G3G250GN3901 1593584

EC centrifugal fan
G3G250-GN39-01
backward curved, single inlet
with housing (flange), Gas blower for gas-condensing heating
ebm-papst Landshut GmbH
Hofmark-Aich-Str. 25 · D-84030 Landshut
Phone +49 871 707-0
Fax +49 871 707-465
[email protected]
www.ebmpapst.com
Nominal data
Type
G3G250-GN39-01
Motor
M3G084-FA
Phase
1~
Nominal voltage
VAC
115
Nominal voltage range
VAC
100 .. 130
Frequency
Hz
50/60
Type of data definition
ml
Speed
min-1
4800
Power input
W
1200
Current draw
A
13
Min. ambient temperature
°C
-20
Max. ambient temperature
°C
60
Min. temp. of flow medium
°C
0
Max. temp. of flow medium
°C
60
ml = max. load · me = max. efficiency · rfa = running at free air · cs = customer specs · cu = customer unit
Subject to alterations
Item no.: 50134-5-9980 · Revision: 66688 · Print-out 07/11/2011 · K. Boruzki (VI-I) · Page 1 of 5
ebm-papst Landshut GmbH · Hofmark-Aich-Str. 25 · D-84030 Landshut · Phone +49 871 707-0 · Fax +49 871 707-465 · [email protected] · www.ebmpapst.com
EC centrifugal fan
G3G250-GN39-01
backward curved, single inlet
with housing (flange), Gas blower for gas-condensing heating
Technical features
Mass
13.2 kg
Size
250 mm
Surface of rotor
Coated in black
Material of protective cover
Polyflam RPP 374-ND CS1 (UL 97-V0)
Material of impeller
Aluminium sheet
Housing material
Die-cast aluminium
Number of blades
7
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 20
Insulation class
"B"
Max. permissible ambient
motor temp. (transp./ storage)
+80 °C
Min. permissible ambient
motor temp. (transp./storage)
-40 °C
Mounting position
Any
Condensate discharge holes
Rotor-side
Operation mode
S1
Motor bearing
Ball bearing
Technical features
- PFC, passive
- Tach output
- Over-temperature protected electronics / motor
- Line undervoltage detection
- Motor current limit
- PWM control input
- Control input 0-10 V
EMC interference immunity
Acc. to EN 61000-6-2 (industrial environment)
EMC interference emission
Acc. to EN 61000-6-4 (industrial environment)
Leakage current
<= 3.5 mA
Electrical leads
With plug
Motor protection
Locked-rotor protection
Protection class
I
Approval
CSA C22.2 Nr.113; UL 507
Item no.: 50134-5-9980 · Revision: 66688 · Print-out 07/11/2011 · K. Boruzki (VI-I) · Page 2 of 5
ebm-papst Landshut GmbH · Hofmark-Aich-Str. 25 · D-84030 Landshut · Phone +49 871 707-0 · Fax +49 871 707-465 · [email protected] · www.ebmpapst.com
G3G250-GN39-01
EC centrifugal fan
backward curved, single inlet
with housing (flange), Gas blower for gas-condensing heating
Product drawing
1
3-pole strip to fit mating connector (not included in standard scope of delivery) tyco No. 350766-1, female connector tyco No.
926884-1
1.1
L
1.2
N
1.3
PE
2
5-pole strip to fit mating connector (not included in standard scope of delivery) Molex No. 39-01-4050, female connector Molex
No. 39-00-0059
2.1
+
2.2
Speed monitoring
2.3
0-10 VDC control input
2.4
PWM input
2.5
-
3
Pressure tap optionally available
Y
Detail Y
Z
View Z / plug assignment
Item no.: 50134-5-9980 · Revision: 66688 · Print-out 07/11/2011 · K. Boruzki (VI-I) · Page 3 of 5
ebm-papst Landshut GmbH · Hofmark-Aich-Str. 25 · D-84030 Landshut · Phone +49 871 707-0 · Fax +49 871 707-465 · [email protected] · www.ebmpapst.com
G3G250-GN39-01
EC centrifugal fan
backward curved, single inlet
with housing (flange), Gas blower for gas-condensing heating
Connection screen
No.
Pin
Signal
Function / assignment
ST1
1; 2; 3
L; N; PE
Power supply 115 VAC, 50 - 60 Hz, phase, neutral, protective earth
ST2
1
UB
External voltage 16 - 45 VDC, residual ripple +/- 3.5%, SELV
ST2
2
DUE
Speed monitoring, 3 pulses per revolution, SELV
ST2
3
0 - 10 V
Control input 0 - 10 V, impedance 100k, SELV
ST2
4
PWM
Control input PWM, 1 - 6 kHz, SELV
ST2
5
GND
Power supply 230 VAC, 50 - 60 Hz, phase, neutral, protective earth
Item no.: 50134-5-9980 · Revision: 66688 · Print-out 07/11/2011 · K. Boruzki (VI-I) · Page 4 of 5
ebm-papst Landshut GmbH · Hofmark-Aich-Str. 25 · D-84030 Landshut · Phone +49 871 707-0 · Fax +49 871 707-465 · [email protected] · www.ebmpapst.com
EC centrifugal fan
G3G250-GN39-01
backward curved, single inlet
with housing (flange), Gas blower for gas-condensing heating
Charts: Air flow 50 Hz
Druck psf [Pa]für Rho=1,2kg/m^3
3.600
0
200
qv[cfm]
600
400
800
1.000
3.500
14
3.400
3.300
13,5
13
3.200
3.100
12,5
4
3.000
2.900
12
11,5
2.800
11
2.700
2.600
10,5
2.500
2.400
10
9,5
2.300
9
2.200
8,5
3
8
1.900
7,5
1.800
7
1.700
1.600
1.500
6,5
1.400
5,5
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
6
1.300
5
1.200
1.100
4,5
2
1.000
4
900
3,5
800
3
700
600
2,5
2
400
1,5
300
200
1
[Pa
spf
500
100
0,5
1
]
0
p sf _E[IN H2O]
sf [Pa]
p
2.100
2.000
Measurement: LU-73322
0
200
400
600
800
1.000
qv[m^3/h]
1.200
1.400
1.600
1.800
0
2.000
Measured values
U
f
n
Pe
I
LpAin
qv
psf
V
Hz
min-1
W
A
dB(A)
m3/h
Pa
1
115
50
4925
1152
12.40
91
1705
0
2
115
50
4770
1200
13.00
89
1405
1000
3
115
50
4830
1182
12.76
81
1100
2000
4
115
50
5090
1056
11.43
79
695
3000
Item no.: 50134-5-9980 · Revision: 66688 · Print-out 07/11/2011 · K. Boruzki (VI-I) · Page 5 of 5