Manual Download

For speed control of 3-phase induction motor
Inverter M1X Series
Operating Instructions
Be sure to provide the customer with a copy of this manual.
● Thank you for purchasing a Panasonic Inverter.
● Be sure to read the instructions thoroughly before attempting to operate the
inverter. After reading, be sure to keep in a safe place for future reference.
Industrial and Appliance Motor Division, Motor Company
Matsushita Electric Industrial Co., Ltd
CONTENTS
Before use
Safety Precaution・・・・・・・4
Introduction ・・・・・・・・・・・・8
● When unpacking・・・・・・・・・・・・・8
● Inverter model check ・・・・・・・・・8
System Configuration・11
Preparation and
adjustment
● Wiring general view ・・・・・・・・・ 11
● Wiring ・・・・・・・・・・・・・・・・・・・・・ 12
● Terminal function ・・・・・・・・・・・ 13
● Precautions when wiring ・・・・ 15
Protective Function・・・ 18
If necessary
● Protective functions ・・・・・・・・・ 18
● Method of resetting trip・・・・・・ 20
Application
Detailed Explanation ・・23
of Parameters
● Parameter functions ・・・・・・・・23
Specifications
Specifications ・・・・・・・・37
Outer Dimensions ・・・・39
- 2 -
Precautions ・・・・・・・・・・・ 9
Installation ・・・・・・・・・・ 10
● Note the following ・・・・・・・・・・・・9
● Inverter・・・・・・・・・・・・・・・・・
・・・・・・・・・・・・・・・・・ 10
precautions in order to use
Preparation and
Adjustment
the inverter properly
Before use
CONTENTS
Parameter Setting ・・・・16
・・・・
● How to set ・・・・・・・・・・・・・・・・16
Troubleshooting ・・・・・22
・・・・・ 22
● Inspection to determine ・・・・22
Application
cause of problem
If necessary
準備と調整
Maintenance/ ・・・・・・・・ 21
Inspection
Specifications
Parameter Setting ・・・ 41
● Parameter overview ・・・・・・・・41
● Parameter configuration ・・・・41
and list of parameters
- 3 -
Safety Precautions
Precautions that must be heeded in order to protect the user and others from harm and
prevent property loss or damage are as follows:
■ The extent of injury or damage that could be suffered by improper
use contrary to directions is ranked and explained as follows:
! DANGER
Situation involving danger which could result in death or serious
injury if equipment is handled incorrectly.
! CAUTION
Situation involving danger which could result in medium to light
injury, or property damage if equipment is handled incorrectly.
Items labeled as ! CAUTION could be connected with core serious consequences,
depending upon the circumstances. In any case, these instructions are extremely important
and should be observed in all cases.
■ Installation
! CAUTION
● Install on non-combustible material such as metal.
Failure to do so could result in fire.
● Do not locate near combustibles.
Doing so could result in fire.
● Do not carry by the front case when moving the inverter.
Doing so is dangerous and could result in injury if dropped.
● Do not allow foreign material such as metal chips to get inside the inverter.
Doing so could result in fire.
● Be sure to install on a base capable of supporting the inverter’s weight in
accordance with the directions giving in the instruction manual.
Doing so is dangerous and could result in injury if dropped.
- 4 -
Safety Precautions
■ Wiring
! DANGER
● Make sure the power is cut off before handling wiring.
Failure to do so could result in electrical shock or fire.
● Be sure to install a no-fuse breaker (NFB).
Failure to do so could result in fire.
● Be sure to ground the GND terminal.
Failure to do so could result in electrical shock or fire.
● Have wiring work done by an electrician.
Failure to do so could result in electrical shock or fire.
● Be sure to install the inverter before wiring.
Failure to do so could result in electrical shock or fire.
! CAUTION
● Do not connect the AC power source with the output terminals (U/L1, V/L2, W/L3).
Doing so could result in injury or fire.
● Make sure the voltage of the AC power source agrees with the rated voltage of the
inverter.
If not, it could result in injury or fire.
- 5 -
Safety Precautions
■ Operation
! DANGER
● Be sure to mount the case and cover before turning the power on. Never remove
the case or cover while the inverter is receiving power.
Failure to mount or removing the case/cover could result in electric shock.
● The operator should secure the area before turning the power on or off.
Failure to do so could result in injury.
● Never operate the switches with wet hands.
Doing so could result in electric shock.
● Never touch the terminals of the inverter when it is charged with power, even when
it is not running. Doing so could result in electric shock.
● If the retry function is selected, the inverter could unexpectedly start operating
again if tripped. Do not approach the inverter in the condition.
Doing so could result in injury.
● If trip reset is carried out with the operate signal ON, the inverter could
unexpectedly start operating again. Do not approach the inverter in the condition.
Doing so could result in injury.
! CAUTION
● The radiator and regenerative resistor become very hot.
Touching these parts could result in skin burning injury.
● It is very easy to set speed from "low" to "high" by an inverter. Set the operating
speed so that it the motor and machine tolerance is not exceeded.
Failure to do so could result in injury.
- 6 -
Safety Precautions
■ Maintenance/inspection
! DANGER
● Wait for at least 5 minutes after turning off the power to perform inspections.
Failure to do so could result in electric shock.
● Maintenance and inspection should not be performed by anyone except a
specialist.
The repairman should remove all metallic objects (watch, rings, etc.) before
performing maintenance or inspection.
Use only insulated tools when performing maintenance or inspection.
Failure to do so could result in electric shock or injury.
■ Other
! DANGER
● Absolutely DO NOT modify the inverter in any way.
Doing so could result in electric shock, injury or fire.
GENERAL PRECAUTIONS
The diagrams given in this instruction manual may show the cases, covers or safety
breakers removed in order to show details.
When operating, be sure to return the cases, covers or safety breakers and operate
as specified in the manual.
- 7 -
Introduction
When unpacking
・Is the model correct?
・Was the equipment damaged in transport?
If there is anything wrong with the equipment, contact your Panasonic
dealer.
Inverter model check
Nameplate
M1SO83CSA
MIXA54ASA
Mo del No
Power
Input
15kW
3PH AC 380∼460V
37A
3PH AC 380∼460V
32A
Output
Ser.No.
50/60Hz
0∼400Hz
9903012
Matsushita Electric Industrial Co., Ltd. Made in Japan
Product No.
M1X
A5
4 B S A
Code
A
Series name
C
Code
Motor capacity
08
15
22
37
55
75
A1
A5
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW
11 kW
15 kW
Code
4
Voltage class
3-phase
Interface specs.
Without communication function/
standard type (NPN logic)
With communication function/
standard type (NPN logic)
Code
Operation panel specs.
S
V
N
Without set volume (standard)
With speed-set volume
Blank cover
Code
Regenerative brake specs.
A
B
Without regenerative brake circuit
With regenerative brake circuit (built-in)
400 V
Consult your Panasonic dealer regarding products with communication functions.
- 8 -
Precautions
Note the following precautions in order to use the inverter properly.
1.
Arrange for the power source capacity to be between 1.5 to 500kVA the inverter's
capacity. An excessively high peak current may flow to the power input circuit, and
damage the converter section if the wiring length is short with a power source
exceeding 500kVA, or the phase-advancing capacitor is switched on the power
source side. In this case, provide individual power factor-enhancing AC reactors that
match the inverter's capacity on the inverter input side.
2.
Do not connect the phase-advancing capacitor to the output side of the inverter. Doing
so could result in damage to the phase-advancing capacitor.
3.
Do not provide a magnetic contactor between the inverter and motor. To run or turn
the motor on/off, use the RUN switch on the control panel or the control input terminal.
Avoid frequently turning the magnetic contactor, provided on the power source, on
and off.
4.
Operating the motor by the inverter could increase leakage current and trip the earth
leakage breaker. In this case, use earth leakage breakers designed for high frequency
for this system and other systems.
5.
Take the following precautions if using a built-in electronic thermal relay contained in
the inverter:
・ Check the rated current of your 3-phase induction motor, and set the appropriate
electronic thermal value.
・ Use one motor for each inverter.
6.
in using the inverter to drive multiple motors connected in parallel, select an inverter of
a capacity that does not exceed the total rated current of the inverter. When
calculating by total output of the motor, the inverter’s rated current may be exceeded,
depending on the type of motor.
7.
The total wiring length between inverter and motor should not exceed 30 meters. If the
wiring is to be longer than this, you should provide a reactor, etc., between inverter
and motor.
8.
Install the inverter securely to avoid injuries in the case of an earthquake.
9.
Before running the inverter following an earthquake, check installation of the inverter
and motor and make sure they are safe to operate.
- 9 -
Installation
Install the inverter properly to prevent equipment failure or accidents.
Inverter
Installation location
① Install the inverter indoors in a place not exposed to rain or direct sunlight. The inverter
is not waterproof.
② Install in a place not exposed to corrosive/flammable gases, grinding fluid, oil mist, metal
powder or chips.
③ Place with adequate ventilation, which is not exposed to excessive humidity, dirt or dust.
④ Place not subject to vibration.
Environmental conditions
Item
Conditions
−10 ∼ 50℃ (Must not freeze)
Ambient temperature
When ambient temperature is higher than +40℃, the air
apron and the linear rubber apron should be disassembled
Ambient humidity
Max. 90%RH(Must be no condensation)
Storage temperature
−20℃ ∼ 65℃ (Must not freeze)
Storage humidity
Max. 90 %RH(Must be no condensation)
Vibration
Max. 5.9 m/s2(10 ∼ 60Hz)
Elevation
Max. 1000 m
* Short-term temperature during transport
Mounting direction and clearance
・ Provide sufficient clearance for effective cooling.
Min. 200 mm
30 mm
×
Min.
100 mm
Upper
Upper
Upper
M1X
M1X
M1X
Lower
Min.
50 mm
Lower
Min.
50 mm
× 30 mm
Lower
30 mm
×
Min.
100 mm
Min.
100 mm
Make sure ambient temperature doesn’t exceed allowable temperature at position indicated
by X in the figure above.
- 10 -
System Configuration and Wiring
Wiring general view
Main circuit
No-fuse breaker (NFB)
or Earth leakage breaker
Used to protect the power line.
Interrupts the circuit in the case of excessive
current.
Noise filter (NF)
Blocks noise from the power line.
Also reduces effect of noise from the servomotor.
Magnetic contactor (MC)
Turn main power to servomotor on/off.
Used with surge absorber mounted.
Reactor (L)
Reduces harmonic current of the power source.
Inverter
DC reactor
GND
Motor
- 11 -
System Configuration and Wiring
Wiring
Standard wiring diagram
External feedback resistor
(5.5 kW-11kW only)
Those lower than 3.7 kW and 15Kw
have no terminals for feedback resistor
External frequency setting volume
1/4W, 5kΩ, B characteristic
Frequency meter
1mA (full scale)
P PB
R/L1
S/L2
T/L3
5V
FIN1
G
FOUT
③ ②
①
Forward/stop switch
Reverse/stop switch
Frequency setting selection (1)
Frequency setting selection (2)
Free-run
Trip reset*
Ground for control
trip output*
(Collector)
O2
Reach-signal*
COM1 (Emitter)
12V
PLC
I1
I2
I3
I4
I5
16
G
Be sure to provide proper treatment
for the shielded wire terminals.
IM
O1 (Collector)
▽
▽
Note1)
Motor
U/T1
V/T2
W/T3
GND terminal
NFB
Power source 3-phase
AC380∼460V
50/60Hz
VCE max.=DC24V
IC max.=50mA
NC
COM2
NO
Trip signal
Contact capacity
AC30V 2A
DC30V 2A
E (Frame ground)
Be sure to ground
Asterisk (*) indicates factory-set function.
Note 1) PLC terminals and 12V terminals connected, it is called synchronized input circuit.
PLC terminals and G terminals connected, it is called power input circuit.
- 12 -
System Configuration and Wiring
Terminal function
Not used
↓
(1) Main circuit terminal
E
R/L1 S/L2 T/L3 U/T1 V/L2W/L3 E
E E
R/L1 S/L2 T/L3 P
750W∼3700W
R/L1 S/L2 T/L3
P
N
U/T1 V/T2 W/T3
15kW
Terminal No.
Terminal
name
Function description
Power
Connect to commercial power source
R/L1, S/L2, T/L3 source input
(3-phase 380-460V 50/60 Hz)
terminal
U/T1, V/T2, W/T3
Output
terminal
Connect to 3-phase induction motor
E
GND
terminal
Terminal for grounding inverter base
P
P terminal
(+) terminals for the recitification part
N
N terminal
(-) terminals for the recitification part
PB terminal
Terminals for external feedback resistor.
Connect the resistor between P and PB.
PB
U/T1 V/T2W/T3
5.5kW∼11kW
Not used
↓
E E
PB
- 13 -
System Configuration and Wiring
(2) Control terminal
COM2 NC
NO
01 02 F1N1 F1N2 FOUT I2 I4 I6 12V
COM1 12V PLC G
I1 I3 I5
G
5V
Terminal No. Terminal name
5V
Power source
terminal for frequency setting
+ 5VDC applied.
12V
External power
terminal
+ 12VDC applied.
The common terminal used for contact input of external power is used.
When power is on (PLC and G connected), a closed terminal in ON,
and an open one, OFF
FIN1
FIN2
G
Input terminal
FOUT
Input terminal
for frequency
setting
Frequency can be set when 0 ~ +5VDC (or 0 - +10VDC) is input
between “FIN1” and “G”, or 4-20mA between "FIN2"-G. If both are input,
the bigger will be pick up.
If using these terminals, change “
−
−
or
.
frequency command” to
Ground for
control
Common ground terminal for contact input. The common terminal used
for contact input of synchronized input is used. When power is on (PLC
and 12V connected), a closed terminal in ON, and an open one, OFF.
Frequency
meter terminal
Outputs voltage proportional to output frequency between “FOUT” and
“G.” Connect full-scale 1 mA DC ammeter. You can output pulses
FOUT switch”.
synchronized with output frequency by altering “
I1
Forward/stop
command
terminal
I2
Reverse /stop
command
terminal
Forward by shorting between “I1” and “G”; stop by release
Reverse by shorting between “I2” and “G”; stop by release
You can change “I1” to run/stop command and “I2” to forward/reverse
I1.12” function selection.
command by altering“
You can select the following functions in operation mode.
I3
I4
I5
Frequency
setting
selection
terminal
I6
G
O2
I4
Reverse
jogging
Frequency setting
selection
I5
Select from among
free-run, external forced
trip, No. 2 acceleration/
deceleration, trip reset
Output signal
terminal
Open-collector output terminal. (Not maintained when power is OFF.)
output signal (1) selection.”
You can select contents by “
Factory setting: “01” is trip signal (transistor ON when tripped)
“O1” (collector) IC max. = 50mA
“C1” (emitter) VCE max. = 24VDC
Output signal
terminal
Relay output terminal. 30VDC 1A (max.)
(Not maintained when power is OFF.)
relay output polarity selection.”
You can select output contents by “
Not built-in to products without regenerative brake circuit.
NC
COM2
4-speed operation mode
8-speed operation mode
16-speed operation mode
I3
Forward
jogging
Contact input common ground terminal.
COM1
NO
Operation mode
2-speed operation mode
Ground for
control
O1
Output terminal
Function description
- 14 -
System Configuration and Wiring
Precautions when wiring
Main circuit
(1) The inverter will be damaged if you invert the connections of the power input terminal
and motor output terminal (U/L1, V/L2 ... W/L3). Absolutely do not invert connections.
(2) Do not ground the main circuit terminal.
(3) Do not short motor output terminals (U/L1, V/L2 ... W/L3) together.
(4) The GND terminal (E) is the frame ground (FG) for the inverter.
(5) Be sure to use insulated crimp terminals for connecting to the main circuit terminals.
Control circuit
(1) Do not apply more than 24VDC, 50mA to the output terminals (O1, O2, −COM1), or
apply voltage to terminal in reverse.
(2) Input terminal configuration is shown in the following figure.
You can control by contact or by open collector output. Do not apply external voltage.
Internal circuits are as follows:
Photo coupler
Inverter internal power source
+12V
I1∼I6
GND
(3) Do not short the frequency setting power source terminal (5V) and ground for control
terminal (G).
(4) To directly drive the relay by the output terminals (O1, O2, −COM), mount a flywheel
diode (FD).
C1 O1/O2
FD(100V 1A)
<Examples>
RY
Fuji Electric ERA15-01
ERB12-01
Pay attention to polarity of diode.
(5) Use shielded wires for the cable to be connected to the control circuit.
- 15 -
Parameter Setting
How to set
Operation Panel
r/min
Hz
A
V
5-digit LED
2-digit LED
RUN
DATA
SET
MODE
^
^
STOP
Frequency Hz is displayed when in the normal monitor mode.
You can display synchronized rotations for the parameter "
display power."
5-digit LED
Displays output frequency, set frequency or display power, cause of error, or
parameter.
2-digit LED
Displays parameter No. Direction of rotation is displayed in the monitor mode.
MODE
button
DATA SET
button
Switch for changing monitor mode. Pressing the switch changes the mode in the
cycle of:
Output frequency Rectificated Motor current
Switch for selecting parameter No. mode and parameter value mode, setting
parameter value.
●
△
▽
button
RUN
button
STOP
button
Mode description
Monitor
mode
Displays output frequency, rectificated voltage or motor current.
Mode when the power is turned on.
When in the parameter No. mode or parameter value mode,
pressing the MODE switch changes to the monitor mode.
Parameter
No. mode
)by flashing.
Displays parameter No.(
∼
When in the monitor mode, pressing the DATA SET
changes to the parameter No. mode.
Parameter
value mode
Displays parameter contents (setting value) by flashing.
You can change the setting value with the △
▽ switches.
After changing the setting, press the DATA SET switch to
enter the setting in the memory.
Enable you to select parameters, and set/change contents.
Commands the inverter to run.
Commands the inverter to stop.
- 16 -
switch
Parameter Setting
Power ON
Push
DATA SET
Monitor mode
Push
MODE
Push
Parameter
number mode
Output frequency
Push
Push
DATA SET
DATA SET
Parameter
value mode
MODE
MODE
Rectificated voltage
Push
MODE
MODE
Motor current
Display
LED used to show
parameter number in
parameter number display
Use
△
▽
to set or Use
△
change set speed of speed 0.
parameter
▽
- 17 -
LED used to show
parameter value in
parameter number display
to select Use
△
value
▽
to select
Protective Function
Protective functions
The protective functions classified as shown below are built-in the inverters of this series.
① Functions that do not display a warning, but act to avoid a tripping of the system.
② Functions that display a warning and shut off inverter output.
③ Functions that trip the inverter. (Trip signal cannot be retained when the power is
turned off.)
Classification
5-digit LED display
Electronic thermal
relay operation
①
Description of protection
Countermeasures, etc.
Monitor display flashes when output Electronic thermal relay trip.
current reaches the electronic thermal Be careful of the size of the
relay level and the timer operates.
load when using.
(Monitor)
(Flashes)
Acceleration/
deceleration stall
prevention
(no display)
②
Prevents tripping when acceleration/ Increase acceleration/
deceleration time becomes too long in deceleration time or
the following situations:
decrease inertia load.
・ DC voltage of the rectificated part
exceeds approx. 775V.
・ Motor current exceeds inverter’s
current limit operation point.
Insufficient voltage
warning
Instantaneous
power failure
protection
③
If DC voltage of the rectificated part Investigate the wiring and
drops below approx. 360V, it is power source information.
regarded as “instantaneous power
failure,” and inverter output is shut off.*1
If it drops below approx. 300V, the
control circuit is reset. If voltage is
restored by the time the control circuit
is reset, operation can be restarted
automatically.*2
Reverse prevention Selecting the reverse prevention Check if the reverse
*3
function prevents reverse operation if command has been given.
the inverter receives a reverse signal.
Restart prevention
when power is
restored *2
Prevents the inverter from restarting After
commanding
the
automatically if already given the run inverter to stop, command it
command when power is turned, to run again.
restored following power failure or
reset.
*1
The inverter will operate correctly if power failure does not exceed approx. 15ms.
*2
Prevents the inverter from restarting automatically if “
restart prevention when power is restored” is selected for
.
*3
Effective only when “
reverse prevention” is selected for
- 18 -
.
Protective Function
Classification
④
5-digit LED display
Description of protection
Countermeasures, etc.
Over-current trip
Trips if inverter output current Possible causes include drop in
exceeds the rated current approx. power source voltage, excessive
by 200%.
GD2 load, acceleration/
deceleration time is set too short,
load short, or grounding. Take the
proper measures to determine
the cause.
Regenerative overvoltage trip
Trips if DC voltage of the If it trips while the inverter is
converter rises above approx. running, deceleration time could
800V.
be too short. Try setting
deceleration time longer. If it trips
when the power is turned on, the
inductance of the power-boosting
AC reactor provided on the input
side of the inverter may be too
high. Select an AC reactor that
matches the inverter capacity.
Over-voltage trip
retry when power is
turned on
If over-voltage trip occurs when
the power is turned on because
the inductance of the powerboosting AC reactor provided on
the input side of the inverter is too
is displayed
high, etc.,
The capacity of the powerboosting AC reactor provided on
the input side of the inverter may
be too large. Select a reactor that
matches the inverter capacity.
and output is shut off.
The trip is automatically reset
when DC voltage of the converter
drops below approx. 800V,
enabling normal operation.*1
*1
Over-load trip
(Electronic thermal
relay)
If motor current continues to Try reducing load, modifying
exceed the electronic thermal operating pattern, or raising
relay setting value, load is capacity of inverter.
regarded as being to high
causing the function to trip.
CPU error
Trips if a control microcomputer A malfunction caused by outside
error is detected.
noise could have occurred.
Check the area for noise and
remove the source of noise.
Effective only when “
over-voltage trip retry when power is turned on” is selected for
- 19 -
.
Protective Function
Classification
④
5-digit LED display
Description of protection
Countermeasures, etc.
There is nothing wrong with the
is equipment. The results of the
change become effective when
the trip is reset.
Self-diagnosis trip
Trips if parameter such as “
operation mode selection”
changed.
External forced trip
Trips when “
I5 function
selection” is set by external
forced trip and I5 – G becomes
open.
Cancel by trip after shorting.
Investigate the cause of overload.
Try reducing the load, changing
the operation pattern, or raising
the capacity of the inverter and
motor.
Method of resetting trip
In the event of a trip, remove the cause and cancel by one of the following methods.
[1] Turn off the inverter’s power. When the trip display disappears, turn the power
on.
[2] Short between both I1 – G and I2 – G for at least 0.1 seconds while the cause of
the current trip is being displayed.*1
[3] Press both △
▽ switches on the operation panel simultaneously for at
least 1 second while the cause of the current trip is being displayed.
[4] Input the trip reset command while the cause of the current trip is being
displayed.*2
※ A CPU error
given above.
*1
Cannot be reset if “
*2
Effective only when “
cannot be reset by methods 2, 3 or 4. Reset by method 1
I1.I2 function selection” is set to I1: Run/stop or I2: Forward/reverse.
I5 function selection” is selected for
- 20 -
.
Maintenance/Inspection
● You should perform maintenance/inspection on a regular basis in order to ensure safety
and keep the inverter in good running order.
Precautions when performing maintenance/inspections
(1) The power should be turned on/off only by the person performing the task.
(2) The internal circuits of the inverter remain charged with high voltage for a short while
after power is turned off. To perform inspection, first turn off the power and then wait for
the LED display on the front panel to go off (min. 5 minutes).
(3) Do not perform insulation resistance measurement on the inverter. Doing so will
damage the inverter.
Inspection items and environment
Ordinary/normal usage conditions
Ambient conditions: Annual mean temperature 30°C, min. 20 hrs/day at max. load rate 80%
Perform daily and periodic inspections in accordance with the following items:
Classification
Inspection cycle
Daily
inspection
Daily
Periodic
inspections
1 year
Inspection items
・Ambient temperature, humidity, dirt, dust, foreign objects, etc.
・Is there abnormal vibration/noise?
・Is main circuit voltage normal?
・Is there strange odor?
・Is there lint in the air holes?
・Cleanliness of control unit
・Is wiring damaged?
・Are equipment connections loose or off center?
・Are foreign objects lodged in at the load side?
・Are fastened sections loose?
・Is there evidence of overheating?
・Are terminal blocks damaged?
<Caution>
Inspection cycle for periodic inspections may vary if usage conditions differ from those
given above.
Approximate period for part replacement
Period for part replacement varies according to how the inverter is used. Parts must be
replaced or repaired when something is wrong with them. Under the ordinary/normal
usage conditions.
Product
name
Part name
Inverter Smoothing capacitor
Cooling fan
Standard replacement
period (hrs)
Approx. 5 years
2∼3 years
(1∼30,000 hrs)
Aluminum electrolytic Approx. 5 years
capacitor of PC board
- 21 -
Remarks
Standard replacement period gives
a number of years for reference
only. If a part becomes faulty it must
be replaced even if the standard
replacement period has not yet
been reached.
Troubleshooting
Inspection to determine cause of problem
When a problem occurs, perform the inspections and take the measures prescribed in the
following table. If you cannot determine the cause of the problem, if you suspect that the
inverter is not working properly, if a part is damaged, or there are any other problems you
cannot solve, contact your Panasonic dealer.
Problem
Description of inspection
Corrective measures, etc.
Is there anything wrong with the Wire correctly.
wiring?
Is power being supplied to the power Turn on the power.
input terminals?
Turn off the power once, and then turn
back on.
Motor doesn’t work.
Is the LED on the operation panel lit?
Recheck the above.
Is the voltage of the power input
terminals normal?
Check power source voltage.
Is an error being displayed?
See “protective function”.
Has free-run been commanded?
Cancel free-run.
Are both the forward AND reverse
switches on?
Turn either the forward OR reverse
switch on, and the other off.
Is there anything wrong with the Check the frequency setting.
frequency setting?
Is the motor locked? (Is the load too
heavy?)
Cancel the motor lock. (Reduce the
load.)
Is phase interruption operation being Recheck the wiring
carried out?
inverter and motor.
Motor turns in
reverse.
between
Is there a mistake in the phase order Match the phase order of the output
of the output terminals (U/T1, V/T2, terminals (U/T1, V/T2, W/T3) with the
motor.
W/T3)?
The motor runs but
Is the load too heavy?
speed doesn’t change.
Reduce the load.
Motor speed is not
correct.
Are the number of poles and voltage
of the motor correct?
Check the specification manual and
name plate.
Is voltage of the power input
terminals (R/L1, S/L2, T/L3) correct?
Check power source voltage.
Is the frequency
normal?
Motor speed is
unsteady.
the
setting
range “
“
lower limit frequency”
upper limit frequency”
Has motor terminal voltage dropped
excessively?
“
“
“
Is the load too heavy?
Reduce the load.
Is load variation too large?
Reduce load variation. Raise the
capacity of the inverter and motor.
- 22 -
base frequency”
max. output voltage adjustment”
V/F reduction characteristics”
Detailed Explanation of Parameters
Parameter functions
No.
Parameter name
Explanation
Setting frequency
Sets the frequency with which you want to run the machine.
(0 speed)
Valid when “
1st speed frequency
This sets the frequency when running in multi-speed mode.
nd
2 speed frequency
frequency command select” is
.
Running mode select” is higher than 4th speed operation.
Valid when “
3rd speed frequency
4th speed frequency
Allows you to set 4th speed frequency to 15th speed frequency when you select
5th speed frequency
16 speed running mode for “
Running Mode Select.”
6th speed frequency
Input Terminal
7th speed frequency
Operation Mode
I3
8th speed frequency
10th speed frequency
16 Speed Operation Mode
11th speed frequency
I5
Frequency Setting
Selections
8 Speed Operation Mode
9th speed frequency
I4
I6
No. 2 Acceleration/
Deceleration
Frequency Setting Selections
12th speed frequency
13th speed frequency
14th speed frequency
15th speed frequency
Run command
This selects the run command from the following.
selection
●
●
■
(PANEL) :
RUN
switch on the operation panel.
(TERMINAL) : Input terminals “I1” and “I2”
(BOTH):
Both operation panel and input terminals are
valid.
※
When
is selected, you cannot use the input terminal as the run
command.
Frequency command
selection
This selects whether to set the 0 speed frequency using “
setting frequency
(0 speed), ” the input terminal for Frequency Setting Selections “F1” or the switch on
the main unit.
■
●
"
setting frequency (0 speed)"
Analog Command “FIN1”
(Voltage Command) DC 0 to 5 V
●
Analog Command “FIN1”
(Voltage Command) DC 0 to 10 V
●
Volume on Main Unit
■ Values set at ex-factory.
- 23 -
Detailed Explanation of Parameters
No.
Parameter name
Explanation
Operation mode
These are the parameters that select the operation mode.
selection
●
■
●
●
2nd Speed mode
●
∼
Torque control
4th Speed mode
8th Speed mode
16th Speed mode
:Manual torque boost
This adjusts the voltage output of the inverter at a low frequency region.
※ Be aware that as the settings are
flow which will cause a trip.
Maximum output voltage
Output voltage
increased, excessive current will
Large
Base frequency
Small
0
●
: Auto-boost
Output frequency
Controls for the optimum auto-torque for the
inverter and motor with the same capacity.
●
: Auto-boost
Controls for the optimum a little weaker auto-
torque for the inverter and motor with the same capacity.
●
: Controls slip frequency compensation.
Controls compensation of the slip frequency for the motor
selected by “
motor selection.”
<Precautions regarding the selection of Auto-boost and slip frequency compensation>
・ Select parameters when the motor is stopped.
・ Do not use when running in serial.
・ There are cases in which the system will be unstable depending on the conditions of
the load.
If that should occur, set the manual torque boost.
・ When running at a high power supply voltage, adjust to lower the output voltage of
Base frequency” or “
the inverter using “
Maximum output voltage
adjustment.”
Jogging frequency
Acceleration time
This sets the frequency for operating in the jogging mode.
This determines the rate of change of the output frequency during acceleration.
・ Sets the time that changes in 50 Hz.
・ When set to 0 seconds, acceleration is at its optimum speed and deceleration will be
0.01 second.
・ When less than 3 seconds set to 0.01 sec intervals; When 3 to 9 seconds set to 0.1
sec intervals; When 10 seconds or more set to 1 sec intervals.
No. 2 Acceleration
time
This sets the acceleration time of the No. 2 Acceleration.
This is valid when you select “
No. 2 accel/decel.time.
■ Values set at ex-factory.
- 24 -
I5 Function Selection” in the
Detailed Explanation of Parameters
No.
Parameter name
No. 3 Acceleration
Explanation
This sets the acceleration time of the No. 3 and No.4 Acceleration.
time
This is valid when you select “
No. 4 Acceleration
Selection” in the
I5 Function Selection” “
I6Function
No. 2 accel/decel.time .
time
DC brake volume
This adjusts the DC brake time and the DC brake volume when shifting from inverter
DC brake time
drive to a stopped state.
- The machine will enter a free-run when either or both the time and volume are set to
0 (zero).
※ The DC brake time when you select a sudden brake (all regions) will be twice the
time of the positioning brake.
DC braking time
This selects the type of DC brake.
■
Starting brake time
: Position ●
: Sudden stop (all regions)
This runs the inverter after applying the DC brake to the motor for the amount of time
set when you are starting up.
This does not function when you set to 0 (zero).
・ The strength (torque) of the DC brake (torque) is the “
DC brake volume”
but be careful because it does not operate when set to 0.
Brake start frequency
This adjusts the frequency for starting to apply the positioning DC brake.
・ The DC brake will be applied when the output frequency is lower than “Brake start
frequency” when you cause a soft-stop using the stop command and stop from
normal operation.
・ The DC brake will be applied when lower than 1 Hz regardless of the settings of
“Brake start frequency” when it stops because the frequency settings are low while
in normal operation.
Carrier frequency
variable
This is the parameter that selects the carrier frequency.
This selects the following 8.
Change the carrier frequency when the motor is stopped. Do not change while it is
operating.
Setting value
Carrier frequency
0
1.2kHz
1
2.6kHz
2
3
Setting value
Carrier frequency
4
8.0kHz
5
10.1kHz
3.9kHz
6
12.0kHz
6.0kHz
7
14.9kHz
■ Values set at ex-factory.
- 25 -
■
Detailed Explanation of Parameters
No.
Parameter name
Deceleration time
Explanation
This determines the rate of change of the output frequency when decelerating.
・ Sets the time that changes in 50 Hz.
・ When set to 0 seconds, acceleration is at its optimum speed and deceleration will
be 0.01 second.
・ When less than 3 seconds set to 0.01 sec intervals; When 3 to 9 seconds set to 0.1
sec intervals; When 10 or more seconds set to 1 sec intervals.
No. 2 Deceleration
This sets the deceleration time of the No. 2 Deceleration.
time
This is valid when you select “
I5 Function Selection” in the
No. 2
accel/decel.time.
No. 3 Deceleration
time
No. 4Deceleration
This sets the deceleration time of the No. 2 Deceleration.
This is valid when you select “
Selection” in the
I5 Function Selection” “
I6Function
No. 2 accel/decel.time.
time
This sets the base frequency (maximum
frequency of the torque region) to any
frequency within the range of 30 to 400 Hz
that matches the motor rating.
Maximum output voltage
Output voltage
Base frequency
(30 ~ 400Hz)
Base frequency
0
This adjusts the maximum output voltage
adjustment
(base frequency voltage).
The range of
adjustment is 0 to 100%.
Output frequency
Maximum output voltage
Output voltage
Max. Output voltage
100 :
Power supply
voltage
Adjustment range
(0 ~ 100%)
Base frequency
0
V/F reduction
characteristics
Adjustment range
Output frequency
This adjusts the V/F characteristics to match
●
●
Rated torque load
Reduction torque load
Output voltage
the load characteristics.
0
1.0
Large Base frequency
Output frequency
You can make fine adjustments between 1.0
and 2.0.
Note: This is valid only when you have selected “torque control” in the manual boost.
■ Values set at ex-factory.
- 26 -
Detailed Explanation of Parameters
Parameter name
Explanation
No. 2 V/F selection
This sets the special V/F pattern using “No. 2 V/F selection.”
No. 2 V/F base
This selects the No. 2 V/F upper pattern
frequency
set using the normal V/F and “No. 2 V/F base frequency” and “No. 2 V/F boost.”
No. 2 V/F boost
■
or the lower pattern
Normal pattern
Output voltage
No.
No. 2 V/F
Normal V/F
0
Upper pattern
Output voltage
●
0
Lower pattern
Output frequency
Upper selection
Output frequency
Output voltage
●
0
Lower selection
Output frequency
Note: This is valid only when you have selected “torque control” in the manual boost
Jump frequency width
This creates areas that cannot set the
Jump frequency 1
frequency in a range set by “
Jump frequency 2
frequency width” above and below as the
Jump frequency 3
center of the frequency set by “
Jump frequency 4
frequency 1” to “
Jump
Set frequency
.
Jump frequency width
Jump
0
Jump frequency 4”
Frequency Frequency Frequency
1
2
3
Frequency command (Between FIN and G)
in order to avoid mechanical resonance.
・ Acceleration time outputs the frequency even in the jump region.
・ If jump frequency ranges are overlapped, it jumps all overlapping ranges.
I1/I2 function selection
This switches the input terminals “I1” and “I2” in the following manner.
Input terminal
Between “I1” and “G”
Short
Forward
■
Operation
Operation
(
:Fwd-Stop/Rev-Stop
■ Values set at ex-factory.
- 27 -
Open
Stop
Stop
Between “I2” and “G”
Short
Reverse
Operation
Reverse
Open
Stop
Forward
:Run-Stop/Fwd-Rev)
Detailed Explanation of Parameters
No.
Parameter name
Explanation
I5 function selection
This selects the input terminals “I5” functions in the following manner.
I6 function selection
●
(FREE)
:“Terminal” – “G” Short → Free-run Stop
● (THeRmal)
:“Terminal” – “G” → External forced trip command
● (UpーDown)
:“Terminal” – “G” short → No. 2 acceleration and deceleration time
selection
■ (ReSeT)
“Terminal” – “G” short →Trip reset command
※ Set the status of the short “Terminal” – “G” before selecting “
.”
When open, a trip occurs.
Multi-speed input
This selects the type of frequency setting for multi-speed operation.
selection
●
(1bit):1 bit input
This selects 1 type of multi-speed frequency for 1 terminal of the “Frequency setting
selection terminals.” This runs the inverter in 3 speeds in 4 speed operation mode
and 4 speeds in 8 speed operation mode.
Ex.) With 8 speed mode operation
■
I3
Input terminals
I4
I5
Open
Open
Open
Short
×
×
Open
Short
×
Open
Open
Short
Frequency setting
No. 0 speed
frequency
No. 1 speed
frequency
No. 2 speed
frequency
No. 3 speed
frequency
・ Open and short
are related to “G”
and terminals.
・ × means there
is no relationship
between short
and open.
(Binary):Binary input
This selects the frequency by setting “Frequency setting selection terminals” in
binary.
Not used
■ Values set at ex-factory.
- 28 -
Detailed Explanation of Parameters
No.
Parameter name
Explanation
Output signal 1 selection This selects the output signal between output terminals “O1” to “O2” in the following
Output signal 2 selection manner.
■
(TRIP)
:Trip output signal (When trip: ON*)
●
(STaBLe)
:Arrival signal (When arrival: ON*)
● (RUN)
:Run/Stop signal (When run: ON*)
●
(FREE)
:Free-run singnal (While Free-run: ON*)
● (Fwd)
:Forward operation signal (While forward operation: ON*)
● (Rev)
:Reverse operation signal (While reverse operation: ON*)
●
(CheckーF)
:Output frequency detection signal
→ Refer to:
Compare frequency A” and “
Compare frequency B”
●
(CheckーC)
:Motor current detection signal
→ Refer to “
Motor current detection level”*
●
(DC-Brake)
:DC brake signal (While DC brake: ON*)
●
(CAUS)
:Trip cause detection signal
The following signals are output when a trip occurs.*
Trip contents
ON time
OFF time
Normal over-current
Continuous
Acceleration over-current
3 seconds
1 second
Deceleration over-current
1 second
3 seconds
Over-voltage
1 second
1 second
External forced trip
0.25 second
0.25 second
Electronic thermal
0.9 second
0.1 second
CPU error
0.1 second
0.4 second
Self-diagnosis
0.5 second
0.5 second
* “
output signal 1 selection” can invert “
selection.”
■ Values set at ex-factory.
- 29 -
output signal 1 polarity
Detailed Explanation of Parameters
No.
Parameter name
Explanation
Relay output selection
This selects the output signal when the relay output between “NC,” “COM2” and “NO” is
used. Trip output signal
●
(TRIP):Trip output signal
(When trip: Between “NC” and “COM2”: Open, Between “NO”
and “COM2”:Closed)
●
(STaBLe):Arrival signal
(When arrival: Between “NC” and “COM2”: Open, Between
“NO” and “COM2”: Closed)
●
(RUN):Run/stop signal
(When run: Between “NC” and “COM2”: Open Between “NO”
and “COM2”: Closed)
●
(FREE):Free-run signal
(When free-run: Between “NC” and “COM2”: Open, Between
“NO” and “COM2”: Closed)
●
(Fwd):Forward operation signal
(When forward operation: Between “NC” and “COM2”: Open,
Between “NO” and “COM2”: Closed)
●
(Rev):Reverse operation signal
(When reverse operation: Between “NC” and “COM2”: Open,
Between “NO” and “COM2”: Closed)
●
(Check-F):Output frequency detection signal
→"
Compare frequency A,” and
Refer to “
●
Compare frequency B."
(Check ー C):Motor current detection signal
→Refer to “
Motor current detection level.”
Motor current
Set the current level you want to detect using a percentage for the rated current of the
detection level
inverter when you selected “
selection” in
.
Output signal 1 selection” and “
Relay output
The output terminal will operate when the motor current
exceeds the detection level you set and it will turn “OFF” when it is below.
Output signal 1
This function inverts the polarity of the output signal between output terminals “O1” and
polarity selection
“COM1.”
■
(NORmal): When operation: transistor “ON”
●
(REVerse): When operation: transistor “OFF
Current limit operating
This limits the operating point for the motor current that was set.
point
Numbers are percentages for the inverter rated current.
■ Values set at ex-factory.
- 30 -
Detailed Explanation of Parameters
No.
Parameter name
Explanation
Stall deceleration
This adjusts the deceleration time when the stall prevention function of the deceleration
magnification
is operating.
・Set in percentages for the deceleration time of the normal setting.
Acceleration mode
This selects the straight line acceleration/deceleration or curved line (S) acceleration/
switch
deceleration independently.
Deceleration mode
■
switch
O utput frequency
● Straight line
S Shape 1
O utpu t freq uen cy
●
S Shape 2
O utp ut fre qu enc y
f2
B ase freq uency
f1
0
0
Tim e
0
T im e
T im e
This is a general
With large output of the
This shows an S
acceleration mode to
motor torque, the incline is
characteristic between
accelerate and decelerate
steep and when the output
running frequencies f1 to f2.
on a straight line up to the
torque is small, the incline
set frequency.
is gentle.
This is a smooth acceleration and deceleration
characteristic.
* This changes using the acceleration and deceleration time set when under the base
frequency if you select
S shape 1, but when over the base frequency,
the incline is gentler than the set time.
Monitor mode switch
This selects the content that displays in the 4 digit LED.
The value to which the “
display magnification” was applied is displayed with the
frequency display.
Display magnification
■
Output frequency ●
●
Set frequency
Output current
●
Converter unit DC voltage
This sets the magnification of the value that displays in the 4 digit LED.
This displays
the motor synchronized rotation or the line speed.
* The parameters related to frequency (below) display the value to which the display
magnification was applied when you change the display magnification.
"
∼
0 to 8th speed frequency”
"
∼
Compare frequency"
"
Jogging frequency" "
Matching detection width"
"
Brake start frequency" "
Instantaneous drop frequency"
"
Lower limit frequency"
Frequency meter full scale indication" "
Upper limit frequency"
"
"
∼
Jump frequency" ■ Values set at ex-factory.
- 31 -
Detailed Explanation of Parameters
No.
Parameter name
Explanation
△
Adjust using the
▽
Frequency meter
This calibrates the frequency meter.
adjustment
the needle on the frequency meter points at the full scale.
Frequency meter full
This indicates the frequency when using the frequency meter full scale.
scale indication
60 Hz full scale at ex-factory so adjust to be used higher than 60 Hz.
“FOUT” switch
This selects the frequency signal to output to the frequency output terminal “FOUT.”
■
Frequency analog output
●
Frequency digital output
●
switches so that
This is set to
Current analog output
Compare frequency A
This sets the frequency to detect when you selected “
Compare frequency B
and “
output signal 1 selection”
relay output selection” in the output frequency detection signal
.
- The output signal is ON when the output frequency exceeds*1 “compare frequency A”
and is OFF when it is less*1 than “compare frequency B.”
Output frequency
Output frequency
A
A
B
B
0
0
ON
Match detection width
ON
ON
Between “01” and “COM”
Between “01” and “COM”
When A ≧ B
When A < B
ON
This adjusts the timing to output the arrival signal during acceleration and deceleration
when you selected “
the
-
output signal 1 selection” and “
relay output selection” in
arrival signal.
The arrival signal is output when the difference of the output frequency and the set
frequency is smaller than “match detection width.”
-
The arrival signal is not output when 0 is set.
The arrival signal is not output when forward/reverse are switched when stopped
or during DC brake.
-
The arrival signal is output until immediately before stopping when “
start frequency” < “match detection width.”
■ Values set at ex-factory.
- 32 -
brake
Detailed Explanation of Parameters
No.
Parameter name
Explanation
Instantaneous drop
This adjusts the output frequency after instantaneous stop or after the power is
frequency
restored.
-
This starts the output from the value that subtracted “Instantaneous drop
frequency” from the output frequency of the instantaneous detection when power
was restored.
-
It starts running from 0.5 Hz in the same way as when turning on the power under
normal conditions even though power is restored and the control circuit was reset
when the power cut was long.
Instantaneous free-
This adjusts the free-run time after instantaneous stop or restoring power.
run time
Restart prevention
This prevents restarting after an instantaneous stop or after power was restored by
when power is
setting
.
restored
Retry selection
You can try to continue running by automatically canceling the trip after “Retry start
Retry start time
time” even when a trip occurs.
This will retry (re-execute) the set number of times but
if a trip does not occur in over approximately 120 minutes, the retry count will be
initialized.
■
(NO): Does not retry
●
∼
:Retries the set number of times
・Outputs a trip signal and stops when the set number of retries is reached but does
not output the trip signal (when trip is “
output signal 1 selection” and “
relay output selection”) during a retry.
*
The retry function is invalid when Restart prevention when power is restored is set
to
.
Frequency setting
This sets the “0 V input frequency” of
bias
the frequency setting input terminal
Set frequency
5 V input frequency
“FIN1.”
0V
0 V input frequency
5V
Frequency setting voltage
(Between “FIN1” and “G”)
Lower limit frequency
This sets the lower limit of the inverter output frequency.
Upper limit frequency
This sets the upper limit of the inverter output frequency.
Constant for input
This sets the constant for input filter of the voltage or the current’s frequency setting
filter
signal from an external source.
* Increase the constant of the filter if you cannot attain stable operation because of
the effects of noise.
As you increase the setting value, response will worsen.
■ Values set at ex-factory.
- 33 -
Detailed Explanation of Parameters
Parameter name
Explanation
and trips when an over-voltage trip occurs when turning
Over-voltage trip retry
This displays the
when power is turned
on the power when you set to
on
Also, the trip is automatically canceled at the point the DC voltage falls below
.
approximately 400 V on the converter.
※ The display will change from
to
and it will consider the
normal over-voltage trip when you continue the over-voltage beyond a prescribed
amount of time after turning on the power supply.
Reverse prevention
This prevents the trouble caused by reversing when you set to
Electronic thermal
This adjusts the amount that the electronic
relay
thermal relay functions.
.
・ Set the percentage for the inverter’s rated
current.
・ The operation panel display unit will flash
when the motor current exceeds the set
Operating time
No.
50
100
150 Parameter value
1 min.
value.
0
100%
150%
※ It is necessary to check the ambient
200%
Motor current
temperature when the setting is higher
than the ex-factory setting.
Trip cause clear
This clears the cause of the trip.
<How to clear>
① Use the
△
switch to switch the power supply with the setting
as it
is.
② After the display extinguishes, it will be cleared when the power is turned back on.
will be displayed in the 4 digit LED.
③ Switch the power supply again if the inverter does not operate in this state and use
after turning on the power again.
Trip cause 1
This remembers the latest 5 trips.
Trip cause 2
Refer to “Monitor” for details regarding the content of the display.
Trip cause 3
Trip cause 4
Trip cause 5
Parameter
This initializes and returns all parameters to our standard ex-factory settings.
initialization
<How to initialize>
① Use the
△
switch to switch the power supply with the setting
as it
is.
② After the display extinguishes, it will be initialized when the power is turned back on.
will be displayed in the 4 digit LED.
③ Switch the power supply again if the inverter does not operate in this state and use
after turning on the power again.
- 34 -
Detailed Explanation of Parameters
No.
Parameter name
Motor selection
Explanation
(slip frequency
Set the motor volume and polarity to use when you selected
compensation control) using “
torque control.”
* Select the motor when it is stopped.
Start-up starting
This sets the inverter output starting frequency.
frequency
※ This increases the starting torque but it is close to a direct startup and is not
appropriate for a shock-less start.
Also, there are cases of a trip occurring
depending on the load.
Automatic voltage
This selects the motor’s rated voltage when using automatic voltage regulation.
regulation reference
voltage
Automatic voltage
This corrects the output voltage and suppresses the variations in the output voltage for
regulation selection
the variations of the input power supply voltage.
However, you cannot output the value higher than the maximum output voltage or the
input power voltage.
Parameter lock
This locks the parameters that you set.
Does not lock parameters
Locks all parameters.
Locks parameters for which setting is unnecessary.
・ Setting to
locks all parameters and the
MODE
△
▽
switches become invalid. None of the parameters can then be set.
( RUN and STOP switches are valid)
・ Setting to
allows setting of only the parameters selected by the “
parameter extraction.”
Parameter copy
This copies parameters.
Does not copy parameters.
Reads parameters to panel.
Writes parameters to main unit.
Parameters initialization on operation panel
Motor rated current
This sets the motor rated current when using the slip frequency compensation control.
*1
Motor current without
This sets the motor current without load when using the slip frequency compensation
control. *1
load
- 35 -
Detailed Explanation of Parameters
No.
Parameter name
Motor 1 primary
Explanation
Sets the motor 1 primary resistance when using slip frequency compensation control.
*1
resistance
Slip correction gain
Adjusts the slip correction gain when using slip frequency compensation control.
Slip correction
Sets the slip correction response time when using slip frequency compensation control.
response time
Parameter extraction
*1
This extracts the parameter.
Refer to “How to Extract Parameters” for details.
Because slip frequency compensation control requires a motor constant, set to our standard motor constant that was
set at ex-factory.
Set the motor constant to use when driving another motor.
- 36 -
Ambient conditions
Control method
Power source
Rated output
Specifications
Part Number
*1
Applicable motor (kW)
*2
Output capacity (kVA)
Rated output current (A)
Rated output voltage
*3
Voltage
M1X84BSA
0.75
2.0
2.5
M1X154BSA
1.5
3.0
3.7
M1S224BSA
2.2
4.4
5.5
M1X374BSA
3.7
7.2
9.0
3-phase AC 380 to 460 V
3-phase AC 380 to 460 V
Frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Control method
Output frequency range
Frequency accuracy
50/60Hz
-15%, +10%
± 5%
Low noise sine wave PWM style
0.5 to 400 Hz (Start and stop from 0.5 Hz)
± 0.5%(25°C ± 10°C)
・Digital: 0.01 Hz
Frequency setting resolution
・Analog: Setting frequency range/1000 Hz (minimum 0.05 Hz)
Frequency setting signal
DC0 to +5V, 0 to +10V, 4 to 20mA
Voltage/Frequency
characteristics
Base frequency: 30 to 400 Hz (1 Hz step), with reduced torque
pattern
Rated overload current
150%/minute
Regenerative brake
150% min.
100% min.
70% min.
torque (Short time)
(Short time)
(Short time)
(Short time)
DC brake
Brake start frequency/break operating time/break volume adjustable.
0 to 3600 s(seconds)
Acceleration/deceleration
(0 to 3s: 0.01s step, 3 to 10s: 0.1s step, 10s or more: 1s step)
time
Time that changes in 50 Hz. Adjustable to a maximum of 4
kinds of acceleration/deceleration speeds.
Jogging frequency range
0 to 30Hz
2-speed operation mode, 4-speed operation mode,
Operation mode
8-speed operation mode, 16-Speed operation mode
Automatic boost, slip frequency compensation control selectable
Others
AVR function/retry function selectable, parameter lock available
Insufficient voltage protection, over-current protection, over voltage protection,
instantaneous power failure protection, stall prevention, over-load limitation (current
Protective functions
limiter), overload trip (electric thermal relay), restart prevention when power is
restored, self-diagnosis trip (the last 5 causes of trips are stored)
-10°C to +50°C (No dew condensation is allowed.)
Ambient temperature When the ambient temperature exceeds +40°C, mount a ventilation
cover and rubber bush.
Ambient humidity
Relative humidity: 90% max. (No dew condensation is allowed)
Atmosphere
Indoor (place free from corrosive gas and dirt or dust)
Altitude
1000m max.
Vibration
5.9m/s2 (0.6G) max. (10 to 60Hz)
Protective structure
Built-in the panel (IP40) (With ventilation cover)
Cooling method
Self-cooling method
Weight (kg)
2.9
*1 Applicable motor: For Panasonic 3-phase induction motor (4 poles)
When using another motor, select the motor within inverter ratings.
*2 Output capacity: If the rated output voltage is 460V.
*3 Output voltage does not become higher than the power source voltage.
- 37 -
Ambient conditions
Control method
Power source
Rated output
Specifications
Part Number
*1
Applicable motor (kW)
*2
Output capacity (kVA)
Rated output current (A)
Rated output voltage
*3
Voltage
M1X554BSA
5.5
10.4
13.0
M1X754BSA
7.5
12.8
16.0
M1XA14BSA
11
19.2
24.0
M1XA54ASA
15
25.5
32.0
3-phase AC 380 to 460 V
3-phase AC 380 to 460 V
Frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Control method
Output frequency range
Frequency accuracy
50/60Hz
-15%, +10%
± 5%
Low noise sine wave PWM style
0.5 to 400 Hz (Start and stop from 0.2 Hz)
± 0.5%(25°C ± 10°C)
・Digital: 0.01 Hz
Frequency setting resolution
・Analog: Setting frequency range/1000 Hz (minimum 0.05 Hz)
Frequency setting signal
DC0 to +5V, 0 to +10V, 4 to 20 mA
Voltage/Frequency
characteristics
Base frequency: 30 to 400 Hz (1 Hz step), with reduced torque
pattern
Rated overload current
150%/minute
Regenerative brake
70% min.
50% min.
30% min.
20% min.
torque (Short time)
(Short time)
(Short time)
(Short time)
(Short time)
DC brake
Brake start frequency/break operating time/break volume adjustable.
0 to 3600 s(seconds)
Acceleration/deceleration
(0 to 3s: 0.01s step, 3 to 10s: 0.1s step, 10s or more: 1s step)
time
*Time that changes in 50 Hz. Adjustable to a maximum of 4 kinds of
acceleration/deceleration speeds.
Jogging frequency range
0 to 30Hz
2-speed operation mode, 4-speed operation mode,
Operation mode
8-speed operation mode, 16-Speed operation mode
Automatic boost, AVR function/retry function selectable
Others
Slip frequency compensation control selectable, parameter lock available
Insufficient voltage protection, over-current protection, overvoltage protection,
instantaneous power failure protection, stall prevention, over-load limitation (current
Protective functions
limiter), overload trip (electric thermal relay), restart prevention when power is
restored, self-diagnosis trip (the last 5 causes of trips are stored)
-10°C to +50°C (No dew condensation is allowed.)
Ambient temperature When the ambient temperature exceeds +40°C, mount a ventilation
cover and rubber bush.
Ambient humidity
Relative humidity: 90% max. (No dew condensation is allowed)
Atmosphere
Indoor (place free from corrosive gas and dirt or dust)
Altitude
1000m max.
Vibration
5.9m/s2 (0.6G) max. (10 to 60Hz)
Protective structure
Closed model (IP20)
Cooling method
Self-cooling method
Weight (kg)
7.8
8.5
*1 Applicable motor:For Panasonic 3-phase induction motor (4 poles)
When using another motor, select the motor within inverter ratings.
*2 Output capacity If the rated output voltage is 460V.
*3 Output voltage does not become higher than the power source voltage.
- 38 -
Outer Dimensions
(Mounting dimension)
● MIX 0.75 ∼ 3.7kW
(Mounting dimension)
(Mounting dimension)
● MIX 5.5 ∼ 11 kW
(Mounting dimension)
- 39 -
Outer Dimensions
(Mounting dimension)
● MIX 15 kW
(Mounting dimension)
- 40 -
Parameter Setting
Parameter overview
Inverters of this series have various parameters that adjust/set characteristics and functions,
etc. The objectives and functions of various parameters are described herein. Get a good
understanding of the parameters and use to adjust inverter to the best condition for the
customer’s operating conditions.
Parameter configuration and list of parameters
No.
Parameter name
Parameter setting
Adjustment range
Min. unit Factory setting Check *1
Setting frequency
(0 speed)
0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
1st speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
50Hz
2nd speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
30Hz
*2
15Hz
rd
3 speed frequency
0、 0.50∼upper limit frequency 0.01Hz
4th speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
5th speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
6 speed frequency
0、 0.50∼upper limit frequency 0.01Hz
*2
0Hz
7th speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
8 speed frequency
0、 0.50∼upper limit frequency 0.01Hz
*2
0Hz
9th speed frequency
0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
10th speed frequency 0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
th
th
th
*2
0Hz
12th speed frequency 0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
11 speed frequency 0、 0.50∼upper limit frequency 0.01Hz
th
*2
0Hz
14th speed frequency 0、 0.50∼upper limit frequency 0.01Hz *2
0Hz
13 speed frequency 0、 0.50∼upper limit frequency 0.01Hz
th
15 speed frequency 0、 0.50∼upper limit frequency 0.01Hz
Run command
selection
Operation panel
Frequency command
selection
Operation panel
*1
*2
Parameters marked by
to use.
0Hz
Terminal block,
Both
Volume
-
Operation mode
selection
*2
0∼5V (4-20 mA)
0∼10V (4-20 mA)
2, 4, 8, 16, speed operation mode
4 speed
operation mode
in the Check column are tripped for safety if modified or memorized. Release the trip
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
- 41 -
Parameter Setting
No.
Parameter name
Parameter setting
Adjustment range
2
0 ∼ 100
, Automatic boost(standard)
Automatic boost(little)
Slip correction control
Torque control
Jogging frequency
Acceleration time
No. 2 acceleration
time
No. 3 acceleration
time
No. 4 acceleration
time
DC brake volume
0、 0.5∼30 Hz
DC brake selection
Starting brake time
Brake start frequency
Carrier frequency
variable
Deceleration time
No. 2 V/F selection
No. 2 V/F base
frequency
No. 2 V/F boost
*1
*2
20
7 Hz
∼ 3 sec : 0.01 sec interval
0∼3600 sec 3 sec∼10 sec : 0.1 sec interval
10 sec∼
: 1 sec interval
5 sec
5 sec
5 sec
0 ∼ 100%
Case of
-
:
0∼3 sec
:
0∼6 sec
Positioning
Sudden stop
0 ∼ 3 sec
0.50 ∼ 400 Hz
2
70
0.05 sec
0.5 sec
0.1 sec
1.0 sec
0.05 sec
0.01 Hz
*2
0,1,2,3,4,5,6,7∗2
0 (nonoperational)
3 Hz
5
5 sec
Not used
Not used
No. 4 deceleration
time
Base cycle
Max. output voltage
adjustment
V/F reduction
characteristics
0.01 Hz
Factory setting Check *1
5 sec
Case of
DC brake time
Min. unit
0∼3600 sec
∼ 3 sec : 0.01 sec interval
3 sec∼10 sec : 0.1 sec interval
10 sec∼
: 1 sec interval
5 sec
5 sec
5 sec
30 ∼ 400 Hz
1 Hz
50 Hz
0 ∼ 100%
1
100
1.0 ∼ 2.0 squared
0.1
1.0
30 ∼ 400 Hz
1 Hz
50 Hz
0 ∼ 100%
2
0
No selected
(usually V/F pattern)
Upper selection
Lower selection
0
Parameters marked by in the Check column are tripped for safety if modified or memorized. Release the trip
to use.
Rated current is 90% if carrier frequency of 3 or 4 is selected.
Rated current is 80% if carrier frequency of 5,6 or 7 is selected.
- 42 -
Parameter Setting
No.
Parameter name
Parameter setting
Factory setting Check *1
Adjustment range
Min. unit
0、 0.50∼400 Hz
0.01 Hz *2
0 Hz
0、 0.50∼400 Hz
0.01 Hz *2
0 Hz
0、 0.50∼400 Hz
0.01 Hz
*2
0 Hz
*2
0 Hz
0 Hz
Jump frequency
width
Jump frequency①
Jump frequency②
Jump frequency③
0、 0.50∼400 Hz
0.01 Hz
Jump frequency④
0、 0.50∼400 Hz
0.01 Hz *2
I1: Forward/Stop、
I2: Reverse/Stop
I1: Run/Stop、
I2: Forward/Reverse
I1/I2 function
selection
Not used
Free-run、
External forced
No. 2 acceleration/deceleration
Trip reset
Multi-speed input
selection
1 bit
Binary
I5 function selection
-
Not used
Output signal ①
selection
Not used
Relay output signal
selection
*Effective only when
relay output
terminals NC, C2 or
NO are used.
Motor current
detection level
Output signal polarity
selection
*1
*2
-
Trip、
Arrival
Running
Free-run
Forward、
Reverse
Output frequency detection
Motor current detection
Trip cause
DC brake
-
Trip、
Arrival
Running
Free-run
Forward、
Reverse
Output frequency detection
Motor current detection
-
50∼150%
5%
100%
Forward polarity,
Reverse polarity
Parameters marked by in the Check column are tripped for safety if modified or memorized. Release the trip
to use.
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
- 43 -
Parameter Setting
No.
Parameter name
Parameter setting
Adjustment range
Min. unit Factory setting Check *1
Current limit operation
point
Stall time deceleration
power
Acceleration mode
switching
Deceleration mode
switching
Monitor mode switching
Display power
Frequency meter
adjustment
Frequency meter full
scale indication
FOUT switching
180%
1、2、4、8、16
Straight line
-
8
-
S-curve①
S-curve②
Set frequency
Output frequency
DC voltage
Output current
-
0.1 ∼ 60.0
0.1
1.0
-
-
-
0 ∼ 400 Hz
1 Hz
60 Hz
Digit
Digital output for frequency
Needle Analogous output for
frequency
Analogous output current
0、0.50∼400 Hz
0.01 Hz
*2
0 Hz
Comparison frequency B
0、0.50∼400 Hz
0.01 Hz
*2
0 Hz
0、0.50∼400 Hz
0.01 Hz
*2
3 Hz
0、0.50∼400 Hz
0.01 Hz
*2
3 Hz
Reduced frequency at
instantaneous stop
Instantaneous stop freerun time
Restart prevention when
power is restored
Retry selection
1、2、3、4、5
1
1
Restart
Restart prevention
No retry
∼
Retry No. of set times
Retry start time
0∼120 sec
2 sec
4 sec
Frequency setting bias
0∼-50 Hz
0.01 Hz
0 Hz
Lower limit frequency
Upper limit frequency
Constant for input filter
Over-current trip retry
when power is turned on
Reverse prevention
Electronic thermal relay
*2
10%
Comparison frequency A
Agreement detection width
*1
50∼200%
0、0.5 ∼
(Maximum frequency-0.01) Hz
(Minimum frequency-0.01)
∼ 400 Hz
0.1 Hz
*2
0 Hz
0.1 Hz
*2
60 Hz
1、2、3、4、5
1
No retry
Retry
Reverse
Reverse prevention
30∼150%
5%
115%
Parameters marked by in the Check column are tripped for safety if modified or memorized. Release the trip
to use.
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
- 44 -
Parameter Setting
No.
Parameter name
Parameter setting
Factory setting Check *1
Adjustment range
Min. unit
Trip cause①
-
-
-
Trip cause②
-
-
-
Trip cause③
-
-
-
Trip cause④
-
-
-
Trip cause⑤
-
-
-
Trip cause clear
Parameter
initialization
Motor selection
Motor capacity *2
No. of motor poles
Start-up starting
frequency
Automatic voltage
adjustment reference
voltage
Automatic voltage
adjustment selection
Parameter lock
Parameter copy
Motor rated current
Motor current
without load
Motor primary
resistance
Slip correction gain
Slip correction
response time
Parameter extraction
*1
*2
*3
0.50∼10 Hz
0.01 Hz
380,400,440,460V
4 poles,
inverter
capacity *3
1
380
No automatic voltage adjustment
Automatic voltage adjustment
No automatic voltage adjustment only when decelerating
No parameter lock
All parameters locked
Parameters that don’t need to
be set locked
Parameters not copied
Parameters read-out to panel
side
Parameters written in inverter
side
Parameters initialization on
operation panel
0.1
0 ∼100A
-
0 ∼100A
0.1
-
0 ∼100Ω
0.01
-
0、1、2、3、4、5、6、7
4
0、1、2、3、4、5、6、7
0
Parameter No.
-
-
Parameters marked by in the Check column are tripped for safety if modified or memorized. Release the trip
to use.
Motor capacity is
: 0.2kW,
: 0.4kW,
: 0.8kW.
4-pole motor of same capacity as inverter rating set when shipped from the factory.
- 45 -
Servicing (Repair)
Repair
● Consult your Panasonic dealer for repairs of your Panasonic inverter.
Consult your machine or device manufacturer when the inverter is installed in a
machine or device.
For your convenience: (Please fill in the blank when you need to consult for repairs.)
Date purchased
Year/Month/Date
Model number
Shop purchased
Phone number
Industrial and Appliance Motor Division, Motor Company,
Matsushita Electric Industrial Co., Ltd.
7-1-1 Morofuku, Daito-shi, Osaka, 574-0044 Japan
Phone: 072-871-1212
IMA ZZ
S0796-0
- 46 -
MEMO
- 47 -
MEMO
- 48 -
MEMO
- 49 -
- 50 -