Download PDF (1.3MB) - Updated 1/2015

Solid State Control
3RM1 Hybrid Starters
SIRIUS
Contents
Pages
3RM1 Compact - Hybrid Starters
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6/2
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6/3
Selection and ordering data. . . . . . . . . . . . . . . . . . . . . . . 6/4
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6/5 - 6/9
Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6/9 - 6/10
Siemens Industry, Inc.
Industrial Controls Catalog
6/1
Compact – Hybrid Starters
SIRIUS 3RM1 Motor Starters
For Use in the Control Cabinet
SIRIUS
SIRIUS 3RM1 Motor Starters
Overview
General data
Overview
Functional density/space savings
The 3RM1 motor starters combine the functions direct/reversing
starting and overload protection and safety-related shutdown in
a single device, without changing the 22.5mm width.
For simple applications (such as starting and reversing threephase loads with overload protection), motor starter combinations of power contactors and a solid-state overload relay, for
example, can be replaced by a single 3RM1 starter. The more
functions are required, the more devices can be replaced. The
footprint area required for each motor starter in the control cabinet is reduced by values of 64 to 82%.
In the case of assemblies and grouped starter units there are
further advantages.
Wiring overhead
3RM12 motor starter with reversing functionality and electronic overload
protection
SIRIUS 3RM1 motor starters are compact devices with a width of
22.5 mm, combining a large number of functions in a single enclosure. They consist of combinations of relay contacts, power
semiconductors (hybrid technology), and a solid-state overload
relay for operational switching of three-phase motors up to 3 HP
(at 480 V).
Feature
Value
Rated current
(wide setting range of
the electronic overload release)
0.1 ... 0.5 A
0.4 ... 2.0 A
1.6 ... 7.0 A (UL=6.1A)
Rated operational voltage
48 ... 500 V
Rated frequency
50/60 Hz
Rated control supply voltage
24 V DC, 110 V DC,
110 ... 230 V AC
Characteristic
3RM10 3RM11 3RM12 3RM13
Direct-on-line starters


--
--
Reversing starters
--
--


Overload protection with wide setting
range




ATEX certification overload protection
--

--

Safety-related shutdown up to SIL 3 / PLe --

--

By combining various functions in a single device, wiring overhead is reduced. The greater the number of starters, the greater
the saving in wiring. Savings can be made in:
• mains wiring and space reduction with the use of the 3RM19
three phase infeed system
• wiring of the reversing contactor assembly thanks to the
integrated design
• reduction of control cables for the coils in group applications
with the 3ZY12 device connectors
8
These savings reduce the time required for the wiring itself, while
at the same time reducing both the risk of wiring errors and the
amount of testing required after control cabinets have been
completed.
Configuration and inventory
The wide setting range of the electronic overload release (up to
1:5) reduces the cost of inventory and the considerations involved in configuration where the actual motor current to be expected is concerned. Compared with protection equipment with
Trip class
CLASS 10A
thermal overload protection, only 3 versions are now required to
The 3RM1 motor starters with overload protection with wide setcover a current range of 0.1 to 7 A with 3RM1, instead of 17 verting range are offered as 3RM10 direct-on-line starters and 3RM12 sions.
reversing starters and as versions with safety-related shutdown.
Connection methods
Hybrid technology
The 3RM1 motor starters combine the benefits of semiconductor
technology and relay technology. This combination is also
known as hybrid technology. The hybrid technology in the motor
starter is characterized by the following features:
• The inrush current is is conducted briefly via the semiconductors.
Advantage: protection of relay contacts, long service life due
to low wear
• The continuous current is conducted via relay contacts.
Advantage: lower heat losses compared with the semiconductor.
• Shutdown is implemented again via the semiconductor.
Advantage: the contacts are only slightly exposed to arcs, and
this results in a longer service life.
The 3RM1 is available with screw terminal, push-in terminals or
a combination of both..
Push-in terminals are a form of spring-type connection allowing
fast wiring without tools for rigid conductors or conductors
equipped with end sleeves.
Fine-stranded or stranded conductors with no end finishing are
wired using a screwdriver (with a 3.0 x 0.5 mm blade).
As with other spring-type terminals, a screwdriver is also required to release the conductor. The same tool as above can be
used for this purpose.
The advantages of the push-in terminals are found, as with all
spring-type terminals, in speed of assembly and disassembly
and vibration-proof connection. There is no need for the
checking and tightening required with screw terminals.
Screw terminals
Spring-type terminals
The terminals are indicated in the corresponding
tables by the symbols shown on blue backgrounds.
6/2
Siemens IC 10 N · 12/2012
Siemens Industry, Inc.
Industrial Controls Catalog
8/13
Compact – Hybrid Starters
SIRIUS 3RM1 Motor Starters
SIRIUS
General Data
Safety-related shutdown/safety integration
Feedback to the control system
Thanks to the redundant design of the main circuit and internal
monitoring, safety-related shutdown in accordance with SIL 3 / PLe
is possible by shutting down the control supply voltage with
3RM11 Failsafe and 3RM13 Failsafe motor starters. Additional
safety relays are not required in the main circuit.
The electronic output in the 24 V DC control voltage version of
the 3RM10 and 3RM12 motor starters allows the status of the
connected motor to be reported to the higher-level control
system. If the motor starter is controlled via inputs IN1 to 2, once
the motor has been switched on and has started up correctly the
output "OUT" is set.
3RM1 motor starter
Infeed system for the main circuit
The 3RM19 infeed system available as an accessory for the
main circuit with three-phase busbars allows fast, virtually errorfree wiring of motor starters on the mains connection side and
may reduce the number of short-circuit protective devices.
IC01_00178
3SK1 safety relay
Motor
Combination of four SIRIUS 3RM1 Failsafe motor starters with SIRIUS
3SK1 safety relay to allow safety-related collective disconnection of
connected motors
3RM1 motor starters are ideal for combining with the 3SK1 safety
relay (see Chapter 13 "Safety Technology" "SIRIUS 3SK1 Safety
Relays"). They can be combined by means of:
• conventional wiring
• a special device connector
8
This makes it very simple to shut down connected motors collectively. The wiring, and ultimately the shutting down of the control
supply voltage in Emergency Stop situations, is performed via
the device connector. There is no further need for complex looping of the connecting cables.
Benefits
Advantages through energy efficiency
y
ef
f ic i e
n cy c
on
rg
Ene
Ide
nt
ifi
n
ti o
ation
alu
Ev
g
l t in
su
ca
according to
EN 16001
Realization
IC01_00135
Overview of the energy management process
We offer you a unique portfolio for efficient industrial energy
management, using an energy management system that helps
to optimally define your energy needs. We split up our industrial
energy management into three phases – identify, evaluate, and
realize – and we support you with the appropriate hardware and
software solutions in every process phase.
The innovative products of the SIRIUS Industrial Controls portfolio can also make a substantial contribution to a plant's energy
efficiency (see www.siemens.com/sirius/energysaving).
Product advantages
The SIRIUS 3RM1 motor starters offer a number of benefits:
• Greater endurance and reduced heat losses thanks to hybrid
technology
• Less space required in the control cabinet (64 to 82%) as a
result of higher functional density
• Less wiring and testing required as a result of integrating
several functions into a single device
• Lower costs for stock keeping and configuration as a result of
the wide setting range of the electronic overload release
(up to 1:5)
• Fast wiring without tools for rigid conductors or conductors
equipped with end sleeves thanks to push-in spring-type
connections
• Motor status feedback to the higher-level control system in the
case of 3RM10 and 3RM12 motor starters in the 24 V DC version
• Virtually error-free wiring on the mains connection side and
reduction in short-circuit protective devices by means of
3RM19 comb busbar and infeed system
With 3RM1 motor starters, control cabinets warm up less because power losses have been reduced by operation:
• Lower intrinsic power loss (than comparable motor starters
with thermal overload trips) thanks to electronic current
analysis
• Lower control circuit power losses (compared with conventional switching devices) as a result of electronic control of
switching points
• Thanks to the above advantages, additional energy savings
are possible because less cooling is required and a more
compact design is possible
6/3
Siemens Industry, Inc.
Industrial Controls Catalog
8/14
Siemens IC 10 N · 12/2012
Compact – Hybrid Starters
• Revised •
09/30/14
Hybrid Starters
SIRIUS
3RM1 up to 3HP
Selection and ordering data
n
Direct and reversing starters in 22.5mm width n
Electronic overload protection — class 10
n
Coil voltages 24VDC, 110-230VAC and 110VDC
n
Screw Terminals or Spring Loaded Terminals
n
Group Installation possible with fuse or UL489 breaker
n
SCCR up to 100kA with J fuses
n
Comb busbar accessories for easy group assembly
n
Removeable terminals
3RM1007-1AA04 3RM1207-2AA04
3RM110.-1AA.4
3RM10 motor starter for direct-on-line starting with electronic overload protection
Single-phase
HP ratings 
UL ratings
at 480VAC
Amp
ratings
FLA
AC53 AC51 115V
LRA
200V
Three-phase
HP ratings 
230V
200V
230V
460V
3RM130.-1AA.4
with
Mixed 
Spring Loaded
& Screw
Terminals
Signaling
contacts
All Screw
Terminals
All Spring
Loaded
Terminals
NO
NC
Order No.
Order No.
Order No.
3RM1 01-3AA04
Rated control supply voltage Us= 24 VDC
0.5
0.5
—
—
—
—
—
—
—
1
1
3RM1 01-1AA04
3RM1 01-2AA04
2
14
2
—
—
—
1⁄8
1⁄3
1⁄3
3⁄4
1
1
3RM1 02-1AA04
3RM1 02-2AA04
3RM1 02-3AA04
6.1
43
7
10
1⁄4
1⁄2
1⁄2
1
1 1⁄2
3
1
1
3RM1 07-1AA04
3RM1 07-2AA04
3RM1 07-3AA04
3RM1 01-1AA14
3RM1 02-1AA14
3RM1 07-1AA14
3RM1 01-2AA14
3RM1 02-2AA14
3RM1 07-2AA14
3RM1 01-3AA14
3RM1 02-3AA14
3RM1 07-3AA14
3.5
Rated control supply voltage Us= 110-230 VAC 50/60 Hz and 110 VDC
0.5
2
6.1
3.5
14
43
0.5
2
7
—
—
10
—
—
1⁄4
—
—
1⁄2
—
1⁄8
1⁄2
—
1⁄3
1
—
3⁄4
3
—
1⁄3
1 1⁄2
1
1
1
1
1
1
Standard DOL Starter
Safety DOL Starter
0
1
0
1
3RM12 motor starter for reversing with electronic overload protection
UL ratings
at 480VAC
Amp
ratings
FLA
AC53
LRA
Single-phase
HP ratings 
AC51 115V
200V
Three-phase
HP ratings 
230V
200V
230V
460V
—
1⁄3
1
—
1⁄3
1 1⁄2
—
3⁄4
3
0
1
with
Mixed 
Spring Loaded
& Screw
Terminals
Signaling
contacts
All Screw
Terminals
All Spring
Loaded
Terminals
NO
NC
Order No.
Order No.
Order No.
1
1
1
1
1
1
3RM1 01-1AA04
3RM1 02-1AA04
3RM1 07-1AA04
3RM1 01-2AA04
3RM1 02-2AA04
3RM1 07-2AA04
3RM1 01-3AA04
3RM1 02-3AA04
3RM1 07-3AA04
3RM1 01-1AA14
3RM1 02-1AA14
3RM1 07-1AA14
3RM1 01-2AA14
3RM1 02-2AA14
3RM1 07-2AA14
3RM1 01-3AA14
3RM1 02-3AA14
3RM1 07-3AA14
Rated control supply voltage Us= 24 VDC
0.5
2
6.1
3.5
14
43
0.5
2
7
—
—
10
—
—
1⁄4
—
—
1⁄2
—
1⁄8
1⁄2
Rated control supply voltage Us= 110-230 VAC 50/60 Hz and 110 VDC
0.5
2
6.1
3.5
14
43
0.5
2
7
—
—
10
—
—
1⁄4
—
—
1⁄2
—
1⁄8
1⁄2
—
1⁄3
1
—
1⁄3
1 1⁄2
—
3⁄4
3
1
1
1
1
1
1
Standard Reversing Starter
Safety Reversing Starter
For detail product manuals, schematics and CAD files:
http://www.usa.siemens.com/3RM1
 Mixed terminal versions have spring loaded terminals
 Selection depends on motor full load amps.
This offers faster control wiring while still being able to
use the 3RM19 comb busbar system on the mains.
Horsepower ratings are for reference only.
6/4
2
3
for the control wiring and screw terminals on the mains.
Product Category: IEC
2
3
2
3
For accessories, see page 6/6 and 6/8
For technical data, see page 6/9 and 6/10
For additional Compact Starters up to 25HP at 480V,
see the 3RA6 series located in section 4
Siemens Industry, Inc.
Industrial Controls Catalog
Compact - Hybrid Starters
SIRIUS 3RM1 Motor Starters
SIRIUS
Accessories
Overview
Accessories for 3RM1 motor starters
The following accessories are available for the 3RM1 motor
starter:
• 3-phase infeed system for the main circuit
• Device connectors for the control circuit
• Spare terminals for main and control circuits
- With screw terminals
- With push-in spring-type terminals
• Push-in lugs for wall mounting the motor starters
• Sealable cover as protection against unauthorized access
Three-phase infeed system
(3RM19 three-phase busbar system)
These busbars are available in three lengths, thus allowing
2, 3 or 5 motor starters (arranged side-by-side) to be connected
at the same time. More than 5 devices can be connected by
clamping the connection tags of an additional busbar rotated by
180° (e.g. 6 devices using one 5-pole busbar and one 2-pole
busbar).
A single motor starter can be removed from the assembly without loosening the terminal screws of neighboring motor starters.
The maximum summation current must not exceed 25 A. Primary
infeed is connected via a three-phase infeed terminal.
The three-phase busbars are finger-safe but empty connection
tags must be fitted with covers.
Special three-phase busbar systems can be used to provide an
easy, time-saving and safe means of feeding two or more 3RM1
motor starters with screw terminals.
IC01_00169a
1
4
180 °
3
1
2
2
3
4
4 3RM1 motor starters on standard mounting rail with one
free slot
3RM1920-1AA three-phase feeder terminal
2 3RM1910-1DA three-phase busbars rotated through 180°
for the connection of up to 9 motor starters
5 covers for 3 3RM1910-6AA connection tags respectively
for unused slots
3RM19 infeed system with three-phase infeed terminal: In the above example, two three-phase busbars (5-pole busbars) rotated through 180° allow
up to 9 3RM1 motor starters to be connected. Contact with the unused connection tags in unoccupied positions is prevented safely by the covers.
Siemens Industry, Inc.
Industrial Controls Catalog
6/5
Compact - Hybrid Starters
SIRIUS 3RM1 Motor Starters
SIRIUS
Accessories
Device connectors for the control circuit
The outlay for cabling between the devices is reduced using
device connectors snapped onto a mounting rail, or screwed
onto a level mounting panel (one device connector per motor
starter).
By using device connectors, several motor starters can be jointly
supplied with a control supply voltage of 24 V DC. This requires
the control supply voltage to be applied to the A1 and A2 terminals of only one motor starter.
Up to ten motor starters can be connected with device connectors. The 24 V DC control supply voltage must be within the
operating range of 0.9 to 1.1 for this purpose. If the full operating
range of 0.8 to 1.25 is to be used, no more than five motor starters can be used.
IC01_00218
Using the device connectors only for feeding in the control
supply voltage
If the motor starters are not to be interconnected side-by-side,
device daisy chain connectors must be used for the gaps.
When removing a motor starter, the corresponding device connector must be replaced by a device daisy chain connector if the
control voltage is not to be interrupted for motor starters on the
right.
The last motor starter in a row can be placed on a device termination connector. Flush termination of the configuration is thus
possible.
Device connectors snapped onto a standard mounting rail to allow the
joint connection of the control supply voltage for 3RM1 motor starters or
connection to the 3SK1 safety relays
Using device connectors in conjunction with 3SK1 safety relays
Usage restrictions for accessories
• The 3RM19 3-phase infeed system for the main circuit can
only be used with 3RM1 motor starters with screw terminals.
• The device connectors are only suitable for 3RM1 motor
starters with a control supply voltage of 24 V DC.
Interconnection of several Standard or Failsafe version motor
starters into a group can also be used for joint disconnection by
a 3SK1 safety relay.
To provide for the simultaneous and safe shutdown of several
motor starters via a SIRIUS 3SK1 Safety Relay, you can simply
interconnect the devices without additional wiring using a device
connector.
The motors can then also be shut down safely according to
SIL 3 / PLe with the motor starters.
Up to five motor starters can be operated on one safety relay
with device connectors. If the motor starters are not to be interconnected side-by-side, device loop through connectors must be
used for the gaps.
The last motor starter in a row must be placed on a device termination connector. This closes the circuits that were built up with
the connectors.
For 3SK1 safety relays and associated device connectors see
Chapter 13 "Safety Technology" "SIRIUS 3SK1 Safety Relays"
6/6
Siemens Industry, Inc.
Industrial Controls Catalog
SIRIUS
Compact – Hybrid Starters
• Revised •
09/30/14
3RM1 Hybrid Starters
3RM1 Accessories
Selection and ordering data
Order No.
Pack Units
Device connectors for busing the control supply connection to 3RM1 Starters
Device connector type 2, 7-pole, 22.5mm
Use for:
•Beginning left hand connector
•Subsequent positions where a starter is present
•Maximum of five starters per system
3ZY1212-2EA00
1
Device loop through connector type 2, 7-pole, 22.5mm
Use for:
•When 22.5mm spacing is required and no starter is present
3ZY1212-2AB00
1
Device termination connector type 2, 7-pole, 22.5mm
Use for:
•Terminating connector for the right hand position
•Terminating cover is assembled to 3ZY1212-2EA00
3ZY1212-2FA00
1
Screw
Terminals
Spring
Terminals
Order No.
Order No.
3ZY1122-1BA00
3ZY1122-2BA00
6
3ZY1131-1BA00
3ZY1131-2BA00
6
Push-in lugs for wall mounting
2 lugs per starter are required. Standard pack quantity is sufficient for 5 starters
3ZY1311-0AA00
10
Seal covers for 3RM1 starters
Protection of current setting dial. - lockable
3ZY1321-2AA00
5
Cooling pins for removable terminals
For mechanical coding of removable terminals
3ZY1440-1AA00
Pack Units
Removable terminals for 3RM1 Starters
Power Terminals (Line and Load)
2-pole, 12-20 AWG
Control Terminals
3-pole, 14-20 AWG (Screw)
3-pole, 14-16 AWG (Spring)
Further accessories
For detail product manuals, schematics and CAD files:
http://www.usa.siemens.com/3RM1
Siemens Industry, Inc.
Industrial Controls Catalog
Product Category: IEC
6/7
Compact – Hybrid Starters
3RM1 Hybrid Starters
SIRIUS
3RM1 Accessories
Selection and ordering data
Type
Version
Order No.
Pack
3RM19 three-phase infeed system for 3RM1 starters
with screw terminals on the mains
3RM1920-1AA
1
For 2 motor starters
3RM1910-1AA
1
For 3 motor starters
3RM1910-1BA
1
For 5 motor starters
3RM1910-1DA
1
For unused slots
3RM1910-6AA
1
Three-phase feeder terminal
Three-phase busbar system
Protective covers
For finger safety / yellow
6/8
Product Category: IEC
Siemens Industry, Inc.
Industrial Controls Catalog
Compact
– Hybrid
For
Use in the
ControlStarters
Cabinet
SIRIUS3RM1
3RM1Motor
MotorStarters
Starters
SIRIUS
SIRIUS
Technical
Data
General data
Application
3RM1 motor starters are designed for applications in which
small motors have to be connected in the most confined spaces.
Main areas of use
• Conveyor systems
• Logistics systems
• Production machines
• Machine tools
• Small elevators
Standards and approvals
The motor starter complies with the following standards:
• IEC/EN 60947-4-2
• UL 508
• ATEX (available soon)
• IEC 61508-1: SIL 3 (available soon)
• ISO 13849: PLe (available soon)
Technical specifications
3RM1
Type
Mechanical components and environment
Dimensions (W x H x D)
• Width
• Height
• Depth
22.5
100
136.5 (from the standard mounting rail)
141.6 (entire enclosure depth)
Ambient temperature
• During operation
• During storage
• During transport
°C
°C
°C
-25 … +60
-40 … +70
-40 … +70
Installation altitude at height above sea level maximum
m
4 000
D
H
mm
mm
mm
W
Shock resistance
6g/11 ms
Vibration resistance
Mounting position
8
1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz
IP degree of protection
IP20
±10°
±10°
NSB0_01703
Electromagnetic compatibility (EMC)
Emitted interference
• Conducted RF interference emission according to CISPR11
Class A for Industrial applications. Class B for residential,
business and commercial applications.
Class A for industrial applications. Class B for residential,
business and commercial applications.
• Non-conducted RF interference emission according to CISPR11
Interference immunity
• Electrostatic discharge according to IEC 61000-4-2
• Conducted interference injection as high frequency interference according to
IEC 61000-4-6
• Conducted interference BURST according to IEC 61000-4-4
• Conducted interference - phase-to-ground SURGE according to IEC 61000-4-5
• Conducted interference - phase-to-phase SURGE according to IEC 61000-4-5
4 kV contact discharge / 8 kV air discharge
10 V
2 kV / 5 kHz
2 kV
1 kV
3RM1 .01
Type
Main circuit
Rated operational voltage maximum
Operating frequency
• 1 rated value
• 2 rated value
Rated insulation voltage
Rated impulse withstand voltage
Rated operational current at 400 V at AC
Active power loss, typical
Minimum load in % of I_M
Adjustable current response value
• of the inverse-time delayed overload release
1)
V
500
Hz
Hz
50
60
3RM1 .02
3RM1 .07
V
600
kV
6
A
0.5
2
71)
W
0.02
0.3
3.3
%
20
A
0.1 … 0.5
0.4 … 2
1.6 … 71)
UL rating is 6.1A at 480V
Siemens Industry, Inc.
Industrial Controls Catalog
6/9
Siemens IC 10 N · 12/2012
8/15
Compact
Starters
For
Use in –theHybrid
Control
Cabinet
SIRIUS
SIRIUS 3RM1
3RM1Motor
MotorStarters
Starters
SIRIUS
Technical
data
General data
Type
3RM1 ...-AA04
3RM1 ...-AA14
Type of voltage of the control supply voltage
DC
AC/DC
V
24
110
V
—
110 … 230
Hz
Hz
—
—
50
60
0.8 … 1.25
0.85 … 1.1
—
0.85 … 1.1
A
0.08
0.05
V
V
24
—
110
110 … 230
Input voltage at the digital input with signal <1>
• At DC
• At AC
V
V
19.2 … 30
—
93 ... 121
93 … 253
Input current at the digital input with signal <1> typical
A
0.01
0.002
3RM1...-14
3RM1...-24
Control circuits
Control supply voltage 1
• At DC
• At 50 Hz
- At AC
Frequency of the control supply voltage
• 1 rated value
• 2 rated value
Operating range factor of the control supply voltage rated value
• At DC
• At 50 Hz
- At AC
Control current
Input voltage at the digital input
• At DC
• At AC
- Rated value
Type
Connection methods
8
Connectable conductor cross-section for main contacts
• Solid
• Finely stranded
- With end sleeves
- Without end sleeves
Connectable conductor cross-section for auxiliary contacts
• Solid
• Finely stranded
- With end sleeves
- Without end sleeves
AWG number as coded connectable conductor cross-section
• For main contacts
• For auxiliary contacts
mm²
0.5 … 4
mm²
mm²
0.5 … 2.5
—
0.5 … 4
mm²
0.5 … 2.5
0.5 … 1.5
mm²
mm²
0.5 … 2.5
—
0.5 … 1
0.5 … 1.5
20 … 12
20 … 14
20 … 16
Note:
All the above technical specifications are relevant for selecting
the motor starters. Details about installation conditions and the
use of the motor starters, and particularly about the derating of
the rated current, can be found in the manual and the data
sheets located at www.usa.siemens.com/3RM1.
6/10
8/16
Siemens IC 10 N · 12/2012
Siemens Industry, Inc.
Industrial Controls Catalog