3.75 in / 95.3 mm 3.13 in / 79.4 mm 1.73 in / 43.9 mm 3.25 in / 82.6 mm 1.00 in / 25.3 mm A. Input Characteristics: 1) Voltage: 230 VAC 2) Frequency: 50/60 Hz. 3) Current: 15A Maximum (12A DERATED FOR NA) 4) Load Capacity: 3.45 KVA 5) Overload Protection: 6x2P/15A UL489 Circuit Breaker 17.50 in / 444.5 mm 6) Power Cord: none 7) Connector: IEC-C14 B. Output Characteristics: 1) Voltage: 230 VAC 2) Current: 15A MAX (12A DERATED FOR NA) 3) Outlets: 6x IEC-C13 (PROTECTED), 2x IEC-C13 (ALWAYS ON) C. Mechanical Characteristics: 1) Material: CRS/G40 Galv. Coating 3) Lettering: Silk-Screen 4) Storage Temp.: -17 to 149C (-25 to 65C) D. Operating Environment: 1) Temperature: 32 to 122F (0 to 50C) 2) Relative Humidity: 0 - 95% (Non-Condensing) 0.20 in / 5.1 mm 3) Elevation: 0 - 10,000FT (0 - 3000 m) TYP E. Regulatory Conformance: 1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1 CHANGE NOTICE 0 REV 2) RoHS: Compliant to Directive 2002/95/EC CN-000084 33.00 in / 838.2 mm 2) Finish: Powder Coated DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: carrs TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 DATE 1/28/2010 ANGLES ± 030' Spectrum Management Systems PDU,0U,8/C13,C14,230V,15A,6/CB THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-115BTHEN-00 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA