PDF Download(9986KB)

Technical Explanation for Solid-state Relays
CSM_SSR_TG_E_9_2
Introduction
Sensors
What Is a Solid State Relay?
A Solid State Relay (SSR) is a relay that does not have a moving contact. In terms of operation, SSRs are not very different from
mechanical relays that have moving contacts. SSRs, however, employ semiconductor switching elements, such as thyristors,
triacs, diodes, and transistors.
Switches
Mechanical Relays
These relays transfer signals with
mechanical motion.
Motion is transferred.
Switch
section
Relays
Relays
Electromagnetic
section
Safety Components
Output
Input
Features
Mechanical relays have contacts
and use electromagnetic force to
mechanically open and close the
contacts to turn ON/OFF signals,
currents, or voltages.
Solid State Relays (SSRs)
These relays transfer signals with
electronic circuits.
Output
Input
Switch section ⇒
Semiconductor switch
(thyristor or other device)
Automation Systems
Electromagnetic
section
⇒ Input circuit
SSRs do not have the mechanical
moving parts that mechanical
relays with contacts do. Instead
they consist of semiconductors
and electronic parts.
SSRs turn ON/OFF signals,
currents, or voltages electronically
by the operation of these
electronic circuits.
Control Components
Signal is transferred (operation is transferred).
* Photocoupler or other device
Features
* For details on mechanical relays, refer to the Technical Explanation for General-purpose Relays.
Structure and Operating Principle
Motion / Drives
SSRs use electronic circuits to transfer a signal.
1. The input device (switch) is turned ON.
Illustration of SSR Structure
ON
Isolated input
Output circuits
circuits
Output circuits
Drive circuit
Electrical isolation
3. The switching element in the output
circuit turns ON.
Output
terminals
ON
Isolated input
Output circuits
circuits
4. When the switching element turns ON,
load current flows and the lamp turns
ON.
SSR Components (Example)
Resistor
LED
Power Supplies /
In Addition
Input circuits
Input
terminals
Energy Conservation Support /
Environment Measure Equipment
Isolated input circuits
2. Current flows to the input circuits, the
photocoupler operates, and an electric
signal is transferred to the trigger
circuit in the output circuits.
Photocoupler Capacitor
OFF
Isolated input
Output circuits
circuits
Others
Power transistor (for DC loads)
Power MOS FET (for AC or DC loads)
Thyristor (for AC loads)
Triac (for AC loads)
Common
5. The input device (switch) is turned OFF.
6. When the photocoupler turns OFF, the
trigger circuit in the output circuits
turns OFF, which turns OFF the
switching element.
7. When the switching element turns
OFF, the lamp turns OFF.
1
Technical Explanation for Solid-state Relays
Features
Sensors
Switches
SSRs are relays that use semiconductor switching elements. They use optical semiconductors called photocouplers to isolate input
and output signals.
The photocouplers change electric signals into optical signals and relay the signals through space, thus fully isolating the input and
output sections while relaying the signals at high speed.
Also, SSRs consist of electronic components with no mechanical contacts. Therefore, SSRs have a variety of features that
mechanical relays do not incorporate.
The greatest feature of SSRs is that SSRs do not use switching contacts that will physically wear out.
Solid State Relays (SSRs)
Representative Example of Switching for AC Loads
Mechanical Relays (General-purpose Relays)
Example of an Electromagnetic Relay (EMR)
An EMR generates electromagnetic force when the input
voltage is applied to the coil. The electromagnetic force
moves the armature. The armature switches the contacts in
synchronization.
Input
Safety Components
Triac
Output
Light
Phototriac coupler
Output
Contact
Moving
contact
Coil
Output circuit
Drive circuit
Release spring
Output
terminals
Control Components
Input
terminals
Armature
Electrical isolation
Isolated input circuits
Relays
Coil
Electromagnetic
force
Input circuit
Input
Resistor
LED
Automation Systems
SSR Components (Example)
Photocoupler Capacitor
Core
Coil terminals
Power transistor (for DC loads)
Power MOS FET (for AC or DC loads)
Thyristor (for AC loads)
Triac (for AC loads)
Fixed NO Fixed NC
contact
contact
Output Terminals
General-purpose Relay
Solid State Relay (SSR)
Compact
More compact than an SSR when the same load capacity is
controlled.
Enable downsizing of multi-pole relays.
Etc.
220-VAC resistive load
100
110-VAC inductive load
cosφ = 0.4
100
220-VAC inductive load
cosφ = 0.4
50
50
24-VDC resistive load
30
25
G3PE-225B (L)
G3PE-525B (L)
20
15
6
5
With the standard heat sink
(Y92B-A100 or Y92B-N50)
4 or an aluminum plate measuring
75 × 75 × 3.2 mm (W×H×t)
3
G3PE-215B (L)
G3PE-515B (L)
10
2
7
1.5
No heat sink
Common
24-VDC inductive load
L/R = 7 ms
Example: G3NA
(Reference Information)
Load current (A)
500
Load current (A)
110-VAC resistive load
Number of operations (×104)
Number of operations (×104)
Example: G3PE
(Reference Information)
Others
Selection points
Derating Curves
Inductive load
500
Etc.
Heat dissipation measures are necessary.
This is due to the greater self heat generation that results
from semiconductor loss compared with electromagnetic
relays (General-purpose Relays).
Etc.
Etc.
Electrical Durability Curves
Example: MY2 (Reference Information)
Resistive Load
Zero cross function.
No operation noise.
Power Supplies /
In Addition
Precautions
Limited number of switching operations.
This is because mechanical switching results in contact
erosion.
Enable high-speed and high-frequency switching.
Unlimited number of switching operations.
Consist of semiconductors, so there is no contact erosion
caused by switching.
Energy Conservation Support /
Environment Measure Equipment
Features
Motion / Drives
Input Terminals
1
10
10
0
−30 −20
0
1
2
3
4
5
6
7
Contact current (A)
0
1
2
3
0
20
40
60
80
100
Ambient temperature (°C)
0
−30 −20
0
20
40
60
80 100
Ambient temperature (°C)
Contact current (A)
2
Technical Explanation for Solid-state Relays
Types of SSRs
Sensors
OMRON classifies the SSRs according to type, as shown in the following table.
Type
Load
current
5 A (10 A) or
lower
These relays have the same shape as
plug-in relays and the same sockets can
be used. They are usually built into
control panels and used for I/O
applications for programmable
controllers and other devices.
G3F(D), G3H(D), G3R-I/O, G3RZ,
G3TA etc.
5 A or lower
SSRs with terminal structure for
mounting to PCBs.
The product lineup also includes MOS
FET relays, which are mainly used for
signal switching and connections.
G3MC, G3M, G3S, G3DZ, etc.
Control Components
PCB-mounted
SSRs *1
Separate installation of heat sinks allows
the customers to select heat sinks to
90 A or lower match the housings of the devices they
G3NA, G3NE, etc.
use. These relays are mainly built into the
devices.
Relays
Relays with the
same shapes
The integrated heat sink enables a slim
design. These relays are mainly installed G3PJ, G3PA, G3PE, G3PH etc.
in control panels.
Safety Components
SSRs with
separate heat
sinks
Typical Relays
Switches
SSRs integrated 150 A or
with heat sinks lower
Points
Automation Systems
*1. Refer to the OMRON Electronic Components Web (www.omron.com/ecb) for information on PCB-mounted SSRs.
*2. MOS FET relays have control circuits that are different from those of traditional SSRs.
Refer to MOS FET Relays on page 10 for the MOS FET relay structure, glossary, and other information.
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
3
Technical Explanation for Solid-state Relays
Control Methods
Sensors
Optimum Cycle Control
The basic principle used for optimum cycle control is zero
cross control, which determines the ON/OFF status each half
cycle. A waveform that accurately matches the average
output time is output.
The accuracy of the zero cross function is the same as for
conventionally zero cross control. With conventional zero
cross control, however, the output remains ON continuously
for a specific period of time, whereas with optimum cycle
control, the ON/OFF status is determined each cycle to
improve output accuracy.
Switches
ON/OFF Control
ON/OFF control is a form of control in which a heater is turned
ON and OFF by turning an SSR ON and OFF in response to
voltage output signals from a temperature controller. The
same kind of control is also possible with an electromagnetic
relay, but an SSR must be used to control the heater if it is
turned ON and OFF at intervals of a few seconds over a
period of several years.
Safety Components
ON/OFF status determined each half cycle.
ON OFF
2s
SSR
EJ1 RS-485
(PLC) communications
SSR +
G3ZA
Power
Controller
Phase Control (Single Phase)
With phase control, the output is changed every half-cycle in
response to the current output signals in the range 4 to 20 mA
from a temperature controller. Using this form of control, highprecision temperature control is possible, and is used widely
with semiconductor equipment.
Cycle Control
With cycle control (with the G32A-EA), output voltage is
turned ON/OFF at a fixed interval of 0.2s. Control is performed
in response to current output from a temperature controller in
the range 4 to 20 mA.
OFF
0.2 s
Half a cycle
Power
Controller
Precise temperature control is possible.
The heater’s service life is increased.
Temperature Current output
Controller
SSR + Cycle
Control Unit
Energy Conservation Support /
Environment Measure Equipment
Temperature Current output
Controller
Motion / Drives
ON
ON
Automation Systems
Many heaters can be control using communications.
Noise-less operation with high-speed response is possible.
Control Components
Low-cost, noiseless operation
without maintenance is possible.
OFF
Relays
Temperature Voltage output
Controller
Noiseless operation with
high-speed response is possible.
Power Supplies /
In Addition
Precautions for Cycle Control
With cycle control, an inrush current flows five times every second (because the control cycle is 0.2 s).
With a transformer load, the following problems may occur due to the large inrush current (approximately 10 times the rated
current), and controlling the power at the transformer primary side may not be possible.
(1) The SSR may be destroyed if there is not sufficient leeway in the SSR rating.
(2) The breaker on the load circuit may be tripped.
Others
Common
4
Technical Explanation for Solid-state Relays
Explanation of Terms
Cirsuit functions
Sensors
Photocoupler
Phototriac coupler
Snubber circuit
An element that transfers the input signal while isolating the
input and output.
A circuit that consists of a resistor R and capacitor C , and is
used to prevent faulty ignition of an SSR triac by suppressing
a sudden rise in the voltage applied to the triac.
Switches
Trigger circuit
A circuit that controls a triac trigger signal, which turns the
load current ON and OFF.
Zero Cross Circuit or Zero Cross Function
Safety Components
A circuit which starts operation with the AC load voltage at close to zero-phase.
Output
(load voltage)
ON
OFF
Relays
Input
Without the zero cross function
Control Components
The zero cross function turns ON the SSR when the AC load voltage is close to 0 V, thereby suppressing the noise generated by
the load current when the load current rises quickly.
The generated noise will be partly imposed on the power line and the rest will be released in the air. The zero cross function
effectively suppresses both noise paths.
With the zero cross function
Voltage drops due to sudden change in
current and noise is generated.
Radiated noise
Load
current
SSR
input
Power
supply
voltage
Automation Systems
Power
supply
voltage
Load
current
ON
ON
SSR
input
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
5
Technical Explanation for Solid-state Relays
Input
Sensors
Input impedance
The voltage that serves as the standard value for an input
signal voltage.
The impedance of the input circuit and the resistance of
current-limiting resistors used.
In SSRs, which have a wide range of input voltages, the input
impedance varies with the input voltage, and that causes the
input current to change.
The permissible voltage range within which an input signal
voltage may fluctuate.
Must Operate Voltage
Must Release Voltage
The maximum input voltage when the output status changes
from ON to OFF.
Input current
100
70
Safety Components
The minimum input voltage when the output status changes
from OFF to ON.
Applicable Input Impedance (Typical Examples)
G3F and G3H (without Indicators)
Input impedance (kΩ)
Input current (mA)
Operating voltage
Switches
Rated voltage
50
30
Input current
10
7
5
Relays
The current that flows through the SSR when the rated
voltage is applied.
3
Input impedance
3
5
7
10
30
50 70 100
Control Components
1
Input voltage (V)
Output
Output ON voltage drop
The effective power supply voltage at which the load can be
switched and the SSR can be continuously used when the
SSR is OFF.
The effective value of the AC voltage across the output
terminals when the maximum load current flows through the
SSR under specified cooling conditions (such as the size,
materials, and thickness of heat sink, and the ambient
temperature radiation conditions).
Maximum load current
Motion / Drives
The effective value of the maximum current that can
continuously flow into the output terminals under specified
cooling conditions (such as the size, materials, and thickness
of the heat sink, and the ambient temperature radiating
conditions).
Automation Systems
Load voltage
Minimum load current
The minimum load current at which the SSR can operate
normally.
Energy Conservation Support /
Environment Measure Equipment
Leakage current
The effective value of the current that flows across the output
terminals when a specified load voltage is applied to the SSR
with output turned OFF.
Varistor
Trigger circuit
Snubber circuit
Leakage
current
Power Supplies /
In Addition
OFF
Input circuit
Switching element
200 VAC
Others
Common
6
Technical Explanation for Solid-state Relays
Characteristics
Sensors
Dielectric strength
A time lag between the moment a specified signal voltage is
applied to the input terminals and the output is turned ON.
The effective AC voltage that the SSR can withstand when it
is applied between the input terminals and output terminals or
between the I/O terminals and metal housing (heat sink) for
more than 1 minute.
Release time
A time lag between the moment the applied signal voltage is
turned OFF and the output is turned OFF.
Insulation resistance
Ambient operating temperature and humidity
The ranges of temperature and humidity in which the SSR can
operate normally under specified cooling, input/output
voltage, and current conditions.
Safety Components
The resistance between the input and output terminals or
between the I/O terminals and metal housing (heat sink) when
a DC voltage is applied.
Switches
Operate time
Storage temperature
The temperature range in which the SSR can be stored
without voltage imposition.
Others
Relays
Bleeder resistance
The maximum non-repeat current (approx. 1 or 2 repetitions
per day) that can flow in the SSR. Expressed using the peak
value at the commercial frequency in one cycle.
The resistance connected in parallel to the load in order to
increase apparently small load currents, so that the ON/OFF
of minute currents functions normally.
* This value was conventianally expressed as the "withstand inrush current",
but has been changed to "surge withstand current" because the former term
was easily mistaken for inrush current of loads.
Control Components
Surge withstand current
Bleeder resistance
Counter-electromotive Force
Load
Automation Systems
A voltage that rises very steeply when the load is turned ON
or OFF.
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
7
Technical Explanation for Solid-state Relays
Further Information
SSR Internal Circuit Configuration Examples
Circuit configuration
Photocoupler
Yes
Photocoupler
Input
terminals
Input
circuit
Trigger
circuit
Isolation
Zero cross
circuit
Zero cross
function
Models
Triac
Snubber Output
circuit
terminals
Input
terminals
Trigger
circuit
Phototriac
Input
circuit
Triac
Snubber Output
circuit
terminals
Input
terminals
Input
circuit
Trigger
circuit
Phototriac
Zero cross
circuit
Yes
Trigger
circuit
Zero cross
circuit
G3PE-2(N) (three phases)
Thyristor module
Trigger
circuit
Phototriac coupler
Thyristor
module
Trigger
circuit
Thyristor
module
Trigger
circuit
Phototriac coupler
Zero cross
circuit
Input
terminals
Input circuit
Phototriac
Trigger
circuit
Zero cross
circuit
Trigger
circuit
Input
circuit
Zero cross
circuit
Input
terminals
Snubber Output
circuit
terminals
---
Output
transistor
Counter
electromotive
force
protective
diode
Output
terminals
G3FD, G3HD-X03
G3BD
G3TA-OD
G3NA-D
Photovoltaic coupler
Input
terminals
Input
circuit
Output
Varistor terminals
G3HD-202SN
Output
Varistor terminals
G3FM
Power Supplies /
In Addition
Photovoltaic
coupler
Drive
circuit
DC load
Drive
circuit
Photocoupler
Photocoupler
G3NA-4@@B
G3PH
G3PA-4@@B
Energy Conservation Support /
Environment Measure Equipment
Input
circuit
Motion / Drives
Input
terminals
G3PE-3(N) (three phases)
Snubber Output
circuit
terminals
Thyristor
module
Photocoupler
Photocoupler
Snubber Output
circuit
terminals
Thyristor
module
Phototriac coupler
Yes
Snubber Output
circuit
terminals
Automation Systems
Zero cross
circuit
Phototriac coupler
Yes
Snubber Output
circuit
terminals
Control Components
Zero cross
circuit
AC load
Input circuit
Input
terminals
Snubber Output
circuit
terminals
Relays
Phototriac
Snubber Output
circuit
terminals
G3PA-VD
G3PE (single phase)
G3NA (DC input)
G3NE
G3F-VD
G3H-VD
G3B-VD
Thyristor module
Phototriac coupler
Yes
Triac
G3NE
G3J
G3F
G3H
G3TA-OA
Safety Components
Phototriac coupler
G3H
G3B
G3F
G3NA (AC input)
Switches
Phototriac coupler
No
Sensors
Load
specifications
Photovoltaic
coupler
Input
terminals
Input
circuit
Output
circuit
AC/DC load No
Drive
circuit
Photovoltaic coupler
Others
Common
8
Technical Explanation for Solid-state Relays
Internal Circuit Configuration Examples of SSRs for PCBs
Isolation
Circuit configuration
No
Phototriac
Yes
Phototriac
Input
terminals
Input
circuit
Models
Triac
Snubber Output
circuit terminals
G3CN, G3TB-OA
Snubber Output
circuit terminals
G3R, G3S, G3M, G3MC, and G3CN
Snubber Output
circuit terminals
G3R, G3M
Switches
Photocoupler
Zero cross
circuit
Photocoupler
Yes
Trigger
circuit
Zero cross
function
Sensors
Load
specifications
Input
terminals
Trigger
circuit
Phototriac coupler
AC load
Input
circuit
Triac
Safety Components
Input
circuit
Trigger
circuit
Zero cross
circuit
Phototriac coupler
Input
terminals
Triac
Photocoupler
No
Photovoltaic
coupler
Input
terminals
Input
circuit
Output
transistor
Drive
circuit
Input
terminals
Input
circuit
G3SD, G3CN-D, G3RD, G3TB-OD,
G3R-ID, and G3R-OD
Output
terminals
MOS FET
Photovoltaic coupler
AC/DC
load
Counter
electromotive
force
protective
diode
Relays
---
Drive
circuit
Phototriac coupler
DC load
Output
terminals
G3DZ, G3RZ
Control Components
Note: The above circuit configurations are examples. Circuit configurations will vary depending on the model of the SSR.
SSRs for PCBs Classified by Application and Applicable Loads
1. Classification by Application
Application
Recommended SSRs (Examples)
G3M
G3CN
G3DZ
G3M
G3S
G3DZ
G3MC
G3R
Motion / Drives
Office Automation, Home Automation, and Entertainment
These SSRs are suitable for applications that require frequent
switching, noiseless operation, and greater resistance to vibration,
shock, dust, or gas than the resistance provided by mechanical
relays.
G3TB
Automation Systems
Interface
These SSRs are suitable for applications in which control outputs
from programmable controllers, positioning controllers, and other
devices are transferred to actuators while providing isolation.
In particular, the G3DZ uses a MOS FET as the output element,
which means it has a low leakage current and it can be used in
either an AC or DC circuit.
G3MC
Load
voltage
110 VAC
24 VDC
48 VDC
100 VDC
Maximum
load
current
Load types
Heater
Single-phase
motor
Three-phase
motor
Lamp load
Valve
Transformer *
1A
0.8 A
---
---
0.5 A
0.5 A
50 W
G3R-102@, G3CN-202@, G3MC-202P@
2A
1.6 A
---
---
1A
1A
100 W
G3S-201@, G3R-201@, G3MC-201P@
1A
0.8 A
15 W
50 W
0.5 A
0.5 A
100 W
G3R-202@, G3CN-202@, G3MC-202P@
2A
1.6 A
35 W
100 W
1A
1A
200 W
G3SD-Z01@
1A
0.8 A
---
---
0.5 A
0.5 A
---
G3CN-DX02@, G3RD-X02@
2A
1.6 A
---
---
1A
1A
---
G3CN-DX03@
3A
2.4 A
---
---
1.5 A
1.5 A
---
1.5 A
0.8 A
---
---
0.5 A
0.5 A
---
0.6 A
---
---
---
0.5 A
0.5 A
60 W
G3RD-101@
5 to 240 VAC
G3DZ-2R6PL
5 to 110 VDC
Others
G3R-101@, G3S-201@, G3MC-101P@
Remarks
Power Supplies /
In Addition
220 VAC
Models
Energy Conservation Support /
Environment Measure Equipment
2. Applicable Load Examples
* If the load is a transformer, do not exceed half of the normal startup power.
Common
Note: The maximum load current of an SSR is determined by assuming that a single SSR is mounted alone and connected to a resistive load.
In actual application conditions, power supply voltage fluctuations, control panel space, and other factors can produce conditions that are
more severe than those used for the testing levels.
To allow sufficient leeway for this, using values that are 20% to 30% less than the rated values is recommended.
For inductive loads, such as transformers and motors, even greater leeway is required since inrush currents occur.
9
Technical Explanation for Solid-state Relays
MOS FET Relays
−
Gate
MOS FET relays operate according to the following principles.
(1) The LED lights when the current flows to the input side.
(2) The light from the LED is received by the photodiode array,
which generates electricity to convert the light back to a voltage.
(3) This voltage passes through the control circuit to become the
gate voltage to drive the MOS FET.
Power MOS FET
Drain
Source Varistor
Gate
Output
LED
Control circuit
Photodiode array
Safety Components
Input
+
Switches
2. Structure and Operating Principle
MOS FET relays use photodiode arrays as the light-receiving elements to operate the power MOS FETs that function as their
output elements.
Sensors
1. What Is a MOS FET Relay?
MOS FET relays are a type of SSR that are mounted on PCBs and use power MOS FETs for their output elements. They are
mainly used in signal switching and connection applications.
Drain
Photo Relay
Panasonic
Photo MOS Relay
NEC
MOSFET Relay
OKI Electric
Industry
Photo MOS Switch
Photo DMOS-FET Relay
HP
Solid-state Relay
OMRON
MOS FET Relay
According to OMRON investigation in December 2015.
Automation Systems
Okita Works
Control Components
Toshiba
Relays
3. Names
MOS FET relays have a relatively short history and have been given a variety of names and brands by their manufacturers.
The table in the right shows examples of relays for
Manufacturer
Name in catalog
signal applications (equivalent to the G3VM)
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
10
Technical Explanation for Solid-state Relays
4. Glossary
Symbol
LED forward current
reduction rate
ΔIF/°C
LED reverse voltage
VR
The rated reverse voltage that can be applied between the cathode and the anode
Junction
temperature
Tj
The rated temperature that is allowed at the LED junction
Load voltage
VOFF
Continuous load
current
IO
ON current reduction
rate
ΔIo/°C
The reduction rate for the current that can flow between the relay output terminals in the ON state
in relation to the ambient temperature
Pulse ON current
IOP
The rated current that can flow instantaneously between the relay output terminals in the ON state
Junction
temperature
Tj
The rated temperature that is allowed at the light-receiving circuit junction
Dielectric strength
between input and output
VI-O
The voltage that the isolation between the input and output can withstand
Ambient operating
temperature
Ta
The ambient temperature range in which the relay can be operated without damaging the
functionality of the relay
Storage temperature
Tstg
The ambient temperature range in which the relay may be stored while not operating
Soldering temperature
---
The rated temperature at which the terminals can be soldered without damaging the functionality of the relay
LED forward voltage
VF
The voltage drop between the LED anode and cathode at a certain forward current
Reverse current
IR
The leakage current flowing in the LED reverse direction (between cathode and anode)
Capacitance between
terminals
CT
The electrostatic capacitance between the LED anode and cathode terminals
---
The minimum input current that is required to change the relay output state
To ensure operation of the relay, a current that is equal to or greater than the highest specified value must be used.
IFT
The minimum value of the input current IF that is required to change a normally-open output MOS
FET to the ON state
IFC
The minimum value of the input current IF that is required to change a normally-closed output MOS
FET to the OFF state
---
The maximum input current that is required to release the relay output state.
To ensure release of the relay, the current must be equal to or less than the minimum specified
value.
IFC
The maximum value of the input current IF that must flow to change a normally-open output MOS
FET to the OFF state
IFT
The maximum value of the input current IF that must flow to change a normally-closed output MOS
FET to the ON state
Input
Output
Input
Trigger LED forward
current
Electrical
characteristics
Output
Release LED forward
current
The reduction rate for the current that can flow in the LED forward direction in relation to the
ambient temperature
The rated voltage that can be applied between the relay output terminals when switching the load
or in the OFF state
The peak voltage for AC
The rated current that can flow between the relay output terminals in the ON state under the
specified temperature conditions
The peak current for AC
Maximum resistance
with output ON
RON
The resistance between the relay output terminals in the specified ON state
Current leakage when
the relay is open
ILeak
The leakage current that flows between the relay output terminals when the specified voltage is
applied in the OFF state
Capacitance between
terminals
COFF
The electrostatic capacitance between the relay output terminals in the specified OFF state
CI-O
The electrostatic capacitance between the input and output terminals
Insulation resistance
between I/O terminals
RI-O
The resistance between the input and output terminals at the specified voltage value
tON
The time required for the output waveform to change after the specified input LED current is applied
NO relay: The time required for the output waveform to change from 100% to 10% after the input
goes from OFF to ON state
NC relay: The time required for the output waveform to change from 100% to 10% after the input
goes from ON to OFF state
tOFF
The time required for the output waveform to change after the specified input LED current is
interrupted
NO relay: The time required for the output waveform to change from 0% to 90% after the input
goes from ON to OFF state
NC relay: The time required for the output waveform to change from 0% to 90% after the input
goes from OFF to ON state
ERT
An indicator of the output transition characteristics for fast signals or pulse signals
The ERT is expressed by the following formula, where trin is the input waveform rise time and trout
is the output waveform rise time after relay transition. The lower the value, the less change there
is in the signal, making for good characteristics.
ERT=√(trout2-trin2)
Turn-ON time
Turn-OFF time
Equivalent rise time
Common
The load current that is maintained when current limiting is activated
Others
ILIM
Power Supplies /
In Addition
Limit current
Capacitance between
I/O terminals
Energy Conservation Support /
Environment Measure Equipment
The rated current that can flow momentarily in the LED forward direction
Motion / Drives
IFP
Automation Systems
The rated current that can flow continuously in the LED forward direction
Control Components
IF
Repetitive peak LED
forward current
Relays
LED forward current
Safety Components
---
Switches
Absolute
maximum
ratings
Description
The maximum values that must never be exceeded even instantaneously
Unless otherwise specified, these values are given at Ta = 25°C.
Absolute maximum
ratings
Sensors
Term
11
Technical Explanation for Solid-state Relays
Item
Recommended operating
conditions
---
Load voltage
VDD
Operating LED forward
current
IF
The recommended LED forward current that includes consideration of derating
Continuous load current
IO
The recommended load current that includes consideration of derating
The peak current for AC
Operating temperature
Ta
The recommended ambient operating temperature that includes consideration of derating
MOS FET ON-state
voltage
VON
Relative capacity
between output terminals
COFF/COFF (0V)
The relative ratio based on the capacity between output terminals when the voltage between the
output terminals is 0 V
Current limiting
---
When an overcurrent exceeds a certain value, this function maintains the load current between the
minimum and maximum values of the limit current characteristic.
Suppressing the current to a fixed value protects the relay and the circuit components connected
after the relay.
---
An indicator of the output characteristics in applications that handle high-frequency signals, fast
signals, etc.
C indicates the capacity between the output terminals in the OFF state (COFF), and R indicates the
resistance between the output terminals in the ON state (RON).
If COFF is large, signal transition even when the relay is OFF (signal delay or isolation reduction)
and the delay in the signal rise time for signal transition when the relay is ON (waveform rounding)
are affected. If RON is large, signal transition loss (voltage drop and insertion loss reduction) is
affected. In these applications, small COFF and RON, i.e., a low C x R characteristic, are important.
Relays
Low C×R
The voltage drop between the output terminals when the output MOS FET is in the ON state
Safety Components
Other terms
The recommended load voltage that includes consideration of derating
The peak voltage for AC
Switches
Reference data
Meaning
Indicators of the maximum ratings and electrical performances that include consideration of
derating to ensure high reliability
Each item is an independent condition, so it is not simultaneously satisfy several conditions.
Sensors
Recommended
operating
conditions
Symbol
Control Components
Automation Systems
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
12
Technical Explanation for Solid-state Relays
Application Circuit Examples
Load
Sensor (Black)
(Blue)
5. ON/OFF Control of Three-phase Inductive Motor
Motor
Input signal
source
Threephase
power
supply
Load power supply
Input
signal
source
Incandescent
lamp
Load power supply
Load
heater
4. Forward and Reverse Operation of Single-phase Motor
Motor
Energy Conservation Support /
Environment Measure Equipment
* Resistor to limit advanced phase capacitor discharge current. To
select a suitable resistor, consult with the manufacturer of the
motor.
Motion / Drives
Note: 1. The voltage between the load terminals of either SSR 1
or SSR 2 turned OFF is approximately twice as high as
the supply voltage due to LC coupling. Be sure to apply
an SSR model with a rated output voltage of at least twice
the supply voltage.
For example, if forward/reverse operation is to be
performed on a single-phase inductive motor with a
supply voltage of 100 VAC, the SSR must have an output
voltage of 200 VAC or higher.
2. Make sure that there is a time lag of 30 ms or more to
switch over SW1 and SW2.
Automation Systems
Load power supply
*
Control Components
Input signal
source and
Temperature
Controller
Relays
3. Temperature Control of Electric Furnace
6. Forward and Reverse Operation of Three-phase Motor
Make sure that signals input into the SSR Units are proper if
the SSR Units are applied to the forward and reverse
operation of a threephase motor. If SW1 and SW2 as shown
in the following circuit diagram are switched over
simultaneously, a phase short-circuit will result on the load
side, which may damage the output elements of the SSR
Units. This is because the SSR has a triac as the output
element and the triac is ON until the load current becomes
zero regardless of the absence of input signals into the SSR.
Therefore, make sure that there is a time lag of 30 ms or more
to switch SW1 and SW2.
The SSR may be damaged due to phase short-circuiting if the
SSR malfunctions with noise in the input circuit of the SSR. To
protect the SSR from phase short-circuiting damage, the
protective resistance R may be inserted into the circuit.
The value of the protective resistance R must be determined
according to the surge withstand current of the SSR.
For example, the G3NA-220B withstands an surge current of
220 A. The value of the protective resistance R is obtained
from the following formula:
R > 220 V x 2 /200 A = 1.4 Ω
Considering the circuit current and ON time, insert the
protective resistance into the side that reduces the current
consumption.
Obtain the consumption power of the resistance from the
following formula:
P = I2R x Safety factor
(I = Load current, R = Protective resistance, Safety factor = 3 to 5)
Safety Components
2. Switching Control of Incandescent Lamp
Switches
Load power supply
(Brown)
Sensors
1. Connection to Sensor
The SSR can be connected directly to a proximity sensor or
photoelectric sensor.
Power Supplies /
In Addition
Others
Common
13
Technical Explanation for Solid-state Relays
Sensors
7. Transformer Tap Selection
SSRs can be used to switch between transformer taps. In this
case, however, be aware of voltage induced on the OFF-side
SSR.
The induced voltage increases in proportion to the number of
turns of the winding that is almost equivalent to the tap
voltage.
See the following example. The power supply voltage is at
200 V, N1 is 100, N2 is 100, and SSR2 is ON. Then the
difference in voltage between output terminals of SSR1 is at
400 V (i.e., twice as high as the power supply voltage).
Switches
Safety Components
SSR1
N1
SSR2
Load heater
N2
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
SSR's surge
withstand
current (A)
Load Power Supply Voltage of 110 V
Applicable SSR
Motion / Drives
Inrush
current
(A)
Automation Systems
Transformer
DC resistance
(Ω)
SSR Rated Current
G3@@-240@
The underlined two digits refer to the rated current (i.e., 40A
in the case of the above model).
Three digits may be used for the G3PH only.
G3PH: G3PH-@075B = 75 A
G3PH-@150 = 150 A
Condition 1: The ambient temperature of the SSR (the
temperature inside the panel) is within the rated
value specified.
Condition 2: The right heat sink is provided to the SSR.
Control Components
Load Power Supply Voltage of 100 V
For applicable SSRs based on the DC resistance of the
primary side of the transformer, refer to the tables below.
These tables list SSRs with corresponding surge withstand
current conditions. When you use SSRs in actual applications,
however, check the steady-state currents of the transformers
satisfy the rated current requirement of each SSR.
Relays
8. Inrush Currents to Transformer Loads
The inrush current from a transformer load will reach its peak
when the secondary side of the transformer is open, when no
mutual reactance will work. It will take half a cycle of the power
supply frequency for the inrush current to reach its peak, the
measurement of which without an oscilloscope will be difficult.
The inrush current can be, however, estimated by measuring
the DC resistance of primary side of the transformer. Due to
the self-reactance of the transformer in actual operation, the
actual inrush current will be less than the calculated value.
I peak = V peak/R = ( 2 × V)/R
If the transformer has a DC resistance of 3 . and the load
power supply voltage is 220 V, the following inrush current will
flow.
I peak = (1.414 × 220)/3 = 103.7 A
The surge withstand current of OMRON's SSRs is specified
on condition that the SSRs are used in nonrepetitive operation
(approximately one or two operations per day). If your
application requires repetitive SSR switching, use an SSR
with a withstand surge current twice as high as the rated value
(Ipeak).
In the above case, use the G3@@-220@ with a surge
withstand current of 207.4 A or more.
The DC resistance of the primary side of the transformer can
be calculated from the withstand surge current by using the
following formula.
R = V peak/I peak =( 2 ×V)/I peak
Inrush
current
(A)
SSR's surge
withstand
current (A)
Applicable SSR
G3NE
G3PH
G3P@
G3NA
G3NE
G3PH
30
60
---
-205@
-205@
---
5.2 min.
30
60
---
-205@
-205@
---
1.9 to 4.7
75
150
-210@
-215@
-210@
-210@
---
2.1 to 5.1
75
150
-210@
-215@
-210@
-210@
---
1.3 to 1.8
110
220
-220@
-225@
-220@
-220@
---
1.5 to 2.0
110
220
-220@
-225@
-220@
-220@
---
0.65 to 1.2
220
440
-235@
-240@
-245@
-260@
-240@
---
---
0.71 to 1.4
220
440
-235@
-240@
-245@
-260@
-240@
---
---
0.36 to 0.64
400
800
---
---
---
-2075@
0.39 to 0.70
400
800
---
---
---
-2075@
0.16 to 0.35
900
1,800
---
---
---
-2150@
0.18 to 0.38
900
1,800
---
---
---
-2150@
Common
G3NA
4.8 min.
Others
G3P@
Transformer
DC resistance
(Ω)
14
Technical Explanation for Solid-state Relays
Load Power Supply Voltage of 400 V
Load Power Supply Voltage of 120 V
5.7 min.
Inrush
current
(A)
30
SSR's surge
withstand
current (A)
Applicable SSR
G3P@
G3NA
G3NE
G3PH
Transformer
DC resistance
(Ω)
60
---
-205@
-205@
---
7.6 min.
-210@
-210@
---
5.2 to 7.5
Inrush
current
(A)
SSR's surge
withstand
current (A)
Applicable SSR
G3NA
G3NE
G3PH
150
---
-410@
---
---
110
220
-420@
-430@
-420@
---
---
440
-435@
-445@
---
---
---
75
75
150
1.6 to 2.2
110
220
-220@
-225@
-220@
-220@
---
2.6 to 5.1
220
400
800
---
---
---
-4075@
220
440
-235@
-240@
-245@
-260@
1.5 to 2.5
0.78 to 1.5
-240@
---
---
0.63 to 1.4
900
1,800
---
---
---
-4150@
0.43 to 0.77
400
800
---
---
---
-2075@
0.19 to 0.42
900
1,800
---
---
---
-2150@
Load Power Supply Voltage of 200 V
Transformer
DC resistance
(Ω)
3.8 to 9.4
2.6 to 3.7
75
110
220
8.3 min.
G3P@
G3NA
G3NE
G3PH
60
---
-205@
-205@
---
150
-210@
-215@
-210@
-210@
---
220
-220@
-225@
-220@
440
-235@
-240@
-245@
-260@
-240@
-220@
---
---
---
800
---
---
---
-2075@
0.32 to 0.70
900
1,800
---
---
---
-2150@
10.4 min.
30
Applicable SSR
G3P@
G3NA
G3NE
G3PH
60
---
-205@
-205@
---
-210@
-210@
---
150
2.9 to 4.1
110
220
-220@
-225@
-220@
-220@
---
1.5 to 2.8
220
440
-235@
-240@
-245@
-260@
-240@
---
---
0.78 to 1.4
400
800
---
---
---
-2075@
0.35 to 0.77
900
1,800
---
---
---
-2150@
Load Power Supply Voltage of 240 V
30
G3PH
---
---
-420@
---
---
5.7 to 8.2
110
220
-420@
-430@
2.9 to 5.6
220
440
-435@
-450@
---
---
---
1.6 to 2.8
400
800
---
---
---
-4075@
0.70 to 1.5
900
1,800
---
---
---
-4150@
Applicable SSR
G3P@
G3NA
G3NE
G3PH
60
---
-205@
-205@
---
-210@
-210@
---
75
150
3.1 to 4.5
110
220
-220@
-225@
-220@
-220@
---
1.6 to 3.0
220
440
-235@
-240@
-245@
-260@
-240@
---
---
0.85 to 1.5
400
800
---
---
---
-2075@
0.38 to 0.84
900
1,800
---
---
---
-2150@
9.1 min.
Inrush
current
(A)
75
SSR's surge
withstand
current (A)
Applicable SSR
G3P@
G3NA
G3NE
G3PH
150
---
-410@
---
---
-420@
---
---
---
---
---
6.2 to 9.0
110
220
-420@
-430@
3.1 to 6.1
220
440
-450@
Others
4.6 to 11.3
-210@
-215@
Transformer
DC resistance
(Ω)
Power Supplies /
In Addition
11.4 min.
SSR's surge
withstand
current (A)
G3NE
-410@
Energy Conservation Support /
Environment Measure Equipment
75
-210@
-215@
Inrush
current
(A)
G3NA
---
Motion / Drives
4.2 to
10.3
Transformer
DC resistance
(Ω)
G3P@
150
Automation Systems
Load Power Supply Voltage of 220 V
SSR's surge
withstand
current (A)
Applicable SSR
Load Power Supply Voltage of 480 V
400
Inrush
current
(A)
75
SSR's surge
withstand
current (A)
Applicable SSR
0.71 to 1.2
Transformer
DC resistance
(Ω)
Inrush
current
(A)
Control Components
1.3 to 2.5
30
SSR's surge
withstand
current (A)
Transformer
DC resistance
(Ω)
Relays
9.5 min.
Inrush
current
(A)
Load Power Supply Voltage of 440 V
Safety Components
2.3 to 5.6
-210@
-215@
Switches
G3P@
Sensors
Transformer
DC resistance
(Ω)
Common
15
Technical Explanation for Solid-state Relays
Location
Input area
Whole Unit
Result
Input element damage
Overvoltage
Output element damage
Overcurrent
Ambient temperature
exceeding maximum
Output element damage
Poor heat radiation
Peak current (A)
IF
IL
Output terminal
Output circuit
Input indicator
Input circuit
Input terminal
Common
A Commercially available heat sink equivalent to an
OMRON-made one can be used, on conditoin that the
thermal resistance of the heat sink is lower than that of the
OMRON-made one.
For example, the Y92B-N100 has a thermal resistance of
1.63°C/W.
If the thermal resistance of the standard heat sink is lower
than this value (i.e., 1.5°C/W, for example), the standard
heat sink can be used for the G3NA-220B.
Thermal resistance indicates a temperature rise per unit
(W). The smaller the value is, the higher the efficiency of
heat radiation will be.
Others
3. Operation Indicator
The operation indicator turns ON when current flows through
the input circuit. It does not indicate that the output element is
ON.
Power Supplies /
In Addition
Time (unit: s)
Energy Conservation Support /
Environment Measure Equipment
2. Heat Sink Selection
SSR models with no heat sinks (i.e., the G3NA, G3NE, and
three-phase G3PE) need external heat sinks. When using
any of these SSRs, select the ideal combination of the SSR
and heat sink according to the load current.
The following combinations are ideal, for example.
G3NA-220B: Y92B-N100,
G3NE-210T(L): Y92B-N50,
G3PE-235B-3H: Y92B-P200
IS
Motion / Drives
IS > IF > IL
Automation Systems
2. Overcurrent Protection
A short-circuit current or an overcurrent flowing through the
load of the SSR will damage the output element of the SSR.
Connect a quick-break fuse in series with the load as an
overcurrent protection measure.
Design a circuit so that the protection coordination conditions
for the quick-break fuse satisfy the relationship between the
SSR surge resistance (IS), quick-break fuse current-limiting
feature (IF), and the load inrush current (IL), shown in the
following chart.
Control Components
Output area
Cause
Overvoltage
Relays
1. SSR Heat Radiation
Triacs, thyristors, and power transistors are
semiconductors that can be used for an SSR output circuit.
These semiconductors have a residual voltage internally
when the SSR is turned ON. This is called output-ON
voltage drop. If the SSR has a load current, the Joule
heating of the SSR will result consequently. The heating
value P (W) is obtained from the following formula.
Heating value P (W) = Output-ON voltage drop (V) ×
Carry current (A)
For example, if a load current of 8 A flows from the G3NA210B, the following heating value will be obtained:
P = 1.6 V × 8 A = 12.8 W
If the SSR employs power MOS FET for SSR output, the
heating value is calculated from the ON-state resistance of
the power MOS FET instead.
In that case, the heating value P (W) can be calculated with
the following formula:
P (W) = Load current2 (A) × ON-state resistance (Ω)
If the G3RZ is used with a load current of 0.5 A, the
following heating value will be obtained:
P (W) = 0.52 A × 2.4 Ω = 0.6 W
The ON-state resistance of a power MOS FET increases
with an increase in the junction temperature of a power
MOS FET.
Therefore, the ON-state resistance varies while the SSR is
in operation. If the load current is 80% of the load current or
higher, as a simple method, the ON-state resistance will be
multiplied by 1.5.
P (W) = 12 A × 2.4 Ω × 1.5 = 3.6 W
The SSR in usual operation switches a current of
approximately 5 A with no heat sink used. If the SSR must
switch a higher current, a heat sink will be required. The
higher the load current is, the larger the heat sink size will
be. If the switching current is 10 A or more, the size of the
SSR with a heat sink will exceed a single mechanical relay.
This is a disadvantage of SSRs in terms of circuit
downsizing.
Safety Components
1. Error Mode
The SSR is an optimum relay for high-frequency switching
and high-speed switching, but misuse or mishandling of the
SSR may damage the elements and cause other problems.
The SSR consists of semiconductor elements, and will break
down if these elements are damaged by surge voltage or
overcurrent. Most faults associated with the elements are
short-circuit malfunctions, whereby the load cannot be turned
OFF.
Therefore, to provide a fail-safe measure for a control circuit
using an SSR, design a circuit in which a contactor or circuit
breaker on the load power supply side will turn OFF the load
when the SSR causes an error. Do not design a circuit that
turns OFF the load power supply only with the SSR. For
example, if the SSR causes a half-wave error in a circuit in
which an AC motor is connected as a load, DC energizing
may cause overcurrent to flow through the motor, thus burning
the motor. To prevent this from occurring, design a circuit in
which a circuit breaker stops overcurrent to the motor.
Switches
Heat Radiation Designing
Sensors
Fail-safe Concept
16
Technical Explanation for Solid-state Relays
Motion / Drives
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Distance
Axial-flow fan: OMRON’s R87B, R87F, and R87T Series
Air conditioner for control panel: Apiste’s ENC Series
Automation Systems
Cool fluid
tc
Control Components
Hot fluid
Relays
Fixed wall
th
Safety Components
Temperature
Usually, a ventilation fan with a required capacity will be
installed. If the fan is not sufficient, an air conditioner for the
control panel will be installed. The air conditioner is ideal for
the long-time operation of the control panel because it will
effectively dehumidify the interior of the control panel and
eliminate dust gathering in the control panel.
Switches
4. Control Panel Heat Radiation Designing
Control equipment using semiconductors will generate
heat, regardless of whether SSRs are used or not. The
failure rate of semiconductors greatly increases when the
ambient temperature rises. It is said that the failure rate of
semiconductors will be doubled when the temperature rises
10°C (Arrhenius model).
Therefore, it is absolutely necessary to suppress the
interior temperature rise of the control panel in order to
ensure the long, reliable operation of the control equipment.
Heat-radiating devices in a wide variety exists in the control
panel. As a matter of course, it is necessary to consider the
total temperature rise as well as local temperature rise of
the control panel. The following description provides
information on the total heat radiation designing of the
control panel.
As shown below, the heat conductivity Q will be obtained
from the following formula, provided that th and tc are the
temperature of the hot fluid and that of the cool fluid
separated by the fixed wall.
Q = k (th - tc) A
Where, k is an overall heat transfer coefficient (W/m2°C).
This formula is called a formula of overall heat transfer.
When this formula is applicable to the heat conductivity of
the control panel under the following conditions, the heat
conductivity Q will be obtained as shown below.
Average rate of overall heat transfer of control panel:
k (W/m2°C)
Internal temperature of control panel: Th (°C)
Ambient temperature: Tc (°C)
Surface area of control panel: S (m2)
Q = k × (Th - Tc) × S
The required cooling capacity is obtained from the following
formula.
Desired internal temperature of control panel: Th (°C)
Total internal heat radiation of control panel: P1 (W)
Required cooling capacity: P2 (W)
P2 = P1 - k × (Th - Tc) × S
The overall heat transfer coefficient k of a standard fixed wall
in a place with natural air ventilation will be 4 to 12 (W/m2°C).
In the case of a standard control panel with no cooling fan, it is
an empirically known fact that a coefficient of 4 to 6 (W/m2°C)
is practically applicable. Based on this, the required cooling
capacity of the control panel is obtained as shown below.
Example
• Desired internal temperature of control panel: 40°C
• Ambient temperature: 30°C
• Control panel size 2.5 × 2 × 0.5 m (W × H × D)
Self-sustained control panel (with the bottom area
excluded from the calculation of the surface area)
• SSRs: 20 G3PA-240B Units in continuous operation at 30 A.
• Total heat radiation of all control devices except SSRs:
500 W
Total heat radiation of control panel: P1
P1 = Output-ON voltage drop 1.6 V × Load current 30 A
× 20 SSRs + Total heat radiation of all control
devices except SSRs
= 960 W + 500 W = 1460 W
Heat radiation from control panel: Q2
Q2 = Rate of overall heat transfer 5 × (40°C − 30°C) ×
(2.5 m × 2 m × 2 + 0.5m × 2 m × 2 + 2.5 m × 0.5 m)
= 662.5 W
Therefore, the required cooling capacity P2 will be obtained
from the following formula:
P2 = 1,460 − 663 = 797 W
Therefore, the heat radiation from the surface of the control
panel is insufficient. More than a heat quantity of 797 W
needs to be radiated outside the control panel.
Sensors
3. Calculating Heat Sink Area
An SSR with an external heat sink can be directly mounted
to control panels under the following conditions.
• If the heat sink is made of steel used for standard panels,
do not apply a current as high as or higher than 10 A,
because the heat conductivity of steel is less than that of
aluminum. Heat conductivity (in units of W·m·°C) varies with
the material as described below.
Steel: 20 to 50
Aluminum: 150 to 220
The use of an aluminum-made heat sink is recommended
if the SSR is directly mounted to control panels. Refer to the
data sheet of the SSR for the required heat sink area.
• Apply heat-dissipation silicone grease (e.g., the YG6260
from Momentive Performance Materials or the G746 from
Shin-Etsu Silicones) or attach a heat conductive sheet
between the SSR and heat sink. There will be a space
between the SSR and heat sink attached to the SSR.
Therefore, the generated heat of the SSR cannot be
radiated properly without the grease. As a result, the SSR
may be overheated and damaged or deteriorated.
The heat dissipation capacity of a heat conduction sheet is
generally inferior to that of silicone grease. If a heat
conduction sheet is used, reduce the load current by
approximately 10% from the Load Current vs. Ambient
Temperature Characteristics graph.
Common
17
Technical Explanation for Solid-state Relays
Air Conditioners for Control Panels
Not only do air conditioners offer the highest cooling capacity,
they also offer resistance to dust and humidity by mutually
isolating the inside and outside of the control panel.
Sensors
5. Types of Cooling Device
Axial-flow Fans (for Ventilation)
These products are used for normal
types of cooling and ventilation.
OMRON’s Axial-flow Fan lineup
includes the R87F and R87T Series.
Note: OMRON does not produce air conditioners for control panels.
Switches
Safety Components
Heat Exchangers
Heat exchangers dissipate the heat inside
control panels along heat pipes. Using a
heat exchanger enables the inside and
outside of the control panel to be mutually
isolated, allowing use in locations subject
to dust or oil mist.
Note: OMRON does not produce heat
exchangers.
Relays
Panel Mounting
2. Relationship between SSRs and Ducts
Duct Depth
50 mm max.
(The recommended
width is half as large
as the depth of G3PA
or less)
Duct
Duct
Between duct
and G3PA
Automation Systems
1. SSR Mounting Pitch
Panel Mounting
Duct
Motion / Drives
60 mm min.
Mounting direction
Better
Vertical
direction
G3PA
Energy Conservation Support /
Environment Measure Equipment
Vertical direction
G3PA
100 mm
Mounting surface
10 mm
Mounting surface
G3PA
30 mm min.
Between duct
and G3PA
Close Mounting can be performed
with no more than three SSRs.
For four or more SSRs leave a gap of
at least 10 mm.
Do not surround the SSR
with ducts, otherwise the
heat radiation of the SSR
will be adversely affected.
Duct
Power Supplies /
In Addition
Close Mounting
Duct
Use a short duct in the
depth direction.
Better
Duct
G3PA
Metal
base
Duct
Common
If the ducts cannot be shortened,
place the SSRs on a metal base
so that it is not surrounded by the
ducts.
Air flow
Others
Mounting surface
Space between 80 mm min.
G3PAs
Control Components
If SSRs are mounted inside an enclosed panel, the radiated heat of the SSR will stay inside, thus not only dropping the carrycurrent capacity of the SSRs but also adversely affecting other electronic device mounted inside. Open some ventilation holes on
the upper and lower sides of the control panel before use. The following illustrations provide a recommended mounting example
of G3PA Units. They provide only a rough guide and so be sure to confirm operating conditions using the procedure detailed in
4. Confirmation after Installation on page 18.
18
Technical Explanation for Solid-state Relays
3. Ventilation
Sensors
Be aware of air flow
Duct
Duct
Duct
Ventilation
outlet
G3PA
Air inlet
Duct
Duct
Energy Conservation Support /
Environment Measure Equipment
Figure 1: Basic Measurement Position
for Ambient Temperature
Motion / Drives
Ambient
temperature
measurement
position
Definition of Ambient Temperature
SSRs basically dissipate heat by natural convection.
Therefore, the ambient temperature is the temperature of
the air that dissipates the heat of the SSR.
Automation Systems
100 mm
(3) If more than one row of SSRs are mounted in the control
panel, measure the ambient temperature of each row,
and use the position with the highest temperature.
Consult your OMRON dealer, however, if the
measurement conditions are different from those given
above.
Control Components
4. Confirmation after Installation
The above conditions are typical examples confirmed by
OMRON. The application environment may affect conditions
and ultimately the ambient temperature must be measured
under power application to confirm that the load currentambient temperature ratings are satisfied for each model.
Ambient Temperature Measurement Conditions
(1) Measure the ambient temperature under the power
application conditions that will produce the highest
temperature in the control panel and after the ambient
temperature has become saturated.
(2) Refer to Figure 1 for the measurement position. If there is
a duct or other equipment within the measurement
distance of 100 mm, refer to Figure 2. If the side
temperature cannot be measured, refer to Figure 3.
Relays
If the air inlet or air outlet has a filter, clean the filter regularly to prevent it from clogging and ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, or otherwise the objects may obstruct the proper ventilation of
the control panel.
A heat exchanger, if used, should be located in front of the G3PA Units to ensure the efficiency of the heat exchanger.
Safety Components
Duct
Switches
G3PA
G3PA
L/2
Other
Device
Power Supplies /
In Addition
Ambient
temperature
measurement
position
L (100 mm or less)
Others
Figure 2: Measurement Position when a
Duct or Other Device is Present
Ambient
temperature
measurement
range
Common
100 mm
Center
Figure 3: Measurement Position when Side
Temperature Cannot be Measured
19
Technical Explanation for Solid-state Relays
FAQs
Sensors
Structures and Functions of SSRs
What is the difference in switching with a
thyristor and a triac?
Momentive Performance Materials: YG6260
Shin-Etsu Silicones: G746, G747
Control Components
Automation Systems
Note: dv/dt = Voltage rise rate.
Relays
There is a difference between thyristors and triacs in
response time to rapid voltage rises or drops.
This difference is expressed by dv/dt (V/μs). This
value of thyristors is larger than that of triacs.
Triacs can switch inductive motor loads that are as
high as 3.7 kW.
Furthermore, a single triac can be the functional
equivalent of a pair of thyristors connected in an
inverse parallel connection and can thus be used to
contribute to downsizing SSRs.
Safety Components
Available Silicone Grease Products for
Heat Dissipation
Thyristors connected in an
inverse parallel connection
Triac
Special silicone grease is used to aid heat dissipation.
The heat conduction of this special silicone grease is
five to ten times higher than that of standard silicone
grease.
This special silicone grease is used to fill the space
between a heat-radiating part, such as an SSR, and
the heat sink to improve the heat conduction of the
SSR.
Unless special silicone grease is applied, the
generated heat of the SSR will not be radiated
properly. As a result, the SSR may break or
deteriorate due to overheating.
Switches
There is no difference between them as long as
resistive loads are switched. For inductive loads,
however, thyristors are superior to triacs due to the
inverse parallel connection of the thyristors.
For the switching element, an SSR uses either a triac
or a pair of thyristors connected in an inverse parallel
connection.
What is silicone grease?
V
Motion / Drives
ΔV
ΔV/ΔT = dv/dt: Voltage rise rate
Resistive load
Inductive load
Over 40 A
3.7 kW max.
Over 3.7 kW
Triac
OK
OK
OK
Not as good
Two
thyristors
OK
OK
OK
OK
Power Supplies /
In Addition
40 A max.
Energy Conservation Support /
Environment Measure Equipment
T
ΔT
Others
Common
20
Technical Explanation for Solid-state Relays
A high inrush current will flow when the lamp is
turned ON, for example. When the zero cross
function is used, the load current always starts
from a point close to 0 V. This will suppress the
inrush current more than SSRs without the zero
cross function.
Without the zero cross function:
Voltage drops due to sudden change
in current and noise is generated.
Radiated noise
SSR
input
G3NE-220T
ON
Power
supply
voltage
150
Non-repetitive
100
Repetitive
SSR
input
ON
Once or
twice a day
500 1,000
5,000
Carry current (ms)
Motion / Drives
Load
current
50 Region allowing any
number of repetitions
in one day
0
10
30 50 100 200
Automation Systems
With the zero cross function:
Region not
allowing
even one
occurrence
200
Control Components
Load
current
Surge current (A. peak)
Power
supply
voltage
Relays
The datasheet of an SSR gives the non-repetitive
surge withstand current of the SSR. The concept of
the surge withstand current of an SSR is the same as
the absolute maximum rating of an element. If the
surge current exceeds the surge withstand current
even once, the SSR will be destroyed. Therefore,
check that the maximum surge current of the SSR in
normal ON/OFF operation is half of the surge
withstand current. Unlike mechanical relays that may
result in contact abrasion, the SSR will provide good
performance as long as the surge current is no higher
than half of the surge withstand current. If the SSR is
in continuous ON/OFF operation and a current
exceeding the rated value flows frequently, however,
the SSR may overheat and a malfunction may result.
Check that the SSR is operated with no overheating.
Roughly speaking, surge currents that are less than
the non-repetitive surge current and greater than the
repetitive surge current can be withstood once or
twice a day (e.g., when power is supplied to devices
once a day).
Safety Components
The zero cross function turns ON the SSR when the
AC load voltage is close to 0 V, thus suppressing the
noise generation of the load current when the load
current rises quickly.
The generated noise will be partly imposed on the
power line and the rest will be released in the air. The
zero cross function effectively suppresses both noise
paths.
Switches
What is the non-repetitive surge current?
Sensors
What is the zero cross function?
Energy Conservation Support /
Environment Measure Equipment
Power Supplies /
In Addition
Others
Common
21
Technical Explanation for Solid-state Relays
Connections and Circuits for SSRs
Yes, it is. SSRs are connected in series mainly to prevent
short circuit failures. Each SSR connected in series
shares the burden of the surge voltage. The
overvoltage is divided among the SSRs, reducing the
load on each.
A high operating voltage, however, cannot be applied
to the SSRs connected in series. The reason is that
the SSRs cannot share the burden of the load voltage
due to the difference between the SSRs in operating
time and reset time when the load is switched.
• Do not connect two or more SSRs in parallel to
drive a load exceeding the capacity each SSRs.
The SSRs may fail to operate.
Input
INPUT
Output
SSR
LOAD
G3J
2.2kW
2.2kW
LOAD
G3J
Example:
It is not possible to
countrol a 3.7-kW heater
with two SSRs for 2.2kW
connected in parallel.
Is it possible to connect two 200-VAC SSRs in
series to a 400-VAC load?
SSR
Effective
ness
Diode
Diode + Zener
diode
Varistor
CR
Most effective
Most effective
Somewhat
effective
Ineffective
+
+
+
+
−
−
−
−
Reference
(1) Selecting a Diode
Withstand voltage = VRM ≥ Power supply voltage × 2
Forward current = IF ≥ load current
(2) Selecting a Zener Diode
Zener voltage = Vz < (Voltage between SSR’s collector
and emitter) * − (Power supply voltage + 2 V)
Zener surge power = PRSM > VZ × Load current × Safety
factor (2 to 3)
Others
Note: When the Zener voltage is increased (VZ), the Zener diode
capacity (PRSM) is also increased.
Common
As an absorption element, the diode is the most
effective element to suppress counter-electromotive
force. The release time for the solenoid or
electromagnetic valve will, however, increase. Be sure
you check the circuit before using it. To shorten the
time, connect a Zener diode and a regular diode in
series. The release time will be shortened at the same
rate that the Zener voltage (Vz) of the Zener diode is
increased.
Absorption
element
Power Supplies /
In Addition
Load
INPUT
Table 1. Absorption Element Example
Energy Conservation Support /
Environment Measure Equipment
Output Noise Surge Countermeasures for SSRs for
DC Load Switching
When an inductive load, such as a solenoid or
electromagnetic valve, is connected, connect a diode
that prevents counter-electromotive force. If the
counter-electromotive force exceeds the withstand
voltage of the SSR output element, it could result in
damage to the SSR output element. To prevent this,
insert the element parallel to the load, as shown in the
following diagram and table.
Motion / Drives
What need to be done for surge absorption elements for SSRs for DC loads?
Automation Systems
No, it is not. The two SSRs are slightly different to
each other in operate time. Therefore, 400 VAC will
be applied instantaneously on the SSR with a longer
operate time.
Control Components
M 3.7kW
SSR
Relays
Load
INPUT
Safety Components
Yes, it is. SSRs are connected in parallel mainly to
prevent open circuit failures. Usually, only one of the
SSR is turned ON due to the difference in output ON
voltage drop between the SSRs.
Therefore, it is not possible to increase the load
current by connecting the SSRs in parallel. If an ONstate SSR is open in operation, the other SSR will turn
ON when the voltage is applied, thus maintaining the
switching operation of the load.
Switches
Is it possible to connect Solid-state Relay for
AC loads in series (AND circuit)?
Sensors
Is it possible to connect Solid-state Relays for
outputs in parallel (OR circuit)?
22
Technical Explanation for Solid-state Relays
Mounting Methods for SSRs
Vertical direction
Load current (A)
G3PE-215B
Panel
Flat Mounting
The SSR may be mounted on a flat
surface, provided that the load current
applied is 30% lower than the rated
load current.
20
3
15
13
12
10
Motion / Drives
8
5.7
5
−20
0
20
40
60
80 100
Ambient temperature (ºC)
0
20
40
60
80 100
Ambient temperature (ºC)
G3PE-225B
30
25
Energy Conservation Support /
Environment Measure Equipment
0
−40
3
20
19
Power Supplies /
In Addition
Load current (A)
Panel
G3PE
Close Mounting (3 or 8 SSRs)
Automation Systems
Vertical direction
Vertical mounting
Mount the SSR vertically.
For close mounting of two or three SSRs,
limit the load current to 80% or less.
Control Components
DIN track
G3PA-210B-VD
G3PA-220B-VD
G3PA-240B-VD
Relays
Vertical direction
G3PA
Safety Components
In the case of close mounting of SSRs, check the
relevant data in the SSR datasheet. If there is no data,
check that the applied load current is 70% of the rated
load current. A 100% load current can be applied if
groups of three SSRs are mounted in a single row
with a space of 10 mm between adjacent groups. If
the SSRs are mounted in two or more rows, it is
necessary to confirm the temperature rise of the SSR
separately. For close mounting of SSRs with heat
sinks, reduce the load current to 80% of the rated load
current. Refer to the SSR’s datasheet for details.
Switches
An SSR consists of semiconductor elements.
Therefore, unlike mechanical relays that incorporate
movable parts, gravity changes have no influence on
the characteristics of the SSR.
Changes in the heat radiation of an SSR may,
however, limit the carry current of the SSR. An SSR
should be mounted vertically. If the SSR has to be
mounted horizontally, check with the SSR’s
datasheet. If there is no data available for the SSR,
use with a load current at least 30% lower than the
rated load current.
Sensors
What precautions are required for close
mounting?
Does an SSR have a mounting direction?
8
15
10
8
7
5
−20
Others
0
−40
Close Mounting Example
Common
DIN track
23
Technical Explanation for Solid-state Relays
Failure Examples and Safety Precautions for SSRs
Single-phase
Load current of
100 V
recommended SSR
25 W
AC 2 to 3 A
40 W
AC 5 A
90 W
Single-phase
Load current of
200 V
recommended SSR
25 W
AC 2 to 3 A
40 W
SSR
LOAD
R = 12 Ω, 20 W
60 W
AC 5 A
Output
Load condition
Short
Does not turn
ON.
Open
Output triac short circuit
(80% of failures)
Does not turn
OFF.
Output triac open circuit
(20% of failures)
Does not turn
ON.
Precautions for Forward/Reverse Operation
(1) In the following circuit, if SSR1 and SSR2 are
turned ON simultaneously, the discharge
current, i, of the capacitor may damage the
SSRs. Therefore, make sure that there is a time
lag of 30 ms or more to switch SW1 and SW2.
If malfunction of the SSRs is possible due to
external noise or the counter-electromotive
force of the motor, connect R to suppress
discharge current i in series with either SSR1 or
SSR2, whichever is less frequently used. A CR
absorber (consisting of 0.1-μF capacitor
withstanding 630 V and 22-Ω resistor
withstanding 2 W) can be connected in parallel
to each SSR to suppress the malfunctioning of
the SSRs.
Insert resistance.
SW1
+
INPUT
SW2
−
Motor
SSR
1
SSR
2
Others
Common
(2) When the motor is in forward/reverse
operation, a voltage that is twice as high as the
power supply voltage may be applied on an
SSR that is OFF due to the LC resonance of the
motor.
When you select an SSR, be careful that this
voltage does not exceed the rated load voltage
of the SSR. (It is necessary to determine
whether use is possible by measuring the
actual voltage applied to the SSR on the OFF
side.)
Power Supplies /
In Addition
+
INPUT
−
Energy Conservation Support /
Environment Measure Equipment
Input
Failure
R = 8 Ω,
40 W
Motion / Drives
OMRON's data indicates that most failures are
caused by overvoltage or overcurrent as a result of
the shortcircuiting of SSRs. This data is based on
SSR output conditions, which include those resulting
from the open or short circuit failures on the input side.
R = 12 Ω, 10 W
Automation Systems
What kind of failure do SSRs have most
frequently?
Protection of motor in
forward/reverse
operation
Load power supply
INPUT
R = 3 Ω,
40 to 50 W
Control Components
Load
R = 6 Ω, 10 W
R = 4 Ω, 20 W
60 W
90 W
100 W lamp
Protection of motor in
forward/reverse
operation
Relays
Connect a load and power supply, and check the voltage
of the load terminals with the input ON and OFF. The
output voltage will be close to the load power supply
voltage with the SSR turned OFF. The voltage will
drop to approximately 1 V with the SSR turned ON.
This is more clearly checked if the dummy load is a
lamp with an output of about 100 W. (However, lamps
that have capacities within the rated ranges of the
SSRs must be used.)
Refer the following table for the protection of capacitor
motors driven by SSRs.
Safety Components
Testing Method
What precautions are necessary for forward/
reverse operation of the singlephase motor?
Switches
No, that is not possible.
The voltage and current in the tester’s internal circuits
are too low to check the operation of the
semiconductor element in the SSR (a triac or
thyristor). The SSR can be tested as described below
if a load is connected.
Sensors
We think an SSR is faulty. Can a voltage tester
be used to check an SSR to see if current is
flowing?
24
Technical Explanation for Solid-state Relays
Relays with the Same Shapes: Power MOS FET Relays
(1) There are SSRs for DC loads and SSRs for AC
loads.
With power MOS FET relays, because 2 MOS FET
relays are connected in series in the way shown on
the right, the load power supply can be connected in
either direction. Also, because power MOS FET
elements have a high dielectric strength, they can be
used for AC loads, where the polarity changes every
cycle.
SSR for DC Loads (e.g., G3HD-X03)
Input circuit
Output
transistor
L
L
SSR for AC Loads (e.g., G3H)
L
Trigger circuit
Input circuit
Triac
L
Direction of current
Relays
Zero cross
circuit
Photocoupler
Safety Components
Drive circuit
Photocoupler
Switches
Why can MOS FET relays be used for both AC
and DC loads?
Sensors
What are the differences between SSRs and
power MOS FET relays?
What kind of applications can power MOS FET
relays be used for?
(2) The leakage current for power MOS FET relays is
small compared to that for SSRs.
SSRs
Bleeder resistance
SSR
Note: Confirm the type of input voltage, polarity, and
output capacity before application.
Snubber circuit
The leakage current is very small (10 μA max.) and so
the lamp does not light. This is because a snubber
circuit is not required to protect the MOS FET output
element. A varistor is used to protect the MOS FET.
Power MOS FET relay
(3)Applications with high-voltage DC loads. In order to
switch a 100-VDC, 1-A load with a relay, an
MM2XP or equivalent is required. With the G3RZ
power MOS FET relay, however, switching at this
size is possible.
Power Supplies /
In Addition
(4)Applications where SSRs are used with a bleeder
resistance. The leakage current for power MOS
FET relays is very small (10 μA max.) and so a
bleeder resistance is not required.
Energy Conservation Support /
Environment Measure Equipment
Power MOS FET Relays
Motion / Drives
(2)Applications with high-frequency switching of
loads, such as for solenoid valves with internally,
fully rectified waves, where the relay (e.g., G2R)
has to be replaced frequently.
Power MOS FET relays have a longer lifetime than
other relays and so the replacement frequency is
less.
The terminal arrangement of the G3RZ is
compatible with that of the G2R-1A-S, so these
models can be exchanged.
Automation Systems
The lamp (see below) is faintly light by the leakage
current. A bleeder resistance is added to prevent this.
With SSRs, a snubber circuit is required to protect the
output element.
(1)Applications where it is not known whether the load
connected to the relay is AC or DC.
Example: Alarm output of robot controller.
Control Components
Power MOS FET relays can be used for both
DC loads or AC loads.
A bleeder resistance is not required and so circuits
can be simplified and production costs reduced.
Others
Common
25
Technical Explanation for Solid-state Relays
Maintenance Guidelines
Failure rate
Initial failure
period
Random failure
period
Time
Life
expectancy
Wear-out failure
period
Cause
Cause of failure
Maintenance method
Maintenance period
guideline
Remarks
Overvoltage
• Lightning surge or counterelectromotive force
Load
When failure occurs
Random failure of
electronic
components
Random failure of electronic components
(semiconductors)
• Manufacturing defects or early failure of
electronic components
Replace the SSR.
When failure occurs
Manufacturing
defects
Manufacturer-caused defects
• Manufacturing defects during the
manufacturing process
• Fault resulting from design errors
Replace the SSR.
When failure occurs
Insulation
deterioration
Insulation deterioration resulting from dirt
around the SSR terminals
High humidity can worsen insulation
deterioration.
Maintenance of
insulation performance
with periodic inspection
and cleaning
--* Determine based
on the application
environment.
Metal fatigue or
solder
deterioration of
joints
Materials with different thermal expansion
coefficients are bonded. Therefore, the
buildup of stress resulting from long-term
temperature fluctuations can result in
metal fatigue
Replace the SSR.
10 yr
* Periodic inspection
that is appropriate
to the application
environment is
recommended.
Depends on the application
environment, such as the heat
dissipation environment and
load ratio.
Common
Trouble Shooting
First the heat dissipation
environment of the application
location must be understood.
• Installation conditions,
ambient temperature, and
environment
• Layout in terms of air
convection
Etc.
Others
--* Determine the
maintenance period
based on the
application
environment.
Power Supplies /
In Addition
Deterioration of
operating
environment
(temperature
conditions)
Maintenance of heat
dissipation environment
Deterioration of heat dissipation
with periodic inspection
environment
and cleaning
• Blockage of ventilation holes
* If the heat dissipation
• Malfunction of ventilation fans, panel
environment
coolers, etc.
continues to worsen, it
• Dirt on heat sinks (fans) for SSRs
could accelerate
Etc.
further deterioration or
metal fatigue.
Energy Conservation Support /
Environment Measure Equipment
Wear-out
failure period
Replace the SSR.
Motion / Drives
Initial or
random
failure period
Etc.
Overcurrent
• Startup current, load short circuit, or
ground fault
Etc.
Automation Systems
Bathtub
curve failure
pattern
Control Components
* The life expectancy is calculated based on OMRON’s testing standards. The actual service life will depend on the application environment.
Relays
(1) Initial Failure Period
This is the period during which the failure rate (due to poor
design, manufacturing defects, or random failure of
components) decreases.
(2) Random Failure Period
This is the period in which failure rate remains steady.
(3) Wear-out Failure Period
This is the period during which the failure rate increases.
Safety Components
Life Expectancies (Expected Value) of SSRs
OMRON designs SSRs to have a life expectancy of at least
10 years if used as rated.
SSR
Bathtub Curve
MTTF
(reciprocal of failure rate)
Switches
Bathtub Curve for Electronic Components and Devices
Electronic components and electronic devices all experience
characteristic changes, such as the deterioration of the
materials they are composed of and their joints or reduced
LED light-emitting efficiency due to heat stress caused by
years of temperature changes in the surrounding environment
and heat generated by their components, even if they are
used properly.
Therefore, in most cases the failure rate of electronic
components and devices follows a bathtub curve after they
are shipped.
The life expectancy of an SSR can also be represented by a
bathtub curve.
Sensors
Unlike standard relays, an SSR uses a semiconductor to switch a circuit and do not contain mechanical contacts. Furthermore,
signal transfer is handled by electronic circuits, so there are no moving parts to cause mechanical friction. Therefore, to determine
the life expectancy of an SSR, you must consider not only the life expectancy of the elements used but also the deterioration of
soldered points and the materials of which the SSR is made.
OMRON generally considers the life expectancy of an SSR to be the point on the bathtub curve where the failure rate begins to
rise and enters the wear-out failure period (for an SSR, this is the period when deterioration begins), which is approximately 10
years, although it will depend on the application environment.
26
Technical Explanation for Solid-state Relays
Troubleshooting
Examples of SSR Failures
Failure of output elements
due to overcurrent
Inrush current
Failure of output elements
due to overvoltage
Inductive load
counter-electromotive force
External surge
Failure of output elements
due to overcurrent
Inrush current
Load short circuit
Failure of output elements
due to overvoltage
Inductive load
counter-electromotive force
External surge
Overheating and
burning
Overheating
SSR installation
Burning
Power Supplies /
In Addition
Precautions
Depending on the type of fault, SSR analysis may be necessary.
Energy Conservation Support /
Environment Measure Equipment
Control panel heat dissipation design
Motion / Drives
Zero cross function not
performed (for half-wave
rectified inductive load)
Automation Systems
Examples of SSR Failure
(or stops
intermittently).
Insulation breakdown
(leakage breaker operation)
Control Components
Even with input,
load does not
operate
Residual voltage to input
Relays
Failure to release
Safety Components
(or operates
intermittently).
Switches
Load short circuit
Even with no input,
load continues to
operate
Sensors
Isolating the Cause of Failure
Problem
Others
Common
27
Technical Explanation for Solid-state Relays
Flow Chart to Investigate SSR Faults
NO
AC SSRs use triac output
elements. SSRs with triac
output elements will fail to
release during rapid ON-to-OFF
or OFF-to-ON transitions
(dv/dt), such as those for a
rectangular waveform.
Rectangular waveform
START
Is the operation indicator
lit?
Does the load turn OFF
when input line is
disconnected?
Is the load power supply
AC, DC, or rectangular
waveform current?
Correction
The SSR may be adversely
affected by residual voltage
from the previous stage
(PLC, input power supply,
etc.), leakage current, or
inductive noise that enters
through the input line.
AC
Add bleeder resistance in
parallel with the load or select
a power MOS FET relay.
G3HD-202SN(-VD),
G3DZ, G3RZ, or G3FM
Correction
YES
Is the load a full-wave
rectified inductive load
with a built-in diode?
DC
Problem
Is the SSR for AC output?
Is there an operation
indicator for the input?
The SSR stays ON
(short circuit)
Forward/reverse operation switching time lag
for the motor is insufficient.
* Refer to the precautions in the datasheet.
The SSR does not
turn ON
(open circuit error).
Is there an operation
indicator for the input on
the SSR?
Is the operation indicator
for the input OFF?
Use a multimeter and check the
input terminal voltage while the input
is connected. Has the must-operate
voltage been applied?
Is the polarity of the input
incorrect?
Bu rn i n g
Reconnect the input line.
SSRs that are not for
PCBs have reverse
connection prevention
diodes built into them and
should not be broken.
An SSR LED failure or
SSR problem, e.g., in the
SSR input circuit due to
external surge, is possible.
An unusual smell is
detected from the SSR.
The exterior of the SSR
is burnt badly.
An unusual smell is
detected from the SSR.
The exterior of the SSR
is burnt lightly.
Due to a motor forward/reverse
operation switching time lag,
the SSR may have been
subject to a surge that greatly
exceeds the SSR’s rating.
Abnormal heat generation
may have occurred due to an
incorrect mounting direction or
mounting interval.
Is the polarity of the
output incorrect?
Use an SSR for DC load.
The SSR may be broken.
Replace the SSR and
connect it correctly.
Use a multimeter and
check the voltage on
output terminals. Has the
rated load voltage been
applied to the terminals?
Is 90 VDC (200-VAC
half-wave rectified load) or
phase control power
supply used while the SSR
has a zero cross function?
Is th e p o l a r i ty o f th e
wi r i n g co r r e ct?
Is a DC-input SSR
operating on AC?
Reconnect the output line.
SSRs that are not SSRs for
PCBs have reverse connection
prevention diodes built into
them and should not be broken.
Change to an AC-input
SSR.
An unusual smell is
detected from the SSR.
The exterior is not burnt.
Is the screw tightening
torque insufficient or is
the socket mated
improperly?
Abnormal heat generation
may have occurred due to
contact resistance.
Correct the wiring and
installation.
Precautions
Depending on the type of malfunction, an SSR analysis may be necessary.
28
Technical Explanation for Solid-state Relays
Sensors
Triac and thyristor output
elements have a 0.1-A
holding current. The holding
current has been affected by
a leakage current which may
have caused a release failure.
Are diodes for absorbing
counter-electromotive
force connected on both
sides of the load?
Is the polarity of the
diode for absorbing
counter-electromotive
force correct?
Install a diode for absorbing counter-electromotive force in parallel with the load
using the correct polarity.
(The cathode side of the diode attaches to the positive side of the power supply.)
Control Components
Does an inrush current
(from lamp loads,
pure-metal heater etc.)
exceed the non-repetitive
surge withstand current of
the SSR?
Has an inrush current or a discharge current that
was caused by simultaneously activating the
reverse and forward operations of a capacitor
motor exceeded the non-repetitive surge
withstand current of the SSR (solid line)?
Relays
For OMRON’s DC-output
SSRs, it is assumed that the
DC waveforms are undistorted
and have a frequency of 0 Hz.
If there is distortion in the DC
waveform, a transistor output
cannot be used.
Is an inductive load
(valve, solenoid, relay,
etc.) connected?
Safety Components
Have you used the SSR in high-frequency
output PWM control, for 90 VDC
(200-VAC half-wave rectification), a
generator, or other application to
intentionally distort the DC waveform or
carry noise?
Does the load have high
inrush current (motor,
lamp, power transformer,
etc.)?
Switches
Is load minute
Is the load minute (0.1 A
or less)?
Vibration, shock, load short
circuit, external surge,
condensation, insulation
deterioration, or other
factor may have caused an
unexpected failure or
internal SSR fault.
Automation Systems
A load short circuit, external surge, or other factor may
have caused an unexpected failure or SSR fault. Does
the load operate properly when the SSR is replaced?
The load is operating normally.
Use an SSR that does
not have the zero cross
function.
The output element of the SSR may have been
destroyed by an inrush current or external surge.
Consider using an SSR with a higher capacity.
Is the current equal to or
greater than the minimum
load current of the SSR?
Wiring may have come
loose as a result of
vibration, shock, or other
factor. Reconnect the SSR
correctly.
H ave m e a s u r e s a g a i n s t
i n r u s h c u r r e n t s ( i . e. ,
c o n n e c t i n g a va r i s t o r )
been implemented?
Have measures against
counter-electromotive
force (i.e., connecting a
diode) been
implemented?
Triac and thyristor output
elements have a 0.1-A
holding current.
The SSR may not operate at
less than this holding current.
The SSR may have an
open circuit error due to
an inrush current.
The SSR may have an
open circuit error due to
an external surge.
Are the mounting
direction and mounting
interval incorrect?
Is the interior of the
control panel
insufficiently ventilated?
Has the wrong heat sink been
selected, is silicone grease
missing anywhere, or is there a
warp in the heat sink?
Internal components may have
experienced burning due to
abnormal heat generation.
Mount the SSR correctly, with an
appropriate mounting interval.
Internal components may have experienced
burning due to abnormal heat generation.
Re-evaluate periodic cleaning inside the control
panel as well as its heat dissipation design, and
check for obstructions of ventilation holes.
Internal components may
have experienced burning due
to abnormal heat generation.
Use a suitable heat
dissipation design.
Are the electric specifications
and load specifications of the
SSR incorrect
Select an SSR that
satisfies the load
specifications and
characteristics.
There may be internal SSR
problems
(such as foreign matter attached
to internal components, faulty
soldering, or faulty components).
Others
(load current, load voltage
fluctuations, etc.)?
Power Supplies /
In Addition
Does the load have a high
counter-electromotive force,
such as an
electromagnetic valve?
Energy Conservation Support /
Environment Measure Equipment
Does the load have a high inrush
current, such as a transformer,
motor, lamp, power transformer,
solenoid, or capacitor
charge/discharge load?
Motion / Drives
Is the wiring loose (e.g., improper
crimping of crimp terminals,
insufficient screw tightening
torque, or faulty soldering of a
PCB-mounted relay)?
Common
29