Specification Sheet

PB314 Series
6 3 6 - 7 4 5 W AT T S B AT T E R Y C H A R G E R S Y S T E M
FEATURES
•
•
•
•
•
•
•
636 - 745W
PSU for Battery Backup
DC UPS Connectable
Constant Float Voltage & Current Limit
Circuit Breaker & Alarm Relays
Optional LVD - Low Volts Battery Disconnect
OPERATIONS & INSTALLATION HANDBOOK AVAILABLE
SPECIFICATIONS
INPUT
Input Voltage
DISPLAYS AND ALARMS
DC OK
LED Green On = OK, Voltage-free changeover
contact (32V, 1A).Alarm on failure of AC/DC PSU
and tripping of over temperature limit.
AC OK
LED Green On = OK, Voltage-free changeover
contact (32V, 1A). Alarm on mains fail.
Battery Ok
LED Green On = OK, Voltage-free changeover
contact(32V, 1A). Alarm on battery low voltage or
on opening of battery circuit breaker.
85-264Vac or 120-360Vdc
Frequency:
47 to 63 Hz
Input Current:
4.1A typical at 200Vac
Inrush current:
40A typical cold start 200Vac
Line regulation
60mV maximum
OUTPUT
Output Voltage
13.8Vdc, 27.6Vdc
Output Power
636W - 745W
Output Current
See Selection Table
Efficiency
Battery low alarm voltage -11.0Vdc
79% typical
Battery Low Voltage
Disconnect
Option LVD:
Battery LVD disconnect 10.5V
Battery LVD reconnect 12.0Vdc
Load regulation
1% typical
Voltage meter
0 to 15Vdc
Ripple
160mVp-p max
Load current meter
0 to 100A
Noise
180mVp-p max
Battery current meter
-100A to +100A scale.
PROTECTION
OPTIONAL FEATURES
Overvoltage shutdown
16.2 to 19.8V latching
Output short circuit
Indefinite protection (Autoresetting)
Battery Charge Limit
Option BCL: Specify battery charge current based
on battery size.
Battery LVD disconnect
Option LVD: For 12V and 24V models, not
available in 48V models.
Battery charger short circuit Indefinite protection (Autoresetting)
Load output protection
Thermal - Magnetic Circuit Breaker
Battery output protection
Thermal - Magnetic Circuit Breaker.
Isolation
Input - Output: 3KVac 1 min
Input - Ground: 2KVac 1 min
Output - Ground: 500Vac 1min
ENVIRONMENT
Operating temperature
-20°C to 71°C
Derating from 50°C to 71°C to 50% power
Humidity
20-90% relative humidity (non condensing)
Cooling
Forced cooling - internal fan
STANDARDS & APPROVALS
C-Tick
AS/NZS CISPR11 Group 1 Class A.
Safety
UL 60950 Class 1
EMC
Emissions comply with AS/NZ CISPR22 Class-B
MECHANICAL
AC input socket
IEC320 fused / on off switch
Output termination
Hirose connector (-H version)
Cage clamp terminals (-C version)
Alarm relay contacts
DB25 socket
Load fault current
proteciton breaker
63 A
Battery fault current
protection breaker
63 A
Rack mount size
264 L x 172 W x 67 H mm
Weight
5.0Kg
Doc. No. PB314 Series Rev.L 09-06-16
PB314 Series
6 3 6 - 7 4 5 W AT T S B AT T E R Y C H A R G E R S Y S T E M
SELECTION TABLE
MODEL NUMBER
OUTPUT
VOLTAGE
OUTPUT
CURRENT
BATTERY
CHARGE CURRENT
POWER
OUTPUT
CONNECTOR
PB314-12-43-H
13.8Vdc
43A
Balance of load current
645W
Hirose
PB314-12-43-C
13.8Vdc
43A
Balance of load current
645W
Cage clamp
PB314-12-53-H
13.8Vdc
53A
Balance of load current
636W
Hirose
PB314-12-53-C
13.8Vdc
53A
Balance of load current
636W
Cage clamp
PB314-24-27-H
27.6Vdc
27A
Balance of load current
745W
Hirose
PB314-24-27-C
27.6Vdc
27A
Balance of load current
745W
Cage clamp
Notes
1. Battery Charge Current is the remainder balance of Load Current.
2. BCL option, specifies battery charge current limit recommended on battery size.
3. LVD option, Low Voltage Battery Disconnect.
TECHNICAL ILLUSTRATIONS
Doc. No. PB314 Series Rev.L 09-06-16
Powering Progress – www.powerbox.com.au
PB314 Series
6 3 6 - 7 4 5 W AT T S B AT T E R Y C H A R G E R S Y S T E M
Doc. No. PB314 Series Rev.L 09-06-16