Specification Sheet

PB256 Series
1 3 8 W AT T S - B AT T E R Y C H A R G E R
FEATURES
•
•
•
•
•
•
•
•
•
•
•
138W 12VDC & 24VDC
Battery Backup System
DC UPS Connectable
Independent Load and Battery Current Limited
Converter ON/OK alarm
Battery Low Alarm
Battery Low Voltage Disconnect
Battery Over Load protection
Conformal Coating option for wet areas
C-Tick Approved
INSTALLATION HANDBOOK AVAILABLE ON REQUEST
SPECIFICATIONS
INPUT
Input Voltage
190-.264Vac, or 190-.400Vdc
Frequency
45 to 65 Hz
Input Current
3A maximum
Inrush current
15A on cold start
Line Regulation
0.2% typical
OUTPUT
13.8Vdc, 27.6Vdc
Output Power
138W, See power derating curve
13.8Vdc: 10A
27.6Vdc: 5A
See Selection Table
2% typical
25 mVp-p (13.8Vdc output)
45mVp-p (27.6Vdc output)
> 80%
Load regulation
Ripple & Noise
Efficiency
PROTECTION
Current limit type
(Load circuit)
Constant current > LVD volts
Foldback & hiccup < LVD volts
Short circuit protection
Indefinite, auto-resetting
15.5 to 19.5 V latching (13.8Vdc output) 31.5
to 39 V latching (27.6Vdc output)
Internal fuse
Input to Output: 2.1Kvdc 1 min
Output to Ground: 2.1Kvdc 1 min
Output to Ground: 700Vdc 1 min
Over-voltage protection
Reverse polarity protection
Isolation
Battery over-load protection
Indicated by voltage-free changeover relay
contacts & green LED: ON=OK
< 11.3Vdc: 12V Battery
< 22.6Vdc: 24V Battery
Indicated by voltage-free changeover relay
contacts & green LED: ON=OK.
10.8V (Typical for 12Vdc battery)
21.6V (Typical for 24Vdc battery)
Electronic circuit breakerauto-reset
Battery to load voltage drop
0.2 V (27.6V output)
Converter ON/OK alarm
Battery low alarm
Low voltage disconnect
Output Voltage
Output Current
ALARMS AND BATTERY
FUNCTIONS
OPTIONAL FEATURES
Battery Charge Limit
Heatsink
Conformal Coating
STANDARDS AND
APPROVALS
C-Tick
Option CC: Tropic protection for moist areas
Safety
Compliles with AS/NZS 60950, Class 1
Emissions comply with AS/NZS CISPR11,
Group 1, Class B. Complies with ACA EMC
Scheme, C-Tick
EMC
0 to 50°C ambient
For derating, see curve in technical
illustrations
Humidity
5 to 90% relative humidity (non-condensing)
AS/NZS CISPR11 Group 1 Class A.
MECHANICAL
Case size
AC Mains 10A Class 1
IEC60320 power inlet
4 way pluggable screw terminal block.
Suitable for up to 1.5mm² wire
6 way pluggable screw terminal block
Suitable for up to 1.5mm² wire
230 L x 93 W x 46 H (mm)
Weight
850g
Security Cabinet
WMBB-C-S Security Cabinet
Input Connector
Load and Battery Connector
ENVIRONMENTAL
Operating temperature
Option BCL: Specify battery charge current
based on battery size.
Option H: Supplementary heatsink
Alarms Connector
Over-temperature protection Automatic & auto-resetting
Cooling requirement
Natural convection
Shock/Impact
50G 11mS once each along x, y and z axis
Doc. No. PB256 Rev.D 25-9-15
PB256 Series
1 3 8 W AT T S - B AT T E R Y C H A R G E R
SELECTION TABLE
MODEL NUMBER
OUTPUT VOLTAGE
TOTAL CURRENT
BATTERY CURRENT
OUTPUT POWER
PB256-1210CML
13.8Vdc
8A
2A
138W
PB256-2405CML
27.6Vdc
4A
1A
138W
TECHNICAL ILLUSTRATIONS
Doc. No. PB256 Rev.D 25-9-15
Powering Progress – www.powerbox.com.au