 61 60 59 58 57 56 55 54 53 52 S 0 2 H V PTC 4 IRIG AN IN V COMM I/O MODULE FEEDER PROTECTION SYSTEM CONTROL UNIT FPS-CTU TRIP ALARM ERROR OPERATOR INTERFACE 91.7 (3.61) POWER 121.1 (4.76) 5.0 (7.50) 165.0 (6.50) RESET AN OUT COMM S H 35 36 37 39 40 + + 41 42 41 42 + - 24 VDC SOURCE DIGITAL INPUTS C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I 43 44 45 46 47 48 49 50 51 12.5 165.0 (0.49) (6.50) 43 44 45 46 47 48 49 50 51 C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I DIGITAL INPUTS 111.0 (4.37) 35 36 37 39 40 - HS + + COMM AN O UT 24 VDC SOURCE RELAY OUTPUTS 1 2 3 4 5 5.0 5 6 7 8 9 10 11 12 13 14 15 16 (0.20) S S P P G L L G A 1 2 1 2 3 4 4A FIGURE 2.1 FPS-CTU Outline and Mounting Details. Installation (0.61) MAX 15.5 97.5 (3.84) 24.0 (1.65) 71.0 MAX (2.80) 98.0 (3.86) OPEN CLOSE RESET OPEN CLOSE LOCAL REMOTE ALARM TRIP 13.7 (0.54) 100.0 MINIMUM (3.94) PANEL-MOUNT CONFIGURATION ENTER ESC FPS-OPI MAIN MA I N MENU ME N U Metering Ñg — Me t e r i n ²Messages ≤ Me s s a g eÑ s — Setup S e t u Ñp — FEEDER PROTECTION SYSTEM LITTELFUSE STARTCO (7.56) 192.0 PANEL-MOUNT CLAMP ADDRESS SWITCH ACCESS COVER CABLE TIE EYELET PANEL THICKNESS 1.6(0.06) TO 4.8(0.19) 10.5 (0.41) 186.0 (7.32) 16.0 (0.63) 165.0 (6.50) 40.0 (1.58) 82.5 (3.25) R4.0 MAXIMUM (0.16) DIMENSIONS IN MILLIMETERS (INCHES). NOTE: 6-32 x 0.38 PAN HEAD SCREW TERMINAL BLOCK SURFACE-MOUNT CONFIGURATION 38.0 (1.50) Ø4.0(0.16) 2 REQ’D Ø 43.2(1.70) 1.25i CONDUIT KNOCKOUT SURFACE-MOUNT DRILL DETAIL PANEL-MOUNT CUTOUT 200.0 MINIMUM (7.87) 92.0 (3.62) 192.0 (7.56) FPS Feeder Protection System Page 2-3 Rev. 1-C-031615 FIGURE 2.2 FPS-OPI Outline and Mounting Details. Installation Page 2-4 Rev. 1-C-031615 FPS Feeder Protection System 33 32 31 5A 1A A 30 29 28 27 5A 1A B PHASE CU RRENT 26 24 25 23 22 20 V N 21 5A 1A EFCT EARTH LEAKA GE 5A 1A C 19 V A 18 V B 17 V C NOTES: VOLTAGE 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. THIS CONFIGURATION CANNOT BE PANEL MOUNTED. 3. SHOWN WITH PLUG-IN TERMINAL BLOCKS INSTALLED. I/O MOD ULE COMM AN IN 2 4 V IRIG 0 PT C + + HS - V + 62 61 60 59 58 57 56 55 54 53 52 4. MOUNTING SCREWS: M4 OR 8-32 PAN HEAD. 5. MAXIMUM DOOR SWING FROM OPI FACE 57.3 (2.26). 5.0 (0.20) 192.0 (7.56) 165.0 (6.50) 159.0 (6.26) 118.0 (4.65) LITTELFUSE STARTCO FEEDER PROTECTION SYSTEM FPS-OPI REMOTE LOCAL MAIN MA I N MENU ME N U Metering Me t e r i nÑ g — ²Messages ≤ Me s s a g eÑ s — Setup S e t u Ñp — 121.1 (4.76) ALARM CLOSE OPEN OPEN ESC ENTER RESET 12.5 (0.49) 41 4 2 + - 24 VDC SOURCE 190.0 (7.50) 165.0 (6.50) 43 44 45 46 47 48 49 50 51 C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I DIG ITA L INPU TS 111.0 (4.37) 35 36 37 39 40 - HS + + COMM AN OUT 98.0 (3.86) TRIP RELAY OUTPUTS 1 2 3 4 5 5 6 7 8 9 10 11 12 13 14 15 16 5.0 (0.20) S S P L L P G 1 2 G A 1 2 3 4 4A FIGURE 2.3 FPS-CTU with OPI Outline and Mounting Details. Installation Page 2-5 Rev. 1-C-031615 FPS Feeder Protection System CABLE-TIE EYELET 4 LOCATIONS 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 C D R S C D R C D R S C D R S H P H INP 8 INP 7 INP 6 INP 5 G INPUT MODULE 87.0 (3.43) PWR CTU/ MPU COMM INP 1 R 1 D 2 C 3 S H 4 INP 2 R 5 D 6 MPS-RTD 2 4 S 0 V D C H R D C V 9 10 11 12 13 14 15 16 17 18 INP 3 C 7 ADDRESS SWITCH ACCESS COVER R 8 INP 4 COMM 52.5 112.5 (4.43) (2.07) 12.5 (0.50) 56.0 (NOTE 3) (2.20) 1. DIMENSIONS IN MILLIMETRES (INCHES). (2.36) 60.0 NOTES: 2. MOUNTING SCREWS: M4 OR 8-32. 3. OVERALL HEIGHT WHEN MOUNTED ON DIN EN50022 35-mm x 7.5-mm TOP-HAT RAIL. (0.57) 14.5 M4 OR 8-32 TAP 6.3 100.0 6.3 (0.25) (3.94) (0.25) FIGURE 2.4 MPS-RTD Outline and Mounting Details. Installation Page 2-6 Rev. 1-C-031615 FPS Feeder Protection System NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. 3. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. 4. RoHS COMPLIANT. 5. EN 60044-1 COMPLIANT. 121.0 (4.76) 121.0 (4.76) 20.5 (0.81) 56.0 (2.21) 46.0 (1.81) 30.0 (1.18) 80.0 (3.15) NOTE 2 M5 SCREWS TOP MOUNTING DETAIL 25.0 (0.98) 30.0 (1.18) EFCT-1 EARTH FA ULT CT 600 V CLASS, INSULATION CLASS A R R LR 53428 5.0 (0.20) Ø RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP 22.0 (0.87) EFCT - 1FC FLUX CONDITIONER (OPTIONAL) .0 82 23) . (3 69 (2.7 .8 5) 126.0 (4.96) US (5.43) 138.0 MAX C 5.5 (0.22) 110.0 (4.33) FRONT 5.5 (0.22) 56.0 (2.21) SIDE FIGURE 2.5 EFCT-1 Outline and Mounting Details. Installation Page 2-7 Rev. 1-C-031615 FPS Feeder Protection System NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M5 OR 10-32. 3. RoHS COMPLIANT. 4. EN 60044-1 COMPLIANT. 215.0 (8.46) 26.5 (1.04) 52.3 (2.06) P S1 2S2 P1 31.0 (1.22) 64.0 (2.52) 215.0 (8.46) 162.0 (6.38) M5 OR 10-32 TAP M5 SCREWS TOP MOUNTING DETAIL 31.0 (1.22) 25.0 (0.98) EFCT-2 EARTH FAULT CT 600 V CLASS, INSULATION CLASS A R R LR 53428 139.7 (5.50) FLUX CONDITIONER (INCLUDED) BONDING SCREW 215.0 (8.46) US 5.0 (0.20) DIA 60.0 (2.36) 236 MAX (9.29) C 8.5 (0.33) 198.0 (7.80) FRONT 8.5 (0.33) SIDE FIGURE 2.6 EFCT-2 Outline and Mounting Details. Installation Page 2-8 Rev. 1-C-031615 FPS Feeder Protection System 68.0 (2.68) 68.0 (2.68) 17.0 (0.67) P S1 2 S2 P1 M4 OR 8-32 TAP 42.6 (1.68) 52.5 (2.07) 26.5 (1.04) 34.0 (1.34) M5 SCREWS 110.0 MAX (0.43) TOP MOUNTING DETAIL 26.5 (1.04) 25.0 (0.98) E F C T- 2 6 E A R T H FA U LT C T 600 V CLASS, INSULATION CLASS A R R C LR 53428 US RECESSED FOR 7-mm HEX NUT 3.0 (0.12) DEEP 7.0 (0.87) 34.0 (1.34) 72.0 (2.83) 4.0 (0.16) Ø .0 26 2) 0 (1. 58.0 (2.28) 52.5 (2.07) 5.0 (0.20) 5.0 (0.20) FRONT SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. MOUNTING FOOT INSTALLATION TOOL 3. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. (DETAIL ‘A’) 4. RoHS COMPLIANT. DETAIL ‘A’ 5. EN 60044-1 COMPLIANT. 6. NOT ALL CERTIFICATIONS SHOWN. FIGURE 2.7 EFCT-26 Outline and Mounting Details. Installation FPS Feeder Protection System 3. SYSTEM WIRING 3.1 GENERAL A typical connection diagram is shown in Fig. 3.1. The FPS-CTU provides the 24-Vdc supply for the peripheral modules and it communicates with them using an RS-485 interface. The total length of the I/O communication system must be less than 1.2 km (4,000’). The power supply in the FPS-CTU will not support more than three I/O modules. An external 24-Vdc power supply is required if more than three modules are used. The FPS-CTU voltage inputs can be directly connected to a system with line-to-line voltages up to 600 Vac. PT's are required for system voltages higher than 600 Vac. Input resistance of the voltage inputs is 3.4 M. NOTE: The current and voltage inputs must be phase sequenced A-B-C with correct polarity observed. Breaker or contactor OPEN and CLOSE commands can be issued through the digital inputs, the network interface, or the FPS-OPI. Breaker or contactor control and interlock contacts can be wired to any of the programmable digital inputs. The five programmable output relays can be used for control, protection, and interlock functions. Relay 5 is a solid-state, low-level output relay not recommended for breaker control. See Section 9 for relay ratings. Page 3-1 Rev. 1-C-031615 3.2.1.2 CURRENT INPUTS The FPS-CTU uses 1-A or 5-A CT’s for phase-current measurement. To maintain specified accuracy, phase CT’s should be selected with a primary rating between 100 and 300% of feeder current rating. Current threshold is 1.5% of CT-primary rating. All CT inputs can withstand a common-mode voltage of 120 Vac so that the FPS-CTU can be connected in series with other CT loads. The connection diagram in Fig. 3.1 shows a typical connection where the FPS-CTU is the only device connected to the phase CT's. The FPS-CTU requires the phase sequence to be A-B-C with correct polarity. A 1-A, 5-A, or sensitive CT is used for core-balance earth-leakage measurement. 3.2.1.3 VOLTAGE INPUTS For all input-voltage connections, the FPS-CTU requires the phase sequence to be A-B-C with correct polarity. If voltage inputs are not used, connect VA, VB, and VC to VN. NOTE: A voltage input is required for line-frequency metering. NOTE: The default configuration has no assignments for digital inputs and relay outputs. 3.2 WIRING CONNECTIONS 3.2.1 FPS-CTU CONNECTIONS The FPS-CTU CT-input terminal blocks accept 22 to 10 AWG (0.3 to 4.0 mm2) conductors. The remaining FPS-CTU clamping blocks accept 24 to 12 AWG (0.2 to 2.5 mm2) conductors. Terminal blocks unplug to allow the FPS-CTU to be easily replaced. 3.2.1.1 SUPPLY VOLTAGE Connect supply voltage to terminals 1 and 2 (L1 and L2) as shown in Fig. 3.1. In 120-Vac systems, L2 is usually designated as the neutral conductor. For directcurrent power supplies, use L1 for the positive terminal and L2 as the negative terminal. Earth terminal 3 ( ). Internal surge-protection devices are connected to terminals 4 (SPG) and 4A (SPGA) to allow dielectricstrength testing. Terminals 4 and 4A must be connected except during dielectric-strength testing. The 24-Vdc I/O module supply (terminals 56 and 60) can support three I/O modules. An external 24-Vdc supply is required if more than three modules are used. System Wiring L2 L1 ALTERNATE CONNECTION SHOWN DOTTED ØC ØB ØA L L 1 2 1 2 5A 1A B 5A 1A A S P G 3 4 S P G A 4A 5 22 21 5 C 2 3 4 5 VOLTAGE 19 18 17 V V V A B C TRIP 52a K1 CLOSE 52b K1 52a (NOTE 2) DIRECT VOLTAGE INPUT (600 VAC MAXIMUM) SOLID STATE RELAY 6 7 8 9 10 11 12 13 14 15 16 K1 1 20 V N RELAY OUTPUTS 5A 1A EFCT EARTH LEAKAGE 24 23 S 1 EARTH FAULT CT LOWER TERMINALS 5A 1A C 27 26 25 1 5 C PHASE CURRENT 30 29 28 1 5 C 33 32 31 1 5 C PHASE CT’S + + 52b 4-20 mA ANALOG OUTPUT TO COMMUNICATIONS NETWORK AN OUT COMM S H 35 36 37 39 40 OPERATOR INTERFACE I/O MODULE 62 61 60 59 58 57 56 55 54 53 52 S 0 2 H V PTC 4 IRIG AN IN V COMM PTC NOTE 1 R E S ET E R ROR ALARM TRIP P OW E R 41 42 24 VDC SOURCE FPS-CTU DIGITAL INPUTS C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I 43 44 45 46 47 48 49 50 51 FEEDER PROTECTION SYSTEM CONTROL UNIT 20 mA ANALOG INPUT + 2 4 V 5 SHOWN WITH 24 VDC CONTACT STATUS MONITORING ENABLED. SEE FIGS. 3.8 AND 3.9 FOR RTD CONNECTIONS. S H 0 L V D 1 2 3 4 UPPER TERMINALS 2 1. NOTES: REAR VIEW - FPS-OPI OPERATOR INTERFACE + MOTOR FPS Feeder Protection System Page 3-2 Rev. 1-C-031615 FIGURE 3.1 Typical FPS Connection Diagram. System Wiring Page 3-3 Rev. 1-C-031615 FPS Feeder Protection System 3.2.1.3.1 DIRECT CONNECTION Potential transformers (PT's) are not required for system voltages up to 600 Vac line-to-line. Connect the voltage inputs as shown in Figs. 3.1 and 3.2. ØA ØB ØC ØA ØB ØC VA VB VC VN 19 18 17 20 FIGURE 3.2 Direct Connection. 3.2.1.3.2 1-PT CONNECTION The 1-PT connection is shown in Fig. 3.3. Connect the PT between phase A and phase B. The PT-secondary voltage must be less than 350 Vac. NOTE: The 1-PT connection does not allow detection of voltage unbalance. VA VB VN VC 19 18 20 17 FIGURE 3.4 2-PT Connection. 3.2.1.3.4 3-PT CONNECTION The 3-PT connection is shown in Fig. 3.5. The PTsecondary voltages must be less than 350 Vac. Since the FPS-CTU measures line-to-line voltage, there is no advantage in using a 3-PT connection over a 2-PT connection. ØA ØB ØC ØA ØB ØC VA VN VB VC 19 20 18 17 FIGURE 3.3 1-PT Connection. 3.2.1.3.3 2-PT CONNECTION The 2-PT connection is shown in Fig. 3.4. The PTsecondary voltages must be less than 350 Vac. Connect the PT secondaries in open delta. VA VB VC VN 19 18 17 20 FIGURE 3.5 3-PT Connection. 3.2.1.4 DIGITAL INPUTS Digital inputs 1 to 8 (terminals 44 to 51) are referenced to COM (terminal 43). These inputs are isolated from all other terminals and operate over a 24 to 130 Vac/Vdc range. Inputs 1 to 7 have programmable functions. See Table 4.2. System Wiring Page 3-4 Rev. 1-C-031615 FPS Feeder Protection System 3.2.1.4.1 DC OPERATION Supply voltage for dc-input operation can be obtained from the 24-Vdc source (terminals 41 and 42), or it can be obtained from an external 24- to 130-Vdc supply. The internal source is current limited at 100 mA and is referenced to the analog output (terminal 40) and the I/O Supply (terminal 56). Connect the “” terminal of the dc source to COM and connect field inputs between “+” and the digital-input terminals. 3.2.1.4.2 AC OPERATION Inputs operate over a 24- to 130-Vac range. Connect the ac neutral to COM and connect field inputs between line and the digital inputs. 3.2.1.4.3 COMBINED AC AND DC OPERATION If both ac and dc inputs are used, connect both the acsupply neutral and dc-supply “” to COM. 3.2.1.5 ANALOG INPUT (AN IN) The analog input (terminal 52 and 53) is a 4–20-mA current input with a 100- input impedance. NOTE: The analog input is referenced to an internal supply with 100-k resistors. Maximum common-mode voltage is ± 5 Vdc with respect to FPS-CTU terminal 4. 3.2.1.6 ANALOG OUTPUT (AN OUT) The analog output is a self-powered current-source output. The current-source output is the “+” (terminal 39) and the common is “” (terminal 40). NOTE: The analog output (terminal 40) is internally referenced to the 24-Vdc source (terminal 42) and the I/O supply (terminal 56). 3.2.1.7 PTC INPUT Terminals 54 and 55 are provided for PTC overtemperature protection. See Section 9 for specifications. 3.2.1.8 IRIG-B INPUT Terminals 61 and 62 are used for an IRIG-B time-code signal. When an IRIG-B signal is detected, the real-time clock (RTC) synchronizes with it. The user must set the FPS date value because the IRIG-B day-of-the-year parameter is not supported. If the time-code generator does not have a local-time adjustment, the IRIG Offset set points can be used to adjust the hour and minute values so that the FPS will read local time. 3.2.1.9 I/O MODULE COMMUNICATION The I/O module communications interface (terminals 56 through 60) is used to support optional modules. The connector labeled Operator Interface on the FPS-CTU top panel is in parallel with terminals 50 to 56. It is used for direct FPS-OPI mounting. See Section 2.3. I/O module communication is based on the two-wire multi-drop RS-485 standard. Overall line length must not exceed 1.2 km (4,000’). For line lengths exceeding 10 m (33’), 150- terminations are required at the cable ends. See Fig. 3.7. 3.2.1.10 RS-485 NETWORK COMMUNICATIONS Terminals 35, 36, and 37 are used for the standard RS-485 interface. See Section 4.2.15. 3.2.2 FPS-OPI CONNECTIONS AND ADDRESS SELECTION Connect the FPS-OPI to the FPS-CTU using shielded cable (Belden 3124A or equivalent). The 24-Vdc supply for the FPS-OPI is provided by the FPS-CTU. The cable shield must be connected at both ends so that FPS-OPI transient protection is operational. See Fig. 3.7. The FPS-OPI has two switches to select its network address. See Figs. 2.2 and 3.6. Up to three FPS-OPI modules can be connected to the I/O MODULE bus, and each active OPI must have a unique address. If one OPI is used, address 1 must be used. If two OPI’s are used, addresses 1 and 2 must be used. If three OPI’s are used, addresses 1, 2, and 3 must be used. Table 3.1 and Fig. 3.6 shows the addressing selection format. TABLE 3.1 FPS-OPI ADDRESS SELECTION ADDRESS SWITCH 1 SWITCH 2 0 (Factory Test) 1 (First OPI) 2 (Second OPI) 3 (Third OPI) Open Open Closed Open Open Closed Closed Closed 1 2 OPEN OPEN CLOSED OPEN FIGURE 3.6 Address Selection Switch Detail. System Wiring Page 3-5 Rev. 1-C-031615 FPS Feeder Protection System 3.2.4 DIELECTRIC-STRENGTH TESTING Dielectric-strength testing should be performed only on CT inputs, PT inputs, output relays, and digital inputs. Unplug all other I/O and remove the SPG connection (terminal 4 to terminal 4A) on the FPS-CTU during dielectric-strength testing. 3.2.3 MPS-RTD CONNECTIONS AND ADDRESS SELECTION MPS-RTD terminal blocks accept 24 to 12 AWG (0.2 to 2.5 mm2) conductors. Connect the MPS-RTD to the FPS-CTU using the fourconductor shielded cable (Belden 3124A or equivalent) as shown in Fig. 3.7. Connect RTD’s to the MPS-RTD as shown in Fig 3.7. Connect the surge-protection (SPG) terminal 20 to terminal 19 ( ), and earth terminal 19. The MPS-RTD has two switches to select its network address. See Figs. 3.6 and 3.8. Only one RTD module is supported. Select address 1 to enable RTD module communication. Table 3.2 shows the addressing selection format. a) FPS-CTU 57 CONTROL UNIT 0 (Offline) 1 (RTD Module Enabled) 2 (Reserved) 3 (Reserved) RED 60 59 TABLE 3.2 MPS-RTD ADDRESS SELECTION ADDRESS SWITCH 1 SWITCH 2 GREEN + - WHITE - Rt 58 BLACK Open Closed Closed Closed 1 18 GREEN + 17 WHITE - 16 MPS-RTD RTD MODULE 11 BLACK 15 19 RED 60 59 57 CONTROL UNIT 58 3 Open OPERATOR INTERFACE 2 RED FPS-CTU Closed FPS-OPI 4 3 3 b) Open 5 + 56 Open 5 + GREEN + - WHITE - Rt 4 FPS-OPI 2 OPERATOR INTERFACE 3 BLACK 20 1 56 BLACK WHITE GREEN NOTES: + 15 MPS-RTD 16 RTD MODULE 17 11 RED 18 19 20 1. INTERCONNECT CABLE BELDEN 3124A OR EQUIVALENT. 2. Rt = 150 OHMS, 1/4 WATT. REQUIRED FOR LINE LENGTHS EXCEEDING 10 M (33’). 3. CONNECT CABLE SHIELD ON BOTH ENDS FOR OPI INSTALLATIONS. FIGURE 3.7 Two Examples of I/O Module Connections. System Wiring Page 3-6 Rev. 1-C-031615 FPS Feeder Protection System 3-WIRE RTD CONNECTION tO tO tO tO tO S C D R H 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 C D R S C D R C D R S C D R S H P H INP 8 INP 7 INP 6 INP 5 G INPUT MODULE PWR MPS-RTD COMM C 3 S H 4 R 5 D 6 C 7 R 8 2 4 S 0 V D C H R D C V 9 10 11 12 13 14 15 16 17 18 INP 4 COMM tO tO RED D 2 INP 3 BLACK R 1 CTU/ MPU INP 2 WHITE INP 1 GREEN REMOVE ACCESS COVER TO ACCESS ADDRESS SELECTION SWITCHES INP 5 ALTERNATE 2-WIRE RTD CONNECTION tO tO WHITE BLACK RED GREEN INTERCONNECT CABLE BELDEN 3124A OR EQUIVALENT 62 61 60 59 58 57 56 55 54 53 52 S 0 2 H V PTC 4 IRIG AN IN V COMM I/O MODULE FEEDER PROTECTION SYSTEM CONTROL UNIT FPS-CTU P OW E R TRIP ALARM E R ROR OPERATOR INTERFACE R E S ET AN OUT COMM S H 35 36 37 39 40 24 VDC SOURCE + + 41 42 DIGITAL INPUTS C I I I I I I I H O N N N N N N N S M 1 2 3 4 5 6 7 I 43 44 45 46 47 48 49 50 51 FIGURE 3.8 FPS-CTU to MPS-RTD Connection Diagram. System Wiring Page 4-1 Rev. 1-C-031615 FPS Feeder Protection System 4. OPERATION AND SETUP 4.1 GENERAL The FPS-CTU can operate independently. It can also operate in conjunction with network communications, the FPS-OPI, and the MPS-RTD. All settings are stored in the FPS-CTU and can be accessed using the OPI or the network communications interface. Use SE-Comm-RIS software and an SE-485PP or SE-485-DIN serial converter to program with a personal computer. In the following sections, menu items and setup parameters are listed in italics and are shown in the format displayed on the OPI. The OPI cannot display subscripts and superscripts. Menu selection is in the following format: Menu 1 | Sub Menu 1 | Sub Menu 2 | Sub Menu 3 |…… Example: For the menu item shown in Fig. 4.1, the notation is Setup | System Ratings | CT Primary Metering Messages Setup Protection System Ratings Starter • • • CT Primary EF-CT-Primary System Voltage Input Voltage • • • FIGURE 4.1 Menu Example. Fig. 4.2 shows the symbols that assist in navigating the menu system and how these symbols relate to the arrow keys on the FPS-OPI. See the menu map in Appendix A. 4.2 FPS-CTU 4.2.1 LED INDICATION The four LED’s on the FPS-CTU indicate POWER (green), TRIP (red), ALARM (yellow), and ERROR (red). The POWER LED is ON when supply voltage is present. The TRIP and ALARM LED’s indicate a trip or alarm condition. The ERROR LED is ON during firmware updates or when there is an FPS-CTU failure. 4.2.2 RESET SWITCH The reset switch is used to simultaneously reset all trips. Trips cannot be held off by a maintained closure. 4.2.3 PHASE-CT INPUTS OPI Menu: Setup | System Ratings | CT Primary The setting range for the CT-primary rating is 1 to 5,000 A. To maintain specified accuracy, phase CT’s should be selected with a primary rating between 100 and 300% of rated current. Current unbalance will indicate “” if the current sequence is B-A-C. If B-A-C sequence is indicated, correct the CT connections so that power measurements will be valid. NOTE: B-A-C sequence will cause a trip if current phasereverse protection is enabled. NOTE: Phase-unbalance and phase-loss testing requires three-phase inputs to the FPS. These symbols indicate the menu level. Up to five submenu-level symbols may be displayed. Use left arrow key or ESC to move back one menu level. Cursor indicates selected menu item and shape indicates available scrolling directions. Indicates top of list. Scroll using down arrow key. Scroll using up or down arrow keys. Indicates bottom of list. Scroll using up arrow key. ¬¬¬¬¬ TITLE Indicates that there are related data displays to the left or right of this display. Use left or right arrow keys to view adjacent data ¬Ñ ½ MENU ITEM 1 Ñ Use right arrow key to select submenu. ² MENU ITEM 2 ¼ « MENU ITEM 3 * Use right arrow key to display data. Indicates active item in list-type set-point displays. FIGURE 4.2 Menu Symbols. Operation and Setup Page 4-2 Rev. 1-C-031615 FPS Feeder Protection System 4.2.4 EARTH-FAULT-CT INPUT OPI Menu: Setup | System Ratings | EF-CT Primary The setting range for the earth-fault-CT-primary rating is 1 to 5,000 A. The CT-primary rating is 5 A for sensitive CT’s—EFCT-1 and EFCT-2. TABLE 4.1 OUTPUT-RELAY FUNCTIONS FUNCTION ASSIGNMENT OR ACTION Trip1 Trip2 4.2.5 VOLTAGE INPUTS OPI Menu: Setup | System Ratings Select the voltage-connection type (1 PT line-line, 2 PT line-line, 3 PT line-neutral/direct) to enable voltagemeasuring functions. System Voltage is the system lineto-line voltage. The system voltage range is 120 V to 75 kV. For the 1-PT and 2-PT connections, Input Voltage is the PT-secondary voltage when system voltage is applied. For the 3-PT connection, the Input Voltage is the PT-secondary line-to-line voltage (208 V for 120-Vsecondary PT’s). For the direct connection, set Input Voltage the same as the System Voltage setting. In all cases, line-to-line voltages are displayed. Voltage unbalance will indicate “” if the voltage sequence is B-A-C. If B-A-C sequence is indicated, correct the PT connections so that power measurements will be valid. NOTE: The 1-PT connection does not allow detection of voltage unbalance. NOTE: B-A-C sequence will cause a trip if voltage phase-reverse protection is enabled. 4.2.6 FREQUENCY OPI Menu: Setup | System Ratings | Frequency Set Frequency at 50 or 60 Hz. Trip3 Alarm1 Alarm2 Alarm3 CB Open (3) CB Close (3) Contactor (3) Trip1 Pulse (1) Local 4.2.7 SET-POINT GROUP OPI Menu: Setup | System Ratings The FPS-CTU supports two set-point groups. The Setup | System Ratings | Set-Point Group menu specifies the active set-point group as Group1 or Group2. If the digital input is used to select the set-point group, it has priority over the menu setting. 4.2.8 OUTPUT RELAY ASSIGNMENT OPI Menu: Setup | Relay Outputs | Relay x Each of the five output relays can be assigned to one of the functions listed in Table 4.1. More than one relay can be assigned the same function. Note that Relay 5 is a solid-state relay with a low current rating. Relay function CB Open, CB Close, and Contactor operate in conjunction with the breaker or contactor control functions. A control type other than Protection Only must be selected in the Breaker Control | Control Type menu. See Section 6. Breaker or contactor close status can be monitored using auxiliary contacts and the digital inputs. See Section 4.2.9. Interlock Current Network Control Group2 Watchdog None (2) (1) (2) (3) Relay operates when a trip occurs in a protective function assigned Trip1, Trip1&2, Trip1&3, or Trip1,2,&3. Fail-safe or nonfail-safe mode selection is active. Relay operates when a trip occurs in a protective function assigned Trip2, Trip1&2, Trip2&3, or Trip1,2,&3. Fail-safe or nonfail-safe mode selection is active. Relay operates when a trip occurs in a protective function assigned Trip3, Trip1&3, Trip2&3, or Trip1,2,&3. Fail-safe or nonfail-safe mode selection is active. Relay operates when an alarm occurs in a protective function assigned Alarm1, Alarm1&2, Alarm1&3, or Alarm1,2,&3. Fail-safe or non-fail-safe mode selection is active. Relay operates when an alarm occurs in a protective function assigned Alarm2, Alarm1&2, Alarm2&3, or Alarm1,2,&3. Failsafe or non-fail-safe mode selection is active. Relay operates when an alarm occurs in a protective function assigned Alarm3, Alarm1&3, Alarm2&3, or Alarm1,2,&3. Failsafe or non-fail-safe mode selection is active. Relay energized momentarily to open circuit breaker. Relay energized momentarily to close circuit breaker. Relay energized to close contactor, deenergized to open/trip contactor. Trip1 energizes the relay for the time duration specified by the RY Pulse Time set point. Relay energized when Local control is selected. Relay is energized when all digital-input interlocks are completed. Relay is energized when current is detected. Relay controlled via network. Relay is energized when Group2-setpoints are active. Relay is energized when the supply voltage is applied and the FPS is operating properly. No Assignment (Default) Assign this function to only one relay. Non-failsafe operation only. Relay outputs must be assigned. Default is None. Only active if a control type is enabled. When a trip occurs, control relays operate to open the breaker or contactor and relays assigned the Trip1, Trip2, or Trip3 function operate. The trip signal may originate from a protective function, from a digital input assigned the Trip1 function, or from a communications network command. See Sections 4.2.9 and 6. Operation and Setup Page 4-3 Rev. 1-C-031615 FPS Feeder Protection System Relays assigned a trip or alarm function operate in failsafe or non-fail-safe mode. Set the mode using the Setup Relay Outputs Relay x Mode menu. Except for overload trips, which can be selected to auto-reset, trips must be reset with an FPS-OPI, a digital input, or a network command. A trip cannot be reset when the trip condition is present. When a protective function issues an alarm, relays assigned to the corresponding Alarm1, Alarm2, or Alarm3 function operate. Alarms auto-reset when the alarm condition is corrected. Relays assigned the Interlock function energize when all digital inputs assigned the Interlock function are valid (voltage detected at digital input). 4.2.9 DIGITAL INPUTS 1 TO 7 OPI Menu: Setup | Digital Inputs | Digital Input x | Input x Function OPI Menu: Setup | Digital Inputs | Digital Input x | In x Start Bypass OPI Menu: Setup | Digital Inputs | Digital Input x | In x Bypass Delay OPI Menu: Setup | Digital Inputs | Digital Input x | In x Trip Delay Each digital input can be assigned to one of the functions listed in Table 4.2. More than one digital input can be assigned the same function. Close inputs are not active when Protection Only is selected as the control type. OPEN on the FPS-OPI is always active. When Control Type is set to None, OPEN initiates a Trip1 signal. Close Bypass, Bypass Delay, and Trip Delay set points apply only when Trip1 is selected. When Close Bypass is enabled, the Trip1 function is bypassed when a close is detected for the duration specified by Bypass Delay. After the Bypass Delay, the Trip1 function is enabled and a trip occurs if the digital-input voltage is removed for the time specified by the Trip Delay. If Close Bypass is disabled, Bypass Delay is not used and the Trip1 function is always enabled. Reset inputs are “one-shot” resets that require a transition from open to closed. Maintaining a reset switch closure does not inhibit trips. LOCAL is selected using the digital input, or by network communications. The Local Select source is responsible for de-selecting. For example if both the digital input and the network communications select LOCAL, both must also de-select LOCAL. In the event that the network fails to deselect LOCAL, de-selection can be performed using the Setup System Config Maintenance Unlock Local Menu. When assigned to Set-Point Group, one of the two groups is selected. The digital-input selection has priority over the Setup | System Ratings | Set-Point Group setting. TABLE 4.2 DIGITAL-INPUT FUNCTIONS FUNCTION STATE (1) Group2 Settings Local Control Permissive 3-Wire Close 2-Wire Close 3-Wire Close (3) Local 2-Wire Close Local (3) 52a Close Status 52b Open Status Interlock (2) Trip1 Reset + Trig - Trig + - Trig Control Power None (1) (2) (3) 1 = Group2 Set Points Active 0 = Group1 Set Points Active 1 = Local Control Mode 0 = Remote Control Mode 1 = Close Allowed 0 = Close Not Allowed (Device Open) 1 = Close Device (Momentary, 3-Wire Open/Close) 1 = Close Device (Maintained) 0 = Open Device 1 = Close Device (Momentary, 3-Wire Open/Close) 1 = Close Device (Maintained) 0 = Open Device 1 = Device Closed 0 = Device Open 1 = Device Open 0 = Device Closed 1 = Close Allowed (If All Interlocks are Valid) 0 = Close Not Allowed 1 = No Trip1 0 = Trip1 (Delays Selectable) 1 = Reset trips 1 = Positive-Edge Record Trigger 1 = Negative-Edge Record Trigger 1 = Transition Trigger 1 = Voltage Present on Input 0 = No Voltage Present on Input No Assignment (Default) 1 = Input voltage applied, 0 = Input voltage not applied. Interlocks bypassed in LOCAL. Operational only in LOCAL. The following rules apply when multiple inputs are assigned the same function: 3-Wire Close and 3-Wire Close Local: Momentary voltage on any input will initiate a close. (FPS must be in LOCAL for Local Close operation.) Permissive: Voltage must be present on all inputs to allow an FPS-controlled close. Interlock: Voltage must be present on all inputs to allow an FPS-controlled close and to energize an interlock output relay. Digital inputs programmed as Interlock are bypassed in LOCAL. 52a Close Status: Voltage must be present on all inputs when device is closed and not present when device is open. Reset: Voltage applied to any input will reset trips. 2-Wire Close: Voltage on any input will initiate a close. All inputs must be removed for valid open. 52b Open Status: Voltage must be present when device open and not present when device is closed. Operation and Setup Page 4-4 Rev. 1-C-031615 FPS Feeder Protection System The Permissive and Interlock settings are used in conjunction with the breaker or contactor control functions. Both must be valid to allow a close operation. The permissive input is typically connected to a normally closed push-button when 3-wire control is used. The distinguishing feature between permissive and interlock inputs is that interlocks are bypassed in LOCAL while permissive inputs must be valid for both REMOTE and LOCAL modes of operation. Device open and close status is monitored by inputs programmed as 52a Close Status and 52b Open Status. The 52a inputs must be valid (voltage present) when the device is closed and the 52b inputs must be valid (voltage present) when the device is open. See Section 6.2.1. For maximum control integrity and immunity to power fluctuations, the 24-Vdc source voltage provided on terminals 41 and 42 should be used for digital-input operation. If external ac voltage is used for digital-input control, it is recommended to connect control voltage to one of the digital inputs programmed for Control Power. This input is used to indicate the presence of control voltage. When voltage is not detected on this input, a 500 ms delay is active on all other inputs to allow the FPS to “ride-through” voltage fluctuations and power-off conditions without a false trip caused by loss of voltage on a digital input. 4.2.10 ANALOG OUTPUT OPI Menu: Setup | Analog Output | Output Parameter A 4-20-mA programmable current output is provided on the CTU. Analog-output parameters are shown in Table 4.3. Factory calibration is 4-20 mA. If calibration is required, use the Analog Output menus. PARAMETER Phase Current Earth Leakage Used I2t Capacity Group A Temperature (1) Group B Temperature (1) Group C Temperature (1) Ambient Temperature (1) Voltage Unbalance (I) Power Factor Real Power Reactive Power Apparent Power Zero Full Scale (1) Zero Calibration: Select Zero in the Output Parameter menu. Measure the output current and adjust the Zero Calibrate setting for the desired output. The calibration number for 4 mA will be in the range of 100 to 110. Full-Scale Calibration: Select Full Scale in the Output Parameter menu. Measure the output current and adjust the FS Calibrate setting for the desired output. The calibration number for 20 mA will be in the range of 540 to 550. Calibration numbers are not changed when factory defaults are loaded. 4.2.11 ANALOG INPUT OPI Menu: Setup | 4-20 Analog In | Input Function The analog input function is selectable as Metering or Protection. 4.2.11.1 METERING ONLY OPI Menu: Setup | 4-20 Analog In Metering Only When Metering Only is selected, an analog input does not affect FPS operation, but its value can be observed in the Metering menu. 4.2.11.2 PROTECTION OPI Menu: Setup | 4-20 Analog In Protection The Protection analog input has high- and low-level trip and alarm set points. A high-level trip or alarm occurs when the 4-20-mA input exceeds the high-level trip or alarm set point. A low-level trip or alarm occurs when the 4-20-mA input is lower than the low-level trip or alarm set point. TABLE 4.3 ANALOG-OUTPUT PARAMETERS FULL SCALE PH-CT-Primary Rating EFCT-Primary Rating 100% I2t 200°C 200°C 200°C 200°C System Voltage 1.0 per Unit or 100% 1.0 CT Primary System Voltage 3 CT Primary System Voltage 3 CT Primary System Voltage 3 Not Applicable Not Applicable COMMENTS Maximum of 3 Phases Maximum of Group A RTD’s Maximum of Group B RTD’s Maximum of Group C RTD’s Maximum of Ambient RTD’s Maximum Line-to-Line Voltage I2/I1 Absolute Value Absolute Value Absolute Value Absolute Value Used for Zero Calibration Used for Full-Scale Calibration Output range is 0 to 200°C. The output defaults to the calibrated zero output for an open or shorted RTD sensor. Operation and Setup FPS Feeder Protection System 4.2.12 BREAKER CONTROL OPI Menu: Setup | Control As a default, Control Type is set to Protection Only. When a Control Type is selected, an output relay must be assigned for breaker control. See Section 4.2.8. Digital inputs must be assigned if breaker-status feedback is required. See Section 4.2.9. See Section 6 for breaker control information. 4.2.13 PROTECTION OPI Menu: Setup | Protection OPI Menu: Setup | System Ratings | Run Mode Delay See Section 5 for protective function details. 4.2.14 MISCELLANEOUS CONFIGURATION OPI Menu: Setup | System Config System Name Appears on many of the display screens and can be set by the user. (18-character alphanumeric field) Password Used to change the 4-character alphanumeric password. Clock Setting Used to set the date, 24-hour clock, and IRIG set points. Daylight savings time is not supported. Password Timeout Used to set the password time-out delay. Delay is measured from last key press. Maintenance Used to clear event records, trip counters, and energy values. Used to load defaults. Used to view firmware version and serial numbers. Used to unlock local control if communication is lost. Used for firmware updates 4.2.15 NETWORK COMMUNICATIONS OPI Menu: Setup Hardware Network Comms The standard interface on the FPS is an RS-485 network. This network supports Modbus® RTU and A-B® DF1 protocols. The protocol, network ID (address), error checking, and baud rate are selectable. See Appendices C, D, E, and F. If equipped with an optional network interface, refer to the appropriate FPS communications interface manual. Page 4-5 Rev. 1-C-031615 4.3 FPS-OPI 4.3.1 GENERAL See Fig. 4.2. The Operator Interface (OPI) is used to perform control functions, display meter readings, and program the FPS-CTU. Set points are not resident in the OPI. Control voltage for the FPS-OPI (24 Vdc) is supplied by the CTU and communications with the CTU is through an RS-485 link. This allows the FPS-OPI to be mounted up to 1.2 km (4,000’) from the CTU. Up to three OPI’s can be used with each CTU. 4.3.2 CONFIGURING THE FPS-CTU FOR OPI OPERATION OPI Menu: Setup | Hardware | OPI Display Select the number of OPI's in the Number of OPI’s menu. The FPS-CTU supports up to three OPI’s. In multiple-OPI systems, all OPI’s display the same information and the CTU will process key presses from all OPI’s. If an OPI is not used, set number of OPI’s to 1 (default). A loss-of-communication trip can be enabled in the OPI-Loss Trip menu. Display intensity can be set in the Intensity menu. To extend the life of the vacuum-florescent display, a screen saver is provided and enabled using the Screen Saver menu. The screen saver activation time is defined by the Setup | System Config | Password Timeout setting. 4.3.3 BREAKER CONTROL OPI Menu: Setup | Control | Control Select Type A control type other than Protection Only must be selected for breaker control functions to become operational. Breaker control operates in one of two modes; REMOTE or LOCAL. REMOTE mode is the default. LOCAL mode is selected using one of the digital inputs, see Table 4.2, or a network command. The OPI REMOTE or LOCAL LED’s indicate the control mode. 4.3.3.1 LOCAL CONTROL OPI Menu: Setup | Digital Inputs | Digital Input x | Input x Function Local control can also be selected with a network command or by a digital input programmed for Local Select. When the LOCAL LED is ON, the FPS is under local control and the digital inputs programmed as 3-Wire Close Local are the only close sources the FPS will respond to. NOTE: The I2t Close Inhibit function and digital inputs programmed as Interlock are bypassed in local control. Each local control source must release local control to allow the FPS to return to Remote Control. Operation and Setup FPS Feeder Protection System Page 4-6 Rev. 1-C-031615 FIGURE 4.3 FPS-OPI Interface. 4.3.3.2 REMOTE CONTROL OPI Menu: Setup | Control | Remote Group When the REMOTE LED is ON, FPS control is from the sources enabled in the Remote Group menu. Source selections are Digital Inputs, OPI, and Network. If Digital Inputs is enabled, digital inputs programmed for Close, and 2-Wire Close are enabled. If OPI is enabled, the close key on the OPI is enabled and if Network is enabled, close commands from the network are enabled. NOTE: The OPI OPEN key and digital OPEN inputs always cause an open. 4.3.4 METERING OPI Menu: Metering OPI Menu: Setup | Hardware | OPI Display | Meter Summary When Metering is selected in the main menu, press the right-arrow key to access a list of metering displays. Use the up- and down-arrow keys to scroll through the display list. Pressing the right-arrow key displays the selected metering information. See FPS-OPI menu map in Appendix A. RESET is a “hot key” that is active in all meter displays. Pressing RESET causes a jump to the Trip and Alarm display to allow trips to be viewed and reset. Pressing ESC or the left-arrow key causes a return to the Metering display. Many displays include per unit (pu) values where 1.0 pu is equal to 100%. Ia, Ib, Ic, I1, and I2 are in per unit of full-load current. Ig is in per unit of earth-fault-CTprimary rating. The unbalance display indicates minus (-) if current inputs are not sequenced A-B-C. The IEEE convention is used for power displays: +Watts, +Vars, -PF (Lag) Importing Watts, Importing Vars +Watts, -Vars, +PF (Lead) Importing Watts, Exporting Vars -Watts, -Vars, -PF (Lag) Exporting Watts, Exporting Vars -Watts, +Vars, +PF (Lead) Exporting Watts, Importing Vars Operating range for energy values is ±4E±304, however the maximum display range is ±2E±34. The Setup | Hardware | OPI Display | Meter Summary menu is used to configure the type of metering display selected by the Metering | Summary menu. In order to view the maximum amount of data, no menu title is displayed. Display selections for the Summary menu are: Operation and Setup Page 4-7 Rev. 1-C-031615 FPS Feeder Protection System IDR Current-based metering (I), digital inputs (D), and relay outputs (R): Average current, current unbalance, earth leakage, used I2t, digital input and relay output status. I: xxxx A Iu: xxxx Ig:xxxx A I2t:xx% Di: 1..7: xxxxxxx Ry: 1..5: xxxxx This selection is the default for the summary display. IVP Current-based metering (I), voltage (V), unbalance, and power (P): Average current, current unbalance, earth leakage, used I2t, average voltage, voltage unbalance, power and power factor. I: xxxx A Iu: x.xx Ig:xxxx A I2t: xx% V: xx.xx kV Vu: x.xx P: xx.x kW PF: x.xx This selection is applicable for an FPS using voltage inputs. IVPA Current-based metering (I), voltage (V), power (P), and analog I/O (A): Average current, average voltage, earth leakage, used I2t, power, power factor, and analog currents. I: xxxx A V: xx.xx kV Ig:xxxx A I2t:xx% P: xx.x kW PF: x.xx Ai:xxx% Ao: xxx% This selection is applicable when the FPS analog output is used in a process control loop. The analog input and output values provide indication of controlsystem operation. For each metering display, Table 4.4 shows the information that can be displayed. 4.3.5 MESSAGES OPI Menu: Messages Selecting this menu item allows trip and alarm messages, status messages, event records, and statistical data to be viewed and resets to be performed. 4.3.5.1 TRIP RESET OPI Menu: Messages | Trip and Alarm Up to fifteen trip and alarm messages can be displayed in a scrollable-list format. Trip messages must be individually selected and reset when the OPI RESET key is used. All trips are simultaneously reset by digitalinput reset, with the FPS-CTU RESET key or with a communications-network command. Alarms are non- latching and are displayed only for the time that the alarm condition exists. RESET is a “hot key” to the Trip and Alarm display, except during set-point entry. In the Trip and Alarm display, pressing ESC or the left-arrow key causes a return to the display shown when RESET was pressed. 4.3.5.2 STATUS OPI Menu: Messages | Status Messages This menu is used to display status messages. Status messages are shown in Table 4.5. 4.3.5.3 DATA LOGGING OPI Menu: Messages | Event Records Trip-record data, start-record data, and Emergency Thermal Resets (ETR) are logged. Trip-record data includes the time of trip, cause of trip, and pre-trip (1) data. ETR records contain a snapshot of the data prior to an ETR. Trip or ETR records include: Time Stamp YY/MM/DD HH:MM:SS Vab, Vbc, Vca, Ia, Ib, Ic, and Ig at time of trip or ETR Unbalance (I2/I1, V2/V1) at time of trip or ETR P, Q, S, and PF at time of trip or ETR (1) Used I2t at time of trip or ETR PTC/RTD temperature data if applicable Record Type .............................. Trip/ETR Number of Records .................... 64 (First In First Out) (1) Recorded values for power quantities (P, Q, S, PF) are averages of measurements over the previous 16 cycles. 4.3.5.4 STATISTICAL DATA OPI Menu: Messages | Statistics OPI Menu: Setup | System Config | Maintenance The FPS records the following statistical data: Running hours (Hours with current detected) Counters for all trips Statistical data can be cleared in the Maintenance menu. 4.3.5.5 EMERGENCY THERMAL RESET OPI Menu: Messages | Emerg I2t Reset The Emerg I2t Reset menu is used to reset the thermal memory. See Section 5.2.2. Operation and Setup Page 4-8 Rev. 1-C-031615 FPS Feeder Protection System METERING MENU Summary Current Unbalance (I) Earth Leakage Thermal Capacity Voltage Unbalance (V) Power Energy Frequency RTD Temperatures I/O Status System State Comm State (1) TABLE 4.4 METERING DISPLAY INFORMATION DISPLAY (1) Displays values as per the Meter Summary menu. IDR, IVP, or IVPA. Ia, Ib, Ic in A and per unit of Ip. I1, I2, in per unit of Ip, I2/I1 in per unit. Ig in A and per unit of Ie. Used I2t in percent. Trend I2t in percent. Displays reset time when tripped on I2t. Displays time to trip if in overload. Displays time to I2t Inhibit removal. Vab, Vbc, Vca in kV and per unit of Vp. V1, V2, in per unit of Vp, V2/V1 in per unit. P in kW, Q in kVA, S in kVAR, PF. kWh, kVAh, kVARh. Frequency in Hz from Phase A voltage input. Summary shows maximum and minimum temperatures for A1, A2, and A3 groups RTD’s in degrees C. RTD ID, name, function, temperature in degrees C for each enabled RTD. Analog input in mA, digital inputs and relay outputs in binary. Displays control state when breaker control is enabled. Displays set-point group. Displays ETR mode. Displays DF1 state as online or timed out. Displays Modbus state as online or timed out. Displays Anybus module error and status. Displays DeviceNet errors and status. All but Summary, RTD, and System State metering displays show System Name. TABLE 4.5 STATUS MESSAGES MESSAGES DESCRIPTION INx Interlock Open INx Open t Disabled by ETR The interlock assigned to digital input x is open, preventing a close. The OPEN switch assigned to digital input x is open, preventing a close. Indicates that the FPS is in ETR mode. Does not prevent a close. 4.3.6 PASSWORD ENTRY AND PROGRAMMING OPI Menu: Setup | System Config | Password Timeout NOTE: Factory default password is 1111. All set points are locked from changes until the fourcharacter password is entered. If set-point access is locked, the user is prompted to enter the password. Once entered, set-point access is allowed and remains enabled until a key has not been pressed for the time defined by the Password Timeout set point. EXAMPLE: Prior to password entry: I2T PICKUP = 1.00 x Ip Locked! Press ª To Enter Password. When ENTER is pressed, the Password Entry display is shown: PASSWORD ENTRY Enter Password And Press ª [****] Use the left- and right-arrow keys to select the position of the flashing cursor. Use the up- and down-arrow keys to select password characters. Press ENTER. When the correct password is entered, a flashing cursor is displayed, the set-point range and units are shown, and set points can be changed. I2T PICKUP = 1.00 x Ip (0.10 ¼ 1.25) x Ip [00001.00] Use the up- and down-arrow keys to change a setpoint update-field character, and use the left- and rightarrow keys to move between characters. Press ENTER Operation and Setup FPS Feeder Protection System Page 4-9 Rev. 1-C-031615 to update the set point, or press ESC to exit the display without changing the set point. A set point is set to the minimum or maximum value of its range if an out-ofrange value is entered. Press ESC to exit the set-pointupdate screen. The sequence for set-point characters depends upon the set-point type. The character sequence for numeric set points is: ...0123456789.0123..... The character sequence for string set points is: . . . [0…9] [A…Z] [a…z] SP - . / [0…9] [A…Z] . . . . . Characters forming a series are shown in brackets and “SP” represents the space character. For set points requiring selection from a list, the up and down arrow keys are used to scroll through the items. In the same manner as menu items, selections are displayed using one of the three cursor symbols (½«²) preceding the item. Pressing ENTER selects the item and that item is indicated by the “” symbol to its right. EXAMPLE: PHASE INVERSE IEEE Moderate Inverse ² IEEE Very Inverse * IEEE Extreme Inverse 4.4 MPS-RTD OPI Menu: Setup | Hardware | RTD Modules OPI Menu: Setup | Protection | RTD Temperature The MPS-RTD module extends FPS protective functions to include multiple-RTD temperature monitoring. It has eight inputs that can be individually configured for RTD type, trip and alarm settings, name, and function. The RTD types are 10- copper, 100- nickel, 120- nickel, and 100- platinum. Three function assemblies (A1, A2, A3) are available. Minimum and maximum temperatures are available for each assembly and for ambient temperature. Control voltage for the MPS-RTD (24 Vdc) is supplied by the FPS-CTU and communication is through an RS-485 link. This allows the MPS-RTD to be mounted up to1.2 km (4,000’) from the FPS-CTU. To enable RTD protection, select enable in the RTD Module menu. When the hardware has been configured, temperature set points and sensor-failure action selections in the RTD Temperature menu are used for RTD temperature protection. See Section 5.22. Operation and Setup FPS Feeder Protection System Page 4-10 Rev. 1-C-031615 This page intentionally left blank. Operation and Setup Page 5-1 Rev. 1-C-031615 FPS Feeder Protection System 5. PROTECTIVE FUNCTIONS 5.1 GENERAL The FPS measures true RMS, peak, and fundamentalfrequency values of current and voltage. Fundamentalfrequency values (magnitude and phase angle) are obtained using Discrete-Fourier Transform (DFT) filtering that rejects dc and harmonics. The type of measurement used for a protective function is indicated in each section. Each protective function can be assigned a trip action that defines the output contact(s) used. Except for overload protection which has auto-reset available, FPS trips are latched. Trips are logged, alarm actions are not. Trip-action selections are: Disable Trip1 Trip2 Trip3 Trip1 and Trip2 Trip1 and Trip3 Trip1 and Trip2 and Trip3 Trip2 and Trip3 Most protection functions can be assigned an alarm action. Alarms auto-reset and are not logged. Alarm-action selections are: Disable Alarm1 Alarm2 Alarm3 Alarm1 and Alarm2 Alarm1 and Alarm3 Alarm1 and Alarm2 and Alarm3 Alarm2 and Alarm3 and CT-input protection elements can be enabled simultaneously to provide low- and high-level earth-fault protection in solidly grounded systems. Phase-overcurrent and earth-fault protection functions have two setting groups; Group 1 and Group 2. Set points are entered for each group and the active group is selected using the menu system, communications, or a digital input. See Section 4.2.9. Group selection allows setting two levels of protection. This is useful in feeder applications where the connected load changes as in tiebreaker systems, or in applications where the feeder is in maintenance mode and operation with reduced trip levels is required. Reduced current settings allows meeting NEC 240.87 Arc Energy Reduction (B) (3) Energyreducing maintenance switching with local status indicator. SE-Comm-RIS PC-interface software can be used to plot FPS protection curves. See Section 8.1.2. NOTE: See Appendix B for default set-point values. Per-unit notation (pu) is used. 1 pu = 100%. 5.2 OVERLOAD 5.2.1 I2t PROTECTION Menu: Setup | Protection | Overload Unlike IEC and IEEE inverse-time overcurrent protection, the I2t protection tracks thermal capacity for currents below the pickup setting. The I2t protection algorithm uses the square of the maximum phase current as an input. The cold-curve time-to-trip (t) in seconds for currents above the I2t Pickup setting is defined by: 2 t = 60 × τ × ln ⎛ IM ⎜ ⎜I 2–1 ⎝ M ⎞ ⎟ ⎟ ⎠ Where: τ = Time Constant setting in minutes To operate output contacts, trip and alarm actions must be assigned to output relays using the Setup Relay Outputs menu. See Section 4.2.8. For phase-overcurrent protection, three protection elements are availableoverload, inverse time, and definite time. Each can be enabled or disabled as required and are individually annunciated. IEC and IEEE inverse-time curves are supported. An IEC time multiplier setting range of 0.05 to 1.0 is provided. For consistency, the same multiplier is used for IEEE curves. For equations and curves see Figs. 5.1 to 5.9 in Section 5.3. For earth-fault protection, inverse time and definitetime elements are available for the calculated zerosequence component (3I0). For the earth-fault CT inputs, only definite-time protection is provided. Calculated (3I0) IM = IMeasured IPickup The time constant for overload protection is set in the Setup Protection Overload Groupx Time Constant menu. This value is specified in minutes. From a given curve, the time constant can be determined by knowing the trip time at six times the pickup value (t6). For this case, the time constant simplifies to: τ = 0.591 × t6 Where: T6 = Time in seconds at 6 × pickup level τ = Time Constant setting in minutes Protective Functions Page 5-2 Rev. 1-C-031615 FPS Feeder Protection System The FPS provides indication of thermal trend and used thermal capacity. Thermal trend is the value that used thermal capacity is tending toward and it is a function of the square of load current. For currents greater than or equal to the pickup current, time-to-trip is displayed in Metering | Thermal Capacity. The thermal trend value (Trend I2t) in percent is: Trend I 2t IM 2 100% For currents less than I2t Pickup current, Trend I2t in percent is a function of the Hot Factor setting given by: Trend I 2t IM 2 HF 100% Where : HF Hot Factor setting Selected I2t overload cold curves are shown in Fig. 5.1. FPS I2t overload protection is dynamic. Time to trip at any overload current depends on the value of Used I2tas Used I2t increases, time to trip decreases. The FPS I2t overload cold and warm protection curves can be plotted using SE-Comm-RIS PC-interface software. An overload trip occurs when Used I2t reaches 100%. When an overload trip occurs, reset is not allowed until Used I2t falls below the I2t Reset Level set point. The time-to-reset in minutes is: t = - Cooling Factor ln(I2t Reset Level) Time-to-reset is displayed in Metering | Thermal Capacity. The thermal model has three different reset modes; Normal, Auto, and Rapid. The I2t-overload reset mode is set using the Setup Protection Overload I2t Reset Type menu, and applies to both set-point groups. A thermal-overload trip reset is not allowed until Used I2t falls below the I2t Reset Level setting. In Normal mode a reset input is required to reset a trip. Normal is the default reset mode. In Auto mode, an I2t-overload trip is automatically reset when Used I2t falls below the I2t Reset Level setting. In Rapid mode, Used I2t decreases exponentially with a fixed two-second time constant when current is not detected. A reset input is required to reset a trip. Cooling Factor ...................... 0.10 to 10.00 x Thermal Time Constant Time Constant ...................... 1.00 to 60.00 minutes I2t Pickup .............................. 0.10 to 1.25 pu of CTPrimary Rating (Ip) Hot Factor............................. 0.10 to 1.00 I2t Alarm ............................... 0.50 to 1.00 pu I2t Trip .................................. 1.00 pu Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... RMS Set-Point Groups .................. Group 1 and Group 2 I2t Reset Level ...................... 0.10 to 0.90 pu (Applies to both groups) 5.2.2 EMERGENCY THERMAL RESET Menu: Messages | Emerg I2t Reset Reset I2t Memory Emergency Thermal Reset (ETR) sets Used I2t to 0% and disables PTC and RTD temperature trips. Password entry is required. Disabled-temperature protection is indicated by t Disabled by ETR in the System State display. If PTC or RTD temperature protection is not enabled, t Disabled by ETR will not be displayed. RTD or PTC trips are reset when ETR is performed regardless of measured temperatures. Temperature protection must be re-enabled in the Messages Emerg I2t Reset Reenable Temp menu, or by cycling supply voltage. Temperature alarms and sensor verification remain enabled during ETR. CAUTION: Temperature protection is not automatically re-enabled after an Emergency Thermal Reset. 5.3 INVERSE-TIME OVERCURRENT Menu: Setup | Protection | Phase Inverse The FPS supports the inverse-time curves listed in Table 5.1. TABLE 5.1 CURVE TYPES CURVE TYPE IEC Normal Inverse, Curve Type A IEC Very Inverse, Curve Type B IEC Extreme Inverse, Curve Type C IEC Short Inverse, Curve Type A IEC Long Inverse, Curve Type B IEEE Moderate Inverse Curves IEEE Very Inverse Curves IEEE Extreme Inverse Curves FIGURE 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 NOTE: The FPS time-multiplier setting of 1.0 corresponds to the IAC/CO “time-dial” setting of 15. The Curve menu is used to select one of the curve shapes listed in Table 5.1. Pickup is in per unit of phase-CT rating and specifies the location of the curve’s vertical asymptote (IM = IDFT/Ipickup = 1). Time Multiplier selects the specific curve within the curve type. The FPS uses the same time-multiplier range of 0.05 to 1.0 for both IEC and IEEE curves. For each curve, treset defines the time to reset after a trip has occurred (IM = 0) The Metering Inverse Status menu indicates whether current is above or below Pickup. Protective Functions Page 5-3 Rev. 1-C-031615 FPS Feeder Protection System Curve .................................... See Table 5.1 Pickup ................................... 0.10 to 10.00 x CT-Primary Rating (Ip) Pickup Curve Threshold ....... 1.1 x Pickup setting Reset Curve Threshold ......... 0.9 x Pickup setting Time Multiplier .................... 0.05 to 1.00 Protection ............................. Enable/Disable Trip1, 2, 3 Measurement Method .......... DFT Set-Point Groups .................. Group 1 and Group 2 I2t OVERLOAD 20000 10000 7000 5000 IM > 1: t = 60 x ? x ln(IM2/(IM2-1)) 3000 2000 TIME IN SECONDS (t) 1000 700 500 300 200 100 70 50 30 20 ?(min) 10 7 5 60 40 30 3 20 2 10 1 0.7 0.5 5 0.3 2 0.2 1 0.1 1 2 3 4 5 6 7 8 9 10 CURRENT IN MULTIPLES OF PICKUP SETTING (I M) 20 FIGURE 5.1 Class-20 Overload Curve. Protective Functions Page 5-4 Rev. 1-C-031615 FPS Feeder Protection System IEC NORMAL INVERSE 100 70 50 IM > 1.1: t = TM x 0.14/(IM0.02 - 1) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 0.14/(1 - IM0.02) 40 30 20 TIME IN SECONDS (t) 10 7 Time Multiplier (TM) 5 4 3 1 2 0.7 0.5 1 0.7 0.3 0.5 0.2 0.4 0.3 0.1 0.2 0.05 0.1 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.2 IEC Normal Inverse, Curve Type A. Protective Functions Page 5-5 Rev. 1-C-031615 FPS Feeder Protection System IEC VERY INVERSE 200 100 70 IM > 1.1: t = TM x 13.5/(IM - 1) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 13.5/(1 - IM) 50 40 30 20 TIME IN SECONDS (t) 10 7 5 4 3 2 Time Multiplier (TM) 1 0.7 1 0.5 0.4 0.7 0.5 0.3 0.3 0.2 0.2 0.1 0.1 0.07 0.05 0.04 0.05 0.03 0.02 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.3 IEC Very Inverse, Curve Type B. Protective Functions Page 5-6 Rev. 1-C-031615 FPS Feeder Protection System IEC EXTREME INVERSE 500 300 200 IM > 1.1: t = TM x 80/(IM2 - 1) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 80/(1 - IM2) 100 70 50 30 TIME IN SECONDS (t) 20 10 7 5 3 2 1 0.7 Time Multiplier (TM) 0.5 0.3 0.2 1 0.7 0.1 0.5 0.07 0.3 0.05 0.2 0.03 0.02 0.1 0.05 0.01 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.4 IEC Extreme Inverse, Curve Type C. Protective Functions Page 5-7 Rev. 1-C-031615 FPS Feeder Protection System IEC SHORT INVERSE 20 10 IM > 1.1: t = TM x 0.05/(IM0.04 - 1) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 0.05/(1 - IM0.04) 7 5 4 3 TIME IN SECONDS (t) 2 1 Time Multiplier (TM) 0.7 0.5 0.4 1.0 0.3 0.7 0.2 0.5 0.3 0.1 0.2 0.07 0.05 0.04 0.1 0.03 0.02 0.05 0.01 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.5 IEC Short Inverse, Curve Type A. Protective Functions Page 5-8 Rev. 1-C-031615 FPS Feeder Protection System IEC LONG INVERSE 2000 1000 700 IM > 1.1: t = TM x 120/(IM - 1) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 120/(1 - IM) 500 400 300 200 TIME IN SECONDS (t) 100 70 50 40 30 20 Time Multiplier (TM) 10 7 1.0 5 4 0.7 3 0.5 2 0.3 0.2 1 0.7 0.1 0.5 0.4 0.05 0.3 0.2 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.6 IEC Long Inverse, Curve Type B. Protective Functions Page 5-9 Rev. 1-C-031615 FPS Feeder Protection System IEEE MODERATE INVERSE 100 70 50 IM > 1.1: t = TM x 3 x (0.0515/(IM0.02 - 1) + 0.114) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 3 x 4.85/(1 - IM2) 40 30 20 TIME IN SECONDS (t) 10 7 4 Time Multiplier (TM) 3 1.0 2 0.7 5 0.5 1 0.3 0.7 0.2 0.5 0.4 0.3 0.1 0.2 0.05 0.1 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.7 IEEE Moderate Inverse Curves. Protective Functions Page 5-10 Rev. 1-C-031615 FPS Feeder Protection System IEEE VERY INVERSE 500 400 300 200 IM > 1.1: t = TM x 3 x (19.61/(IM2 - 1) + 0.491) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 3 x 21.6/(1 - IM2) 100 70 50 40 TIME IN SECONDS (t) 30 20 10 7 5 4 Time Multiplier (TM) 3 2 1.0 0.7 1 0.5 0.7 0.5 0.4 0.3 0.3 0.2 0.2 0.1 0.1 0.05 0.07 0.05 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.8 IEEE Very Inverse Curves. Protective Functions Page 5-11 Rev. 1-C-031615 FPS Feeder Protection System IEEE EXTREMELY INVERSE 500 300 200 IM > 1.1: t = TM x 3 x (28.2/(IM2 - 1) + 0.1217) IM > 20: t = tIM=20 IM < 0.9: treset = TM x 3 x 29.1/(1 - IM2) 100 70 50 30 TIME IN SECONDS (t) 20 10 7 5 3 2 Time Multiplier (TM) 1 0.7 1.0 0.5 0.7 0.3 0.5 0.2 0.3 0.2 0.1 0.07 0.1 0.05 0.03 0.05 0.02 1 2 3 4 5 6 7 8 9 10 20 CURRENT IN MULTIPLES OF PICKUP SETTING (IM) FIGURE 5.9 IEEE Extremely Inverse Curves. Protective Functions FPS Feeder Protection System 5.4 DEFINITE-TIME OVERCURRENT Menu: Setup | Protection | Ph Def Time The definite-time overcurrent function has both trip and alarm settings. With the DFT measurement method it may be possible to set the overcurrent protection closer to the desired value as compared to an RMS measurement method. The asymmetrical-current multipliers for RMS and DFT measuring methods are shown in Fig. 5.10. Typical X/R values are 6.6 for a low-voltage system, 15 for a medium-voltage system, and can be as high as 25 for a high-voltage system. The DFT filters the dc component so that the overcurrent setting can be set closer to the symmetrical fault value. ASYMMETRICAL MULTIPLYING FACTOR 1.8 1.7 RMS 1.6 1.5 1.4 1.3 1.2 DFT 1.1 Page 5-12 Rev. 1-C-031615 Trip Level............................. 0.10 to 15.00 x CT-Primary Rating (Ip) Trip Delay (D)...................... 0.00 to 10.00 s (see Table 5.2) Alarm Level ......................... 0.10 to 15.00 x Ip Alarm Delay (D) .................. 0.00 to 10.00 s (see Table 5.2) Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... DFT Set-Point Groups .................. Group 1 and Group 2 5.5 INVERSE-TIME 3I0 EARTH FAULT Menu: Setup Protection 3I0 Inverse This protection function is based on the zero-sequence current calculated from the three phase currents. The Curve menu is used to select one of the curve shapes listed in Table 5.1. Pickup is in per unit of phase CT rating and specifies the location of the curve’s vertical asymptote (IM = IDFT/Ipickup = 1). Time Multiplier selects the specific curve within the curve type. The FPS uses the same time multiplier range of 0.05 to 1.0 for both IEC and IEEE curves. The Metering Inverse Status menu indicates whether current is above or below Pickup. Total clearing time is the sum of minimum fault duration (FD, Table 5.2), delay time (D), output relay operating time (for D < 45 ms), and interrupting device operating time. Curve .................................... Table 5.1 Pickup .................................. 0.10 to 10.00 x CT-Primary Rating (Ip) Pickup Curve Threshold....... 1.1 x Pickup setting Reset Curve Threshold ......... 0.9 x Pickup setting Time Multiplier .................... 0.05 to 1.00 Protection ............................. Enable/Disable Trip1, 2, 3 Measurement Method .......... DFT – derived 3I0 Set-Point Groups .................. Group 1 and Group 2 TABLE 5.2 FAULT DURATION REQUIRED FOR TRIP(1)(2) FAULT LEVEL FAULT DURATION (FD) NOTE: For IEEE curves, a multiplier of 1 corresponds to a IAC/CO “time-dial” setting of 15. 1.0 0 2 4 6 8 10 12 14 16 18 20 X/R FIGURE 5.10 Asymmetrical-Current Multipliers. (Multiples of trIpLevel Setting) (1) (2) (3) 2 5 10 (ms) D 30 ms 10 5 5 (3) D > 30 ms (3) D - 20 D - 25 D - 28 For overcurrent less than 15 x CT-Primary Rating. For earth faults less than 1 x EF-CT-Primary Rating. Fixed frequency, 60 Hz. Minimum relay operating time: 25 to 45 ms. D is the trip-time setting. 5.6 DEFINITE-TIME 3I0 EARTH FAULT Menu: Setup | Protection | 3I0 Def Time This protection is based on the zero-sequence current calculated from the phase currents. Trip Level............................. 0.10 to 15.00 x CT-Primary Rating (Ip) Trip Delay (D)...................... 0.00 to 10.00 s (see Table 5.2) Alarm Level ......................... 0.10 to 15.00 x Ip Alarm Delay (D) .................. 0.00 to 10.00 s (see Table 5.2) Protection ............................ Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... DFTderived 3I0 Set-Point Groups .................. Group 1 and Group 2 Protective Functions FPS Feeder Protection System 5.7 DEFINITE-TIME EARTH FAULT Menu: Setup | Protection | Ict Def Time This protection function uses the earth-fault-CT input. The protection setting range is equal to the earth-faultCT-primary rating (Ie). Trip Level ............................. 0.01 to 1.00 x Earth-Fault CT primary rating (Ie) Trip Delay (D) ...................... 0.00 to 100.00 s (see Table 5.2) Alarm Level ......................... 0.01 to 1.00 x Ie Alarm Delay (D)................... 0.00 to 100.00 s (see Table 5.2) Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method ........... DFT c/w saturation compensation Set-Point Groups .................. Group 1 and Group 2 Page 5-13 Rev. 1-C-031615 5.9 PHASE LOSSCURRENT Menu: Setup | Protection | Phase Loss (I) Phase loss is a severe form of unbalance and can be used to detect open-circuit faults. When phase loss occurs on a three-phase load, negative-sequence current (I2) is equal to positive-sequence current (I1). The phase-loss algorithm considers I2/I1 from 0.90 to 1.00 to be a phase loss. Set the phase-loss trip delay shorter than the unbalance trip delay to avoid an unbalance trip in the event of a phase loss. The phase-loss threshold is fixed at 10% of the CT-primary rating (Ip). Trip Delay ............................ 1.00 to 100.00 s Alarm Delay ......................... 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... DFT 5.8 CURRENT UNBALANCE Menu: Setup | Protection | Unbalance (I) Menu: Setup | System Config | I2/I1 Threshold Positive-sequence current (I1) and negative-sequence current (I2) are used to determine current unbalance (I2/I1). The unbalance display range is 0.00 to 1.00 where 1.00 is 100% unbalance—a single-phase condition. Single-phase loads generate unbalance that may cause false trips when feeder currents are low. The I2/I1 Threshold sets the current level where unbalance protection becomes active. The threshold is based on the maximum of the threephase currents. Set this value above the single-phase load value to avoid false trips. Negative unbalance is indicated when current inputs are connected B-A-C (negativesequence current is greater than positive-sequence current). Severe unbalance may also be indicated if phase-CT polarity is incorrect. 5.10 PHASE REVERSECURRENT Menu: Setup | Protection | Phase Rev (I) If the current phase sequence is B-A-C, the magnitude of negative-sequence current will be larger than the magnitude of positive-sequence current. To maintain magnitude consistency for set points, the I2/I1 ratio is inverted for the protection algorithm when phase sequence is B-A-C. A negative unbalance is indicated in the meter display for B-A-C sequence. The phase-reverse threshold is fixed at 10% of the CT-primary rating (Ip). Trip Level ............................. 0.05 to 1.00 Trip Delay ............................ 1.00 to 100.00 s Alarm Level ......................... 0.05 to 1.00 Alarm Delay ......................... 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Threshold.............................. 0.10 to 0.50 x Ip Measurement Method ........... DFT 5.11 OVERVOLTAGE OPI Menu: Setup | Protection | Overvoltage A trip or alarm occurs if the maximum line-to-line voltage exceeds the set point. Trip Delay ............................ 1.00 to 100.00 s Alarm Delay ......................... 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm 1, 2, 3 Measurement Method .......... DFT Trip Level............................. 1.00 to 1.40 x System Voltage Rating (Vp) Trip Delay ............................ 1.00 to 500.00 s Alarm Level ......................... 1.00 to 1.40 x Vp Alarm Delay ......................... 1.00 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... DFT Protective Functions FPS Feeder Protection System 5.12 VOLTAGE UNBALANCE OPI Menu: Setup | Protection | Unbalance (V) Positive-sequence voltage (V1) and negative-sequence voltage (V2) are used to determine voltage unbalance (V2/V1). The unbalance display range is 0.00 to 1.00 where 1.00 is 100% unbalance—a single-phase condition. A negative unbalance will be indicated if voltage inputs are connected B-A-C. Trip Level ............................. 0.05 to 1.00 Trip Delay ............................ 1.00 to 100.00 s Alarm Level ......................... 0.05 to 1.00 Alarm Delay ......................... 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method ........... DFT 5.13 PHASE LOSS—VOLTAGE OPI Menu: Setup | Protection | Phase Loss (V) Phase loss is a severe form of unbalance. When phase loss occurs, negative-sequence voltage (V2) is equal to positive-sequence voltage (V1) and voltage unbalance is 100% or 1.00 pu. The phase-loss algorithm considers V2/V1 from 0.90 to 1.00 to be a phase loss. Set the phaseloss trip delay lower than the unbalance trip delay to avoid an unbalance trip in the event of a phase loss. Trip Delay ............................ 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Measurement Method ........... DFT 5.14 PHASE REVERSE—VOLTAGE OPI Menu: Setup | Protection | Phase Rev (V) If the voltage phase sequence is B-A-C, the magnitude of the negative-sequence voltage will be larger than the magnitude of the positive-sequence voltage. Trip and Alarm Delay (1)....... 1.00 to 100.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method ........... DFT (1) Single set point applies to Trip and Alarm. 5.15 UNDERVOLTAGE OPI Menu: Setup | Protection | Undervoltage A trip or alarm occurs if the minimum line-to-line voltage is less than the set point. Trip Level ............................. 0.50 to 1.00 x System Voltage Rating (Vp) Trip Delay ............................ 1.00 to 500.00 s Page 5-14 Rev. 1-C-031615 Alarm Level ......................... 0.50 to 1.00 x Vp Alarm Delay ......................... 1.00 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Measurement Method .......... DFT 5.16 REVERSEPOWER OPI Menu: Setup | Protection | Reversepower Apparent power (S) is defined as S = P +jQ. A trip or alarm is initiated when the real reverse power (P) magnitude (negative power) is higher than the set point for the programmed delay. See Section 7.2. The Reversepower setting is in per unit of rated power where 1.00 pu is defined as the System Voltage x PH-CT Primary x √3. The magnitude of the negative power is used and protection is only active when negative power is detected. Trip Level............................. 0.10 to 1.00 Trip Delay ............................ 0.50 to 500.00 s Alarm Level ......................... 0.10 to 1.00 Alarm Delay ......................... 0.50 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.17 POWER FACTOR—LAG OPI Menu: Setup | Protection | PF Lag OPI Menu: Setup | System Config | I2/I1 Threshold A trip or alarm occurs if the absolute value of lagging power factor is less than the set point. System conditions have “P positive”, “S positive” (Q1) or “P negative”, “S negative” with lagging (-) power factor (Q3). The I2/I1 Threshold sets the point where power-factor protection becomes active. Trip Level............................. 0.50 to 1.00 Trip Delay ............................ 1.00 to 500.00 s Alarm Level ......................... 0.50 to 1.00 Alarm Delay ......................... 1.00 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.18 POWER FACTOR—LEAD OPI Menu: Setup | Protection | PF Lead OPI Menu: Setup | System Config | I2/I1 Threshold A trip or alarm occurs if the absolute value of power factor is less than the set point. System conditions have “P positive”, “S negative” (Q4) or “P negative”, “S positive” with leading (+) power factor (Q2). The I2/I1 Threshold sets the point where power-factor protection becomes active. Trip Level............................. 0.50 to 1.00 Trip Delay ............................ 1.00 to 500.00 s Alarm Level ......................... 0.50 to 1.00 Alarm Delay ......................... 1.00 to 500.00 s Protective Functions FPS Feeder Protection System Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.19 UNDERFREQUENCY OPI Menu: Setup | Protection | Underfrequency A trip or alarm occurs when the frequency of the input voltage (VA) is below the set point. Underfrequency protection is inhibited when the input voltage is less than 50% of rated input (Vp). Trip Level ............................. 30.00 to 80.00 Hz Trip Delay ............................ 1.00 to 500.00 s Alarm Level ......................... 30.00 to 80.00 Hz Alarm Delay ......................... 1.00 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.20 OVERFREQUENCY OPI Menu: Setup | Protection | Overfrequency A trip or alarm occurs when the frequency of the input voltage (VA) is above the set point. Overfrequency protection is inhibited when the input voltage is less than 50% of rated (Vp). Trip Level ............................. 30.00 to 80.00 Hz Trip Delay ............................ 1.00 to 500.00 s Alarm Level ......................... 30.00 to 80.00 Hz Alarm Delay ......................... 1.00 to 500.00 s Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.21 PTC TEMPERATURE Menu: Setup | Hardware | Temp Sensor Type Menu: Setup | Protection | PTC Local Temp Configure the local-temperature-sensor input for a positive-temperature-coefficient (PTC) thermistor sensor using the Setup | Hardware | Temp Sensor Type menu. The total resistance of series-connected PTC thermistors must be less than 1,500 at 20°C. A trip or alarm will occur when series resistance exceeds 2,800 . During Emergency Thermal Reset, a PTC trip is reset and PTC-temperature protection is disabled. See Section 5.2.2. Page 5-15 Rev. 1-C-031615 During Emergency Thermal Reset, an RTD trip is reset and RTD-temperature protection is disabled. See Section 5.2.2. RTD failure detection is provided. The actions for an RTD failure are selectable as Trip1, 2, or 3 and as Alarm1, 2, or 3. The selections apply to all RTD’s. Name .................................... 18 Character, Alphanumeric Type ..................................... Disable, Pt100, Ni100, Ni120, Cu10 Function ............................... Stator, Bearing, Load, Ambient Trip and Alarm Range.......... 40.00 to 200.00°C Display Range ...................... -40.00 to 200.00°C Error Codes .......................... -100 = No Sensor -90 = Open Sensor -80 = Shorted Sensor -70 = No Data/Module Error (Codes accessed via network communications) 5.23 RTD UNDERTEMPERATURE OPI Menu: Setup | Protection | RTD Undertemperature When an RTD module is connected, the FPS provides RTD Undertemperature protection for a select range of temperatures between +20 and -20°C. Trip and alarm settings are provided. When a temperature drops below the setting, a trip or alarm is indicated. For alarm settings, a 5°C hysteresis is used (when an alarm occurs, it remains active until the temperature is 5°C above the setting). The alarm feature can be used to implement a “bang-bang” temperature controller. Undertemperature protection is only provided for RTD’s that are assigned to Group A. Trips can be assigned to Trip1, 2, and 3 and alarms can be assigned to Alarm1, 2, and 3. Trip Level............................. 20, 15, 10, 5, 0, -5, -10, -15, -20°C Alarm Level ......................... 20, 15, 10, 5, 0, -5, -10, -15, -20°C Protection ............................. Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 Protection ......................... Enable/Disable Trip1, 2, 3 Enable/Disable Alarm1, 2, 3 5.22 RTD TEMPERATURE OPI Menu: Setup | Protection | RTD Temperature The FPS supports a single MPS-RTD module. The RTD module can monitor up to eight RTD’s Enable the RTD module in the Setup | Hardware | RTD Module menu. RTD type, function, and trip and alarm set points are programmable for each RTD. When an RTD type is selected, both Trip1 and Alarm1 functions are enabled. A trip or alarm occurs when an RTD indicates a temperature above the set point. Protective Functions FPS Feeder Protection System Page 5-16 Rev. 1-C-031615 5.24 ANALOG INPUT OPI Menu: Setup | Analog Input | 4–20 Input Type The analog input function is selectable as Metering Only, or Protection. In Metering Only, the 4-20 mA protection is disabled. In Protection mode, 4-20 mA set points are enabled. The protection input has high-level and low-level trip and alarm set points. A high-level trip or alarm occurs when the 4-20-mA input exceeds the high-level trip or alarm set point, and a low-level trip or alarm occurs when the 4-20-mA input is lower than the low-level trip or alarm set point. High Level Trip .................... 0.10 to 20.00 mA Low Level Trip..................... 0.10 to 20.00 mA Trip Delay ............................ 0.01 to 100.00 s High Level Alarm................. 0.10 to 20.00 mA Low Level Alarm ................. 0.10 to 20.00 mA Alarm Delay ......................... 0.01 to 100.00 s Protective Functions Page 6-1 Rev. 1-C-031615 FPS Feeder Protection System 6. CONTROL METHOD OPI Menu: Setup | Breaker Control 6.1 GENERAL From the OPI Control Type menu, select a control type or select Protection Only. When Protection Only is selected, all control functions except OPEN are disabled and all OPI control-select LED’s will be OFF. Any OPEN signal will initiate a Trip1 when the FPS is in Protection Only. CAUTION: When Protection Only is selected, OPEN will not function if Trip1 is not assigned to a relay output. NOTE: When control functions are used, protective functions will open operate the CB Open output to open the breaker or contactor when a trip occurs. Reset is required. Table 6.1 indicates the available close sources. TABLE 6.1 CLOSE-SOURCE SUMMARY (1) CONTROL (7) SELECTION REMOTE (2) CLOSE SOURCE 3-Wire Close 2-Wire Close (4) CLOSE Key Close Command DIGITAL INPUTS (3) OPI (3) NETWORK The FPS can operate in one of two control modes, REMOTE or LOCAL. The control source is selected using network communication, or a digital input. In each of the control selections, the Close Source can be selected as shown in Table 6.1. When a control type is selected, control can be performed with the digital inputs, OPI, or network communications. See Section 4.3.3 for details on selecting breaker-control sources. The digital inputs allow concurrent operation of two control methods; three-wire open/close and two-wire open/close. Three-wire control requires two digital inputs, one programmed for 3-Wire Close (N.O. momentary switch) and one programmed for Permissive (N.C. momentary switch) as shown in Fig. 6.1. Two-wire control uses one input, programmed as 2-Wire Close, for open/close control and can be used where a single contact provides open/close operation. See Fig. 6.2. If close was activated by a two-wire input, any other OPEN will initiate a latching Trip1 as well as operating the CB Open output. In all other cases, OPEN does not cause a trip. N (3) LOCAL (5)(6) (1) (2) (3) (4) (5) (6) (7) All OPEN sources are always enabled. Factory default has all sources enabled and REMOTE selected. Can be enabled or disabled using the Setup | Control Method | Remote Group menu. OPEN causes a latching trip. LOCAL is selected by a network command or by a digital input programmed for Local Select. Each Local Select source must de-select local control for the FPS to return to the previous control setting. Interlocks are bypassed. Can be enabled or disabled using the Setup Control Method Local Group menu. COM 43 + IN1 44 - 42 OPEN IN2 45 COM 43 IN1 44 IN2 45 CLOSE OPEN AC INPUT 41 24 VDC CLOSE L 3-Wire Close 2-Wire Close (4) CLOSE Key DIGITAL INPUTS (3) OPI (7) DC INPUT FIGURE 6.1 Typical Three-Wire Control. Control Functions Page 6-2 Rev. 1-C-031615 FPS Feeder Protection System N COM 43 + 41 - 42 COM 43 24 VDC L CLOSE IN1 44 CLOSE AC INPUT 1 44 IN1 DC INPUT FIGURE 6.2 Typical Two-Wire Control. 6.2 OPEN/CLOSE CONTROL OPI Menu: Setup | Device Control OPI Menu: Setup | Relay Outputs Three selections in the Setup | Device Control | Control Type menu define how the assigned output relays operate. The selections are None, Contactor, and 2-Coil Device. When set to None, control functions are disabled. When set to Contactor or 2-Coil Device, control functions are enabled. Trips can be selected to cause the interrupting device to open or the control function can be set to operate independently. Use the Setup | Control Method | Trip Sources menu to select the combinations of Trip1, Trip2, or Trip3 that cause the device to open when a trip occurs. Default is Trip1, Trip2, or Trip3. NOTE: When two-wire close control is used, Trip Sources must include Trip1 so that when an OPEN command is received while the two-wire input is active, a reclose is prevented. Device will reclose after RESET is performed. When a control type other than None is selected, the yellow OPI CLOSE and OPEN LED’s provide indication of the state of the control function. When the breaker or contactor is closed, the CLOSE LED will be on, when the contactor or breaker is open, the OPEN LED will be on. During transitions from open to close, both LED’s are on. Depending on the control state, loss of permissive inputs or interlocks may not generate a trip or alarm condition but may prevent a close operation. The Messages | Status Messages menu will display a digitalinput identifier and related message indicating what is preventing the close operation. Select a control type of None for applications in which a manually operated, electrically tripped device such as a shunt-trip or under-voltage breaker is used. No breaker or contactor open/close control is used and the shunt or under-voltage coil must be connected to an output relay assigned to Trip1, Trip2, or Trip3. The output relay assignments associated with breaker or contactor control (CB Open, CB Close, Contactor) are disabled when the control type is set to None. The REMOTE and LOCAL LED’s are off with this selection. For shunt-trip breakers, use a normally open output contact and set the relay mode to Non-Fail-Safe. For undervoltage breakers, use a normally open output contact and set the relay mode to Fail-Safe. NOTE: The OPEN key on the OPI is always enabled. When the control type is set to None a “Trip1” is generated when pressed. The Contactor control type selection is for applications where an electrically held device such as a contactor is used. An output relay must be assigned to Contactor. In contactor-control mode, the CLOSE and OPEN functions are operational. Control sources include the OPI, digital inputs, and network communications. When there are no trips and CLOSE is issued, the relay assigned to Contactor will energize and stay energized until an OPEN command is issued or a trip occurs. An OPEN command operates the output contacts but does not generate a trip, except when two-wire digital-input control is used. In this case, an OPEN command will also issue a “Trip1”, requiring a reset. Use the 2-Coil Device control type selection to control bi-stable devices such as a two-coil breaker. Two output relays are used to control the device’s close and open/trip coils. Assign two FPS output relays as CB Close and CB Open in the Setup | Relay Outputs menu. When a breaker with a close coil and undervoltagerelease coil is used, use the normally-closed contact of the output relay that is assigned to CB Open. In this configuration the contact opens momentarily to release the breaker on an open request. Figs. 6.3 and 6.4 show two examples of breaker control. In 2-coil-device mode, the CLOSE and OPEN functions are operational. Control sources include the OPI, digital inputs, and network communications. When there are no trips and CLOSE is issued, the relay assigned to CB Close will energize for the maximum time duration Control Functions Page 6-3 Rev. 1-C-031615 FPS Feeder Protection System defined by the Close Pulse Time. When OPEN is issued, the relay assigned to CB Open will energize for the time duration defined by the Open Pulse Time. The full Open Pulse Time is always used. If status is not valid after the Open Pulse Time has expired, the FPS will attempt an open retry. The retry count is selected between zero (no retries) and five retries. A time delay between successive retries is used and this delay is also defined by the Open Pulse Time. If the open status is not valid on power up, retries are attempted based on the selected settings. NOTE: For digital inputs set to 2-Wire Close, an OPEN command generates a Trip1 and the FPS will indicate “CB OPEN Press Trip”. Trip Sources must be set to enable Trip1 or the breaker will close as soon as OPEN is released. 6.2.1 CONTACT STATUS MONITOR For the control type selection of Contactor and 2-Coil Device, the device open/close status can be monitored by a digital input connected to an auxiliary contact. Status monitoring is enabled when a digital input is assigned as 52a Close Status or 52b Open Status. When 52a Close Status is selected, the digital input should have voltage applied (logic 1) when the device is closed and no voltage (logic 0) when the device is open. When 52b Open Status is selected, the digital input should have voltage applied (logic 1) when the device is open and no voltage (logic 0) when the device is closed. During device operation, status must be valid within the time specified by the Close Pulse Time for device close operation and the Open Pulse Time device open operation. The FPS will issue a Trip1 and indicate a CB 52 Contact Trip if the status contact does not indicate a valid status within the open or close pulse time. When in the open or closed state, contact status is checked every 50 ms and a CB 52 Contact Trip will occur if the input status is incorrect. If ac control voltage is used for the digital input, it is recommended to program one of the inputs as Control Power. See Section 4.2.9. RELAY 1 5 6 CLOSE COIL RELAY 2 7 8 OPEN COIL FIGURE 6.3 Breaker with Close and Open Coils. RELAY 1 5 6 CLOSE COIL RELAY 3 10 11 UV COIL FIGURE 6.4 Breaker with Close and UV Coils. Control Functions FPS Feeder Protection System Page 6-4 Rev. 1-C-031615 This page intentionally left blank. Control Functions Page 7-1 Rev. 1-C-031615 FPS Feeder Protection System 7. THEORY OF OPERATION 7.1 SIGNAL-PROCESSING ALGORITHMS The FPS sampling rate is sixteen samples per cycle of the fundamental frequency. A Discrete-FourierTransform (DFT) algorithm is used to obtain the magnitude and phase angles of the fundamental-frequency components of the current and voltage waveforms. These values provide true positive- and negative-sequence components. True RMS values of line currents are calculated for use by the thermal-model algorithm. RMS values include up to the 8th harmonic. All calculated values are updated at the sampling frequency to achieve a fast response to fault conditions. RMS values of the fundamental components of current and voltage are displayed. The FPS uses the input voltage VA for frequency measurement. The input voltage must be above 30 Vac and a sixteen-cycle interval is used to determine frequency. Frequency protection is inhibited when system voltage is less than 50% of the System Voltage setting. 7.2 POWER ALGORITHM Apparent power (S) is calculated by: S P jQ Real power (P) is determined from the in-phase components of I and V, and reactive power (Q) is determined from the quadrature components of I with respect to V. Power factor is the magnitude of the ratio of P to S. The one-PT connection assumes balanced voltages for power calculations. Power calculations for the other connections are valid for both balanced and unbalanced conditions. In all cases, power calculations use the twowattmeter method and assume three-wire loads. The IEEE convention is used for power displays: +Watts, +Vars, -PF (Lag) Importing Watts, Importing Vars +Watts, -Vars, +PF (Lead) Importing Watts, Exporting Vars -Watts, -Vars, -PF (Lag) Exporting Watts, Exporting Vars -Watts, +Vars, +PF (Lead) Exporting Watts, Importing Vars 7.3 OPERATOR INTERFACE (FPS-OPI) The OPI is a terminal device used to communicate with the FPS-CTU. All set points, operating parameters, and menus are stored in the FPS-CTU. The OPI contains a microprocessor used to communicate with the FPS-CTU, read key presses, and perform display functions. On multiple-OPI systems, all OPI’s display the same information. Key presses on any OPI will be processed by the FPS-CTU. 7.4 RTD MODULE (MPS-RTD) The RTD module contains a microprocessor, A/D converter, and analog multiplexers used to measure up to eight RTD’s. The RTD-measuring circuit is isolated from the I/O Module network. All eight RTD’s are scanned every three seconds. RTD linearization, open/short detection, and lead compensation are performed by the RTD module. RTD temperature is sent to the FPS-CTU where temperature monitoring occurs. 7.5 FIRMWARE DIAGNOSTICS In the event of an internal fault, a diagnostic error code is generated and can be viewed with the OPI. The last error code can be viewed by selecting Setup System Config Maintenance Firmware Version. The diagnostic code is a two or three digit hexadecimal number. 02 to FF: 100: 200: 400: 500: 600: 700: 800: 900: Processor Fault Protection Algorithm Fault Relay-Control Algorithm Fault Menu Display Fault OPI Key Handler Fault Real-Time Clock Fault Communication-Handler Fault RTD Temperature-Handler Fault A/D Communication-Interface Fault The last diagnostic error code is saved in non-volatile memory. The diagnostic code is overwritten by any new codes but can also be manually set to zero. To clear the error code, press RESET while in the Firmware Version menu. A diagnostic error generates a Trip1 and increments the trip counter, however, a trip record is not generated. Theory of Operation FPS Feeder Protection System Page 7-2 Rev. 1-C-031615 This page intentionally left blank Theory of Operation FPS Feeder Protection System 8. COMMUNICATIONS 8.1 PERSONAL-COMPUTER INTERFACE 8.1.1 FIRMWARE UPGRADE The FPS-CTU control program is stored in flash memory. Field updates can be made through the I/O module communications connection. The following are required: A Windows PC, with the SE-Flash program installed a file containing the FPS-CTU control program (.s19 file) an RS-232/RS-485 converter that operates at 57,600 bit/s. Use the Littelfuse Startco SE-485-PP or SE485-DIN. SE-Flash is available at www.littelfuse.com/ relayscontrols. 8.1.2 SE-COMM-RIS SE-Comm-RIS is a Windows-based program used to access FPS functions with a personal computer (PC) via the RS-485 network interface or Modbus TCP. Use SE-Comm-RIS to program an FPS either by changing individual set points or by downloading set-point files. Existing FPS set points can be transferred to the PC. Metered values can be viewed and the FPS can be controlled with the computer. SE-Comm-RIS extends the event-record storage capability of the FPS by allowing the user to transfer data to PC memory at a programmable interval. Protection curve plotting capability is included. SE-Comm-RIS is available at www.littelfuse.com/relayscontrols. 8.2 NETWORK INTERFACE For detailed information see Appendices to this manual and applicable communications manuals. 8.2.1 RS-485 COMMUNICATIONS RS-485 communications support Modbus RTU and Allen-Bradley DF1 half-duplex protocols. All set points and meter values are accessible. Commands are provided to perform trips, resets, and starter control. Modbus RTU function codes supported: Read Holding Registers (Code 3) Read Input Registers (Code 4) Write Single Register (Code 6) Write Multiple Registers (Code 16) Command Instruction (Code 5) Page 8-1 Rev. 1-C-031615 DF1 Commands Supported: Unprotected Read (CMD = 01) Unprotected Write (CMD = 08) Typed Read (CMD = 0F, FNC = 68) Typed Write (CMD = 0F, FNC = 67) Typed Logical Read (CMD = 0F, FNC = A2) Typed Logical Write (CMD = 0F, FNC = AA) 8.2.2 DEVICENET COMMUNICATIONS DeviceNetTM communications support Explicit Messaging and Polled I/O. All set points and meter values are accessible using Explicit Messaging. The Polled I/O connection supports the following ODVA input assemblies: Basic Overload (50) Extended Overload (51) Basic Motor Starter (52) Extended Motor Starter 1 (53) Extended Motor Starter 2 (53) In addition to the ODVA assemblies, a userconfigurable fixed block of 64 bytes is available. The Polled I/O connection supports the following ODVA output assemblies: Basic Overload (2) Basic Motor Starter (3) An Electronic Data Sheet (EDS) file is provided for use with DeviceNet configuration tools such as RSNetWorx and DeltaV. 8.2.3 ETHERNET COMMUNICATIONS The FPS supports Modbus TCP and Ethernet/IP using the Anybus-S module from HMS Fieldbus Systems AB. Data from the FPS consists of a 64-byte assembly representing user-defined register data. A command structure is provided to write set-point and FPS commands. 8.2.4 PROFIBUS DP COMMUNICATIONS The FPS supports Profibus-DP using the Anybus-S module. Data from the FPS consists of a 64-byte assembly representing user-defined register data. A command structure is provided to write set-point and FPS commands. Communications FPS Feeder Protection System Page 8-2 Rev. 1-C-031615 This page intentionally left blank Communications Page 9-1 Rev. 1-C-031615 FPS Feeder Protection System 9. TECHNICAL SPECIFICATIONS 9.1 CONTROL UNIT (FPS-CTU) Supply ...................................... 25 VA, 65 to 265 Vac, 40 to 400 Hz, power factor corrected. 25 W, 80 to 275 Vdc. Power-Up Time ........................ 800 ms at 120 Vac Ride-Through Time .................. 100 ms minimum 24-Vdc Source (1) ...................... 100 mA maximum AC Measurements: Methods .............................. True RMS and DFT, Positive- and negativesequence components of the fundamental Sample Rate ........................ 16 samples/cycle Frequency: Fixed ................................... 50, 60 Hz Phase-Current Inputs: (2) Range .................................. 18 x CT-Primary Rating (Ip) Accuracy: (3) I < Ip .............................. 1% Ip I > Ip .............................. 1% Reading Burden ................................ < 0.01 Unbalance Accuracy ........... 0.01 pu Common-Mode Voltage ..... 120 Vac maximum Thermal Withstand: Continuous .................... 5 x CT Rating 1-Second ....................... 80 x CT Rating Earth-Leakage Input: Range .................................. 1.5 x Earth-Fault-CTPrimary Rating (Ie) Accuracy (3) ......................... 1% Ie Burden ................................ < 0.01 (1- and 5-A inputs), 10 for EFCT Common-Mode Voltage ..... 120 Vac maximum Thermal Withstand: Continuous .................... 5 x CT Rating 1-Second ....................... 80 x CT Rating Phase-Voltage Inputs: (4, 5) Nominal Input ..................... 30 to 600 Vac line-to-line Input Resistance .................. 3.4 M Range .................................. 1.4 x PT-Primary Rating (Vp) Accuracy: (3) V < Vp ........................... 1% Vp V > Vp ........................... 1% Reading Unbalance Accuracy ........... 0.01 pu Frequency Metering: Range .................................. 5 to 100 Hz Uses VA input, Sine wave assumed Accuracy ............................. 0.05 Hz PTC-Thermistor Input: (1) Cold Resistance................... 1500 maximum at 20C Trip Level ........................... 2800 ± 100 Sensor Current .................... 2 mA maximum 4-20 mA Analog Input: Input Burden ....................... 100 Common-Mode Voltage (6) ............................ ± 5 Vdc 4-20 mA Analog Output: (1) Load .................................... 500 maximum Range .................................. 0 to 25 mA Update Time ....................... 500 ms Timing Accuracies: (7) Set Points ............................ -10%, +0% (Minimum 25 to 45 ms) Overload Curve ................... Greater of 2% or +200 ms (Minimum 25 to 45 ms) IEC/IEEE Curves ................ ±5% (Minimum 25 to 45 ms) Starter-Control Stop Time: Digital Input ........................ 30 to 80 ms OPI ...................................... 70 to 200 ms Network .............................. 30 to 80 ms Relay Contacts (Relays 1 and 2): Configuration ...................... N.O. (Form A) CSA/UL Contact Rating ..... 8 A resistive 250 Vac, 5 A resistive 30 Vdc Supplemental Contact Ratings: Make/Carry 0.2 s .............. 30 A Communications Page 9-2 Rev. 1-C-031615 FPS Feeder Protection System Break: dc .................................. 75 W resistive, 35 W inductive (L/R = 0.04) ac ................................... 2,000 VA resistive, 1,500 VA inductive (PF = 0.4) Subject to maximums of 8 A and 250 V (ac or dc). Relay Contacts (Relays 3 and 4): Configuration ...................... N.O. and N.C. (Form C) CSA/UL Contact Rating ....... 8 A resistive 250 Vac, 8 A resistive 30 Vdc Supplemental Contact Ratings: Make/Carry 0.2 s.............. 20 A Break: dc .................................. 50 W resistive, 25 W inductive (L/R = 0.04) ac ................................... 2000 VA resistive, 1,500 VA inductive (PF = 0.4) Subject to maximums of 8 A and 250 V (ac or dc). Solid-State Output (Relay 5): Configuration ...................... N.O. (Form A) Rating ................................. 100 mA, 250 V (ac or dc) On Resistance ..................... 30 maximum Digital Inputs: (1) Range .................................. 12 to 120 V (ac or dc), 5 mA Guaranteed On .................... 12 Vdc at 3 mA, 20 Vac at 3 mA Guaranteed Off ................... 3 Vdc at 2 mA, 2.5 Vac at 0.3 mA IRIG-B: Format ................................ Amplitude Modulated IRIG-B122 Amplitude ........................... 1 to 10 Vpp Impedance........................... 10 k Ratio ................................... 3:1 to 6:1 I/O Module Interface (OPI and RTD): Module Supply (1) ............... 24 Vdc, 400 mA maximum Configuration ...................... RS-485, 2-wire multidrop Bus Length.......................... 1.2 km (4,000’) maximum Cable ................................... Belden 3124A or equivalent Standard Network Communications: Configuration ...................... RS-485, 2-wire multidrop Baud Rate............................ 1.2, 2.4, 4.8, 9.6, 19.2 kbit/s Protocols ............................. Modbus RTU and A-B DF1 Isolation .............................. 120 Vac Bus Length .......................... 1.2 km (4,000’) maximum Real-Time Clock and Non-Volatile RAM: Power-Off Retention ........... 7 Years at 20C (68°F) Battery Shelf Life................ > 50 Years at 20C (68°F) Dimensions: Height ...................................121 mm (4.8”) Width ....................................190 mm (7.5”) Depth ....................................127 mm (5.0”) Shipping Weight ....................... 2.0 kg (4.4 lb) PWB Conformal Coating.......... MIL-1-46058 qualified UL QMJU2 recognized Environment: Operating Temperature ....... 40 to 60C (-40 to 140°F) Storage Temperature ........... 55 to 80C (-67 to 160°F) Humidity ............................. 85% Non-Condensing Surge Withstand ....................... ANSI/IEEE C37.90.11989 (Oscillatory and Fast Transient) Certification .............................. CSA, Canada and USA To: CSA C22.2 No. 14 Industrial Control Equipment UL 508 Industrial Control Equipment UL 1053 Ground Fault Sensing and Relaying Equipment Australia N11659 Communications Page 9-3 Rev. 1-C-031615 FPS Feeder Protection System NOTES: (1) The I/O module supply (terminal 56), PTC (terminal 54), AN OUT (terminal 40), and 24-Vdc source (terminal 42) are referenced to the same common. (2) Current threshold is 1.5% CT-Primary Rating. Power readings are not displayed for currents below this threshold. To maintain specified accuracy, phase CT’s should be selected with a primary rating between 100% and 300% of nominal full-load current. (3) Transformer accuracy not included. (4) Voltage unbalance is not displayed for positivesequence voltage levels below 20% of system voltage setting. (5) Direct connection for system voltages up to 600 Vac line-to-line. (6) Common-mode voltage relative to CTU terminal 3. (7) Also see Tables 5.1 and 5.2. 9.2 OPERATOR INTERFACE (FPS-OPI) Supply (1) .................................. 20 to 30 Vdc, 80 mA Display Type ............................ 4 x 20 Alphanumeric Vacuum Fluorescent Dimensions: Height.....................................98 mm (3.9”) Width .....................................192 mm (7.6”) Depth ......................................113 mm (4.5”) Shipping Weight ....................... 0.6 kg (1.3 lb) CSA C22.2 No. 213-M1987 – Non-Incendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations UL 508 Industrial Control Equipment UL 1053 Ground Fault Sensing and Relaying Equipment Australia N11659 NOTES: (1) The I/O module supply (terminal 56), PTC (terminal 54), AN OUT (terminal 40), and 24-Vdc source (terminal 42) are referenced to the same common. 9.3 RTD MODULE (MPS-RTD) Supply (1) ................................... 2 W, 15 to 32 Vdc Configuration ............................ 8 inputs, 3-wire RTD RTD Types ............................... Pt100, Ni100, Ni120, Cu10 Measurement Range ................. -40 to 200°C (-40 to 392°F), with open and short detection Sensor Current .......................... 2 mA Lead Compensation .................. 20 maximum PWB Conformal Coating ......... MIL-1-46058 qualified UL QMJU2 recognized Accuracy: Pt100, Ni100, Ni120 RTD.....1C Cu10 RTD ........................... 3C Environment: Operating Temperature ....... 40 to 60C (-40 to 140°F) Storage Temperature........... 55 to 80C (-67 to 160°F) Humidity ............................. 85% Non-Condensing Interconnection Cable: Type .................................... Belden 3124A or equivalent Maximum Length ................ 1.2 km (4,000’) Supplied length.................... 4 m (13’) Surge Withstand ....................... ANSI/IEEE C37.90.11989 (Oscillatory and Fast Transient) Certification.............................. CSA, Canada and USA Shipping Weight ....................... 0.4 kg (0.9 lb) PWB Conformal Coating.......... MIL-1-46058 qualified UL QMJU2 recognized Dimensions: Height .....................................87 mm (3.4”) Width......................................113 mm (4.4”) Depth ......................................53 mm (2.1”) Hazardous-Location............ Class I Zone 2 Ex nA II T6 Class I, Division 2, Groups A, B, C, D To: CSA C22.2 No. 14 Industrial Control Equipment Technical Specifications FPS Feeder Protection System Page 9-4 Rev. 1-C-031615 Environment: Operating Temperature ....... 40 to 60C (-40 to 140°F) Storage Temperature........... 55 to 80C (-67 to 160°F) Humidity ............................. 85% Non-Condensing Surge Withstand ....................... ANSI/IEEE C37.90.11989 (Oscillatory and Fast Transient) Certification.............................. CSA, Canada and USA UL Recognized Hazardous-Location ........... Class I Zone 2 Ex nA II T6 Class I, Division 2, Groups A, B, C, D To: CSA C22.2 No. 14 Industrial Control Equipment CSA C22.2 No. 213-M1987 – Non-Incendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations UL 508 Industrial Control Equipment CSA E60079-15: 02 Electrical Apparatus for Explosive Gas Atmospheres UL 60079-15 Electrical Apparatus for Explosive Gas Atmospheres NOTES: The I/O module supply (terminal 56), PTC (terminal 54), AN OUT (terminal 40), and 24-Vdc source (terminal 42) are referenced to the same common. (1) 10. WARRANTY The FPS Motor Protection System is warranted to be free from defects in material and workmanship for a period of ten years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco’s option) repair, replace, or refund the original purchase price of an FPS-CTU, FPS-OPI, or MPS-RTD that is determined by Littelfuse Startco to be defective if it is returned to the factory, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse Startco does not warrant products repaired or modified by nonLittelfuse Startco personnel. Warranty Page A-1 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 4 5 6 7 APPENDIX A FPS MENU LEVEL Metering Summary {Display based on menu setting} Current {Ia, Ib, Ic in amperes and per unit} Unbalance (I) {I1, I2, and unbalance (I2/I1) in per unit} Earth Leakage {Measured (Ict) earth leakage in amperes and per unit} Thermal Status {Thermal capacity, time-to-trip, reset times} Voltage {Vab, Vbc, Vca} Unbalance (V) {V1, V2, and unbalance (V2/V1) in per unit} Power {Real, Apparent, Reactive, Power Factor} Energy {kWh, kVAh, kVARh} Frequency {Frequency reading from Vab} RTD Temperature{RTD summary and individual temperatures} Inverse Status {Indicates if current is above the pickup level} I/O Status {Digital input state, relay-output state} System Status {Active set-point group, RTC time} Network Status {Network type and state} Messages Trip and Alarm {Trips and Alarms as per Type T90 per Appendix x} Status Messages {Messages} Event Records {0 to 63 trip records} Statistics {Trip counters and run times} Emerg I2t Reset Reset I2t Memory [Y/N] Setup Protection Overload Group 1 I2t Trip Action I2t Pickup Hot Factor Cooling Factor Time Constant I2t Alarm Level I2t Alarm Action Group 2 <same as group 1> 2 I t Reset Type 1 2 3 4 5 6 [T42] [X] [X] [X] [X] [X] [T43] [T38] 7 Appendix A, FPS Menu Level Page A-2 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 4 5 6 7 2 I t Reset Level Phase Inverse Group 1 Trip Action Curve Pickup Time Multiplier Group 2 <same as group 1> Phase Definite Time Group 1 Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Group 2 <same as group 1> 3Io Inverse Group 1 Trip Action Curve Pickup Time Multiplier Group 2 <same as group 1> 3Io Definite Time Group 1 Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Group 2 <same as group 1> Ict Definite Time Group 1 Trip Action Trip Level 1 2 3 4 5 6 [X[ [T42] [T73] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [T73] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] 7 Appendix A, FPS Menu Level Page A-3 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 4 5 6 7 Trip Delay Alarm Action Alarm Level Alarm Delay Group 2 <same as group 1> Unbalance (I) Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Phase Loss (I) Trip Action Trip Delay Alarm Action Alarm Delay Phase Reverse (I) Trip Action Trip Delay Alarm Action Alarm Delay Unbalance (V) Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Phase Loss (V) Trip Action Trip Delay Alarm Action Alarm Delay Phase Reverse (V) Trip Action Trip Delay Alarm Action Alarm Delay Undervoltage 1 2 3 4 5 6 [X] [T43] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] [T43] [X] [T42] [X] [T43] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] [T43] [X] [T42] [X] [T43] [X] 7 Appendix A, FPS Menu Level FPS Feeder Protection System Menu Level 1 2 3 1 2 4 5 6 Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Overvoltage Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Underfrequency (V) Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Overfrequency (V) Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Power Factor Lag Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Power Factor Lead Trip Action Trip Level Trip Delay Alarm Action Alarm Level Alarm Delay Reversepower 7 [T42] [X] [X] [T43] [X] [X] 3 7 4 5 6 Page A-4 Rev. 1-C-031615 [T42] [X] [X] [T43] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] [X] [T43] [X] [X] [T42] [X] [X] [T43] [X] [X] Appendix A, FPS Menu Level Page A-5 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 4 5 6 7 Trip Action [T42] Trip Level [X] Trip Delay [X] Alarm Action [T43] Alarm Level [X] Alarm Delay [X] PTC Local Temp Trip Action [T42] Alarm Action [T43] RTD Temperature RTD #1 #1 Name #1 Type #1 Function #1 Trip Level #1 Alarm Level RTD #2 #2 Name #2 Type #2 Function #2 Trip Level #2 Alarm Level RTD #3 #3 Name #3 Type #3 Function #3 Trip Level #3 Alarm Level RTD #4 #4 Name #4 Type #4 Function #4 Trip Level #4 Alarm Level RTD #5 #5 Name #5 Type #5 Function #5 Trip Level #5 Alarm Level [S] [T20] [T89] [X] [X] [S] [T20] [T89] [X] [X] [S] [T20] [T89] [X] [X] [S] [T20] [T89] [X] [X] [S] [T20] [T89] [X] [X] RTD #6 1 2 3 4 5 6 7 Appendix A, FPS Menu Level Page A-6 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 1 4 5 6 7 #6 Name #6 Type #6 Function #6 Trip Level #6 Alarm Level RTD #7 #7 Name #7 Type #7 Function #7 Trip Level #7 Alarm Level RTD #8 #8 Name #8 Type #8 Function #8 Trip Level #8 Alarm Level [S] [T20] [T89] [X] [X] Sensor Trip Act Sensor Alarm Act [T42] [T43] Undertemperature Trip Action Trip Level Alarm Action Alarm Level [T42] [T108] [T43] [T108] System Ratings Phase-CT Primary EF-CT Primary System Voltage Input Voltage V Connection Frequency Set-Point Group [X] [X] [X] [X] [T9] [T10] [T81] Device Control Control Type Close Pulse Time Open Pulse Time Open Retry Trip Sources [T103] [X] [X] [T107] [T104] 2 3 4 5 6 [S] [T20] [T89] [X] [X] [S] [T20] [T89] [X] [X] 7 Appendix A, FPS Menu Level FPS Feeder Protection System Menu Level 1 2 3 4 5 6 Remote Group Dig In Control Net Control OPI Control Local Group OPI Control Page A-7 Rev. 1-C-031615 7 [T6] [T6] [T6] [T6] Digital Input Digital Input 1 Input 1 Function [T86] IN1 Close Bypass [T6] IN1 Bypass Delay [X] IN1 Trip Delay [X] <Repeat for digital input 2 to 7> Relay Outputs Relay 1 Relay 1 Function Relay 1 Mode Relay 2 Relay 2 Function Relay 2 Mode Relay 3 Relay 3 Function Relay 3 Mode Relay 4 Relay 4 Function Relay 4 Mode Relay 5 Relay 5 Function Relay 5 Mode RY Pulse Time [T76] [T14] [T76] [T14] [T76] [T14] [T76] [T14] [T76] [T14] [X] Analog Input Input Function [T92] Protection Trip Action [T42] High Level Trip [X] Low Level Trip [X] Trip Delay [X] Alarm Action [T43] High Level Alarm [X] 1 2 3 4 5 6 7 Appendix A, FPS Menu Level FPS Feeder Protection System Menu Level 1 2 3 Page A-8 Rev. 1-C-031615 4 5 6 7 Low Level Alarm [X] Alarm Delay [X] Analog Output Output Parameter [T87] Zero Calibrate [X] FS Calibrate [X] Hardware Display Trip Action [T42] Number of OPI [T40] Intensity N/A Screen Saver [T6] Meter Summary N/A OPI Ctrl Select Remote Select [T6] OPI Select [T6] RTD Module Total Modules [T88] Err Trip Action [T42] Err Alarm Action [T43] Network Comms Network Type [T16] Network ID [X] Network Baud [T17] Net Error Check [T18] Ethernet IP [EA] Ethernet Mask [EA] Default Gateway [EA] Net Trip Action [T42] Net Alarm Action [T43] Net Write Access N/A (From OPI Only) Remote Trip Action [T42] Remote Alarm Action [T43] DeviceNet Produce [T84] DeviceNet Consume [T85] User Registers Register 0 [X] <Repeat for 1 to 31 registers> System Config 1 2 3 4 5 6 7 Appendix A, FPS Menu Level Page A-9 Rev. 1-C-031615 FPS Feeder Protection System Menu Level 1 2 3 4 5 6 7 System Name [S] Password [S] Password Timeout [X] I2/I1 Threshold [X] Clock Settings RTC Date/Time [S] IRIG Offset (h) [X] IRIG Offset (min) [X] UPI LED [T74] Maintenance Clr Event Records Clr Trip Counts Clr Energy Values Load Defaults Unlock Local Restart FPS Firmware Update Firmware Version Serial Number [Y/N] [Y/N] [Y/N] [Y/N] [Y/N] [Y/N] [Y/N] [S] [X] LEGEND : This menu item has a sub menu, press right key view sub menu. : Last menu, press right key to view data. [Y/N]: Yes/No. [X]: Numeric. [S]: String. Specific string format may be required. [E]: Selection is from a list of values. [EA]: Ethernet Address (xxx.xxx.xxx.xxx). [E/D]: Enable/Disable. [Txx]: See Appendix x for data type specified by xx. 1 2 3 4 5 6 7 Appendix A, FPS Menu Level FPS Feeder Protection System Page A-10 Rev. 1-C-031615 This page intentionally left blank Appendix A, FPS Menu Level Page B-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX B FPS SET-UP RECORD Motor:______________________________ FPS S/N: ___________________________ Date: ______________________ Firmware Revision:___________________________ PART I: SYSTEM PARAMETERS PARAMETER AND SETTINGS System Ratings PH-CT Primary (Ip) EF-CT Primary (Ie) System Voltage Input Voltage Input Voltage Connection Frequency Set-Point Group Digital Inputs Input 1: Function Close Bypass Bypass Delay Trip Delay Input 2: Function Close Bypass Bypass Delay Trip Delay Input 3: Function Close Bypass Bypass Delay Trip Delay Input 4: Function Close Bypass Bypass Delay Trip Delay Input 5: Function Close Bypass Bypass Delay Trip Delay Input 6: Function Close Bypass Bypass Delay Trip Delay Input 7: Function Close Bypass Bypass Delay Trip Delay MIN DEFAULT MAX UNIT 1 1 0.12 0.06 100.00 5.00 0.60 0.12 5,000 5,000 75 0.6 A A kV kV None 60 Hz Group2 See Table 4.2 Input Function Definition None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s None Disable 0.5 5.00 100 s 0.01 0.10 100 s PROGRAM SELECTION None 1PT 50 Group1 Group2 2PT 3PT/Direct 60 Enable Disable Enable Disable Enable Disable Enable Disable Enable Disable Enable Disable Enable Disable Appendix B, FPS Set-Up Record Page B-2 Rev. 1-C-031615 FPS Feeder Protection System PARAMETER AND SETTINGS Relay Outputs Relay 1: Function Mode Relay 2: Function Mode Relay 3: Function Mode Relay 4: Function Mode Relay 5: Function Mode RY Pulse Time Analog Input MIN DEFAULT MAX UNIT See Table 4.1 Output Function Definition None Fail-Safe None Fail-Safe None Fail-Safe None Fail-Safe None Fail-Safe 0.05 0.25 10 s Metering Only 4-20 Input Type Protection: High-Level Trip Low-Level Trip Trip Delay High-Level Alarm Low-Level Alarm Alarm Delay Analog Output Output Parameter Zero Calibrate Full-Scale Calibrate OPI Display OPI-Loss Trip Number of OPI’s Intensity Screen Saver Meter Summary RTD Modules Total Modules RTD-Module-Error Trip Action RTD-Module-Error Alarm Action Network Communications Network Type 0.1 0.1 0.01 0.1 0.1 0.01 16.00 7.00 5.00 14.00 9.00 1.00 20 20 100 20 20 100 1 IDR 0 Disable Disable Modbus Non-Fail-Safe Fail-Safe Non-Fail-Safe Fail-Safe Non-Fail-Safe Fail-Safe Non-Fail-Safe Fail-Safe Non-Fail-Safe Metering Only Protection Sync. To ASD Motor Speed See Table 4.3 Analog Output Parameter Definition Trip1 Enable Fail-Safe mA mA s mA mA s Phase Current Factory Calibrated Factory Calibrated 100 PROGRAM SELECTION % Disable Trip2 1 2 25 50 Enable IDR IVP Trip1 Trip3 3 0 Disable Trip2 Disable Alarm2 1 Trip1 Trip3 Alarm1 Alarm3 None AB DF1 Modbus RTU DeviceNet Anybus Modbus TCP 75 100 Disable IVPA Appendix B, FPS Set-Up Record Page B-3 Rev. 1-C-031615 FPS Feeder Protection System PARAMETER AND SETTINGS Network ID MIN 0 Baud Rate DEFAULT 254 SCI 9600 Not Selected 192.168. 000.001 255.255. 255.000 000.000 000.000 Error Checking Ethenet IP Ethernet Mask Default Gateway Network-Error Trip Action Disable Network-Error Alarm Action Disable Net Write Access All Remote Trip Action Disable Remote Alarm Action Disable DeviceNet Producing Assembly 0x36 DeviceNet Consuming Assembly None User Registers User Register 0 User Register 1 User Register 2 User Register 3 User Register 4 User Register 5 User Register 6 User Register 7 User Register 8 User Register 9 User Register 10 User Register 11 User Register 12 User Register 13 User Register 14 User Register 15 User Register 16 User Register 17 User Register 18 MAX 255 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 UNIT PROGRAM SELECTION SCI 1200 SCI 2400 SCI 4800 SCI 9600 SCI 19200 Not Selected CRC DN125 DN250 DN500 Disable Trip2 Disable Alarm2 All Commands Only Disable Trip2 Disable Alarm2 None 0x33 0x35 None 0x03 Trip1 Trip3 Alarm1 Alarm3 Settings Only No Write Access Trip1 Trip3 Alarm1 Alarm3 0x32 0x34 0x64 0x02 BCC 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 1399 Appendix B, FPS Set-Up Record Page B-4 Rev. 1-C-031615 FPS Feeder Protection System PARAMETER AND SETTINGS User Register 19 User Register 20 User Register 21 User Register 22 User Register 23 User Register 24 SYSTEM CONFIG System Name Change Password Password Timeout I2/I1 Threshold MIN 0 0 0 0 0 0 DEFAULT 0 0 0 0 0 0 MAX 1399 1399 1399 1399 1399 1399 UNIT 1 0.05 FPS 1111 10.00 0.50 60 0.50 min. PROGRAM SELECTION PART II: PROTECTION SET POINTS FUNCTION & SET POINT Overload – Group1 MIN I2t Trip Action DEFAULT MAX UNIT Trip1 I2t Alarm Action Alarm1 PROGRAM SELECTION Disable Trip2 Disable Alarm2 Trip1 Trip3 Alarm1 Alarm3 Disable Trip2 Disable Alarm2 Trip1 Trip3 Alarm1 Alarm3 Normal Auto Rapid Disable Trip2 Trip1 Trip3 2 I t Pickup (Ip is Phase-CT-Primary Rating) Hot Factor Cooling Factor Time Constant I2t Alarm level (Per Unit Based on 100% I2t) Overload – Group2 0.10 1.00 1.25 x Ip 0.10 0.10 1.00 0.50 1.00 10.0 1.00 10.00 60.00 min 0.50 0.90 1.00 pu I2t Trip Action Trip1 I2t Alarm Action I2t Pickup (Ip is Phase-CT-Primary Rating) Hot Factor Cooling Factor Time Constant I2t Alarm level (Per Unit Based on 100% I2t) Overload Reset Type Overload Reset Level Phase Inverse – Group1 Alarm1 0.10 1.00 1.25 x Ip 0.10 0.10 1.00 0.50 1.00 10.0 1.00 10.00 60.00 min 0.50 0.90 1.00 pu Normal 0.10 0.30 Trip Action Trip1 Curve Type IEC Normal Curve Pickup (Ip is Phase-CT-Primary Rating) Curve Multiplier 0.90 pu See Table 5.1 0.10 2.00 10.00 0.05 0.20 1.00 x Ip Appendix B, FPS Set-Up Record Page B-5 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT Phase Inverse – Group2 MIN DEFAULT Trip Action Trip1 Curve Type IEC Normal Curve Pickup (Ip is Phase-CT-Primary Rating) Curve Multiplier Phase Definite Time – Group1 10.0 0.05 0.20 1.00 Trip Level (Ip is Phase-CT-Primary Rating) Trip Delay 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Alarm Action Alarm Level (Ip is Phase-CT-Primary Rating) Alarm Delay Earth-Fault 3I0 Inverse – Group1 Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Trip Action Trip1 Curve Type IEC Normal Curve Pickup (Ip is Phase-CT-Primary Rating) Curve Multiplier Earth-Fault 3I0 Inverse – Group2 2.00 10.00 0.05 0.20 1.00 Trip1 Curve Type IEC Normal Curve Pickup (Ip is Phase-CT-Primary Rating) Curve Multiplier Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 See Table 5.1 0.10 Trip Action Trip1 Trip3 x Ip Disable Trip Action PROGRAM SELECTION See Table 5.1 2.00 Alarm Action Alarm Level (Ip is Phase-CT-Primary Rating) Alarm Delay Phase Definite Time – Group2 UNIT Disable Trip2 0.10 Trip Action Trip Level (Ip is Phase-CT-Primary Rating) Trip Delay MAX x Ip Disable Trip2 Trip1 Trip3 See Table 5.1 0.10 2.00 10.00 0.05 0.20 1.00 x Ip Appendix B, FPS Set-Up Record Page B-6 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT Earth-Fault 3I0 Definite Time – Group1 MIN Trip Action Trip Level (Ip is Phase-CT-Primary Rating) Trip Delay 10.00 15.00 x Ip 0.00 0.05 10.00 s Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Alarm Action Alarm Level (Ip is Phase-CT-Primary Rating) Alarm Delay Earth-Fault CT Input Definite Time – Group1 Disable 0.10 10.00 15.00 x Ip 0.00 0.05 10.00 s Trip Action Trip Level (Ie is EF-CT-Primary Rating) Trip Delay Trip1 0.01 0.40 1.00 x Ie 0.00 0.25 100.00 s Alarm Action Alarm Level (Ie is EF-CT-Primary Rating) Alarm Delay Earth-Fault CT Input Definite Time – Group2 Alarm1 0.01 0.20 1.00 x Ie 0.00 1.00 100.00 s Trip Action Trip Level (Ie is EF-CT-Primary Rating) Trip Delay Trip1 0.01 0.40 1.00 x Ie 0.00 0.25 100.00 s Alarm Action Alarm Level (Ie is EF-CT-Primary Rating) Alarm Delay UNIT 0.10 Trip Action Trip Level (Ip is Phase-CT-Primary Rating) Trip Delay MAX Disable Alarm Action Alarm Level (Ip is Phase-CT-Primary Rating) Alarm Delay Earth-Fault 3I0 Definite Time – Group2 DEFAULT Alarm1 0.01 0.20 1.00 x Ie 0.00 1.00 100.00 s PROGRAM SELECTION Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Appendix B, FPS Set-Up Record Page B-7 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT Unbalance (I) MIN Trip Action Trip Level (Per Unit Based on I2/I1) Trip Delay 0.25 1.00 pu 1.00 15.00 100.00 s Alarm1 0.05 0.10 1.00 pu 1.00 10.00 100.00 s Disable 1.00 Alarm Action Alarm Delay Phase Reverse (I) Trip Action Trip Delay Trip Level (Per Unit of Rated Power) Trip Delay 1.00 1.00 1.00 5.00 100.00 2.00 100.00 pu 0.50 5.00 500 s Disable 0.10 0.10 1 pu 0.50 1.00 500 s Trip1 1 1 15.00 100 0.05 1 1 15.00 100 5.00 100 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 pu Disable 1 Alarm1 Alarm3 pu Alarm1 0.05 Disable Alarm2 s 1 0.10 Trip1 Trip3 s 0.10 0.05 Disable Trip2 s 0.10 Trip Action Phase Loss Delay 100.00 Disable Alarm Action Alarm Level (Per Unit Based on V2/V1) Alarm Delay Phase Loss (V) 2.00 PROGRAM SELECTION s Disable Trip Action Trip Level (Per Unit Based on V2/V1) Trip Delay 100.00 Disable Alarm Action Alarm Level (Per Unit of Rated Power) Alarm Delay Unbalance (V) 5.00 Disable Alarm Action Alarm Delay Reversepower Trip Action UNIT 0.05 Trip Action Trip Delay MAX Trip1 Alarm Action Alarm Level (Per Unit Based on I2/I1) Alarm Delay Phase Loss (I) DEFAULT °C Appendix B, FPS Set-Up Record Page B-8 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT Phase Reverse (V) MIN Trip Action 1 1.4 x Vp 1 5.00 500 s Alarm1 1 1.10 1.4 1 5.00 500 Trip Level Trip Delay 0.5 0.70 1 x Vp 1 5.00 500 s Disable 0.5 0.80 1 x Vp 1 5.00 500 s Disable 30 1 Alarm Action Alarm Level Alarm Delay Overfrequency 30 1 48 2 80 500 30 1.0 65 2 80 500 62 2 80 500 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Hz s Hz s Disable 30 1 Trip1 Trip3 Alarm1 Alarm3 Hz s Disable Alarm Action Alarm Level Alarm Delay 80 500 Disable Trip Action Trip Level Trip Delay 45 5 Disable Trip2 Disable Alarm2 x Vp Disable Trip Action PROGRAM SELECTION s 1.20 Alarm Action Alarm Level (Vp is Input Voltage) Alarm Delay Underfrequency 100 1 Trip Action Trip Level (Vp is Input Voltage) Trip Delay 2.00 Trip1 Alarm Action Alarm Level (Vp is Input Voltage) Alarm Delay Undervoltage UNIT Alarm1 Trip Action Trip Level (Vp is Input Voltage) Trip Delay MAX Trip1 Alarm Action Phase Reverse Trip and Alarm Delay Overvoltage DEFAULT Hz s Appendix B, FPS Set-Up Record Page B-9 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT PF Lag MIN Trip Action Trip Level Trip Delay 0.5 1 0.5 1 0.80 5 0.90 2 0.5 1 0.90 2 Disable Alarm Action Disable RTD TEMPERATURE Requires RTD Module(s) RTD M1 #1: Name 500 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Trip1 Trip3 Disable Alarm2 Alarm1 Alarm3 Disable Trip2 Disable Alarm2 Trip1 Trip3 Alarm1 Alarm3 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 s 1 500 s 1 500 s Disable Function Stator 40 40 130.00 110.00 200 200 Load Ambient °C °C RTD Module 1 #2 Type Disable Pt100 Ni100 Stator Bearing Disable Function Stator 40 40 130.00 110.00 200 200 Ni120 Cu10 Load Ambient °C °C RTD Module 1 #3 Type Disable Pt100 Ni100 Stator Bearing Disable Function Trip Alarm Trip1 Trip3 RTD Module 1 #1 Type Trip Alarm RTD M1 #3: Name Disable Trip2 s Disable 0.5 1 PROGRAM SELECTION 1 0.80 5 Trip Action Trip Alarm RTD M1 #2: Name 1 500 Disable Alarm Action Alarm Level Alarm Delay PTC Temperature UNIT Disable Trip Action Trip Level Trip Delay MAX Disable Alarm Action Alarm Level Alarm Delay PF Lead DEFAULT Stator 40 40 130.00 110.00 200 200 Ni120 Cu10 Load Ambient °C °C Appendix B, FPS Set-Up Record Page B-10 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT RTD M1 #4: Name MIN Stator 40 40 200 200 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 Disable Pt100 Ni100 Stator Bearing Ni120 Cu10 Disable Trip2 Disable Alarm2 Trip1 Trip3 Alarm1 Alarm3 Load Ambient °C °C Stator 40 40 130.00 110.00 200 200 Load Ambient °C °C RTD Module 1 #6 Type Disable Function Stator 40 40 130.00 110.00 200 200 Load Ambient °C °C RTD Module 1 #7 Type Disable Function Stator 40 40 130.00 110.00 200 200 Load Ambient °C °C RTD Module 1 #8 Type Disable Function Trip Alarm 130.00 110.00 Disable Function Trip Alarm RTD M1 #8: Name PROGRAM SELECTION RTD Module 1 #5 Type Trip Alarm RTD M1 #7: Name UNIT Disable Function Trip Alarm RTD M1 #6: Name MAX RTD Module 1 #4 Type Trip Alarm RTD M1 #5: Name DEFAULT Stator 40 40 130.00 110.00 RTD Sensor Trip Action Disable RTD Sensor Alarm Action Disable 200 200 Load Ambient °C °C Appendix B, FPS Set-Up Record Page B-11 Rev. 1-C-031615 FPS Feeder Protection System FUNCTION & SET POINT RTD Undertemperature: MIN DEFAULT Trip Action Disable Alarm Action Disable Trip Level MAX 0 Alarm Level UNIT °C 0 °C PROGRAM SELECTION Disable Trip2 Disable Alarm2 + 20 + 15 + 10 +5 0 + 20 + 15 + 10 +5 0 Trip1 Trip3 Alarm1 Alarm3 -5 - 10 - 15 - 20 -5 - 10 - 15 - 20 PART III: CONTROL PARAMETER MIN DEFAULT MAX UNIT 0.1 0.1 1 1 5 5 s s Control Type Close Pulse Time Open Pulse Time Trip Sources PROGRAM SELECTION None 2-Coil Device Contactor Trip1 | Trip2 | Trip3 Disable Trip1 Trip2 Trip3 Trip1 | Trip2 Trip1 | Trip3 Trip1 | Trip2 | Trip3 Trip2 | Trip3 Remote Group: Digital Input Control Network Control OPI Control Local Group: OPI Control Enable Enable Enable Enable Enable Enable Disable Disable Disable Disable Breaker Open Retry 0 Enable 0 (None) 1 Retry 2 Retries Disable 3 Retries 4 Retries 5 Retries Appendix B, FPS Set-Up Record FPS Feeder Protection System Page B-12 Rev. 1-C-031615 This page intentionally left blank. Appendix B, FPS Set-Up Record Page C-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX C FPS MODBUS PROTOCOL C.1 PROTOCOL C.4 FUNCTION CODES SUPPORTED ® The FPS implements the Modbus RTU protocol as described in the Gould Modbus Reference Guide, Publication PI-MBUS-300 Rev. B. The communications system consists of a single master and up to thirty-two FPS-CTU slaves connected using a two-wire RS-485 network. If the master does not have an RS-485 port, an RS-232 to RS-485 converter is required. The converter must have automatic send-data control (SD). SD control does not require hand-shaking lines since it uses the data line to control the transmit/receive line on the RS-485 transceivers. Only the master can initiate a message transaction. Messages can be addressed to individual slaves or they can be broadcast messages. Broadcast messages are executed on the FPS slaves but unlike individually addressed messages, the slaves do not generate a reply message. C.2 MESSAGE SYNCHRONIZATION Message synchronization is accomplished by detection of an idle communication line. The communication line is considered idle when no communication exists for an equivalent delay of 3.5 characters. The first byte received after idle-line detection is interpreted as the address byte of the next message. Message bytes must be transmitted in a continuous stream until the complete message has been sent. If a delay of more than 3.5 characters exists within the message, the message is discarded. Response messages from the FPS are delayed by at least 3.5 character delays. C.3 ERROR CHECKING Modbus RTU uses a 16-bit cyclic redundancy check (CRC). The error check includes all of the message bytes, starting with the first address byte. When a CRC error is detected, the message is discarded and there will be no response. If the CRC check is correct but the internal data in the message is not correct, the FPS will respond with an exception response code. Modicon Modbus® is a registered trademark of Schneider Electric. The FPS Modbus Protocol supports the following function codes: Read Holding Registers (Function Code 3) Read Input Registers (Function Code 4) Write Single Register (Function Code 6) Write Multiple Registers (Function Code 16) Command Instruction (Function Code 5) Function Codes 3 and 4 perform the same function in the FPS. Registers in Modbus start at 40001 decimal and the register address generated for this register is 0. C4.1 APPLICATION LAYER The hexadecimal system is used. Value representations use the “C” convention. For hexadecimal, 0x precedes the value. C.4.2 READ INPUT/HOLDING REGISTERS (CODE 04/03) The first byte of the read message is the slave address. The second byte is the function code. Bytes three and four indicate the starting register. The next two bytes specify the number of 16-bit registers to read. The last two bytes contain the CRC code for the message. TABLE C.1 READ REGISTERS (CODE 04/03) HEX BYTE DESCRIPTION Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Slave Address Function Code MSB Register Address LSB Register Address MSB Number of Registers LSB Number of Registers LSB CRC MSB CRC The two-byte values of starting register and number of registers to read are transmitted with the high-order byte followed by the low-order byte. The CRC value is sent with the LSB followed by the MSB. The following message will obtain the value of register 1 (Modbus 40002) from slave 1. Note that Modbus registers are numbered from zero (40001 = zero, 40002 = one, etc.): 0x01 0x03 0x00 0x01 0x00 0x01 0xD5 0xC The addressed slave responds with its address and Function Code 3, followed by the information field. The information field contains an 8-bit byte count and the 16-bit data from the slave. The byte count specifies the number of Appendix C, FPS Modbus Protocol Page C-2 Rev. 1-C-031615 FPS Feeder Protection System bytes of data in the information field. The data in the information field consists of 16-bit data arranged so that the MSB is followed by the LSB. The maximum number of 16-bit registers that can be read is 120. C.4.3 WRITE TO REGISTER Function Code 6 or 16 is used to make set-point changes. C.4.3.1 WRITE SINGLE REGISTER (CODE 6) The function code format for writing a single register is shown in Table C.2. The message consists of the FPS address followed by the Function Code 6 and two 16-bit values. The first 16-bit value specifies the register to be modified and the second value is the 16-bit data. Provided no errors occurred, the slave will re-send the original message to the master. The response message is returned only after the command has been executed by the FPS. The following message will set register 3 to 300 in slave 5: 0x05 0x06 0x00 0x03 0x01 0x2C 0x78 0x03 TABLE C.2 WRITE SINGLE REGISTER (CODE 6) HEX BYTE DESCRIPTION Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Slave Address Function Code MSB Register Address LSB Register Address MSB of Data LSB of Data LSB of CRC MSB of CRC C.4.3.2 WRITE MULTIPLE REGISTERS (CODE 16) The function-code format in Table C.3 can be used for writing single or multiple registers. TABLE C.3 WRITE MULTIPLE REGISTERS (CODE 16) BYTE # DESCRIPTION Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 . . . Byte n Slave Address Function Code MSB Register Address LSB Register Address MSB of Quantity LSB of Quantity Byte Count MSB of Data LSB of Data LSB of CRC MSB of CRC The FPS will reply with the slave address, function code, register address, and the quantity followed by the CRC code for a total of 8 bytes. C.4.4 COMMAND INSTRUCTION (CODE 5) Modbus Function Code 5 (Force Single Coil) is used to issue commands to the FPS. The format for the message is listed in Table C.4 and the command code actions and corresponding coil number are listed in Table C.5. TABLE C.4 COMMAND FORMAT CODE 5 HEX BYTE DESCRIPTION Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Slave Address Function Code MSB of Command Code LSB of Command Code Fixed at 0xff Fixed at 00 LSB of CRC MSB of CRC TABLE C.5 SUPPORTED COMMANDS COMMAND CODE 0x0000 0x0001 0x0003 0x0004 0x0005 0x0006 0x0007 0x0008 0x0009 0x000A 0x000B 0x000C 0x000D 0x000E 0x000F 0x0010 0x0011 0x0012 COIL NUMBER 1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 ACTION OPEN CLOSE Reset Trips Set Real-Time Clock Clear Data-Logging Records Clear Trip Counters Clear Energy Totals Clear Running Hours Emergency I2t and Trip Reset Select Local Control De-select Local Control Re-enable Temperature Protection Remote/Net Trip Set Remote/Net Trip Clear Remote/Net Alarm Set Remote/Net Alarm Clear Run1 Set Run1 Clear Except for a broadcast address, the slave will return the original packet to the master. C.4.5 COMMAND INSTRUCTIONS USING WRITE COMMANDS For PLC's not supporting Function Code 5, FPS commands can be issued using Write Single Register (Code 6) and Write Multiple Register (Code 16). Commands are written to FPS register 6 (Modbus register 40007). Supported commands are listed in the COMMAND CODE column in Table C.5. When using the Write Multiple Registers function code, the write should be to the single FPS Register 6. If multiple registers are written starting at FPS Register 6, the first data element will be interpreted as the command code but no other registers will be written. If the command is successful, the FPS will return a valid response message. Appendix C, FPS Modbus Protocol Page C-3 Rev. 1-C-031615 FPS Feeder Protection System C.4.6 EXCEPTION RESPONSES The FPS supports the following exception responses: Boundry Error (1)—Applies to writes of 32-bit values. The high-order word must be written first followed by the write to the low-order word. If this sequence is not followed, a Boundry Error is returned and the value will not stored. This does not apply on read requests. Address Error (2)—All accesses to communication registers must be within the specified address range or the Address Error code is returned. Command Error (3)—This error code is returned if the command code is not supported. Illegal Function Code (4)—The function code (Byte 2) is not supported. The exception message consists of the slave address followed by a retransmission of the original function code. The function code will have the most-significant bit set to indicate an error. The 8-bit byte following the function code is the exception response code. The 16-bit CRC is at the end of the message. C.5.2 CUSTOM DATA ACCESS Data access can be customized with the User-Defined Registers and the User-Data Registers. User-Defined Registers are located in non-volatile memory and contain the register numbers from which data is required. To access the data, read the corresponding User-Data Registers. The format of the User Data is a function of the corresponding register entered in the User-Defined-Register area. C.6 NETWORK TIMEOUT The FPS can be configured to trip or alarm on a network timeout using the Setup Hardware Network Comms menu. The Net Trip Action and Net Alarm Action set points set the actions to be taken when a timeout occurs. To prevent a timeout, a valid message, addressed to the slave, must be received at time intervals less than five seconds. CAUTION: Set protocol to None before selecting Network Error actions; then, select protocol. C.5 FPS DATABASE C.7 SPECIFICATIONS Appendix E contains the Modbus Register in the Communications Database Table. The table starts at register 0 (Modbus 40001) and each register is 16-bits wide. Types “long” and “float” are 32-bit values. For both long and float types, the low-order word is transmitted first followed by the high-order word. Word values have the high byte followed by the low byte. Float types as per IEEE 754 Floating-Point Standard. All bytes of long and float types must be written using one message or an error will result. This does not apply for read commands. Interface ....................................... Isolated RS-485, 2-wire, multi-drop, half duplex Protocol........................................ Modbus RTU Baud Rate .................................... 1,200 to 19,200 bit/s Bit Format.................................... 8 bits, no parity, one stop bit(1) Number of CTU's Connected ..... Maximum of 32 units Bus length .................................... 1,200 m (4,000’) total(2) C.5.1 DATA RECORDS Only one event record can be read at a time. Record data is for the record indicated by the Record Selector. To select a record, write the record number to Record Selector and then read the values in the record. Record Head points to the next available record. The last event record captured is at Record Head minus one. Both Record Selector and Record Head values are in the range of 0 to 63. Values outside this range will select record 0. (1) Terminal “-” is negative with respect to terminal “+” for a binary 1 (MARK or OFF) state. Terminal “-” is positive with respect to terminal “+” for a binary 0 (SPACE or ON) state. (2) For line lengths exceeding 10 m (30’), 150- terminations are required at the cable ends. Appendix C, FPS Modbus Protocol FPS Feeder Protection System Page C-4 Rev. 1-C-031615 This page intentionally left blank. Appendix C, FPS Modbus Protocol Page D-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX D FPS A-B DF1 PROTOCOL D.1 PROTOCOL D.2 PLC-5 / SLC 500 CHANNEL-0 SETUP The FPS A-B® Protocol is based on the half-duplex master/slave Allen-Bradley (A-B) Data Highway Protocol (DF1) as described in Allen-Bradley Bulletin 1770-6.5.16 October 1996. This publication is available from the A-B web site at www.ab.com. The communications system consists of a single master and up to thirty-two slaves connected to a two-wire RS-485 multi-drop network. FPS Control Units are slave devices on this network. If the master does not have an RS-485 port, an RS-232 to RS-485 converter is required. The RS-485 converter should have automatic send-data control (SD). SD control does not require handshaking lines since it uses the data line to control the RS-485 transmitter. The SE-485-DIN converter is recommended. It includes optical isolation and baud rate selections from 9,600 to 57,600 bits per second. For additional information on converters, see Technical Information TI 9.9. The FPS supports the DF1 commands shown in Table D.1. Each PLC has limitations when using a particular command. Determine the best command to use for a particular application. COMMAND TABLE D.1 DF1 COMMANDS CMD Unprotected Read Unprotected Write Typed Read Typed Write Typed Logical Read Typed Logical Write 01 08 0F 0F 0F 0F FNC 68 67 A2 AA The PLC-5 and SLC 500 support reading and writing to integer files (Type N) and float files (Type F). Since FPS meter values are float types, these will typically be stored in a PLC Type-F file. It is also possible to read float types from the FPS as two integers; however, further processing is required to obtain the float value. The PLC requires two communication ports—a PLC programming port and an FPS communications port. Typically, a DH+ port will be used for PLC programming and the RS-232 port is used for FPS communications via an SE-485-DIN converter. A-B® is a registered trademark of Rockwell International Corporation. The RS-232 Channel-0 port is set up for a DF1 halfduplex master. Set the Channel-0 baud rate and CRC to match the FPS settings. The parity bit is not supported on the FPS. Where applicable, set Reply Message Wait to 100 ms. Additional recommended PLC settings: DF1 Retries = 3 RTS Send Delay = 1 (20 ms) RTS Off Delay = 0 Ack timeout = 5 (100 ms) Reply msg wait = 3 (60 ms) For the polling mode, select MESSAGE BASED (DO NOT ALLOW SLAVE TO INITIATE MESSAGES) or STANDARD (MULTIPLE MESSAGE-TRANSFER PER NODE SCAN). The FPS can buffer up to 3 messages. The selection MESSAGE BASED (DO NOT ALLOW SLAVE TO INITIATE MESSAGES) is recommended. D.3 TYPED-READ The Typed-Read message is used to read data from the FPS. The Typed-Read message requires a Control Block where the message configuration is stored. In the SLC, this is normally N7:0 but could be any other file that supports the control-block data. Use the following MSG settings: Read/Write: Target Device: Local/Remote: Control Block: Read PLC5 Local N7:0 NOTE: For the PLC-5, the message block must be of type MG so that the channel number can be set in the message setup screen. The Setup screen is used to specify file information. In the This Controller section, Data Table Address is the destination in the PLC where data is to be stored. This can be a float (Fx:x) file or an integer (Nx:x) file. Element Size must be set to the number of elements to transfer. This is a decimal value and this value is limited in some controllers. In the SLC 500, the maximum value for integers is 100 and for floats it is 50. Appendix D, FPS A-B DF1 Protocol Page D-2 Rev. 1-C-031615 FPS Feeder Protection System In Target Device, set Data Table Address to the A-B File address listed in Appendix E. The A-B File in Appendix E is coded as FILE:ELEMENT. To read or write the element as floats, the PLC-5 address would be <F><FILE>:<ELEMENT> (Example F9:222). To read or write the element as integers, add 20 to the file number and preceed with N, <N><FILE+20>:<ELEMENT> (Example N29:222). Local Address is the FPS address. Example settings for reading 25 registers as float type (25 meter readings): Data Table Address: ..... F8:0 Element Size:................ 25 Target Device Data Table Address:.......... F6:0 Local Address:.............. 9 (Must match FPS setting) NOTE: To read float values, both data table addresses must be specified as float (F) type. Example settings for reading a block of 100 registers (16-bit integer): This could be a mix of float and integer values since floats can be transferred as two integers in the FPS. Data Table Address: ..... N9:0 Element Size:................ 100 Target Device Data Table Address:.......... N23:264 (Start of Digital Inputs) Local Address:.............. 9 (Must match FPS setting) If an FPS float has been read into the PLC as two integers and stored in an N-type file, the float can be recovered by using two copy commands. Assume that the two integers from the FPS read command are stored in N9:0 and N9:1. The first copy command is used to swap the two words so they are in the correct order; copy N9:0 to N9:11, and copy N9:1 to N9:10. The second copy command will copy the two integers to the F-type file; copy N9:10 to F8:0 with a size of 1. The two integers are now combined correctly as a single 4-byte float located in F8:0. D.4 TYPED-WRITE The Typed-Write message is used to write data to the FPS. Read/Write: Target Device: Local/Remote: Control Block: Write PLC5 Local N7:0 The Setup screen is used to specify file information. In the This Controller section, Data Table Address is the source file in the SLC. This can be a float (Fx:x) file or an integer (Nx:x) file. Element Size must be set to the number of elements to transfer. For the FPS, the maximum element size is 100 for integers and 50 for floats. In Target Device, set Data Table Address to the A-B File address listed in Appendix E. Both integer and float values sent from the SLC are in the correct byte order and interpreted correctly by the FPS. The FPS will do a range check on all messages to ensure valid data. Local Address is the FPS address. Example settings for writing a single float to set the FLA Rating: Data-Table Address: .....F8:0 (Location of FLA value) Element Size: ................1 Target-Device DataTable Address: ..........F3:225 Local Address: ..............9 (Must match FPS setting) Reset commands to the FPS are issued by writing an integer command code to FPS Register 6 (N23:6) A command message should only be issued when the command is required. Valid commands are shown Table D.2. TABLE D.2 FPS COMMANDS COMMAND CODE ACTION 0x0000 0x0001 0x0003 0x0004 0x0005 0x0006 0x0007 0x0008 0x0009 0x000A 0x000B 0x000C 0x000D 0x000E 0x000F 0x0010 0x0011 0x0012 OPEN CLOSE Reset Trips Set Real-Time Clock Clear Data-Logging Records Clear Trip Counters Clear Energy Totals Clear Running Hours Emergency I2t and Trip Reset Select Local Control De-select Local Control Re-enable Temperature Protection Remote/Net Trip Set Remote/Net Trip Clear Remote/Net Alarm Set Remote/Net Alarm Clear Run1 Set Run1 Clear Example settings for writing an FPS reset command. Data-Table Address: .....N9:0 (Reset code = 3) Element Size: ................1 Target-Device DataTable Address: ..........N23:6 (FPS Command Register location) Local Address: ..............9 (Must match FPS setting) Appendix D, FPS A-B DF1 Protocol Page D-3 Rev. 1-C-031615 FPS Feeder Protection System D.5 UNPROTECTED READ/WRITE D.9 NETWORK TIMEOUT For PLC-2 and PLC-3 processors not supporting Typed Read/Write messages, Unprotected Read/Write commands can be used. For these messages, the data address is the Octal value of the FPS Register in Appendix E. The size is the number of registers. The maximum number of registers that can be transferred in a single message is 100. Unprotected Read/Write commands are used by the SE-Comm-FPS communication program. The FPS can be configured to trip or alarm on a network timeout using the Setup Hardware Network Comms menu. The Net Trip Action and Net Alarm Action set points set the actions to be taken when a timeout occurs. To prevent a timeout, a valid message, addressed to the slave, must be received at time intervals less than five seconds. D.6 TYPED LOGICAL READ/WRITE The Typed Logical Read (CMD = 0F, FNC = A2) and Typed Logical Write (CMD = 0F, FNC = AA) messages are supported by the full line of SLC 500 processors and Prosoft MVIxx-DFCM communication interfaces. Both float (F) and integer (N) types are supported. Unlike the typed commands in Section D.3 and D.4 a file offset is not required for integer values. Use the A-B file address as listed in the FPS manual Appendix E and precede the address with F for float values and N for integer values. The maximum number of integers and floats that can be read is 100 and 50 respectively. Reset commands to the FPS are issued by writing one of the COMMAND CODES listed in Table D.2 to Register 6 (N3:6). D.7 DATA RECORDS CAUTION: Set protocol to None before selecting Network Error actions; then, select protocol. D.10 SPECIFICATIONS Interface ....................................... Isolated RS-485, 2-wire, multi-drop, half duplex Protocol........................................ Modbus RTU Baud Rate .................................... 1,200 to 19,200 bit/s Bit Format.................................... 8 bits, no parity, one stop bit (1) Number of CTU's Connected ..... Maximum of 32 units Bus length .................................... 1,200 m (4,000’) total (2) (1) Terminal “-” is negative with respect to terminal “+” for a binary 1 (MARK or OFF) state. Terminal “-” is positive with respect to terminal “+” for a binary 0 (SPACE or ON) state. (2) For line lengths exceeding 10 m (30’), 150- terminations are required at the cable ends. Only one event record can be read at a time. Data is for the record indicated by the Record Selector. To select a record, write the record number to Record Selector and then read the values in the record. Record-Head points to the next available record. The last event record captured is at Record Head minus one. Both Record-Selector and Record-Head values are in the range of 0 to 63. Values outside this range will select record 0. D.8 CUSTOM DATA ACCESS Data access can be customized with the User-Defined Registers and the User Data Register. Enter the required data-register numbers in the UserDefined Registers. The format of user data is a function of the corresponding register. To access the data, read the corresponding User-Data Register. Appendix D, FPS A-B DF1 Protocol FPS Feeder Protection System Page D-4 Rev. 1-C-031615 This page intentionally left blank. Appendix D, FPS A-B DF1 Protocol Page E-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX E COMMUNICATIONS DATABASE TABLE FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Model Information 0 40001 1 40002 2 40003 3 40004 4 5 6 40007 7 40008 Overload Group1 8 40009 9 40010 10 40011 11 40012 12 40013 13 40014 14 40015 15 40016 16 40017 17 40018 18 40019 19 40020 20 40021 21 40022 22 40023 Overload Group2 26 40027 27 40028 28 40029 29 40030 30 40031 31 40032 32 40033 33 40034 34 40035 35 40036 36 40037 37 40038 38 40039 39 40040 40 40041 OBJECT A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 1-1-3 1-1-64 1-1-6 3:0 3:1 3:2 3:3 29-1-64 3:6 3:7 2C-1-64 2C-1-65 3:8 3:9 3:10 3:11 3:12 3:13 3:14 3:15 3:16 3:17 3:18 3:19 3:20 3:21 3:22 2C-1-67 2C-1-69 2C-1-6A 2C-1-6B 2C-1-6C 2C-2-64 2C-2-65 2C-2-67 2C-2-69 2C-2-6A 2C-2-6B 2C-2-6C 3:26 3:27 3:28 3:29 3:30 3:31 3:32 3:33 3:34 3:35 3:36 3:37 3:38 3:39 3:40 ACCESS RANGE TYPE Model Code (202) Software Version Serial Number Read Only Read Only Read Only T3 T3 T2 (Low) T2 (High) Diagnostic Code Command Register Reserved Read Only Write Only R/W 0-1 T3 T101 T81 Trip Action Alarm Action Reserved Pickup in pu of CT Rating R/W R/W 0-7 0-7 T42 T43 R/W 0.1 - 1.25 Reserved R/W 1 - 10 Hot Factor R/W 0.1 - 1.0 Cold Factor R/W 0.1 - 1.0 Time Constant R/W 1 - 60 min Alarm Level R/W 0.5 - 1.0 T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) Trip Action Alarm Action Reserved Pickup in pu of CT Rating R/W R/W 0-7 0-7 T42 T43 R/W 0.1 - 1.25 Reserved R/W 1 - 10 Hot Factor R/W 0.1 - 1.0 Cold Factor R/W 0.1 - 1.0 Time Constant R/W 1 - 60 min Alarm Level R/W 0.5 - 1.0 T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) Appendix E, Communications Database Table Page E-2 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) Reduced Overcurrent 44 40045 2C-0-64 45 40046 2C-0-65 46 40047 Phase Inverse Group1 50 40051 65-1-1 51 40052 65-1-2 52 40053 65-1-3 53 40054 54 40055 65-1-4 55 40056 Phase Inverse Group2 60 40061 65-2-1 61 40062 65-2-2 62 40063 65-2-3 63 40064 64 40065 65-2-4 65 40066 Phase Definite-Time Group1 70 40071 64-1-1 71 40072 64-1-2 72 40073 64-1-3 73 40074 74 40075 64-1-4 75 40076 76 40077 64-1-5 77 40078 78 40079 64-1-6 79 40080 Phase Definite-Time Group2 84 40085 64-2-1 85 40086 64-2-2 86 40087 64-2-3 87 40088 88 40089 64-2-4 89 40090 90 40091 64-2-5 91 40092 92 40093 64-2-6 93 40094 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) ACCESS RANGE TYPE 3:44 3:45 3:46 I2t Reset Type I2t Reset Level R/W R/W 0-2 0.1 - 0.9 T38 T1 (Low) T1 (High) 3:50 3:51 3:52 3:53 3:54 3:55 Trip Action Curve Type Time Multiplier R/W R/W R/W 0-7 0-7 0.05 - 1.0 Pickup in pu of CT Rating R/W 0.1 - 10 x Ip T42 T73 T1(Low) T1(High) T1(Low) T1(High) 3:60 3:61 3:62 3:63 3:64 3:65 Trip Action Curve Type Time Multiplier R/W R/W R/W 0-7 0-7 0.05 - 1.0 Pickup in pu of CT Rating R/W 0.1 - 10 x Ip 3:70 3:71 3:72 3:73 3:74 3:75 3:76 3:77 3:78 3:79 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.1 - 15 x Ip Trip Delay R/W 0 - 10 s Alarm Level R/W 0.1 - 15 x Ip Alarm Delay R/W 0 -10 s 3:84 3: 85 3:86 3:87 3:88 3:89 3:90 3:91 3:92 3:93 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.1 - 15 x Ip Trip Delay R/W 0 - 10 s Alarm Level R/W 0.1 - 15 x Ip Alarm Delay R/W 0 -10 s T42 T73 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T43 T42 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T43 T42 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-3 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS A-B FILE REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) (DECIMAL) (NOTE 4) Earth-Fault 3I0 Inverse Group1 100 40101 65-3-1 3:100 101 40102 65-3-2 3:101 102 40103 65-3-3 3:102 103 40104 3:103 104 40105 65-3-4 3:104 105 40106 3:105 Earth-Fault 3I0 Inverse Group2 110 40111 65-4-1 3:110 111 40112 65-4-2 3:111 112 40113 65-4-3 3:112 113 40114 3:113 114 40115 65-4-4 3:114 115 40116 3:115 Earth-Fault 3I0 Definite-Time Group1 120 40121 64-3-1 3:120 121 40122 64-3-2 3:121 122 40123 64-3-3 3:122 123 40124 3:123 124 40125 64-3-4 3:124 125 40126 3:125 126 40127 64-3-5 3:126 127 40128 3:127 128 40129 64-3-6 3:128 129 40130 3:129 Earth-Fault 3I0 Definite-Time Group2 136 40137 64-4-1 3:136 137 40138 64-4-2 3:137 138 40139 64-4-3 3:138 139 40140 3:139 140 40141 64-4-4 3:140 141 40142 3:141 142 40143 64-4-5 3:142 143 40144 3:143 144 40145 64-4-6 3:144 145 40146 3:145 DESCRIPTION ACCESS RANGE Trip Action Curve Type Time Multiplier R/W R/W R/W 0-7 0-7 0.5 - 1.0 Pickup in pu of CT Rating R/W 0 - 1.0 Trip Action Curve Type Time Multiplier R/W R/W R/W 0-7 0-7 0.5 - 1.0 Pickup in pu of CT Rating R/W 0 - 1.0 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.1 - 15 x Ip Trip Delay R/W 1 - 100 s Alarm Level R/W 0.1 - 15 x Ip Alarm Delay R/W 0 - 10 s Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.1 - 15 x Ip Trip Delay R/W 1 - 100 s Alarm Level R/W 0.1 - 15 x Ip Alarm Delay R/W 0 - 10 s TYPE T42 T73 T1(Low) T1(High) T1(Low) T1(High) T42 T73 T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-4 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS A-B FILE REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) (DECIMAL) (NOTE 4) Earth-Fault CT-Input Definite-Time Group1 150 40151 64-5-1 3:150 151 40152 64-5-2 3:151 152 40153 64-5-3 3:152 153 40154 3:153 154 40155 64-5-4 3:154 155 40156 3:155 156 40157 64-5-5 3:156 157 40158 3:157 158 40159 64-5-6 3:158 159 40160 3:159 Earth-Fault CT-Input Definite-Time Group2 166 40167 64-6-1 3:166 167 40168 64-6-2 3:167 168 40169 64-6-3 3:168 169 40170 3:169 170 40171 64-6-4 3:170 171 40172 3:171 172 40173 64-6-5 3:172 173 40174 3:173 174 40175 64-6-6 3:174 175 40176 3:175 Unbalance (I) 180 40181 64-7-1 3:180 181 40182 64-7-2 3:181 182 40183 64-7-3 3:182 183 40184 3:183 184 40185 64-7-4 3:184 185 40186 3:185 186 40187 64-7-5 3:186 187 40188 3:187 188 40189 64-7-6 3:188 189 40190 3:189 Phase Loss (I) 192 40193 64-8-1 3:192 193 40194 64-8-2 3:193 194 40195 64-8-4 3:194 195 40196 3:195 196 40197 64-8-6 3:196 197 40198 3:197 DESCRIPTION ACCESS RANGE Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.01 - 1 x Ie Trip Delay R/W 0 - 100 s Alarm Level R/W 0.01 - 1 x Ie Alarm Delay R/W 0 - 100 s Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.01 - 1 x Ie Trip Delay R/W 0 - 100 s Alarm Level R/W 0.01 - 1 x Ie Alarm Delay R/W 0 - 100 s Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.01 - 1 x Ie Trip Delay R/W 0 - 100 s Alarm Level R/W 0.01 - 1 x Ie Alarm Delay R/W 0 - 100 s Trip Action Alarm Action Trip Delay R/W R/W R/W 0-7 0-7 1 - 100 s Alarm Delay R/W 1 - 100 s TYPE T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(High) T1(Low) T1(High) T1(Low) Appendix E, Communications Database Table Page E-5 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Phase Reverse (I) 198 40199 199 40200 200 40201 201 40202 202 40203 203 40204 Reversepower 204 40205 205 40206 206 40207 207 40208 208 40209 209 40210 210 40211 211 40212 212 40213 213 40214 Unbalance (V) 214 40215 215 40216 216 40217 217 40218 218 40219 219 40220 220 40221 221 40222 222 40223 223 40224 Phase Loss (V) 224 40225 225 40226 226 40227 227 40228 228 40229 229 40230 Phase Reverse (V) 234 40235 235 40236 236 40237 237 40238 238 40239 239 40240 OBJECT 64-9-1 64-9-2 64-9-4 64-9-6 64-14-01 64-14-02 64-14-03 64-14-04 64-14-05 64-14-06 64-0a-1 64-0a-2 64-0a-3 64-0a-4 64-0a-5 64-0a-6 64-0b-1 64-0b-2 64-0b-4 64-0b-6 64-0c-1 64-0c-2 64-0c-4 64-0c-6 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) ACCESS RANGE 3:198 3:199 3:200 3:201 3:202 3:203 Trip Action Alarm Action Trip Delay R/W R/W R/W 0-7 0-7 1 - 100 s Alarm Delay R/W 1 - 100 s 3:204 3:205 3:206 3:207 3:208 3:209 3:210 3:211 3:212 3:213 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.1 - 1 pu Trip Delay R/W 0.5 - 500 s Alarm Level R/W 0.1 - 1 pu Alarm Delay R/W 0.5 - 500 s Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.05 - 1.0 Trip Delay R/W 0 - 100 s Alarm Level R/W 0.05 - 1.0 Alarm Delay R/W 0 - 100 s 3:198 3:199 3:200 3:201 3:202 3:203 Trip Action Alarm Action Trip Delay R/W R/W R/W 0-7 0-7 1 - 100 s Alarm Delay R/W 1 - 100 s 3:198 3:199 3:200 3:201 3:202 3:203 Trip Action Alarm Action Trip Delay R/W R/W R/W 0-7 0-7 1 - 100 s Alarm Delay R/W 1 - 100 s 3:214 3:215 3:216 3:217 3:218 3:219 3:220 3:221 3:222 3:223 TYPE T42 T43 T1(High) T1(Low) T1(High) T1(Low) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(High) T1(Low) T1(High) T1(Low) T42 T43 T1(High) T1(Low) T1(High) T1(Low) Appendix E, Communications Database Table Page E-6 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Undervoltage 242 40243 243 40244 244 40245 245 40246 246 40247 247 40248 248 40249 249 40250 250 40251 251 40252 Undervoltage 254 40255 255 40256 256 40257 257 40258 258 40259 259 40260 260 40261 261 40262 262 40263 263 40264 Underfrequency 270 40271 271 40272 272 40273 273 40274 274 40275 275 40276 276 40277 277 40278 278 40279 279 40280 Overfrequency 280 40281 281 40282 282 40283 283 40284 284 40285 285 40286 286 40287 287 40288 288 40289 289 40290 OBJECT 64-0d-1 64-0d-2 64-0d-3 64-0d-4 64-0d-5 64-0d-6 64-0e-1 64-0e-2 64-0e-3 64-0e-4 64-0e-5 64-0e-6 64-0f-1 64-0f-2 64-0f-3 64-0f-4 64-0f-5 64-0f-6 64-10-1 64-102 64-10-3 64-10-4 64-10-5 64-10-6 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 3:242 3:243 3:244 3:245 3:246 3:247 3:248 3:249 3:250 3:251 ACCESS RANGE Trip Action Alarm Action Trip Level R/W R/W R/W Trip Delay R/W Alarm Level R/W Alarm Delay R/W 3:254 3:255 3:256 3:257 3:258 3:259 3:260 3:261 3:262 3:263 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 1 - 1.4 x Vp Trip Delay R/W 0 - 500 s Alarm Level R/W 1 - 1.4 x Vp Alarm Delay R/W 0 - 500 s 3:270 3:271 3:272 3:273 3:274 3:275 3:276 3:277 3:278 3:279 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 30 - 80 Hz Trip Delay R/W 0.5 - 500 s Alarm Level R/W 30 - 80 Hz Alarm Delay R/W 0.5 - 500 s 3:280 3:281 3:282 3:283 3:284 3:285 3:286 3:287 3:288 3:289 Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 30 - 80 Hz Trip Delay R/W 0.5 - 500 s Alarm Level R/W 30 - 80 Hz Alarm Delay R/W 0.5 - 500 s TYPE 0-7 T42 0-7 T43 0.05 - 1.0 x Vp T1(Low) T1(High) 0 - 500 s T1(Low) T1(High) 0.05 - 1.0 x Vp T1(Low) T1(High) 0 - 500 s T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-7 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Power-Factor Lag 294 40295 295 40296 296 40297 297 40298 298 40299 299 40300 300 40301 301 40302 302 40303 303 40304 Power-Factor Lead 304 40305 305 40306 306 40307 307 40308 308 40309 309 40310 310 40311 311 40312 312 40313 313 40314 Undertemperature 314 40315 315 40316 316 40317 317 40318 PTC Temperature 324 40325 325 40326 RTD Module 328 40329 329 40330 330 40331 331 40332 332 40333 RTD Type 336 40337 337 40338 338 40339 339 40340 340 40341 341 40342 342 40343 343 40344 OBJECT 64-11-1 64-11-2 64-11-3 64-11-4 64-11-5 64-11-6 64-12-1 64-12-2 64-12-3 64-12-4 64-12-5 64-12-6 A-B FILE (DECIMAL) (NOTE 4) 3:294 3:295 3:296 3:297 3:298 3:299 3:300 3:301 3:302 3:303 3:304 3:305 3:306 3:307 3:308 3:309 3:310 3:311 3:312 3:313 ACCESS RANGE Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.5 - 1.0 Trip Delay R/W 1 - 500 s Alarm Level R/W 0.5 - 1.0 Alarm Delay R/W 1 - 500 s Trip Action Alarm Action Trip Level R/W R/W R/W 0-7 0-7 0.5 - 1.0 Trip Delay R/W 1 - 500 s Alarm Level R/W 0.5 - 1.0 Alarm Delay R/W 1 - 500 s DESCRIPTION TYPE T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) 68-00-78 68-00-79 68-00-7A 68-00-7B 3:314 3:315 3:316 3:317 Trip Level Alarm Level Trip Action Alarm Action R/W R/W R/W R/W 0-8 0-8 0-7 0-7 T108 T108 T42 T43 64-13-1 64-13-2 3:324 3:325 Trip Action Alarm Action R/W R/W 0-7 0-7 T42 T43 68-00-64 68-00-67 68-00-68 68-00-65 68-00-66 3:328 3:329 3:330 3:331 3:332 Number of Modules Module Error Trip Action Module Error Alarm Action Sensor Error Trip Action Sensor Error Alarm Action R/W R/W R/W R/W R/W 0-1 0-7 0-7 0-7 0-7 T88 T43 T42 T43 T43 68-01-01 68-01-02 68-01-03 68-01-04 68-01-05 68-01-06 68-01-07 68-01-08 3:336 3:337 3:338 3:339 3:340 3:341 3:342 3:343 #1 Type #2 Type #3 Type #4 Type #5 Type #6 Type #7 Type #8 Type R/W R/W R/W R/W R/W R/W R/W R/W 0-4 0-4 0-4 0-4 0-4 0-4 0-4 0-4 T20 T20 T20 T20 T20 T20 T20 T20 Appendix E, Communications Database Table Page E-8 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) RTD Function 344 40345 68-01-09 345 40346 68-01-0a 346 40347 68-01-0b 347 40348 68-01-0c 348 40349 68-01-0d 349 40350 68-01-0e 350 40351 68-01-0f 351 40352 68-01-10 RTD Trip1/Alarm1 Setpoints 352 40353 68-01-11 353 40354 354 40355 68-01-12 355 40356 356 40357 68-01-13 357 40358 358 40359 68-01-14 359 40360 360 40361 68-01-15 361 40362 362 40363 68-01-16 363 40364 364 40365 68-01-17 365 40366 366 40367 68-01-18 367 40368 368 40369 68-01-19 369 40370 370 40371 68-01-0a 371 40372 372 40373 68-01-0b 373 40374 374 40375 68-01-0c 375 40376 376 40377 68-01-0d 377 40378 378 40379 68-01-0e 379 40380 380 40381 68-01-0f 381 40382 382 40383 68-01-20 383 40384 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) ACCESS RANGE TYPE 3:344 3:345 3:346 3:347 3:348 3:349 3:350 3:351 #1 Function #2 Function #3 Function #4 Function #5 Function #6 Function #7 Function #8 Function R/W R/W R/W R/W R/W R/W R/W R/W 0-3 0-3 0-3 0-3 0-3 0-3 0-3 0-3 T89 T89 T89 T89 T89 T89 T89 T89 3:352 3:353 3:354 3:355 3:356 3:357 3:358 3:359 3:360 3:361 3:362 3:363 3:364 3:365 3:366 3:367 3:368 3:369 3:370 3:371 3:372 3:373 3:374 3:375 3:376 3:377 3:378 3:379 3:380 3:381 3:382 3:383 #1 Trip Level R/W 40 - 200°C #1 Alarm Level R/W 40 - 200°C #2 Trip Level R/W 40 - 200°C #2 Alarm Level R/W 40 - 200°C #3 Trip Level R/W 40 - 200°C #3 Alarm Level R/W 40 - 200°C #4 Trip Level R/W 40 - 200°C #4 Alarm Level R/W 40 - 200°C #5 Trip Level R/W 40 - 200°C #5 Alarm Level R/W 40 - 200°C #6 Trip Level R/W 40 - 200°C #6 Alarm Level R/W 40 - 200°C #7 Trip Level R/W 40 - 200°C #7 Alarm Level R/W 40 - 200°C #8 Trip Level R/W 40 - 200°C #8 Alarm Level R/W 40 - 200°C T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-9 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) RTD Name 384 40385 394 40395 404 40405 414 40415 424 40425 434 40435 444 40445 454 40455 System Ratings 480 40481 481 40482 482 40483 483 40484 484 40485 485 40486 486 40487 487 40488 488 40489 489 40490 490 40491 491 40492 492 40493 Operator Interface 504 40505 505 40506 506 40507 507 40508 508 40509 509 40510 510 40511 Control Method 520 40521 521 524 525 526 527 528 529 530 531 532 40522 40525 40526 40527 40528 40529 40530 40531 40532 40533 OBJECT A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) ACCESS RANGE TYPE 68-01-21 68-01-22 68-01-23 68-01-24 68-01-25 68-01-26 68-01-27 68-01-28 4:0 4:1 4:2 4:3 4:4 4:5 4:6 4:7 #1 Name #2 Name #3 Name #4 Name #5 Name #6 Name #7 Name #8 Name R/W R/W R/W R/W R/W R/W R/W R/W 29-01-9c 4:96 Phase CT Primary R/W 1 - 5,000 A 29-01-9d Earth Fault CT Primary R/W 1 - 5,000 A 29-01-9e System Voltage (Line-to-Line) R/W 120 - 75 kV 29-01-9f Input Voltage R/W 60 - 600 V 29-01-a0 29-01-a1 29-01-a2 29-01-a3 Voltage Connection Type Frequency Set-Point Group Unbalance-Current Threshold R/W R/W R/W R/W 0-3 0-1 0-1 0.1 - 0.5 x Ip Display Failure Trip Action Number of OPI’s Password Timeout R/W R/W R/W 0-7 0-2 1 - 60 min Screen Saver Meter Summary Default Display R/W R/W R/W 0-1 R/W 0-2 T103 29-01-74 29-01-70 29-01-71 29-01-72 29-01-77 Control Type Breaker/Contactor Trip Source Remote Group—Din Input Ctl Remote Group—Network Ctl Remote Group—OPI Ctl CB Close Pulse Width R/W R/W R/W R/W R/W 0-7 0-1 0-1 0-1 0.1 - 5 s 29-01-78 CB Open Pulse Width R/W 0.1 - 5 s 29-01-79 29-01-7A Local Group—OPI Ctl Breaker Open Retry R/W R/W 0-1 0-5 T104 T6 T6 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T6 T107 29-01-6a 29-01-6b 29-01-67 4:120 NA NA NA 29-01-73 4:136 T22 T22 T22 T22 T22 T22 T22 T22 T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T1 (Low) T1 (High) T9 T10 T81 T1 (Low) T1 (High) T42 T40 T1 (Low) T1 (High) T6 T98 Appendix E, Communications Database Table Page E-10 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Digital Input 540 40541 541 40542 542 40543 543 40544 544 40545 545 40546 Digital Input 550 40551 551 40552 552 40553 553 40554 554 40555 555 40556 560 40561 561 40562 562 40563 563 40564 564 40565 565 40566 570 40571 571 40572 572 40573 573 40574 574 40575 575 40576 580 40581 581 40582 582 40583 583 40584 584 40585 585 40586 590 40591 591 40592 592 40593 593 40594 594 40595 595 40596 600 40601 601 40602 602 40603 603 40604 604 40605 605 40606 OBJECT 66-01-01 66-01-02 66-01-03 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 4:156 66-01-04 66-02-01 66-02-02 66-02-03 4:166 66-02-04 66-03-01 66-03-02 66-03-03 4:176 66-03-04 66-04-01 66-04-02 66-04-03 4:186 66-04-04 66-05-01 66-05-02 66-05-03 4:196 66-05-04 66-06-01 66-06-02 66-06-03 4:206 66-06-04 66-07-01 66-07-02 66-07-03 66-07-04 4:216 ACCESS RANGE TYPE Input 1 Function Input 1 Bypass Enable Input 1 Bypass Delay R/W R/W R/W Input 1 Trip Delay R/W T86 0-1 T6 0.5 - 100 s T1 (Low) T1 (High) 0.01 - 100 s T1 (Low) T1 (High) Input 2 Function Input 2 Bypass Enable Input 2 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 2 Trip Delay R/W 0.01 - 100 s Input 3 Function Input 3 Bypass Enable Input 3 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 3 Trip Delay R/W 0.01 - 100 s Input 4 Function Input 4 Bypass Enable Input 4 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 4 Trip Delay R/W 0.01 - 100 s Input 5 Function Input 5 Bypass Enable Input 5 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 5 Trip Delay R/W 0.01 - 100 s Input 6 Function Input 6 Bypass Enable Input 6 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 6 Trip Delay R/W 0.01 - 100 s Input 7 Function Input 7 Bypass Enable Input 7 Bypass Delay R/W R/W R/W 0-1 0.5 - 100 s Input 7 Trip Delay R/W 0.01 - 100 s T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) T86 T6 T1 (Low) T1 (High) T1 (Low) T1 (High) Appendix E, Communications Database Table Page E-11 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Relay Output Function 610 40611 611 40612 612 40613 613 40614 614 40615 615 40616 616 40617 617 40618 618 40619 619 40620 620 40621 621 40622 Analog Input 630 40631 631 40632 632 40633 633 40634 634 40635 635 40636 636 40637 637 40638 638 40639 639 40640 640 40641 641 40642 642 40643 643 40644 644 40645 Analog Ouput 650 40651 651 40652 652 40653 653 40654 654 40655 OBJECT A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 29-01-80 29-01-81 29-01-82 29-01-83 29-01-84 29-01-85 29-01-86 29-01-87 29-01-88 29-01-89 29-01-8a 4:226 67-01-01 67-01-02 67-01-03 67-01-04 4:246 ACCESS RANGE Relay 1 Output Function Relay 1 Mode Relay 2 Output Function Relay 2 Mode Relay 3 Output Function Relay 3 Mode Relay 4 Output Function Relay 4 Mode Relay 5 Output Function Relay 5 Mode Relay Pulse Time R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W Analog Input Time Trip Action Alarm Action High-Level Trip R/W R/W R/W R/W 0-7 0-7 0.1 - 20 mA 67-01-05 Low-Level Trip R/W 0.1 - 20 mA 67-01-06 Trip Delay R/W 0.01 - 100 s 67-01-07 High-Level Alarm R/W 0.1 - 20 mA 67-01-08 Low-Level Alarm R/W 0.1 - 20 mA 67-01-09 Alarm Delay R/W 0.01 - 100 s Analog Output Parameter Zero Calibration R/W R/W 0 - 1,000 Full-Scale Calibration R/W 0 - 1,000 67-01-0a 4:266 0-1 0-1 0-1 0-1 0-1 0.05 - 10 s TYPE T106 T14 T106 T14 T106 T14 T106 T14 T106 T14 T1(Low) T1(High) T92 T42 T43 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T87 T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-12 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) Network Communication 660 40661 661 40662 662 40663 663 664 665 666 667 668 669 670 671 40664 40665 40666 40667 40668 40669 40670 40671 40672 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 4:276 03-01-64 03-01-65 680 40681 690 40691 Real-Time Clock Reading 720 40721 69-01-03 4:336 721 40722 722 40723 69-01-04 723 40724 724 40725 69-01-02 725 40726 726 40727 69-01-01 727 40728 728 40729 69-01-05 Character Strings (10 words, 20 characters) 40741 01-01-66 4:356 740 40751 01-01-65 4:366 750 Meter Values 860 40861 29-01-b0 5:0 861 40862 862 40863 29-01-b1 863 40864 864 40865 29-01-b2 865 40866 866 40867 29-01-b3 867 40868 868 40869 29-01-b4 869 40870 ACCESS RANGE TYPE Network Type Network Baud Modbus RTU/AB DF1 Error Check Network ID (Slave ID) R/W R/W R/W 0-5 0-7 0-2 T16 T17 T18 R/W 0 - 255 Network-Error Trip Action Network-Error Alarm Action Remote Trip Action Remote Alarm Action DeviceNet Producing Instance DeviceNet Consuming Instance Reserved R/W R/W R/W R/W R/W R/W R/W 0-7 0-7 0-7 0-7 T1(Low) T1(High) T42 T43 T42 T43 T84 T85 Ethernet IP Ethernet Mask R/W R/W T22 T22 RTC Date Read Only RTC Time Read Only IRIG Offset in Minutes R/W IRIG Offset in Hours R/W Clock Setting R/W T23(Low) T23(High) T24(Low) T24(High) T1(Low) T1(High) T1(Low) T1(High) T31 Password Setting (4 Chars) System Name R/W R/W T22 T22 Ia (A) Read Only Ib (A) Read Only Ic (A) Read Only Iave (A) Read Only Earth Leakage From CT Read Only T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-13 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) 870 40871 871 40872 872 40873 873 40874 874 40875 875 40876 876 40877 877 40878 878 40879 879 40880 880 40881 881 40882 882 40883 883 40884 884 40885 885 40886 886 40887 887 40888 888 40889 889 40890 890 40891 891 40892 892 40893 893 40894 894 40895 895 40896 896 40897 897 40898 898 40899 899 40900 900 40901 901 40902 902 40903 903 40904 904 40905 905 40906 906 40907 907 40908 908 40909 909 40910 910 40911 911 40912 912 40913 913 40914 OBJECT 29-01-b5 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) Earth Leakage, Residual (A) ACCESS Read Only 29-01-b6 Vab (kV) Read Only 29-01-b7 Vbc (kV) Read Only 29-01-b8 Vca (kV) Read Only 29-01-b9 Va (kV) Read Only 29-01-ba Vb (kV) Read Only 29-01-bb Vc (kV) Read Only 29-01-bc Apparent Power (S) in kVA Read Only 29-01-bd Reactive Power (Q) in kVAR Read Only 29-01-be Real Power (P) in kW Read Only 29-01-bf Power Factor (-1 to +1) Read Only 29-01-c0 Thermal Capacity (pu) Read Only 29-01-c1 Thermal Trend (pu) Read Only 29-01-c2 Overload Trip/Reset Time (min) Read Only 29-01-c3 Positive-Sequence Current (pu) Read Only 29-01-c4 Negative-Sequence I (pu) Read Only 29-01-c5 Current Unbalance (pu) Read Only 29-01-c6 Positive-Sequence V (pu) Read Only 29-01-c7 Negative-Sequence V (pu) Read Only 29-01-c8 Voltage Unbalance (pu) Read Only 29-01-c9 Analog Input (mA) Read Only 29-01-ca Frequency (Hz) Read Only RANGE TYPE T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-14 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) 914 40915 915 40916 916 40917 917 40918 918 40919 919 40920 920 40921 921 40922 922 40923 923 40924 924 40925 925 40926 926 40927 927 40928 928 40929 929 40930 930 40931 931 40932 932 40933 933 40934 934 40935 935 40936 936 40937 937 40938 938 40939 939 40940 940 40941 941 40942 942 40943 943 40944 944 40945 945 40946 946 40947 947 40948 948 40949 949 40950 950 40951 951 40952 952 40953 953 40954 954 40955 955 40956 956 40957 957 40958 OBJECT 29-01-cb A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) Running Time (s) ACCESS Read Only 29-01-cc High Speed Input Frequency Read Only 68-01-29 #1 Temperature(3) Read Only 68-01-2a #2 Temperature(3) Read Only 68-01-2b #3 Temperature(3) Read Only 68-01-2c #4 Temperature(3) Read Only 68-01-2d #5 Temperature(3) Read Only 68-01-2e #6 Temperature(3) Read Only 68-01-2f #7 Temperature(3) Read Only 68-01-30 #8 Temperature(3) Read Only 68-00-70 Max Group A Temperature Read Only 68-00-71 Max Group B Temperature Read Only 68-00-72 Max Group C Temperature Read Only 68-00-73 Max Ambient Temperature Read Only 68-00-74 Min Group A Temperature Read Only 68-00-75 Min Group B Temperature Read Only 68-00-76 Min Group C Temperature Read Only 68-00-77 Min Ambient Temperature Read Only 29-01-cd kW Seconds Read Only 29-01-ce kVA Seconds Read Only RANGE TYPE T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T4(Word1) T4(Word2) T4(Word3) T4(Word4) T4(Word1) T4(Word2) T4(Word3) T4(Word4) Appendix E, Communications Database Table Page E-15 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) 958 40959 29-01-cf 959 40960 960 40961 961 40962 Event Records 980 981 982 983 984 985 986 987 988 989 990 991 992 993 994 995 996 997 998 999 1000 1001 1002 1003 1004 1005 1006 1007 1008 1009 1010 1011 1012 1013 1014 1015 1016 40981 40982 40983 40984 40985 40986 40987 40988 40989 40990 40991 40992 40993 40994 40995 40996 40997 40998 40999 41000 41001 41002 41003 41004 41005 41006 41007 41008 41009 41010 41011 41012 41013 41014 41015 41016 41017 6b-01-01 6b-01-02 6b-01-03 6b-01-04 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) kVAR Seconds 6:0 ACCESS RANGE Read Only Number of Records Record Head (Next Record) Record Selector Record Date Read Only Read Only Read Only Read Only 6b-01-05 Record Time Read Only 6b-01-06 6b-01-07 6b-01-08 Record Type Record Trip/Alarm Code Ia Read Only Read Only Read Only 6b-01-09 Ib Read Only 6b-01-0a Ic Read Only 6b-01-0b Earth Leakage from CT Read Only 6b-01-0c 3I0, Phase Calculation Read Only 6b-01-0d Vab (kV) Read Only 6b-01-0e Vbc (kV) Read Only 6b-01-0f Vca (kV) Read Only 6b-01-10 Va (kV) Read Only 6b-01-11 Vb (kV) Read Only 6b-01-12 Vc (kV) Read Only 6b-01-13 Analog Input Read Only 6b-01-14 Current Unbalance Read Only 6b-01-15 Voltage Unbalance Read Only TYPE T4(Word1) T4(Word2) T4(Word3) T4(Word4) 0 - 65535 0 - 99 0 - 99 T3 T3 T3 T23(Low) T23(High) T24(Low) T24(High) T99 T90 T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) Appendix E, Communications Database Table Page E-16 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) 1017 41018 1018 41019 1019 41020 1020 41021 1021 41022 1022 41023 1023 41024 1024 41025 1025 41026 1026 41027 1027 41028 1028 41029 1029 41030 1030 41031 1031 41032 1032 41033 1033 41034 1034 41035 1035 41036 1036 41037 1037 41038 1038 41039 1039 41040 1040 41041 1041 41042 1042 41043 1043 41044 1044 41045 Status 1110 41111 1111 41112 Message Stack 1112 41113 1113 41114 1114 41115 1115 41116 1116 41117 OBJECT 6b-01-16 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) Used Thermal Capacity ACCESS Read Only 6b-01-17 Frequency (Hz) Read Only 6b-01-18 Apparent Power (S) in kVA Read Only 6b-01-19 Real Power (P) in kW Read Only 6b-01-1a Reactive Power (Q) in kVAR Read Only 6b-01-1b Power Factor (-1 to +1) Read Only 6b-01-1c #1 Temperature(3) Read Only 6b-01-1d #2 Temperature(3) Read Only 61-01-1e #3 Temperature(3) Read Only 61-01-1f #4 Temperature(3) Read Only 6b-01-20 #5 Temperature(3) Read Only 6b-01-21 #6 Temperature(3) Read Only 6b-01-22 #7 Temperature(3) Read Only 6b-01-23 #8 Temperature(3) Read Only RANGE TYPE T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) T1(Low) T1(High) 29-01-90 29-01-91 7:0 7:1 T/A, Inverse-Curve Status Read Only Digital Input and Relay Status Read Only T94 T93 29-01-92 29-01-93 29-01-94 29-01-95 29-01-96 7:2 Message 0 Message 1 Message 2 Message 3 Message 4 T45 T46 T47 T48 T49 Read Only Read Only Read Only Read Only Read Only Appendix E, Communications Database Table Page E-17 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) Trip Counters 1130 41131 1131 1132 1133 1134 1135 1136 1137 1138 1139 1140 1141 1142 1143 1144 1145 1146 1147 1148 1149 1150 1151 1152 1153 1154 1155 1156 1157 1158 1159 1160 1161 1162 1163 1164 1165 1166 1167 1168 1169 1170 1171 1172 1173 41174 OBJECT 2C-01-6D 2C-02-6D 65-01-05 65-02-05 64-01-07 64-02-07 65-03-05 65-04-05 64-03-07 64-04-07 64-05-07 64-06-07 64-07-07 64-08-07 64-09-07 64-0a-07 64-0b-07 64-0c-07 64-0e-07 64-0d-07 64-0f-07 64-10-07 64-11-07 64-12-07 67-01-0b 67-01-0c 64-13-07 66-01-05 66-02-05 66-03-05 66-04-05 66-05-05 66-06-05 66-07-05 68-01-31 68-01-32 68-01-33 68-01-34 68-01-35 68-01-36 68-01-37 68-01-38 68-00-69 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 7:20 Overload Group 1 Overload Group 2 Phase Inverse Group 1 Phase Inverse Group 2 Phase Definite Time Group 1 Phase Definite Time Group 2 EF 3I0 Inverse Group 1 EF 3I0 Inverse Group 2 3I0 Definite Time Group 1 3I0 Definite Time Group2 EF CT Definite Time Group 1 EF CT Definite Time Group 2 Unbalance (I) Phase Loss (I) Phase Reverse (I) Unbalance (V) Phase Loss (V) Phase Reverse (V) Overvoltage Undervoltage Underfrequency Overfrequency PF Lag PF Lead Reserved Analog High Analog Low PTC Temperature Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input 5 Digital Input 6 Digital Input 7 RTD 1 RTD 2 RTD 3 RTD 4 RTD 5 RTD 6 RTD 7 RTD 8 RTD Module Comm Error ACCESS RANGE TYPE Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 Appendix E, Communications Database Table Page E-18 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER (DECIMAL) (DECIMAL) 1174 41175 1175 41176 1176 41177 1177 41178 1178 41179 1179 41180 1180 41181 1181 41182 1182 41183 1183 41184 1184 41185 1185 41186 1186 41187 1187 41188 1188 41189 1189 41190 1190 41191 1191 41192 User Defined Registers 1400 41401 1401 41402 1402 41403 1403 41404 1404 41405 1405 41406 1406 41407 1407 41408 1408 41409 1409 41410 1410 41411 1411 41412 1412 41413 1413 41414 1414 41415 1415 41416 1416 41417 1417 41418 1418 41419 1419 41420 1420 41421 A-B FILE (DECIMAL) DESCRIPTION (NOTE 4) 68-00-6c RTD Sensor Error Reserved 29-01-7b Breaker Open SW Pressed 29-01-7c Breaker Contact Status Reserved Reserved Non-Volatile All Non-Volatile Enum Error Non-Volatile Number Error Non-Volatile String Error Non-Vol. Event Record Error Non-Volatile Thermal Error Operator Interface Error Circuit diagnostic Network Comm Error Remote Trips 64-14-07 Reversepower 64-14-7C Undertemperature OBJECT 6a-1-1 6a-1-2 6a-1-3 6a-1-4 6a-1-5 6a-1-6 6a-1-7 6a-1-8 6a-1-9 6a-1-A 6a-1-B 6a-1-C 6a-1-D 6a-1-E 6a-1-F 6a-1-10 6a-1-11 6a-1-12 6a-1-13 6a-1-14 6a-1-15 8:0 8:1 8:2 8:3 8:4 8:5 8:6 8:7 8:8 8:9 8:10 8:11 8:12 8:13 8:14 8:15 8:16 8:17 8:18 8:19 8:20 User Register 0 User Register 1 User Register 2 User Register 3 User Register 4 User Register 5 User Register 6 User Register 7 User Register 8 User Register 9 User Register 10 User Register 11 User Register 12 User Register 13 User Register 14 User Register 15 User Register 16 User Register 17 User Register 18 User Register 19 User Register 20 ACCESS RANGE TYPE Read Only T3 Read Only Read Only T3 T3 Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 Appendix E, Communications Database Table Page E-19 Rev. 1-C-031615 FPS Feeder Protection System FPS MODBUS REGISTER REGISTER OBJECT (DECIMAL) (DECIMAL) 1421 41422 6a-1-16 1422 41423 6a-1-17 1423 41424 6a-1-18 1424 41425 6a-1-19 1425 41426 6a-1-1A 1426 41427 6a-1-1B 1427 41428 6a-1-1C 1428 41429 6a-1-1D 1429 41430 6a-1-1E 1430 41431 6a-1-1F 1431 41432 6a-1-20 User Defined Register Data 1432 41433 1433 1434 1435 1436 1437 1438 1439 1440 1441 1442 1443 1444 1445 1446 1447 1448 1449 1450 1451 1452 1453 1454 1455 1456 1457 1458 1459 1460 1461 1462 1463 41434 41435 41436 41437 41438 41439 41440 41441 41442 41443 41444 41445 41446 41447 41448 41449 41450 41451 41452 41453 41454 41455 41456 41457 41458 41459 41460 41461 41462 41463 41464 A-B FILE (DECIMAL) (NOTE 4) 8:21 8:22 8:23 8:24 8:25 8:26 8:27 8:28 8:29 8:30 8:31 DESCRIPTION ACCESS User Register 21 User Register 22 User Register 23 User Register 24 User Register 25 User Register 26 User Register 27 User Register 28 User Register 29 User Register 30 User Register 31 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W 9:0 User Register 0 Data Read Only 9:1 9:2 9:3 9:4 9:5 9:6 9:7 9:8 9:9 9:10 9:11 9:12 9:13 9:14 9:15 9:16 9:17 9:18 9:19 9:20 9:21 9:22 9:23 9:24 9:25 9:26 9:27 9:28 9:29 9:30 9:31 User Register 1 Data User Register 2 Data User Register 3 Data User Register 4 Data User Register 5 Data User Register 6 Data User Register 7 Data User Register 8 Data User Register 9 Data User Register 10 Data User Register 11 Data User Register 12 Data User Register 13 Data User Register 14 Data User Register 15 Data User Register 16 Data User Register 17 Data User Register 18 Data User Register 19 Data User Register 20 Data User Register 21 Data User Register 22 Data User Register 23 Data User Register 24 Data User Register 25 Data User Register 26 Data User Register 27 Data User Register 28 Data User Register 29 Data User Register 30 Data User Register 31 Data Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only Read Only RANGE TYPE T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 T3 Range and Type defined by user register value Appendix E, Communications Database Table FPS Feeder Protection System Page E-20 Rev. 1-C-031615 NOTES: (1) The A-B File is coded as FILE:ELEMENT. To read or write the element as floats, the PLC-5 or SLC 500 address would be <F><FILE>:<ELEMENT> (Example F9:222). To read or write the element as integers using PLC-5 Typed Read and Typed Write commands, add 20 to the file number and precede with N, <N><FILE+20>:<ELEMENT> (Example N29:222). File offset not required for SLC 500 Protected Typed Logical read and write commands. (2) Undefined registers in this table read zero. Registers greater than 1463 return error. (3) The following MPS-RTD error codes are supported: -100 = No RTD Sensor -90 = Open Sensor -80 = Shorted Sensor -70 = No Data/Module Communication Error (4) The A-B File is coded as FILE:ELEMENT. To read or write the element as floats, the PLC-5 or SLC 500 address would be <F><FILE>:<ELEMENT> (Example F9:222). To read or write the element as integers using PLC-5 Typed Read and Typed Write commands, add 20 to the file number and precede with N, <N><FILE+20>:<ELEMENT> (Example N29:222). File offset not required for SLC 500 Protected Typed Logical read and write commands. Appendix E, Communications Database Table Page F-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX F REGISTER FORMATS TYPE T1 C TYPE Float DESCRIPTION IEEE 32-Bit Floating-Point Number Bit 31: Sign Bits 30..23: Exponent Bits 22..0: Mantissa Float (high): Bits 31..16 Float (low): Bits 15..0 T2 Long 32-Bit Integer (High) Bits 31..16 (Low) Bits 15..0 T3 Short 16-Bit Integer T4 Double IEEE 64-Fit Floating-Point Number Bit 63: Sign Bits 62..52: Exponent Bits 51..0: Mantissa Word 1 (Least Significant Word) … Word 4 (Most Significant Word) T6 Short Enable/Disable 0: Enabled 1: Disabled T9 Short Voltage-Connection Type 0: No Voltage Input 1: 1PT 2: 2PT 3: 3PT and Direct Connection T10 Short Frequency 0: 50 Hz 1: 60 Hz T14 Short Relay Mode 0: Fail Safe 1: Non Fail Safe T16 Short Network Communication Type 0: None (Disabled) 1: A-B DF1 2: Modbus RTU 3: AnyBus 4: DeviceNet 5: Modbus TCP Appendix F, Register Formats FPS Feeder Protection System Page F-2 Rev. 1-C-031615 TYPE T17 C TYPE Short DESCRIPTION Network Baud Rate 0: 1.2 kbit/s 1: 2.4 kbit/s 2: 4.8 kbit/s 3: 9.6 kbit/s 4: 19.2 kbit/s 5: DeviceNet 125 kbit/s 6: DeviceNet 250 kbit/s 7: DeviceNet 500 kbit/s T18 Short Error Checking (AB DF1 Only) 0: Not Selected 1: CRC Check 2: BCC Check T20 Short RTD Type 0: Disable 1: Platinum 100 2: Nickel 100 3: Nickel 120 4: Copper 10 T22 Char 20 ASCII characters Register +0: Char[0] and Char[1]. Char [0] at MSByte Register +1: Char[2] and Char[3]. Char [2] at MSByte Register +2: Char[4] and Char[5]. Char [4] at MSByte Register +3: Char[6] and Char[7]. Char [6] at MSByte Register +4: Char[8] and Char[9]. Char [8] at MSByte Register +5: Char[10] and Char[11]. Char [10] at MSByte Register +6: Char[12] and Char[13]. Char [12] at MSByte Register +7: Char[14] and Char[15]. Char [14] at MSByte Register +8: Char[16] and Char[17]. Char [16] at MSByte Register +9: Char[18] and Char[19]. Char [18] at MSByte A character value of 0 (NULL) will terminate the string and the following characters will be ignored. Ethernet address strings are of the form: “ddd.ddd.ddd.ddd”. The MAC address is a hex string of the form: “hhhhhhhhhhhh”. T23 Long Date Bits 31..16: Year in Binary Bits 15..8: 1-12 Months in Binary Bits 7..0: 1-31 Days in Binary T24 Long Time Bits 31..24: 0-23 Hours in Binary Bits 23..16: 0-60 Minutes in Binary Bits 15..8: 0-60 Seconds in Binary Bits 7..0: 0-99 Hundredths of Seconds in Binary Appendix F, Register Formats FPS Feeder Protection System TYPE T31 C TYPE Char DESCRIPTION RTC ASCII Character Setting String: Format: YY/MM/DD HH:mm:SS YY: 2-digit Year (Year 2000 - 2099) MM: Month 1-12 DD: Day 1-31 HH: Hour 0-23 mm: Minute 0-59 SS: Seconds 0-59 RTC is updated when “Set RTC” command is issued. T32 Short Free Record Pointer Subtract 1 to obtain last record. Range is 0 to 63. T33 Short Thermal Model Type 0: NEMA 1: K-Factor T38 Short Overload Reset Type 0: Normal 1: Auto Reset 2: Rapid T42 Short Trip Action 0: Disabled 1: Trip1 2: Trip2 3: Trip3 4: Trip1 & Trip2 5: Trip1 & Trip3 6: Trip1 & Trip2 & Trip3 7: Trip2 & Trip3 T43 Short Alarm Action 0: Disabled 1: Alarm1 2: Alarm2 3: Alarm3 4: Alarm1 & Alarm2 5: Alarm1 & Alarm3 6: Alarm1 & Alarm2 & Alarm3 7: Alarm2 & Alarm3 Page F-3 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T67 C TYPE Short DESCRIPTION Trip and Alarm Summary Bit 0 .. Bit 3: 0 Bit 4: 1 = Trip1 Bit 5: 1 = Trip2 Bit 6: 1 = Trip3 Bit 7: 1 = Alarm1 Bit 8: 1 = Alarm2 Bit 9: 1 = Alarm3 Bit 10 .. Bit 15: 0 T73 Short Inverse Time Curve 0:IEC Normal Inverse A 1:IEC Very Inverse B 2:IEC Extreme Inverse C 3:IEC Short Inverse A 4:IEC Long Inverse B 5:IEEE Moderate Inverse 6:IEEE Very Inverse 7:IEEE Extreme Inverse T80 Short Record Type 0: Empty Record 1: Trip Record 3: ETR Record T81 Short Set Point Group 0: Group 1 1: Group 2 T84 Short DeviceNet Producing Instance 0: None 1: 0x32 Basic Overload 2: 0x33 Extended Overload 3: 0x34 Basic Motor Starter 4: 0x35 Extended Motor Starter 1 5: 0x64 User Registers T85 Short DeviceNet Consuming Instance 0: None 1: 0x02 Basic Overload 2: 0x03 Basic Motor Starter Page F-4 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T86 C TYPE Short Page F-5 Rev. 1-C-031615 DESCRIPTION Digital Input Function 0: None 1: Group2 Settings 1: Group 2 Set Points Active 0: Group 1 Set Points Active 2: Local Control 1: Local Control Mode Enabled 0: Local Control Mode Disabled 3: Permissive 1: Close is Allowed 0: Close is Not Allowed 4: 3-W Close 1: Close (Momentary) 0: No Close Action 5: 2-W Close 1: Close (Sustained) Any other Open signal causes a trip. 0: Open 6: 3-W Close Local 1: Close (Momentary). 3-Wire, only enabled in LOCAL. 0: No Close Action 7: 2-W Close Local 1: Close (Momentary). 3-Wire, only enabled in LOCAL. 0: No Close Action 8: 52a Close Status 1: Status contact closed when device is closed. 0: Status contact open when device is open. 9: 52b Open Status 1: Status contact closed when device is open. 0: Status contact open when device is closed. 10: UV Coil Supervision RESERVED 10 See description in manual. 11: SH Coil Supervision RESERVED 11 Input signal requirement is defined by coil-sensing setting. 12: Close Supervision RESERVED 12 Input signal requirement is defined by coil-sensing setting. 13: Interlock 1: Close is Allowed 0: Close is Not Allowed 14: Trip1 1: Input is Valid, No Trip 0: Trip (Trip Delay Active). Trip Bypass Available. 15: Reset 16: Positive Edge Record Trigger 17: Negative Edge Record Trigger 18: Transition Record Trigger 19: Control Power 1: Digital inputs updated at 50 ms intervals. 2: Digital inputs held for 500 ms. Appendix F, Register Formats FPS Feeder Protection System TYPE T87 C TYPE Short DESCRIPTION Analog Output Parameter 0: Phase Current 1: Earth Leakage 2: Thermal Capacity 3: Group A RTD 4: Group B RTD 5: Group C RTD 6: Ambient RTD 7: Voltage 8: Unbalance 9: Power Factor 10: Real Power 11: Reactive Power 12: Apparent Power 13: Zero 14: Full Scale T88 Short Number of RTD Modules 0: No RTD Module 1: 1 RTD Module T89 Short RTD Function 0: Transformer 1: Bus 2: Breaker 3: Ambient T90 Short Trip Code 0: Overload Trip, G1 1: Overload Trip, G2 2: Overload Alarm, G1 3: Overload Alarm, G2 4: Phase Inverse O/C Trip G1 5: Phase Inverse O/C Trip G2 6: Phase Timed O/C Trip G1 7: Phase Timed O/C Trip G2 8: Phase Timed O/C Alarm G1 9: Phase Timed O/C Alarm G2 10: 3Io Inverse Trip G1 11: 3Io Inverse Trip G2 12: 3Io Timed Trip G1 13: 3Io Timed Trip G2 14: 3Io Timed Alarm G1 15: 3Io Timed Alarm G2 Page F-6 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T90 C TYPE Page F-7 Rev. 1-C-031615 DESCRIPTION 16: EFCT Timed Trip G1 17: EFCT Timed Trip G2 18: EFCT Timed Alarm G1 19: EFCT Timed Alarm G2 20: Unbalance (Current) Trip 21: Unbalance (Current) Alarm 22: Phase Loss (Current) Trip 23: Phase Loss (Current) Alarm 24: Phase Reverse (Current) Trip 25: Phase Reverse (Current) Alarm 26: Unbalance (Voltage) Trip 27: Unbalance (Voltage) Alarm 28: Phase Loss (Voltage) Trip 29: Phase Loss (Voltage) Alarm 30: Phase Reverse (Voltage) Trip 31: Phase Reverse (Voltage) Alarm 32: Overvoltage Trip 33: Overvoltage Alarm 34: Undervoltage Trip 35: Undervoltage Alarm 36: Underfrequency Trip 37: Underfrequency Alarm 38: Overfrequency Trip 39: Overfrequency Alarm 40: PF Quadrant 3 Trip 41: PF Quadrant 3 Alarm 42: PF Quadrant 4 Trip 43: PF Quadrant 4 Alarm 44: Differential Trip 45: Differential Alarm 46: Analog-Input-High Trip 47: Analog-Input-High Alarm 48: Analog-Input-Low Trip 49: Analog-Input-Low Alarm 50: PTC Temperature Trip 51: PTC Temperature Alarm 52: Digital 1 Trip 53: Digital 2 Trip 54: Digital 3 Trip 55: Digital 4 Trip 56: Digital 5 Trip 57: Digital 6 Trip 58: Digital 7 Trip 59: RTD Module 1 INP 1 Trip 60: RTD Module 1 INP 1 Alarm 61: RTD Module 1 INP 2 Trip 62: RTD Module 1 INP 2 Alarm Appendix F, Register Formats FPS Feeder Protection System TYPE T90 C TYPE Page F-8 Rev. 1-C-031615 DESCRIPTION 63: RTD Module 1 INP 3 Trip 64: RTD Module 1 INP 3 Alarm 65: RTD Module 1 INP 4 Trip 66: RTD Module 1 INP 4 Alarm 67: RTD Module 1 INP 5 Trip 68: RTD Module 1 INP 5 Alarm 69: RTD Module 1 INP 6 Trip 70: RTD Module 1 INP 6 Alarm 71: RTD Module 1 INP 7 Trip 72: RTD Module 1 INP 7 Alarm 73: RTD Module 1 INP 8 Trip 74: RTD Module 1 INP 8 Alarm 75: RTD Module 1 Trip 76: RTD Module 1 Alarm 77: RTD Sensor-Failure Trip 78: RTD Sensor Failure Alarm 79: DIF Module Trip 80: DIF Module Alarm 81: Open Press Trip 82: 52a/b Status Trip 83: Trip-coil Supervision Trip 84: Close-coil Supervision Trip 85 to 93 Reserved 94: Memory Error, All Defaults Loaded 95: Memory Error, Enum 96: Memory Error, Numeric 97: Memory Error, String 98: Memory Error, Records1 99: Memory Error, Records2 100: Display Error 101: Reserved 102: Diagnostic Error (A/D) 103: Network Comm Trip 104: Network Comm Alarm 105: Remote Trip via Network 106: Remote Alarm via Network 107: Reversepower Trip 108: Reversepower Alarm 109: Undertemperature Trip 110: Undertemperature Alarm 111 to 250: Reserved 251: Positive Trigger 252: Negative Trigger 253: Transition Trigger 254: ETR Request 255: No Trip or Alarm Appendix F, Register Formats FPS Feeder Protection System TYPE T91 C TYPE Short DESCRIPTION 4-20 mA Analog Input Type 0: Metering Only 1: Generic 4-20 mA T92 Short 4-20 mA Analog Input Type 0: Metering Only 1: Protection T93 Short Digital Input and Relay Status Bit 0: Digital Input 1 Valid Bit 1: Digital Input 2 Valid Bit 2: Digital Input 3 Valid Bit 3: Digital Input 4 Valid Bit 4: Digital Input 5 Valid Bit 5: Digital Input 6 Valid Bit 6: Spare Bit 7: Spare Bit 8: Relay 1 Energized Bit 9: Relay 2 Energized Bit 10: Relay 3 Energized Bit 11: Relay 4 Energized Bit 12: Relay 5 Energized T94 Short FPS Status Bit 0: 1 = Current > Threshold Bit 1: 1 = 3Io Inverse Curve Picked Up Bit 2: 1 = Ph Inverse Curve Picked Up Bit 3: Spare Bit 4: 1 = Trip1 Bit 5: 1 = Trip2 Bit 6: 1 = Trip3 Bit 7: 1 = Alarm1 Bit 8: 1 = Alarm2 Bit 9: 1 = Alarm3 Bit 10: 1 = ETR is ON Bit 11: 1 = PTC is Open Bit 12: 1 = Interlock is Valid Bit 13: 1 = Permissive is Valid Bit 14: 1 = FPS Control Indicates Breaker Closed. Bit 15: Spare T98 Short Default Menu 0: Main 1: Summary 2: Current Page F-9 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T98 C TYPE DESCRIPTION 3: Unbalance (I) 4: Earth Leakage 5: Thermal Status 6: Voltage 7: Unbalance 8: Power 9: Energy 10: Frequency 11: RTD Temperature 12: Inverse Status 13: I/O Status 14: System Status 15: Network Status T99 Short Trigger Source 0: Empty Record 1: Trip Record 2: Digital Input Positive Edge Trigger Record 3: Digital Input Negative Edge Trigger Record 4: Digital Input Transition Trigger Record T100 Short User Programmable Indicator 0: None (LED Off) 1: Trip1 2: Trip2 3: Trip3 4: Alarm1 5: Alarm2 6: Alarm3 7: Relay1 8: Relay2 9: Relay3 10: Relay4 11: Relay5 12: Din1 13: Din2 14: Din3 15: Din4 16: Din5 17: Din6 18: Din7 19: Current Detected 20: 3Io Pickup 21: Phase Pickup 22: ETR State 23: Network Run1 24: Net Activity Page F-10 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T101 C TYPE Short DESCRIPTION FPS Communications Command 0: Open 1: Close 2: Reserved 3: Reset Trips (Not Remote/Network Trips) 4: Set RTC 5: Clear Data-Logging Records. 6: Clear Trip Counters 7: Clear Energy Totals 8: Clear running hours 9: Emergency Thermal Reset 10: Select Local Control 11: De-select Local Control 12: Re-enable Temperature Protection 13: Remote/Network Trip Set 14: Remote/Network Trip Reset 15: Remote/Network Alarm Set 16: Remote/Network Alarm Reset 17: Run1 Set 18: Run1 Clear T102 Short FPS Coil Supervision Sense Location T103 Short Breaker Control Type T104 Short Breaker Trip Source 0: Disabled 1: Trip1 2: Trip2 3: Trip3 4: Trip1 or Trip2 5: Trip1 or Trip3 6: Trip1 or Trip2 or Trip3 7: Trip2 or Trip3 T105 Short Differential Module Number 0: Disabled 1: One DIF Module Page F-11 Rev. 1-C-031615 Appendix F, Register Formats FPS Feeder Protection System TYPE T106 C TYPE Short T107 Short T108 Short Page F-12 Rev. 1-C-031615 DESCRIPTION Output Relay Function 0: None (Relay De-Energized) 1: Trip1 2: Trip2 3: Trip3 4: Alarm1 5: Alarm2 6: Alarm3 7: CB Close 8: CB Open 9: Contactor 10: Trip1 Pulse 11: Local 12: Interlock 13: Current 14: Network Run1 15: Group2 16: Watchdog Breaker Open Retry Count 0: No Retry 1: 1 Retry 2: 2 Retries 3: 3 Retries 4: 4 Retries 5: 5 Retries RTD Undertemperature 0: +20°C 1: +15°C 2: +10°C 3: +5°C 4: 0°C 5: -5°C 6: -10°C 7: -15°C 8: -20°C NOTES: (1) All values are actual numbers unless indicated by “Bitx”. (2) Not a trip code. Used by event records to indicate a start record type. Appendix F, Register Formats Page G-1 Rev. 1-C-031615 FPS Feeder Protection System APPENDIX G FPS REVISION HISTORY MANUAL RELEASE DATE G.1 FPS-CTU REVISION HISTORY HARDWARE MANUAL REVISION(1) REVISION (REVISION NUMBER ON PRODUCT LABEL) March 16, 2015 1-C-031615 December 1, 2014 1-B-120114 June 19, 2014 1-A-061914 November 16, 2011 00 FIRMWARE REVISION 1.13 01A 1.12 1.10 00B 01 1.05 00A, 01 1.04 1.03 00A 1.02 00, 00A (1) 1.01 At time of release. MANUAL REVISION HISTORY REVISION 1-C-031615 APPENDIX G Updated revision history. REVISION 1-B-120114 SECTION 2 Figs. 2.5 and 2.6 updated. APPENDIX G Updated revision history. REVISION 1-A-061914 SECTION 1 Reversepower, RTD overtemperature, and RTD undertemperature features added. SECTION 5 Reversepower (5.16) and RTD undertemperature (5.23) sections added. SECTION 6 Retries explanation added. APPENDIX A Reversepower, undertemperature and open retry added to menu levels. APPENDIX B Reversepower, undertemperature, and RTD sensor trip and alarm actions added to set-up record. Part III Control added. APPENDIX E Reversepower, undertemperature and breaker open retry added to communication database table. APPENDIX F Reversepower, undertemperature and breaker open retry count added to register formats table. APPENDIX G Added revision history. REVISION 0 Initial release. Appendix G, FPS Revision History FPS Feeder Protection System Page G-2 Rev. 1-C-031615 HARDWARE REVISION HISTORY HARDWARE REVISION 01A Updated opto-coupler relay drive circuit and RTC battery. HARDWARE REVISION 01 Power supply updated. HARDWARE REVISION 00B Updated opto-coupler relay drive circuit and RTC battery. HARDWARE REVISION 00A Processor module memory size increased. HARDWARE REVISION 00 Initial release. FIRMWARE REVISION HISTORY FIRMWARE REVISION 1.13 Corrected current and voltage unbalance error. FIRMWARE REVISION 1.12 Corrected earth-fault and overcurrent inverse-time error. FIRMWARE REVISION 1.10 Added reversepower, RTD undertemperature, and breaker-open retry. Loss of communication trip increased to 10 s. FIRMWARE REVISION 1.05 Added capability to initiate firmware updates using FPS-OPI. FIRMWARE REVISION 1.04 Breaker open time no longer truncated by open status indication. FIRMWARE REVISION 1.03 Fixed RTD reading for unused RTD’s. FIRMWARE REVISION 1.02 Fixed EtherNet/IP issue with Explicit Messaging. FIRMWARE REVISION 1.01 Added support for alternate DeviceNet controller. FIRMWARE REVISION 1.00 Added delay to digital input assigned to Control Power. FIRMWARE REVISION 0.01 Initial release. Appendix G, FPS Revision History Page G-3 Rev. 1-C-031615 FPS Feeder Protection System MANUAL RELEASE DATE G.2 FPS-OPI REVISION HISTORY HARDWARE REVISION MANUAL (REVISION NUMBER REVISION ON PRODUCT LABEL) December 1, 2014 1-B-120114 June 19, 2014 1-A-061914 FIRMWARE REVISION 00 1.60 HARDWARE REVISION HISTORY HARDWARE REVISION 00 Initial release. FIRMWARE REVISION HISTORY FIRMWARE REVISION 1.60 Firmware update to support new display and equivalent LCD version. MANUAL RELEASE DATE G.3 MPS-RTD REVISION HISTORY FPS MANUAL PRODUCT REVISION REVISION (REVISION NUMBER ON PRODUCT LABEL) December 1, 2014 1-B-120114 June 19, 2014 1-A-061914 02 PRODUCT REVISION HISTORY PRODUCT REVISION 02 New analog PWB and power supply PWB. Increased accuracy. Wider input voltage range. Appendix G, FPS Revision History FPS Feeder Protection System Page G-4 Rev. 1-C-031615 This page intentionally left blank. Appendix G, FPS Revision History