AA™3350 Thermal Window - Architectural Detail Manual

JULY, 2014
AATM3350 IsoPortTM Window
INDEX
FIXED WINDOW................................................................................. 3-5
SINGLE HUNG WINDOW................................................................ 6-10
DOUBLE HUNG WINDOW............................................................ 11-15
HORIZONTAL SLIDER WINDOW.................................................. 16-20
WIND LOAD CHARTS................................................................... 21-28
DEADLOAD CHARTS........................................................................ 29
RECEPTORS, SUB SILLS AND ANCHORING.................................. 30
THERMAL CHARTS...................................................................... 31-53
LAWS AND BUILDING AND SAFETY CODES GOVERNING THE DESIGN AND USE OF GLAZED
ENTRANCE, WINDOW, AND CURTAIN WALL PRODUCTS VARY WIDELY. KAWNEER DOES NOT
CONTROL THE SELECTION OF PRODUCT CONFIGURATIONS, OPERATING HARDWARE, OR
GLAZING MATERIALS, AND ASSUMES NO RESPONSIBILITY THEREFOR.
Metric (SI) conversion figures are included throughout these details for reference.
Numbers in parentheses (
) are millimeters unless otherwise noted.
The following metric (SI) units are found in these details:
m –meter
cm – centimeter
mm –millimeter
s –second
Pa –pascal
MPa –megapascal
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
1
Kawneer reserves the right to change configurations without prior notice when deemed necessary
for product improvement.
kawneer.com
ADME050
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
AATM3350 IsoPortTM Window
BLANK PAGE
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
2
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
FIXED WINDOW
Standard Features
•
•
•
•
•
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
• High Performance Commercial Window
• IsoPortTM Thermal Break
Screw and Spline Frame Corner Joinery
Factory Silicone Glazed
Interior Applied Glazing Bead
Architectural Anodized Finishes and Applied Coatings
Two Year Manufacturer's Warranty
Exterior
Interior
Fixed Window
For specific product applications,
Consult your Kawneer representative.
kawneer.com
ADME050
Thermal Break
3
AATM3350 IsoPortTM Window
JULY, 2014
FIXED WINDOW
EC 97911-063
CLASS CW-PG50-FW / AW-PG50-FW
OPTIONAL CLASS and GRADE
CLASS AW-PG70-FW
TESTING STANDARD
AAMA / WDMA / CSA / 101 / I.S.2 / A440-08 (NAFS-08)
FRAME DEPTH
3-1/2" Overall Frame Depth
TYPICAL WALL THICKNESS
.070" Nominal
TYPICAL MAX. VENT SIZE
60" x 99"
TYPICAL MIN. VENT SIZE
15" x 15"
TYPICAL CONFIGURATIONS
STANDARD INFILL OPTIONS
1"
STANDARD HARDWARE
Not Applicable
OPTIONAL HARDWARE
Not Applicable
OTHER OPTIONS
Between the Glass Muntin Grids
Exterior Applied Muntin Grids
Perimeters and Sills
Exterior Pannings and Interior Trims
True Intermediate Muntin
Structural Mullions
Vertically or Horizontally Stacked
Strap Anchors
Nailing Fin Flange
FIXED WINDOW PRODUCT PERFORMANCE
Air
Infiltration
NAFS-08
Water
Resistance
NAFS-08
Design
Load
NAFS-08
Thermal
Transmittance
AAMA 507
NFRC 100
Condensation
Resistance*
AAMA 1503
≤ 0.10 Cfm/ft2
CW - 10 PSF
AW - 15 PSF
50 PSF
70 PSF
"U" Factor
0.33 to 0.56
CRF frame - 67
CRF glass - 71
Condensation
Sound
Temperature Transmittance**
Index*
ASTM E 1425
CSA A440.2
ASTM E 1332
I frame - 60
I glass - 62
STC - 36
OITC - 28
Note:"U" Values based on computer simulations utilizing Insulating Glass, Low E Coatings and Warm Edge Spacers. See Thermal Charts for various glass types.
* CRF and Temperature index based on high performance Low E Glass and Warm Edge Spacers.
** Acoustical test based on laminated glass.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
CLASS and GRADE
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
4
© Kawneer Company, Inc., 2014
3/8"
kawneer.com
3-1/2"
3-1/2"
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
1-13/16"
4
JAMB
D.L.O
D.L.O
3
3
SILL
TYPICAL ELEVATION
Log onto www.kawneer.com for other configurations
2-1/2"
D.L.O
5
VERTICAL
ADME050
D.L.O
1-13/16"
D.L.O
6
D.L.O
4
2
HORIZONTAL
2-1/2"
5
D.L.O
D.L.O
W.D.
W.D.
O.D.
O.D.
1-13/16"
W.D.
O.D.
1
HEAD
O.D.
3/8"
AATM3350 IsoPortTM FIXED WINDOW
Standard Design
W.D.
1
3/8"
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
AATM3350 IsoPortTM Window
EC 97911-063
FIXED WINDOW
SCALE : 3" = 1'-0"
3-1/2"
2
1-13/16"
6
JAMB
3/8"
5
AATM3350 IsoPortTM Window
JULY, 2014
SINGLE HUNG WINDOW
EC 97911-063
Standard Features
Screw and Spline Frame and Sash Corner Joinery
Factory Silicone Glazed
Interior Applied Glazing Bead
Architectural Anodized Finishes and Applied Coatings
Two Year Manufacturer's Warranty
Thermal Break
Exterior
Interior
Single Hung Window
For specific product applications,
Consult your Kawneer representative.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
•
•
•
•
•
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
• High Performance Commercial Window
• IsoPortTM Thermal Break
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
6
AATM3350 IsoPortTM Window
JULY, 2014
SINGLE HUNG WINDOW
CLASS and GRADE
CLASS CW-PG50-H / AW-PG50-H
OPTIONAL CLASS and GRADE
CLASS AW-PG70-H (MAX. SIZE 52" X 99")
TEST STANDARD
AAMA / WDMA / CSA / 101 / I.S.2 / A440-08 (NAFS-08)
FRAME DEPTH
3-1/2" Overall Frame Depth
TYPICAL WALL THICKNESS
.070" Nominal
TYPICAL MAXIMUM SIZE
60" x 99" (AW), 56" x 91" (CW)
TYPICAL MINIMUM SIZE
20" x 32-1/2" (10 PSF Sill), 20" x 33-1/2" (15 PSF Sill)
TYPICAL CONFIGURATIONS
STANDARD INFILL OPTIONS
1"
STANDARD HARDWARE
Heavy Duty Balances
Zinc Die Cast Sweep Locks
Sash Stops
OPTIONAL HARDWARE
Sill Auto Lock
OTHER OPTIONS
Between the Glass Muntin Grids
Exterior Applied Muntin Grids
Perimeters and Sills
Exterior Pannings and Interior Trims
Structural Mullions
Vertically or Horizontally Stacked
Strap Anchors
Sill for 10 PSF or 15 PSF Water Performance
Insect Screens
Nailing Fin Flange
SINGLE HUNG WINDOW PRODUCT PERFORMANCE
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
Air
Infiltration
NAFS-08
Water
Resistance
NAFS-08
Design
Load
NAFS-08
Thermal
Transmittance
AAMA 507
NFRC 100
Condensation
Resistance*
AAMA 1503
≤ 0.30 Cfm/ft2
CW - 10 PSF
AW - 15 PSF
50 PSF
70 PSF
"U" Factor
0.38 to 0.57
CRF frame - 57
CRF glass - 60
Condensation
Sound
Temperature Transmittance**
Index*
ASTM E 1425
CSA A440.2
ASTM E 1332
I frame - 39
I glass - 58
STC - 36
OITC - 30
Note:"U" Values based on computer simulations utilizing Insulating Glass, Low E Coatings and Warm Edge Spacers. See Thermal Charts for various glass types.
* CRF and Temperature index based on high performance Low E Glass and Warm Edge Spacers.
** Acoustical test based on laminated glass.
kawneer.com
ADME050
7
3/8"
3
SILL
10 PSF
2-5/8"
3/8"
D.L.O
O.D.
W.D.
4
JAMB
D.L.O
W.D.
ADME050
W.D.
TYPICAL ELEVATION
Log onto www.kawneer.com for other configurations
D.L.O
2
HORIZONTAL
D.L.O
D.L.O
4
1-13/16"
W.D.
3/8"
3-1/2"
2
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
2-7/16"
SINGLE HUNG WINDOW
3-11/16"
O.D.
3/8"
5
JAMB
kawneer.com
© Kawneer Company, Inc., 2014
D.L.O
1
4-1/4"
5
O.D.
1
HEAD
O.D.
AATM3350 IsoPortTM Window
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3-1/2"
8
JULY, 2014
EC 97911-063
SCALE : 3" = 1'-0"
AATM3350 IsoPortTM SINGLE HUNG WINDOW
Commercial Window, Class CW-PG50-H
3
3/8"
kawneer.com
3/8"
3-1/2"
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
2-5/8"
D.L.O
4
JAMB
D.L.O
W.D.
W.D.
O.D.
O.D.
5
JAMB
ADME050
D.L.O
2
3
TYPICAL ELEVATION
Log onto www.kawneer.com for other configurations
3
SILL
15 PSF
3-11/16"
3/8"
D.L.O
1-13/16"
3/8"
1
5-1/4"
W.D.
2
HORIZONTAL
2-7/16"
4
W.D.
1
HEAD
O.D.
EC 97911-063
O.D.
D.L.O
5
D.L.O
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
AATM3350 IsoPortTM Window
SINGLE HUNG WINDOW
SCALE : 3" = 1'-0"
AATM3350 IsoPortTM SINGLE HUNG WINDOW
Architectural Window, Class AW-PG50-H
Class AW-PG70-H (Optional)
3-1/2"
9
AATM3350 IsoPortTM Window
EC 97911-063
A class 5 adjustable spring balance with excellent operating
forces capable of balancing heavier sash weights. The
balance utilizes stainless steel components and is cycle
tested for longevity.
ZINC SWEEP LOCK AND KEEPER
Zinc die cast sweep locks and keepers with a durable black
powder coat finish and cycle tested for longevity. Includes a
push button lock feature providing added security.
AUTO LOCK
An optional black rigid PVC spring operated auto lock
conveniently located under the sash lift handle. The lock
automatically engages the integral sill keeper upon closing
the sash.
COVERED WEEPS
A polycarbonate weep with an integral hinged cover to allow
maximum drainage of infiltrating water with a positive closing
cover to block drafts and insects. The weep is available in black,
white and silver finishes.
SASH CAMS
Adjustable glass filled nylon cams located left and right on the
sash ensure proper alignment and smooth operation.
SASH STOPS
Black PVC sash stops are inserted into the vertical jambs without
exposed fasteners to prevent excessive sash travel.
WEATHERING BLOCK
Weathering blocks located left and right at the meeting rails
significantly improve resistance to air and water infiltration.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
HEAVY DUTY BALANCES
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SINGLE HUNG WINDOW
JULY, 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
10
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
DOUBLE HUNG WINDOW
Standard Features
•
•
•
•
•
Screw and Spline Frame and Sash Corner Joinery
Factory Silicone Glazed
Interior Applied Glazing Bead
Architectural Anodized Finishes and Applied Coatings
Two Year Manufacturer's Warranty
Thermal Break
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
• High Performance Commercial Window
• IsoPortTM Thermal Break
Exterior
Double Hung Window
For specific product applications,
Consult your Kawneer representative.
kawneer.com
ADME050
Interior
11
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
CLASS CW-PG50-H / AW-PG50-H
OPTIONAL CLASS and GRADE
CLASS AW-PG70-H (MAXIMUM SIZE 52" x 99")
TESTING STANDARD
AAMA / WDMA / CSA / 101 / I.S.2 / A440-08 (NAFS-08)
FRAME DEPTH
3-1/2" Overall Frame Depth
TYPICAL WALL THICKNESS
.070" Nominal
TYPICAL MAXIMUM SIZE
60" x 99" (AW), 56" x 91" (CW)
TYPICAL MINIMUM SIZE
20" x 34" (10 PSF Sill), 20" x 35" (15 PSF Sill)
TYPICAL CONFIGURATIONS
STANDARD INFILL OPTIONS
1"
STANDARD HARDWARE
Heavy Duty Balances
Zinc Die Cast Sweep Locks
Sash Stops
Upper Sash Auto Lock
OPTIONAL HARDWARE
Sill Auto Lock
OTHER OPTIONS
Between the Glass Muntin Grids
Exterior Applied Muntin Grids
Perimeters and Sills
Exterior Pannings and Interior Trims
Structural Mullions
Vertically or Horizontally Stacked
Strap Anchors
Sill for 10 PSF or 15 PSF Water Performance
Insect Screens
Nailing Fin Flange
DOUBLE HUNG WINDOW PRODUCT PERFORMANCE
Air
Infiltration
NAFS-08
Water
Resistance
NAFS-08
Design
Load
NAFS-08
Thermal
Transmittance
AAMA 507
NFRC 100
Condensation
Resistance*
AAMA 1503
≤ 0.30 Cfm/ft2
CW - 10 PSF
AW - 15 PSF
50 PSF
70 PSF
"U" Factor
0.39 to 0.57
CRF frame - 57
CRF glass - 60
Condensation
Sound
Temperature Transmittance**
Index*
ASTM E 1425
CSA A440.2
ASTM E 1332
I frame - 33
I glass - 60
STC - 34
OITC - 29
Note:"U" Values based on computer simulations utilizing Insulating Glass, Low E Coatings and Warm Edge Spacers. See Thermal Charts for various glass types.
* CRF and Temperature index based on high performance Low E Glass and Warm Edge Spacers.
** Acoustical test based on laminated glass.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
CLASS and GRADE
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
DOUBLE HUNG WINDOW
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
12
© Kawneer Company, Inc., 2014
3/8"
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3-11/16"
3/8"
kawneer.com
D.L.O
D.L.O
2
2
HORIZONTAL
5
TYPICAL ELEVATION
Log onto www.kawneer.com for other configurations
D.L.O
W.D.
W.D.
O.D.
O.D.
4
JAMB
5
JAMB
ADME050
3
SILL
10 PSF
3-11/16"
3/8"
D.L.O
2-7/16"
3/8"
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
Commercial Window, Class CW-PG50-H
3-11/16"
O.D.
4
W.D.
1
HEAD
O.D.
D.L.O
1
W.D.
EC 97911-063
4-1/4"
3
D.L.O
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
AATM3350 IsoPortTM Window
DOUBLE HUNG WINDOW
SCALE : 3" = 1'-0"
3-1/2"
13
3/8"
3-11/16"
4
JAMB
D.L.O
D.L.O
D.L.O
W.D.
D.L.O
W.D.
O.D.
O.D.
ADME050
2
HORIZONTAL
TYPICAL ELEVATION
Log onto www.kawneer.com for other configurations
3
SILL
15 PSF
5
3-11/16"
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
2-7/16"
3/8"
DOUBLE HUNG WINDOW
3-11/16"
3/8"
5
JAMB
kawneer.com
© Kawneer Company, Inc., 2014
D.L.O
2
O.D.
4
W.D.
1
HEAD
O.D.
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
Architectural Window, Class AW-PG50-H
Class AW-PG70-H (Optional)
5-1/4"
3
D.L.O
1
W.D.
AATM3350 IsoPortTM Window
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3/8"
14
JULY, 2014
EC 97911-063
SCALE : 3" = 1'-0"
3-1/2"
JULY, 2014
AATM3350 IsoPortTM Window
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
15
DOUBLE HUNG WINDOW
HEAVY DUTY BALANCES
A class 5 adjustable spring balance with excellent operating
forces capable of balancing heavier sash weights. The
balance utilizes stainless steel components and is cycle
tested for longevity.
ZINC SWEEP LOCK AND KEEPER
Zinc die cast sweep locks and keepers with a durable black
powder coat finish and cycle tested for longevity. Includes a
push button lock feature providing added security.
AUTO LOCK AND KEEPER
A black rigid PVC spring operated auto lock located on the
upper sash. The lock automatically engages the head keeper
securing the upper sash in the closed position. The auto lock is
an option for the lower sash.
COVERED WEEPS
A polycarbonate weep with an integral hinged cover to allow
maximum drainage of infiltrating water with a positive closing
cover to block drafts and insects. The weep is available in black,
white and silver finishes.
SASH CAMS
Adjustable glass filled nylon cams located left and right on the
sash ensure proper alignment and smooth operation.
SASH STOPS
Black PVC sash stops are inserted into the vertical jambs without
exposed fasteners to prevent excessive sash travel.
WEATHERING BLOCK
Weathering blocks located left and right at the meeting rails
significantly improve resistance to air and water infiltration.
kawneer.com
ADME050
AATM3350 IsoPortTM Window
JULY, 2014
HORIZONTAL SLIDER
EC 97911-063
Standard Features
Horizontal Sliding Window
For specific product applications,
Consult your Kawneer representative.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Thermal Break
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Screw and Spline Frame and Sash Corner Joinery
Factory Silicone Glazed
Interior Applied Glazing Bead with Bulb Gasket
Architectural Anodized Finishes and Applied Coatings
Two Year Manufacturer's Warranty
Interior
•
•
•
•
•
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
• High Performance Window
• IsoPortTM Thermal Break
Exterior
16
AATM3350 IsoPortTM Window
JULY, 2014
HORIZONTAL SLIDER
CLASS and GRADE
Class CW-PG50-HS / AW-PG50-HS
OPTIONAL CLASS and GRADE
Class AW-PG70-HS (Max Size: 99" x 71" OX)
TESTING STANDARD
AAMA / WDMA / CSA 101 / I.S. 2 / A440-08 (NAFS-08)
FRAME DEPTH
3-1/2" Overall Frame Depth
TYPICAL WALL THICKNESS
.070" Nominal
TYPICAL MAXIMUM SIZE
99" x 79" (OX,XO,XX) 148-1/2" x 79" (OXO,XOX)
TYPICAL MINIMUM SIZE
32" x 20" (OX,XO,XX) 48" x 20" (OXO,XOX)
TYPICAL CONFIGURATIONS
STANDARD INFILL OPTIONS1"
STANDARD HARDWARE
Composite Adjustable Tandem Roller
Zinc Die Cast Sweep Lock
OPTIONAL HARDWARE
PVC Auto Lock
OTHER OPTIONS
Between the Glass Muntin Grids
Exterior Applied Muntin Grids
Perimeters and Sills
Exterior Pannings and Interior Trims
Structural Mullions
Vertically or Horizontally Stacked
Sill for 10 PSF or 15 PSF Water Performance
Insect Screens
HORIZONTAL SLIDER WINDOW PRODUCT PERFORMANCE
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
17
Air
Infiltration
NAFS-08
Water
Resistance
NAFS-08
Design
Load
NAFS-08
Thermal
Transmittance
AAMA 507
NFRC 100
Condensation
Resistance*
AAMA 1503
Condensation
Temperature
Index*
CSA A440.2
Sound
Transmittance**
ASTM E 1425
ASTM E 1332
≤ 0.30 Cfm/ft2
CW - 10 PSF
AW - 15 PSF
50 PSF
70 PSF
"U" Factor
0.37 to 0.54
CRF frame - 66
CRF glass - 66
I frame - 45
I glass - 62
STC - 37
OITC - 29
Note:"U" Values based on computer simulations utilizing Insulating Glass, Low E Coatings and Warm Edge Spacers. See Thermal Charts for various glass types.
* CRF and Temperature index based on high performance Low E Glass and Warm Edge Spacers.
** Acoustical test based on laminated glass.
kawneer.com
ADME050
3/8"
3/8"
2
4
TYPICAL ELEVATION
Log onto www.kawneer.com
for other configurations
2-5/8"
D.L.O
5
FIXED SASH
JAMB
D.L.O
W.D.
2-7/16"
O.D.
6
INTERLOCK
ADME050
2-5/8"
3/8"
3-1/2"
3
HEAD WITH
OPERABLE
SASH
7
2
SILL WITH
FIXED SASH
(10 PSF)
4
SILL WITH
OPERABLE
SASH
(10 PSF)
D.L.O
D.L.O
W.D.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
3-11/16"
W.D.
HORIZONTAL SLIDER
3-11/16"
O.D.
3/8"
7
OPERABLE SASH
JAMB
kawneer.com
© Kawneer Company, Inc., 2014
6
D.L.O
1
HEAD WITH
FIXED SASH
6-1/8"
5
D.L.O
3
W.D.
1
O.D.
AATM3350 IsoPortTM
OX HORIZONTAL SLIDER
Commercial Window,
Class CW-PG50-HS
5-1/16"
O.D.
AATM3350 IsoPortTM Window
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
3-15/32"
18
JULY, 2014
EC 97911-063
SCALE : 3" = 1'-0"
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
HORIZONTAL SLIDER
5
6
3-11/16"
2-5/8"
O.D.
3
HEAD WITH
OPERABLE
SASH
D.L.O
1
HEAD WITH
FIXED SASH
7
4
4
SILL WITH
OPERABLE
SASH
(15 PSF)
D.L.O
2
SILL WITH
FIXED SASH
(15 PSF)
7-1/8"
3/8"
6-1/16"
TYPICAL ELEVATION
Log onto www.kawneer.com
for other configurations
W.D.
2
3-15/32"
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
W.D.
3
1
3-1/2"
3/8"
AATM3350 IsoPortTM
OX HORIZONTAL SLIDER
Architectural Window,
Class AW-PG50-HS
Class AW-PG70-HS (Optional)
O.D.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
SCALE : 3" = 1'-0"
D.L.O
2-5/8"
3/8"
D.L.O
2-7/16"
O.D.
5
FIXED SASH
JAMB
kawneer.com
D.L.O
D.L.O
3-11/16"
W.D.
W.D.
O.D.
6
INTERLOCK
ADME050
7
OPERABLE SASH
JAMB
3/8"
19
AATM3350 IsoPortTM Window
EC 97911-063
Glass filled nylon housing, die cast zamak roller support, precision
sealed ball bearing rollers with nylon tires.
PVC AUTO LOCK AND KEEPER
A black rigid PVC, spring operated auto lock, located on the
jamb. The lock automatically engages the jamb keeper securing
the sash in the closed position. The auto lock is standard for the
exterior sash of the XX configuration only.
COVERED WEEP
A polycarbonate weep with an integral hinged cover to allow
maximum drainage of infiltrating water with a positive closing
cover to block drafts and insects. The weep is available in black,
white and silver finishes.
ZINC SWEEP LOCK AND KEEPER
Zinc die cast sweep locks and keepers with a durable black
powder coat finish and cycle tested for longevity. Includes a
push button lock feature providing added security.
SASH STOPS
Black PVC sash stops are inserted into the head without
exposed fasteners to prevent excessive sash travel.
ADME050
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
COMPOSITE ADJUSTABLE
TANDEM ROLLER
kawneer.com
© Kawneer Company, Inc., 2014
HORIZONTAL SLIDER
JULY, 2014
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
20
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
21
WIND LOAD CHARTS
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
A = 40 PSF (1915)
B = 50 PSF (2394)
C = 60 PSF (2873)
D = 70 PSF (3352)
E = 80 PSF (3830)
HORIZONTAL WIDTH IN METERS
1.0
SINGLE HUNG INTERMEDIATE
CW-RATED
4
3
A
2
B
C
D
E
1
0
0
1
2
3
4
1.0
SASH HEIGHT IN METERS
SASH HEIGHT IN FEET
5
5
HORIZONTAL WIDTH IN METERS
1.0
SINGLE HUNG INTERMEDIATE
AW-RATED
4
A
1.0
3
B
C
D
E
2
1
0
0
1
2
3
4
SASH HEIGHT IN METERS
SASH HEIGHT IN FEET
5
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
HORIZONTAL WIDTH IN FEET
5
HORIZONTAL WIDTH IN FEET
kawneer.com
ADME050
AATM3350 IsoPortTM Window
22
JULY, 2014
WIND LOAD CHARTS
EC 97911-063
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
MUNTIN CENTERS IN METERS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
A = 40 PSF (1915)
B = 50 PSF (2394)
C = 60 PSF (2873)
D = 70 PSF (3352)
E = 80 PSF (3830)
1.0
8
TRUE MUNTIN FOR
FIXED WINDOW
MUNTIN HEIGHT IN FEET
2.0
6
5
4
A
B
1.0
C
D
E
3
2
1
1
2
3
4
MUNTIN HEIGHT IN METERS
7
5
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WITH HORIZONTALS
MUNTIN CENTERS IN METERS
1.0
8
MUNTIN HEIGHT IN FEET
7
2.0
6
A
B
C
D
E
5
4
1.0
3
MUNTIN HEIGHT IN METERS
TRUE MUNTIN FOR
FIXED WINDOW
2
1
1
2
3
4
5
MUNTIN CENTERS IN FEET
WITHOUT HORIZONTALS
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
MUNTIN CENTERS IN FEET
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
23
WIND LOAD CHARTS
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
MULLION CENTERS IN METERS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1.0
9
SHALLOW THREE PIECE
MULLION
MULLION HEIGHT IN FEET
B
7
C
6
2.0
D
5
4
1.0
3
2
0
1
2
3
4
MULLION HEIGHT IN METERS
A
8
A = 30 PSF (1436)
B = 40 PSF (1915)
C = 50 PSF (2394)
D = 60 PSF (2873)
5
MULLION CENTERS IN FEET
1.0
10
3.0
DEEP THREE PIECE
MULLION
8
7
2.0
6
A
B
C
D
E
5
4
A = 40 PSF (1915)
B = 50 PSF (2394)
C = 60 PSF (2873)
D = 70 PSF (3352)
E = 80 PSF (3830)
1.0
3
2
MULLION HEIGHT IN METERS
MULLION HEIGHT IN FEET
9
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
MULLION CENTERS IN METERS
0
1
2
3
4
5
MULLION CENTERS IN FEET
kawneer.com
ADME050
AATM3350 IsoPortTM Window
24
JULY, 2014
WIND LOAD CHARTS
EC 97911-063
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
MUNTIN CENTERS IN METERS
2.0
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1.0
9
8
MUNTIN HEIGHT IN FEET
7
2.0
6
5
4
A
1.0
3
MUNTIN HEIGHT IN METERS
VERTICAL STACK JAMBS
FIXED / FIXED
B
2
CD
E
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
1
1
2
3
4
5
6
7
8
9
MUNTIN CENTERS IN FEET
MUNTIN CENTERS IN METERS
2.0
1.0
9
8
MUNTIN HEIGHT IN FEET
7
2.0
6
5
A
4
1.0
B
C
DE
3
2
1
1
2
3
4
5
6
7
8
MUNTIN HEIGHT IN METERS
VERTICAL STACK JAMBS
FIXED / DOUBLE HUNG
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
9
MUNTIN CENTERS IN FEET
WITH HORIZONTALS
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WITH HORIZONTALS
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
25
WIND LOAD CHARTS
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
2.0
1.0
9
VERTICAL STACK JAMBS
FIXED / SINGLE HUNG
7
2.0
6
5
4
A
1.0
3
MUNTIN HEIGHT IN METERS
8
MUNTIN HEIGHT IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
MUNTIN CENTERS IN METERS
B
2
1
CD
E
1
2
3
4
5
6
7
8
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
9
MUNTIN CENTERS IN FEET
MUNTIN CENTERS IN METERS
1.0
2.0
9
8
MUNTIN HEIGHT IN FEET
2.0
6
5
4
A
1.0
3
B
2
CD
E
1
1
2
3
4
5
6
7
8
9
MUNTIN CENTERS IN FEET
WITH HORIZONTALS
kawneer.com
ADME050
MUNTIN HEIGHT IN METERS
VERTICAL STACK JAMBS
DOUBLE HUNG / DOUBLE HUNG
7
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
WITH HORIZONTALS
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
AATM3350 IsoPortTM Window
26
JULY, 2014
WIND LOAD CHARTS
EC 97911-063
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
MUNTIN CENTERS IN METERS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
2.0
1.0
9
VERTICAL STACK JAMBS
SINGLE HUNG / SINGLE HUNG
2.0
6
5
A
4
1.0
3
B
CD
E
2
1
2
3
4
5
6
7
8
9
MUNTIN CENTERS IN FEET
WITH HORIZONTALS
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
1
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
MUNTIN HEIGHT IN FEET
7
MUNTIN HEIGHT IN METERS
8
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
27
WIND LOAD CHARTS
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
1.0
2.0
9
LOCK STILE
HORIZONTAL SLIDER
7
2.0
6
A
5
B
C
D
E
4
SASH HEIGHT IN METERS
8
SASH HEIGHT IN FEET
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
MODULE CENTERS IN METERS
1.0
3
2
1
1
2
MODULE CENTERS IN FEET
5
3
6
7
4
WITHOUT HORIZONTALS
8
A = 40 PSF (1915)
B = 50 PSF (2394)
C = 60 PSF (2873)
D = 70 PSF (3352)
E = 80 PSF (3830)
9
1.0
2.0
9
A
LOCK STILE
HORIZONTAL SLIDER
7
B
6
C
D
E
5
4
1.0
3
2
1
1
2
3
4
5
6
7
MODULE CENTERS IN FEET
8
9
WITHOUT HORIZONTALS
kawneer.com
2.0
ADME050
SASH HEIGHT IN METERS
SASH HEIGHT IN FEET
8
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
MODULE CENTERS IN METERS
AATM3350 IsoPortTM Window
28
JULY, 2014
EC 97911-063
WIND LOAD CHARTS
WIND LOAD CHARTS:
THESE CHARTS ARE BASED ON A MAXIMUM DEFLECTION OF L\175 AND\OR A MAXIMUM STRESS OF 15,152 psi (104 MPa). If the design wind
load is determined through the analytical procedures of ASCE/SEI 7-10 or earlier editions, the load shall be based on the nominal loads used in
allowable stress design. A 4/3 increase in allowable stress has not been used to develop these curves.
MODULE CENTERS IN METERS
2.0
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
9
A
7
2.0
6
B
5
C
4
D
E
1.0
3
WINDOW HEIGHT IN METERS
WINDOW HEIGHT IN FEET
8
VERTICAL STACK JAMBS
HORIZONTAL SLIDER
2
1
2
3
4
5
6
7
8
9
MODULE CENTERS IN FEET
A = 20 PSF (958)
B = 35 PSF (1676)
C = 50 PSF (2394)
D = 65 PSF (3112)
E = 80 PSF (3830)
WITHOUT HORIZONTALS
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
1
MODULE CENTERS IN METERS
1.0
2.0
9
A
7
2.0
6
B
5
C
4
D
E
1.0
3
WINDOW HEIGHT IN METERS
WINDOW HEIGHT IN FEET
8
"XX" VERTICAL STACK JAMBS
HORIZONTAL SLIDER
2
1
1
2
3
4
5
6
7
8
9
MODULE CENTERS IN FEET
WITHOUT HORIZONTALS
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
1.0
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
29
DEADLOAD CHARTS
DEADLOAD CHARTS:
Horizontal deadload limitations are based upon 1/8" (3.2) maximum allowable deflection at the center of an
intermediate horizontal member. The accompanying charts are calculated for the glass types indicated supported
on two setting blocks at eight point loading but no more than 6" from the edge of glass.
HORIZONTAL WIDTH IN METERS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1.0
8
SINGLE HUNG OR DOUBLE HUNG
HORIZONTAL
7
GLAZING HEIGHT IN FEET
5
4
1.0
3
A
2
B
C
GLAZING HEIGHT IN METERS
2.0
6
GLASS TYPE:
A = 1/8" - 3/4" A.S. - 1/8"
B = 3/16" - 5/8" A.S. - 3/16"
C = 1/4" - 1/2" A.S. - 1/4"
1
0
0
1
2
3
4
5
6
HORIZONTAL WIDTH IN METERS
1.0
8
TRUE HORIZONTAL MUNTIN
FOR FIXED WINDOW
7
6
5
4
3
A
2
B
C
1.0
GLAZING HEIGHT IN METERS
GLAZING HEIGHT IN FEET
2.0
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
HORIZONTAL WIDTH IN FEET
1
0
0
1
2
3
4
5
6
HORIZONTAL WIDTH IN FEET
kawneer.com
ADME050
GLASS TYPE:
A = 1/8" - 3/4" A.S. - 1/8"
B = 3/16" - 5/8" A.S. - 3/16"
C = 1/4" - 1/2" A.S. - 1/4"
AATM3350 IsoPortTM Window
30
JULY, 2014
EC 97911-063
RECEPTORS, SUB SILLS AND ANCHORING
SCALE : 3" = 1'-0"
TYPICAL RECEPTOR SYSTEM
325059
4-1/4"
335225
JAMB
RECEPTOR
(Interior Installation)
4-3/8"
335225
1-13/16"
FULL DEPTH
SILL
1-5/16"
5/8"
335226
ANCHORING
335400
335400
260100
3-1/2"
246500
246501
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
STRAP ANCHOR
WITH HUNG WINDOW
STRAP ANCHOR
WITH FIXED WINDOW
335306
260475
UNEQUAL LEG SILL
INTERIOR SNAP TRIM
ANCHORING
FLANGE / NAILING FIN
335471
335400
335472
STRAP ANCHOR WITH
HORIZONTAL SLIDER
PVC PERIMETER
(Head and Jamb of XX Slider
and Female Stack Jambs of
Double Hung similar)
ADME050
PVC PERIMETER
(Typical at Head and Jamb of
XO/OX/XOX/OXO Slider and
Female Stack Jambs of Single
Hung similar)
kawneer.com
© Kawneer Company, Inc., 2014
325059
HEAD
RECEPTOR
(Interior Installation)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
1-5/16"
4-1/4"
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
31
FIXED WINDOW THERMAL CHARTS
Project Specific U-Factor Example Calculation
56-3/8"
(1432)
Example Glass U-Factor = 0.42 Btu/hr • ft2 • °F
5'-0"
(1524)
Total Daylight Opening
= 32-3/8" • 56-3/8" = 12.67ft2
Total Projected Area
= 3'-0" • 5'-0" = 15 ft2
0.90
(5.00)
0.85
Percent of Glass
= (Total Daylight Opening ÷ Total Projected Area)100
= (12.67 ÷ 15)100 = 85%
0.80
32-3/8"
(822)
(4.50)
0.75
System U-factor vs Percent of Glass Area
0.70
(4.00)
0.65
0.60
0.46 (2.61)
0.44 (2.50)
0.42 (2.39)
0.40 (2.27)
0.38 (2.16)
0.36 (2.05)
0.34 (1.93)
© Kawneer Company, Inc., 2014
0.32 (1.82)
0.50
0.44
Btu
hr • ft2 • °F
System U-factor
0.48 (2.73)
0.55
E IGN
PL S
M E
A D
EX OR
F
T
O
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
N
COG
U-factor
(3.50)
(3.00)
0.45
(2.50)
0.40
0.35
0.30 (1.71)
(2.00)
0.28 (1.59)
0.30
0.26 (1.48)
0.24 (1.37)
0.22 (1.25)
0.25
0.20 (1.14)
0.20
0.85
Percent of Glass Area
Based on 85% glass and center of glass (COG) U-factor of 0.42
System U-factor is equal to 0.44 Btu/hr • ft2 • °F
kawneer.com
ADME050
(1.50)
W
m2 • °C
System U-factor
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
3'-0"
(915)
AATM3350 IsoPortTM Window
32
JULY, 2014
EC 97911-063
FIXED WINDOW THERMAL CHARTS
AATM3350 IsoPortTM FIXED WINDOW
Note:
Values in parentheses are metric.
COG = Center of Glass.
Charts are generated per AMMA 507
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
System U-factor vs Percent of Glass Area
0.90
(5.00)
0.85
0.80
(4.50)
0.75
0.70
(4.00)
0.55
COG
U-factor
0.50
0.48 (2.73)
(3.00)
0.46 (2.61)
0.44 (2.50)
0.45
0.42 (2.39)
(2.50)
0.40 (2.27)
0.38 (2.16)
0.40
0.36 (2.05)
0.34 (1.93)
0.32 (1.82)
0.35
0.30 (1.71)
(2.00)
0.28 (1.59)
0.30
0.26 (1.48)
0.24 (1.37)
0.22 (1.25)
0.25
0.20 (1.14)
(1.50)
0.20
Percent of Glass Area = Vision Area/Total Area
Daylight Opening / Projected Area
Notes for System U-factor, SHGC and VT charts:
For glass values that are not listed, linear interpolation is permitted.
Glass properties are based on center of glass values and are obtained from your glass supplier.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
(3.50)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Btu
hr • ft2 • °F
System U-factor
0.60
W
m2 • °C
System U-factor
0.65
System VT
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
kawneer.com
AATM3350 IsoPortTM Window
EC 97911-063
FIXED WINDOW THERMAL CHARTS
AATM3350 IsoPortTM FIXED WINDOW
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
COG
SHGC
Vision Area / Total Area (%)
System Visible Transmittance (VT) vs Percent of Vision Area
COG
VT
Vision Area / Total Area (%)
ADME050
33
34
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
FIXED WINDOW THERMAL PERFORMANCE MATRIX (NFRC SIZE)
AATM3350 IsoPortTM FIXED WINDOW
Thermal Transmittance1 (BTU/hr • ft 2 • °F)
Overall U-Factor 4
0.48
0.56
0.46
0.54
0.44
0.52
0.42
0.51
0.40
0.49
0.38
0.48
0.36
0.46
0.34
0.44
0.32
0.43
0.30
0.41
0.28
0.40
0.26
0.38
0.24
0.36
0.22
0.35
0.20
0.33
Glass SHGC 3
Overall Glass U-Factor 4
Glass VT 3
Overall VT 4
0.75
0.65
0.75
0.64
0.70
0.61
0.70
0.60
0.65
0.57
0.65
0.56
0.60
0.53
0.60
0.51
0.55
0.48
0.55
0.47
0.50
0.44
0.50
0.43
0.45
0.40
0.45
0.39
0.40
0.35
0.40
0.34
0.35
0.31
0.35
0.30
0.30
0.27
0.30
0.26
0.25
0.23
0.25
0.21
0.20
0.18
0.20
0.17
0.15
0.14
0.15
0.13
0.10
0.10
0.10
0.09
0.05
0.05
0.05
0.04
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
1200mm wide by 1500mm high (47-1/4" by 59-1/16").
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Visible Transmittance 2
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
SHGC Matrix 2
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Glass U-Factor 3
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
35
SINGLE HUNG THERMAL CHARTS
Generic Project Specific U-factor Example Calculation
(Percent of Glass will vary on specific products depending on sitelines)
3'-0"
(915)
25-3/4"
(654)
5'-0"
(1524)
25-3/4"
(654)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
30-3/4"
(781)
28-5/8"
(727)
Example Glass U-Factor = 0.42 Btu/hr • ft2 • °F
Total Daylight Opening
= (30-3/4" • 25-3/4") + (28-5/8" • 25-3/4") = 10.62 ft2
Total Projected Area
= 3'-0" • 5'-0" = 15 ft2
Percent of Glass
= (Total Daylight Opening ÷ Total Projected Area)100
= (10.62 ÷ 15)100 = 71%
System U-factor vs Percent of Glass Area
(5.00)
0.85
0.80
© Kawneer Company, Inc., 2014
(2.73)
(2.61)
(2.50)
(2.39)
(2.27)
(2.16)
(2.05)
(1.93)
(1.82)
(1.71)
(1.59)
(1.48)
(1.37)
(1.25)
(1.14)
0.65
0.60
0.55
0.50 0.51
0.45
(4.00)
(3.50)
(3.00)
(2.50)
0.40
0.35
(2.00)
0.30
0.25
0.20
70
71%
75
65
60
55
Percent of Glass Area
Based on 71% glass and center of glass (COG) U-factor of 0.42
System U-factor is equal to 0.51 Btu/hr • ft2 • °F
kawneer.com
Btu
hr • ft2 • °F
System U-factor
E IGN
PL S
M E
A D
EX OR
F
T
O
COG
U-factor
0.48
0.46
0.44
0.42
0.40
0.38
0.36
0.34
0.32
0.30
0.28
0.26
0.24
0.22
0.20
0.70
ADME050
50
(1.50)
W
m2 • °C
System U-factor
(4.50)
0.75
N
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
0.90
36
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
SINGLE HUNG THERMAL CHARTS
AATM3350 IsoPortTM SINGLE HUNG WINDOW
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Note:
Values in parentheses are metric.
COG = Center of Glass.
Charts are generated per AMMA 507
Percent of Glass Area = Vision Area/Total Area
Daylight Opening / Projected Area
Notes for System U-factor, SHGC and VT charts:
For glass values that are not listed, linear interpolation is permitted.
Glass properties are based on center of glass values and are obtained from your glass supplier.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
COG
U-factor
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Btu
hr • ft2 • °F
System U-factor
System U-factor vs Percent of Glass Area
System VT
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
kawneer.com
AATM3350 IsoPortTM Window
EC 97911-063
Vision Area / Total Area (%)
ADME050
37
SINGLE HUNG THERMAL CHARTS
AATM3350 IsoPortTM SINGLE HUNG WINDOW
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
COG
SHGC
Vision Area / Total Area (%)
System Visible Transmittance (VT) vs Percent of Vision Area
COG
VT
With Warm Edge Spacer
With Aluminum Spacer
AATM3350 IsoPortTM SINGLE HUNG WINDOW
Thermal Transmittance1 (BTU/hr • ft 2 • °F)
Glass U-Factor 3
Overall U-Factor 4
0.48
0.57
0.46
0.55
0.44
0.54
0.42
0.53
0.40
0.51
0.38
0.50
0.36
0.49
0.34
0.47
0.32
0.46
0.30
0.45
0.28
0.43
0.26
0.42
0.24
0.40
0.22
0.39
0.20
0.38
0.38
0.47
0.36
0.45
0.34
0.44
0.32
0.42
0.30
0.41
0.28
0.40
0.26
0.39
0.24
0.37
0.22
0.35
0.20
0.34
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
SINGLE HUNG THERMAL PERFORMANCE MATRIX (NFRC SIZE)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
AATM3350 IsoPortTM Window
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
38
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM Window
JULY, 2014
SINGLE HUNG THERMAL PERFORMANCE MATRIX (NFRC SIZE)
AATM3350 IsoPortTM SINGLE HUNG WINDOW
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall Glass U-Factor 4
Glass VT 3
Overall VT 4
0.75
0.57
0.75
0.56
0.70
0.53
0.70
0.52
0.65
0.49
0.65
0.48
0.60
0.46
0.60
0.45
0.55
0.42
0.55
0.41
0.50
0.38
0.50
0.37
0.45
0.34
0.45
0.33
0.40
0.31
0.40
0.30
0.35
0.27
0.35
0.26
0.30
0.23
0.30
0.22
0.25
0.20
0.25
0.19
0.20
0.16
0.20
0.15
0.15
0.12
0.15
0.11
0.10
0.08
0.10
0.07
0.05
0.05
0.05
0.04
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
1200mm wide by 1500mm high (47-1/4" by 59-1/16").
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
kawneer.com
ADME050
39
AATM3350 IsoPortTM Window
40
JULY, 2014
EC 97911-063
DOUBLE HUNG THERMAL CHARTS
Generic Project Specific U-factor Example Calculation
(Percent of Glass will vary on specific products depending on sitelines)
3'-0"
(915)
24-31/32"
(634)
5'-0"
(1524)
24-31/32"
(634)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
28-5/8"
(727)
28-5/8"
(727)
Example Glass U-Factor = 0.42 Btu/hr • ft2 • °F
Total Daylight Opening
= (28-5/8" • 24-31/32") + (28-5/8" • 24-31/32") = 9.21 ft2
Total Projected Area
= 3'-0" • 5'-0" = 15 ft2
Percent of Glass
= (Total Daylight Opening ÷ Total Projected Area)100
= (9.21 ÷ 15)100 = 61%
System U-factor vs Percent of Glass Area
0.90
E IGN
PL S
M E
A D
EX OR
F
T
O
(2.73)
(2.61)
(2.50)
(2.39)
(2.27)
(2.16)
(2.05)
(1.93)
(1.82)
(1.71)
(1.59)
(1.48)
(1.37)
(1.25)
(1.14)
0.65
0.60
Btu
hr • ft2 • °F
System U-factor
N
COG
U-factor
(4.00)
(3.50)
0.550.55
0.50
0.45
(3.00)
(2.50)
0.40
0.35
(2.00)
0.30
0.25
(1.50)
0.20
75
70
60
65
Percent of Glass Area
55
50
61%
0.48
0.46
0.44
0.42
0.40
0.38
0.36
0.34
0.32
0.30
0.28
0.26
0.24
0.22
0.20
0.70
W
m2 • °C
System U-factor
(4.50)
0.75
Based on 61% glass and center of glass (COG) U-factor of 0.42
System U-factor is equal to 0.55 Btu/hr • ft2 • °F
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
0.80
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
(5.00)
0.85
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
DOUBLE HUNG THERMAL CHARTS
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Note:
Values in parentheses are metric.
COG = Center of Glass.
Charts are generated per AMMA 507
Btu
hr • ft2 • °F
System U-factor
System U-factor vs Percent of Glass Area
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
COG
U-factor
Percent of Glass Area = Vision Area/Total Area
Daylight Opening / Projected Area
Notes for System U-factor, SHGC and VT charts:
For glass values that are not listed, linear interpolation is permitted.
Glass properties are based on center of glass values and are obtained from your glass supplier.
kawneer.com
ADME050
41
COG
SHGC
Vision Area / Total Area (%)
System Visible Transmittance (VT) vs Percent of Vision Area
COG
VT
Vision Area / Total Area (%)
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
DOUBLE HUNG THERMAL CHARTS
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
System SHGC
AATM3350 IsoPortTM Window
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System VT
42
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
With Warm Edge Spacer
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
With Aluminum Spacer
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
kawneer.com
AATM3350 IsoPortTM Window
EC 97911-063
DOUBLE HUNG THERMAL PERFORMANCE MATRIX (NFRC SIZE)
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
Thermal Transmittance1 (BTU/hr • ft 2 • °F)
Glass U-Factor 3
Overall U-Factor 4
0.48
0.57
0.46
0.56
0.44
0.55
0.42
0.53
0.40
0.52
0.38
0.51
0.36
0.50
0.34
0.48
0.32
0.47
0.30
0.46
0.28
0.44
0.26
0.43
0.24
0.42
0.22
0.41
0.20
0.39
0.38
0.48
0.36
0.46
0.34
0.45
0.32
0.44
0.30
0.42
0.28
0.41
0.26
0.40
0.24
0.38
0.22
0.37
0.20
0.36
ADME050
43
AATM3350 IsoPortTM Window
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM DOUBLE HUNG WINDOW
Visible Transmittance 2
Glass SHGC 3
Overall Glass U-Factor 4
Glass VT 3
Overall VT 4
0.75
0.54
0.75
0.53
0.70
0.50
0.70
0.49
0.65
0.47
0.65
0.46
0.60
0.43
0.60
0.42
0.55
0.40
0.55
0.39
0.50
0.39
0.50
0.35
0.45
0.33
0.45
0.32
0.40
0.29
0.40
0.28
0.35
0.26
0.35
0.25
0.30
0.22
0.30
0.21
0.25
0.19
0.25
0.18
0.20
0.15
0.20
0.14
0.15
0.12
0.15
0.11
0.10
0.08
0.10
0.07
0.05
0.05
0.05
0.04
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
SHGC Matrix 2
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
1200mm wide by 1500mm high (47-1/4" by 59-1/16").
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
DOUBLE HUNG THERMAL PERFORMANCE MATRIX (NFRC SIZE)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
44
JULY, 2014
AATM3350 IsoPortTM Window
EC 97911-063
OX HORIZONTAL SLIDER THERMAL CHARTS
45
Generic Project Specific U-factor Example Calculation
(Percent of Glass will vary on specific products depending on sitelines)
25-5/8"
(651)
3'-0"
(915)
26-3/16"
(665)
28-5/16"
(719)
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
5'-0"
(1524)
25-5/8"
(651)
Example Glass U-Factor = 0.42 Btu/hr • ft2 • °F
Total Daylight Opening
= (25-5/8" • 28-5/16") + (25-5/8" • 26-3/16") = 9.70 ft2
Total Projected Area
= 3'-0" • 5'-0" = 15 ft2
Percent of Glass
= (Total Daylight Opening ÷ Total Projected Area)100
= (9.70 ÷ 15)100 = 65%
System U-factor vs Percent of Glass Area
(5.00)
0.85
0.80
© Kawneer Company, Inc., 2014
(2.73)
(2.61)
(2.50)
(2.39)
(2.27)
(2.16)
(2.05)
(1.93)
(1.82)
(1.71)
(1.59)
(1.48)
(1.37)
(1.25)
(1.14)
0.65
0.60
0.55
0.50
0.45
0.35
(3.50)
(3.00)
(2.50)
(2.00)
0.30
0.20
65
65%
70
60
55
Percent of Glass Area
Based on 65% glass and center of glass (COG) U-factor of 0.42
System U-factor is equal to 0.53 Btu/hr • ft2 • °F
kawneer.com
0.53
(4.00)
0.40
0.25
75
Btu
hr • ft2 • °F
System U-factor
E IGN
PL S
M E
A D
EX OR
F
T
O
COG
U-factor
0.48
0.46
0.44
0.42
0.40
0.38
0.36
0.34
0.32
0.30
0.28
0.26
0.24
0.22
0.20
0.70
ADME050
50
(1.50)
W
m2 • °C
System U-factor
(4.50)
0.75
N
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
0.90
46
AATM3350 IsoPortTM Window
JULY, 2014
OX HORIZONTAL SLIDER THERMAL CHARTS
EC 97911-063
AATM3350 IsoPortTM OX HORIZONTAL SLIDER WINDOW
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Note:
Values in parentheses are metric.
COG = Center of Glass.
Charts are generated per AMMA 507
System U-factor vs Percent of Glass Area
Percent of Glass Area = Vision Area/Total Area
Daylight Opening / Projected Area
Notes for System U-factor, SHGC and VT charts:
For glass values that are not listed, linear interpolation is permitted.
Glass properties are based on center of glass values and are obtained from your glass supplier.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Btu
hr • ft2 • °F
System U-factor
COG
U-factor
System VT
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
AATM3350 IsoPortTM Window
EC 97911-063
OX HORIZONTAL SLIDER THERMAL CHARTS
Vision Area / Total Area (%)
kawneer.com
ADME050
47
AATM3350 IsoPortTM OX HORIZONTAL SLIDER WINDOW
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
COG
SHGC
Vision Area / Total Area (%)
System Visible Transmittance (VT) vs Percent of Vision Area
COG
VT
AATM3350 IsoPortTM OX HORIZONTAL SLIDER WINDOW
Thermal Transmittance1 (BTU/hr • ft 2 • °F)
Glass U-Factor 3
Overall U-Factor 4
0.47
0.54
0.46
0.53
0.44
0.52
0.42
0.50
0.40
0.49
0.38
0.48
0.36
0.47
0.34
0.46
0.32
0.44
0.30
0.43
0.28
0.42
0.26
0.41
0.24
0.39
0.22
0.38
0.20
0.37
0.18
0.35
0.16
0.34
0.14
0.33
0.12
0.32
0.10
0.30
ADME050
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
OX HORIZONTAL SLIDER THERMAL PERFORMANCE MATRIX (NFRC SIZE)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
AATM3350 IsoPortTM Window
kawneer.com
© Kawneer Company, Inc., 2014
With Aluminum Spacer
48
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM Window
JULY, 2014
OX HORIZONTAL SLIDER THERMAL PERFORMANCE MATRIX (NFRC SIZE)
AATM3350 IsoPortTM OX HORIZONTAL SLIDER WINDOW
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall Glass U-Factor 4
Glass VT 3
Overall VT 4
0.75
0.53
0.75
0.52
0.70
0.50
0.70
0.49
0.65
0.46
0.65
0.45
0.60
0.43
0.60
0.42
0.55
0.39
0.55
0.38
0.50
0.36
0.50
0.35
0.45
0.32
0.45
0.31
0.40
0.29
0.40
0.28
0.35
0.25
0.35
0.24
0.30
0.22
0.30
0.21
0.25
0.18
0.25
0.17
0.20
0.15
0.20
0.14
0.15
0.11
0.15
0.10
0.10
0.08
0.10
0.07
0.05
0.04
0.05
0.03
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
1500mm wide by 1200mm high (59-1/16" by 47-1/4").
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
kawneer.com
ADME050
49
50
AATM3350 IsoPortTM Window
JULY, 2014
XX HORIZONTAL SLIDER THERMAL CHARTS
EC 97911-063
AATM3350 IsoPortTM XX HORIZONTAL SLIDER WINDOW
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
Note:
Values in parentheses are metric.
COG = Center of Glass.
Charts are generated per AMMA 507
System U-factor vs Percent of Glass Area
Percent of Glass Area = Vision Area/Total Area
Daylight Opening / Projected Area
Notes for System U-factor, SHGC and VT charts:
For glass values that are not listed, linear interpolation is permitted.
Glass properties are based on center of glass values and are obtained from your glass supplier.
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Btu
hr • ft2 • °F
System U-factor
COG
U-factor
System VT
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
System SHGC
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
JULY, 2014
AATM3350 IsoPortTM Window
EC 97911-063
XX HORIZONTAL SLIDER THERMAL CHARTS
Vision Area / Total Area (%)
kawneer.com
ADME050
51
AATM3350 IsoPortTM XX HORIZONTAL SLIDER WINDOW
System Solar Heat Gain Coefficient (SHGC) vs Percent of Vision Area
COG
SHGC
Vision Area / Total Area (%)
System Visible Transmittance (VT) vs Percent of Vision Area
COG
VT
AATM3350 IsoPortTM XX HORIZONTAL SLIDER WINDOW
Thermal Transmittance1 (BTU/hr • ft 2 • °F)
Glass U-Factor 3
Overall U-Factor 4
0.47
0.56
0.46
0.55
0.44
0.54
0.42
0.52
0.40
0.51
0.38
0.50
0.36
0.49
0.34
0.48
0.32
0.47
0.30
0.45
0.28
0.44
0.26
0.43
0.24
0.42
0.22
0.41
0.20
0.40
0.18
0.38
0.16
0.37
0.14
0.36
0.12
0.35
0.10
0.34
ADME050
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
XX HORIZONTAL SLIDER THERMAL PERFORMANCE MATRIX (NFRC SIZE)
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
AATM3350 IsoPortTM Window
kawneer.com
© Kawneer Company, Inc., 2014
With Aluminum Spacer
52
JULY, 2014
EC 97911-063
AATM3350 IsoPortTM Window
JULY, 2014
XX HORIZONTAL SLIDER THERMAL PERFORMANCE MATRIX (NFRC SIZE)
AATM3350 IsoPortTM XX HORIZONTAL SLIDER WINDOW
SHGC Matrix 2
Visible Transmittance 2
Glass SHGC 3
Overall Glass U-Factor 4
Glass VT 3
Overall VT 4
0.75
0.51
0.75
0.50
0.70
0.47
0.70
0.46
0.65
0.44
0.65
0.43
0.60
0.41
0.60
0.40
0.55
0.37
0.55
0.36
0.50
0.34
0.50
0.33
0.45
0.31
0.45
0.30
0.40
0.28
0.40
0.26
0.35
0.24
0.35
0.23
0.30
0.21
0.30
0.20
0.25
0.18
0.25
0.17
0.20
0.14
0.20
0.13
0.15
0.11
0.15
0.10
0.10
0.08
0.10
0.07
0.05
0.04
0.05
0.03
NOTE: For glass values that are not listed, linear interpolation is permitted.
1. U-Factors are determined in accordance with NFRC 100.
2. SHGC and VT values are determined in accordance with NFRC 200.
3. Glass properties are based on center of glass values and are obtained from your glass supplier.
4. Overall U-Factor, SHGC, and VT Matricies are based on the standard NFRC specimen size of
1500mm wide by 1200mm high (59-1/16" by 47-1/4").
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
EC 97911-063
kawneer.com
ADME050
53
Laws and building and safety codes governing the design and use of glazed
entrance, window, and curtain wall products vary widely. Kawneer does not control
the selection of product configurations, operating hardware, or glazing materials,
and assumes no responsibility therefor.
AATM3350 IsoPortTM Window
BLANK PAGE
ADME050
kawneer.com
© Kawneer Company, Inc., 2014
Kawneer reserves the right to change configuration without prior notice when deemed
necessary for product improvement.
54
JULY, 2014
EC 97911-063