Specification Sheet

PB251A-RM Series
B AT T E R Y C H A R G E R S Y S T E M
FEATURES
•
•
•
•
•
•
•
•
•
•
•
•
•
220 - 330W Battery Charger System
DC UPS Connectable
Digital Display System
Rack Mounting
Constant Float Voltage & Current Limit
Circuit Breakers & Alarm Relays
Independent Battery Charging Output
DC OK & Battery OK Alarms
Battery Connected Test Battery Low Volts Disconnect
Optional Battery Charge Current Limit
Optional Network Connected
Optional Battery Temperature Probe
OPERATIONS INSTALLATION HANDBOOK AVAILABLE
SPECIFICATIONS
ALARMS & BATTERY
INPUT
Input Voltage:
190 to 264Vac, or 225 to 400Vdc
Frequency
45 to 65 Hz
Input Current:
1.4A maximum
Inrush current:
10A maximum
Line regulation:
0.2%typical
DC Ok alarm
Charger voltage OK alarm
OUTPUT
Battery low voltage
disconnect(LVD)
Green LED : ON=OK voltage free change over relay
contacts (32V,1A) Alarms on loss of AC mains power
or failure of off-line AC/DC converter / battery charger
Green LED : ON=OK voltage free change over relay
contacts (32V,1A) Alarms on battery low voltage,
failure of battery fuse or battery disconnected. Alarm
cancelled when fuse or battery replaced, or AC input
restored
Low voltage disconnect 10.5V for 12V battery, 21V for
24V battery, adjustable 1.6 to 2.0V / cell all models
Output Voltage
13.8Vdc, 27.6Vdc
Output Power
275W - 330W
Output Current
13.8Vdc: 20A
27.6Vdc: 12A
Load regulation
0.5% typical
Battery to load voltage drop 0.2 to 0.35V typical model dependant
Ripple & noise
100 MHz bandwidth 28mVp-p (13.8Vdc output)
55mVp-p (27.6Vdc output)
OPTIONAL FEATURES
Efficiency
> 80%
Battery Charging Limit
Current limit
Load circuit - Constant current
Battery circuit - Constant current
Network enabled
Short circuit protection
Indefinite, auto-resetting
Over-voltage protection
17.5 to 20V latching (13.8Vdc output)
31.5 to 39V latching (27.6Vdc output)
Analogue meters
Isolation
Input to Output: 4.2Kvdc 1 min
Output to Ground: 2.1Kvdc 1 min
Output to Ground: 700Vdc 1 min
Option T: 2.5m cable probe
Option T5: 5m cable probe
Temperature compensation
Float voltage set to 2.3V/cell at 25°C with
compensation of 3.3mv/°C cell
Charger over-load protection Auto-resetting electronic circuit breaker
Reverse polarity protection
PROTECTION
ENVIRONMENT
Operating temperature
0 to 70°C ambient
Derating from 40°C at 2.5%/°C
Humidity
5 to 90% relative humidity (non-condensing)
Natural convection
STANDARDS
Option BCL: Factory set to maximum of the total rated
output current. The BCL charging current based on
A/H battery size and make of battery.
Option N: Internal network card in conjunction with
PB251A becomes a network enabled device
combining the benefits of SNMP V1, XML and
embedded webpage.
Option M: Load voltage, load current, battery charge
and discharge.
Contact Powerbox for further information
MECHANICAL
Input connector
Over-temperature protection Automatic & auto-resetting
Cooling requirement
Battery Capacity Test
Internal battery fuse
IEC60320 inlet,10A Class 1
2 meter IEC mains cord with Australian plug is
supplied with each unit
PB251A-RML: M4 screw terminals
Output and battery connector PB251A-B: Hirose HS28R-4A.
Mating connector is Hirose HS28P-4A (not supplied)
C-Tick
AS/NZS CISPR11 Group 1 Class A.
Safety
Complies with AS/NZS 60950, class 1,
NSW Office of Fair Trading Approval N20602
Alarm terminal
PB251A-RML: M3.5 screw terminals
PB251A-B: DB25 female
Emissions comply with AS/NZS CISPR11, Group
1, Class B. Complies with ACA EMC Scheme,
Safety & EMC Regulatory Compliance Marked
Enclosure
EMC
19" Rack Mount, 2RU height, 232mm
Mounting slots suitable for M6 hardware
Weight
5.5kg
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. PB251A-RM Rev.C 12-02-16
PB251A-RM Series
B AT T E R Y C H A R G E R S Y S T E M
SELECTION TABLE
MODEL NUMBER
OUTPUT VOLTAGE
TOTAL CURRENT BATTERY CURRENT
OUTPUT POWER MECHANICAL
PB251A-12RML
13.8V
20A
4A
275W
Rack Mount / Screw terminals
PB251A-24RML
27.6V
12A
2A
330W
Rack Mount / Screw terminals
PB251A-12B
13.8V
20A
20A
275W
Rack Mount / Hirose connector
PB251A-24B
27.6V
12A
12A
330W
Rack Mount / Hirose connector
NOTES
1). Total output current is sum of load and battery charging current.
2). Other BCL option, Battery Charging Limits, available on request, factory set.
3). Example models number, PB251A-12RML-M-10, Includes analogue meters and 5A battery charge current.
4). PB251A-B versions, in standard unit the battery current limit set to maximum.
TECHNICAL ILLUSTRATIONS
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. PB251A-RM Rev.C 12-02-16
PB251A-RM Series
B AT T E R Y C H A R G E R S Y S T E M
TECHNICAL ILLUSTRATIONS
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. PB251A-RM Rev.C 12-02-16