VISTA-128FBP Data Sheet

VISTA®-128FBP/V128FBP-24
COMMERCIAL PARTITIONED FIRE AND BURGLARY
ALARM CONTROL PANEL
Now UL864 9th Edition Approved
The new VISTA-128FBP provides the ultimate protection of
initiating devices, notification circuits, communication devices,
life and property. This UL Listed commercial fire and burglary
keypads, RF receivers and relays are also supported. The
control panel supports up to eight partitions and up to 128
VISTA-128FBP has been designed to mount quickly and
zones/points using hardwired, wireless and V-Plex
easily in an attack resistant cabinet, and is available in 12V
addressable technologies. A diverse line of Honeywell
and 24V models.
®
FEATURES
• Eight hardwired zones standard,
expandable to 120 V-Plex
addressable points/zones or
128 wireless points/zones
• Can control eight separate areas
independently (8 partitions)
• Supports commercial wireless fire
and burglary devices
• Stores up to 512 events
• Accommodates 150 user codes
and up to 250 access card holders
using VISTAKEY®
• Supports V-Plex addressable
VISTAKEY access control
(1 to 8 doors)
• Two on-board notification (bell)
circuits delivering 2.3A @ 12V
• Automatic smoke detector sensitivity
maintenance testing
• Four-wire smoke reset using
onboard J2 output trigger
• Supports Dynamic Signaling for
AlarmNet Communicators
• Supports Internet and GSM
alarm reporting*
• Supports graphical user interfaces
for burglary use
• Supports 6160CR-2 multi-LED
fire keypad
• Listed to UL864 9th Edition
• Upload/download via Ethernet*
• Carbon monoxide (CO)
zone support
* When used with AlarmNet devices.
VISTA®-128FBP/V128FBP-24
COMMERCIAL PARTITIONED FIRE AND
BURGLARY ALARM CONTROL PANEL
ADDITIONAL FEATURES
• Notification Appliance Circuits (two):
- Programmable
- Temporal code compliant
- Individually silenceable
• Programmable on-board auxiliary relay
• False alarm reduction features:
- Exit error logic
- Exit delay reset
- Cross zoning
- Call waiting defeat
- Recent close report
• Supports commercial hardwired,
addressable V-Plex® polling loop and
wireless zones
• Hardwired zones
- Individually assignable to any of
eight partitions
- Up to 16 two-wire smoke detectors each
on zone one and two (32 total)
- Up to 50 two-wire glassbreak detectors
on zone eight
• Patented addressable V-Plex polling
loop technology
- Supports 120 two-wire zones points
- Global polling technology for faster
processing
- Supervised by panel
- Zones individually assignable to
partitions, notification circuit (bell) output
or auxiliary relay
- 4,000 ft. capability without the use of
shielded cable
- Provides eight style B hardwired zones
- Extender/Isolation bus modules
- EOLR supervised for Fire and UL burglary
installations- Supports N.O. or N.C sensors
- Eight zone - Class A and B expander
module
- Eight zone - Class B expander module
- Single-zone supervised contact module
• UL Listed wireless expansion
- Supports up to 128 wireless zones/points
- Supervised by control for check-in signals
- Tamper protection for transmitters
- Individually assignable up to eight partitions
- Supports commercial wireless smoke
detectors
• Up to eight doors using VISTAKEY V-Plex
Access Control
• Event reporting
• Local printer for event log printing
• Communication
- Phone line, GSM and IP communicator
support
- Panel operation during download
SPECIFICATIONS
Applications
Main Dialer
Agency Listings
The VISTA-128FBP control is well suited
for a variety of applications as an
integrated fire and burglary control. Some
of the applications supported are:
medical and professional buildings,
churches or synagogues, office buildings,
schools, strip malls, larger residences
and factory or warehouse environments.
• Line seize: Double Pole
• UL609 Grade A Local Mercantile
Premises and Mercantile Safe and Vault
Electrical
• Primary power: 18VAC @ 72VA
Honeywell No. 1451
• Control panel quiescent current draw:
300mA
• Backup battery:
- 12VDC, 12AH min to 34.4AH max
- Lead acid battery (gel type)
• Alarm power: 12VDC, 1.7A max for
each notification (bell) circuit output
Total 2.3A 12V
• Aux. standby pwr: 12VDC, 1A max
• Total power: 2.3A at 12VDC
• Standby time: 24 hours with 1A
standby load using 34.4AH battery
• Fusing: Battery input, aux. and
notification (bell) circuit outputs are
protected using PTC circuit protectors.
All outputs are power limited.
• Optional 24-volt kit
• Ringer equiv: 0.7B
• Formats: ADEMCO® Low Speed,
ADEMCO 4+2 Express, ADEMCO High
Speed, ADEMCO Contact ID, Sescoa
and Radionics
Backup Communication
• Dual phone line capability using
5140DLM module
• AlarmNet® GSM, i-GSM and IP
Communicators
Cabinet Dimensions
• 18" H x 14.5" W x 4.3"D
Environmental
• Storage temp: 14° F to 158° F
(-10° C to 70° C)
• Operating temp: 32° F to 122° F
(0° C to 50° C)
• Humidity: 85% RH
• EMI: Meets or exceeds the following
requirements:
- FCC Part 15, Class B Device
- FCC Part 68
- IEC EMC Directive
• UL611/1610 Grades A, AA, Central
Station
• UL365 Grades A, AA Police Connect
• UL864/NFPA72 Local, Central
Station and Remote Station
• UL985
• Factory Mutual
• California State Fire Marshal
• MEA
• CAN/ULC S304 – Central and
Monitoring Station Burglar Alarm Unit
• CAN/ULC S527 – Central Unit for Fire
Alarm Systems
• CAN/ULC S303 – Local Burglar
Alarm Unit
• CAN/ULC S525 – Audible Signal
Appliances
VISTA®-128FBP/V128FBP-24
COMMERCIAL PARTITIONED FIRE AND BURGLARY ALARM CONTROL PANEL
COMPATIBLE DEVICES
Auxiliary Devices
• 4208SNF Class A/B Expander Module
• 6160CR-2 - Red Fire Keypad
• 4190SN Remote Point Module two zones
• 6160 - Burglary Keypad
• 4204 - Relay Module, four form
• 4204CF - Two supervised output
circuits
• 5881 Series RF receiver
4100SM serial module
• 5817CB - Wireless Commercial
Transmitter
V-Plex Extender/Isolation Modules
• 5869 - Hold-Up Transmitter
• 4297 Extender/Isolator Module
• 5881ENHC - RF Receiver
• VSI Isolator Module
• 5883H - RF Receiver
• 5883H RF receiver
• 6220S - System printer used with
Detector
• 5809 - Wireless Heat Detector
• 4193SN and 4193SNP Two-zone
Expander Modules
C contacts
• 5806W3 - Photoelectric Smoke
V-Plex Smoke Detectors
Access Control
• 5193SD
• VISTAKEY® V-Plex (addressable)
Access Control
• 5193SDT
Two-Wire Smoke Detectors
• VISTAKEY-SK Starter Kit
Conventional
V-Plex Passive Infrared Detectors
• System Sensor
• 998MX
• ESL
• IS2500SN
• DSC
• DT7500SN
• 7845i-ENT - Internet/Intranet
Horn/Strobes
V-Plex (Addressable) Contacts
• 7845GSM - Digital Cellular
• VISTAKEY-EX Expansion Kit
Alarm Communications
Communicator
• System Sensor
• 4939SN-WH
• Wheelock
• 4944SN-WH
• Gentex
• 4959SN
Communicator
• 7845i-GSM - Internet and Digital
Cellular Communicator
Manual Pull Stations
V-Plex Glassbreak Detectors
• 5140MPS-1
• FG1625SN
• 5140MPS-2
Optional 24V Kit
V-Plex (Addressable) Devices
• Order number: V128FBP924KT
• 4208U Universal Eight-zone Expansion
Commercial Wireless Devices
Module
• GSMCF/iGSMCF - Commercial Fire
Communication Kits (when available)
• IPGSM-DP Internet and Digital Cellular
Communicator
• 5808W3 - Photoelectric Smoke/Heat
• 4101SN Single Relay/Zone Module
Detector
Product specifications subject to change.
ORDERING
V128FBP-9
V128FBP9-24
Commercial Fire and Partitioned Burglary Alarm Control Panel 12V Model
Commercial Fire and Partitioned Burglary Alarm Control Panel 24V Model
For more information: www.honeywell.com/security
Automation and Control Solutions
Honeywell Security Products Americas
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747
1.800.467.5875
www.honeywell.com
L/VSTA128FBPD/D
September 2012
© 2012 Honeywell International Inc.