Download

Smart Measurement and Monitor Units
KE1
Unit structure that enables Power and
Earth Leakage Monitoring with just one
Unit.*
Use just one Unit to implement multicircuit measurements.
• Connect CT and ZCT Expansion Units for multi-circuit
measurements.
• Many standard features: Open phase, reversed phase,
undercurrent, overcurrent, undervoltage, and overvoltage
protection and RS-485 communications (Modbus and
For the most recent information on Unit certification, refer to your
CompoWay/F).
OMRON website.
• Voltage fluctuation data before and after momentary voltage
Use a UL-compliant current transformer (CT) (KM20-CTF-@@@AU)
for application as a UL-certified component.
sags is logged in memory. Alarms can be output for
momentary voltage sags as short as 25 ms (with the Momentary Voltage Sag Monitor Unit).
• Expansion with DeviceNet Communications Unit to enable reading 30 words of instantaneous power in 100 ms.
• Monitor operation from a computer with the Easy KM-Manager Data Collection Software. (Download it from our
website.)
Features
Monitor Power and Earth Leakage with
Just One Unit
KE1-PGR1C-FLK
You can monitor power to save energy and monitor earth leakage for
electrical equipment all with just one Unit. You can flexibly add CT or
ZCT Units to measure multiple circuits as required.
There is an increasing need to detect problems in advance to protect
against extensive losses from production line and production facility
stoppage due to earth leakage faults.
There is also a need to introduce power monitoring to save energy.
There is a need to measure both earth leakage and power from a
switch panel or distribution panel with only one infrastructure
investment.
The KE1 is the first product line in the world to respond to the need for
smart multi-circuit measurements for power monitoring and earth
leakage monitoring.
Power Fluctuation Logging
KE1-PVS1C-FLK and KE1-VSU1B-FLK
Momentary voltage sags are a serious problem for precision
equipment, such as semiconductor and liquid crystal manufacturing
facilities. The power grid in emerging countries is often unstable,
resulting in problems such as facility stoppage and failure due to
momentary voltage sags. The KE1 detects momentary voltage sags
and outputs an alarm in 25 ms. It also logs voltage fluctuations in the
Unit’s internal memory for 1,000 ms before and after a voltage sag so
that you can check for the impact of the voltage sag on quality. You
can also use it for SEMI-F47 traceability information to enable
effective facility maintenance.
Monitor for
Momentary
Voltage Sags
High-speed alarm
output in 25 ms.
Protect Motors
Save Energy
Monitor power
for large facilities.
Alarm outputs are
provided for open phases,
reversed phases,
overcurrents,
and earth leakage
in power equipment.
Protect
Equipment
Log Data
Alarm output for
open phases,
reversed phases,
overvoltages,
and undervoltages.
Voltage fluctuations before
and after momentary power sags
are recorded in the Unit’s internal memory.
This data is ideal for traceability.
Monitor Earth Leakage Monitor Facilities
Constantly monitor insulation
deterioration from cutting
oil mist and equipment
cleaning water.
DeviceNet communications
for 30 words of power
information in 100 ms.
Alarms for 25-ms Voltage Sags and
1
KE1
System Configuration
The KE1 is built by combining four types of Units: Measurement Masters, Function Slaves, CT Expansion Slaves, and Communications Slaves.
The Measurement Masters and Function Slaves can also be used for standalone operation.
You can connect a Measurement Master and Slaves to save both wiring work and space.
Maximum Configuration
You can connect up to four Function Slaves and CT Expansion Slaves and one Communications Slave (i.e., a total of five Slaves) to one
Measurement Master. You cannot connect only Function Slaves together.
KE1 Unit Combination Table
OK: Can be added, No: Cannot be added.
Slaves
Master
KE1-PGR1C-FLK (Power/Earth Leakage)
KE1-PVS1C-FLK (Power/Momentary Voltage Sag)
KE1-VSU1B-FLK (Momentary
Voltage Sag)
OK
OK
KE1-VAU1B-FLK (Voltage/
Current)
OK
OK
KE1-CTD8E (CT Expansion)
OK
OK
KE1-ZCT8E (ZCT Expansion)
OK
No
KE1-DRT-FLK (DeviceNet
Communications)
OK
OK
Note: Refer to the KM1 Product Catalog (Cat. No. N170) for details on the KM1.
Model Number Structure
Model Number Legend
K E 1 - @ @ @ @ - @@@
1
2
3
4
5
6
1. Basic Model
Code
KE
4. Number of Input Circuits
Series
Measurement and Monitor Units
2. Basic Model
Code
1
Series
Series number
3. Unit Type
Code
PGR
PVS
VSU
VAU
CTD
ZCT
DRT
Unit type
Power/Earth Leakage Monitor Unit
Power/Momentary Voltage Sag Monitor Unit
Momentary Voltage Sag Monitor Unit
Voltage/Current Monitor Unit
CT Expansion Unit
ZCT Expansion Unit
DeviceNet Communications Unit
Code
Blank
1
8
5. Output Form
Code
Blank
B *1
C *2
E
Output form
No output
Two SPST-NO relay outputs
One SPST-NO output and one NPN transistor output
One small-signal SPST-NO relay output
*1. The KE1-VSU1B-FLK has one SPST-NO relay output and one
SSR output.
*2. The KE1-PVS1C-FLK has one SSR output and one NPN
transistor output.
6. Communications Specification
Code
Blank
FLK
2
Number of input circuits
No input circuits
1 input circuit
8 input circuits
Communications specification
No communications
RS-485 (Modbus and CompoWay/F)
KE1
Ordering Information
Main Units
Model
Unit type
KE1-PGR1C-FLK
Power/Earth Leakage Monitor Unit
KE1-PVS1C-FLK
Power/Momentary Voltage Sag Monitor Unit
KE1-VSU1B-FLK
Momentary Voltage Sag Monitor Unit
KE1-VAU1B-FLK
Voltage/Current Monitor Unit
Power supply
voltage
Communications
100 to 240 VAC
RS-485
CT Expansion Slave
Not required.*
---
Communications Slave
100 to 240 VAC
RS-485 DeviceNet
Unit category
Measurement Master
Function Slave
KE1-CTD8E
CT Expansion Unit
KE1-ZCT8E
ZCT Expansion Unit
KE1-DRT-FLK
DeviceNet Communications Unit
* The CT and ZCT Expansion Units cannot be used in standalone operation. They must be used together with a Measurement Master Unit.
Power is supplied to the CT and ZCT Expansion Units from the Measurement Master Unit. Power supply wiring is not required.
Options (Order Separately)
CT Input
Current Transformers (CTs)
Model
Rated primary current
KM20-CTF-5A
5A
KM20-CTF-50A
50 A
KM20-CTF-100A
100 A
KM20-CTF-200A
200 A
KM20-CTF-400A
400 A
KM20-CTF-600A
600 A
KM20-CTB-5A/50A
Rated secondary current
Installation
Split-type
Special output
In-panel mounting
(through-hole)
5 A/50 A
Note: CT Cables are not included with the CTs.
Current Transformers (CTs) (UL-compliant)
Model
Rated primary current
KM20-CTF-5AU
Rated secondary current
Installation
Special output
Split-type
5A
KM20-CTF-50AU
50 A
KM20-CTF-100AU
100 A
KM20-CTF-200AU
200 A
KM20-CTF-400AU
400 A
KM20-CTF-600AU
600 A
Note: CT Cables are not included with the CTs.
Current Transformer (CT) Cable
Model
Specification
KM20-CTF-CB3
3-m cable
Note: Use only the CT Cable specified by OMRON.
ZCT Input
Zero-phase Current Transformers (Compatible ZCTs)
Structure
Rated
current
50 A
100 A
150 A
200 A
400 A
600 A
1,000 A
Indoor, through-hole
Through-hole
Model
diameter
(mm)
21
OTG-L21
30
OTG-L30
----42
OTG-L42
68
OTG-L68
82
OTG-L82
156
TG-L156
Indoor, split-type
Through-hole
diameter (mm)
------52
77
112
---
Model
------OTG-CN52
OTG-CN77
OTG-CN112
---
Outdoor, through-hole
Through-hole
diameter (mm)
--30
-----------
Model
--OTG-LA30W
-----------
Outdoor, split-type
Through-hole
diameter (mm)
----36
---------
Model
----TG-CN36W
---------
Current Transformer for Ground Wires
Structure
Rated
current
2A
Indoor, split-type
Through-hole
Model
diameter (mm)
22
K6ER-CN22
3
KE1
Related Devices (Sold Separately)
When Connected to a Computer
Communications Interface Converters
Model
K3SC-10 AC100-240
K3SC-10 AC/DC24
4
Size (mm)
30 × 80 × 78 (W×H×D)
Communications conversion
RS-232C, USB <-> Half-duplex RS-485
Power supply voltage
100 to 240 VAC
24 VAC/DC
KE1
Specifications
Ratings
Model
Item
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
Applicable phase wiring method Single-phase two-wire, single-phase three-wire, three-phase three-wire, and three-phase four-wire
Power
supply
Rated power supply
voltage
100 to 240 VAC, 50/60 Hz
---
Allowable supply
voltage range
85% to 110% of rated power supply voltage
---
Power supply
fluctuation
frequency range
45 to 65 Hz
---
Power consumption
Standalone: 10 VA max.,
Maximum connections: 14 VA
max.
Power interruption
compensation
method
---
10 VA max.
Backup for 1.2 seconds min. with
electric double-layer capacitor for
voltage measurement only.
---
Rated input voltage
100 to 480 VAC (single-phase, 2-wire): Line voltage
100/200 VAC (single-phase, 3-wire): Phase voltage/line voltage
100 to 480 VAC (3-phase, 3-wire): Line voltage
58 to 277 VAC/100 to 480 VAC (3-phase, 4-wire): Phase voltage/line
voltage
Rated input current
for CT
5 A, 50 A, 100 A, 200 A, 400 A, or
600 A
Special CTs used.
Rated input current
for ZCT
50 A, 100 A, 150
A, 200 A, 400 A,
600 A, or
1,000 A
---
5 A, 50 A, 100 A, 200 A, 400 A, or
600 A
Special CTs used.
---
50 A, 100 A, 150
A, 200 A, 400 A,
600 A, or
1,000 A
--With 5-A CT: 4
kW
With 50-A CT:
40 kW
With 100-A CT:
80 kW
With 200-A CT:
160 kW
With 400-A CT:
320 kW
With 600-A CT:
80 kW
Rated input power
With 5-A CT: 4 kW
With 50-A CT: 40 kW
With 100-A CT: 80 kW
With 200-A CT: 160 kW
With 400-A CT: 320 kW
With 600-A CT: 480 kW
Rated input
frequency
50/60 Hz
---
Input frequency
fluctuation range
45 to 65 Hz
---
Input leakage
current
1,000 mA
Allowable input
voltage
110% of rated input voltage (continuous)
Allowable input
current
120% of rated input current
(continuous)
Input
---
Rated input load
---
---
1,000 mA
---
---
120% of rated current (continuous)
Voltage input: 0.5 VA max. (excluding power supply)
Clock
---
Current input: 0.5 VA max. (for each input)
---
-----
Current input:
0.5 VA max. (for
each input)
---
Clock setting
2012 to 2099 (Adjusted for leap years during this period.)
---
Clock accuracy
±1.5 min./month (at 23°C)
---
Seven-day backup with an electric double-layer capacitor (after being
Clock backup period powered for at least 24 hours and when the power is interrupted at
23°C)
Ambient operating temperature
−10 to 55°C (with no condensation or icing)
Storage temperature
−25 to 65°C (with no condensation or icing)
Ambient operating humidity
25% to 85%
Storage humidity
25% to 85%
Altitude
2,000 m max.
Installation environment
Overvoltage category II, pollution degree 2, measurement category II
---
5
KE1
Model
Item
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
EN 61010-2-030 (IEC 61010-2-030)
EN61326-1 Industrial electromagnetic environment
UL61010-1 (*)
UL61010-2-030 (*)
Compliant
All KE1 Units
standards
* Use a UL-compliant current transformer (CT) (KM20-CTF-@@@AU) for application as a UL-certified component.
Characteristics
Model
Item
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
Voltage
±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under
the same conditions.
Current
±1.0% FS ±1 digit
However, the accuracy is ±2.0%
FS ±1 digit for the phase-S current
for a three-phase, three-wire
circuit and the phase-N current for
a single-phase, three-wire circuit
under the same conditions.
Leakage current
30 to 200 mA:
±5% rdg ±1 digit
200 to 1,000
mA: ±1%FS ±1
digit
Accuracy
*1
---
Frequency
Power factor*2
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
---
±1.0% FS ±1 digit
However, the accuracy is ±2.0%
FS ±1 digit for the phase-S current
for a three-phase, three-wire
circuit and the phase-N current for
a single-phase, three-wire circuit
under the same conditions.
---
30 to 200 mA:
±5% rdg ±1 digit
200 to 1,000
mA: ±1%FS ±1
digit
---
Active power and reactive power
Power (active power
±2.0% FS ±1 digit (power factor =
and reactive power)
1)
---
Active power
and reactive
power
±2.0% FS ±1
digit (Power
factor = 1)
---
±5.0% FS
(Power factor =
0.5 to 1 to 0.5)
±0.3 Hz ±1 digit
---
---
±5.0% FS (power factor = 0.5 to 1
to 0.5)
Temperature
6
KE1-VAU1BFLK (Voltage/
Current)
---
---
Temperature influence*1
±1.0% FS (percentage of the measurement value at an ambient temperature of 23°C, rated input, rated
frequency, and a power factor of 1 in the operating temperature range)
Frequency influence*1
±1.0% FS (percentage of the measurement value at an ambient temperature of 23°C, rated input, rated
frequency, and a power factor of 1 in the rated frequency ±5 Hz range)
Influence of harmonics*1
±0.5% FS (at ambient temperature of 23°C, error for superimposed 2nd, 3rd, 5th, 7th, 9th, 11th, and 13th
harmonics for a content percentage of 30% for current and 5% for voltage of the basic wave)
Low-cut current set value
0.1% to 19.9% of rated input in
0.1% increments
Low-cut leakage current set
value
Variable in 0.1mA increments
between 0.1
and 30.0 mA
Sampling cycle
100 ms for measurement voltage at 50 Hz and 83.3 ms for measurement voltage at 60 Hz
Insulation resistance
Insulation resistance: 20 MΩ (at 500 VDC)
Dielectric strength
All models: Locations to which 2,000 V was applied for one minute: Between all terminals and case
KE1-PGR1C-FLK: Between the power supply terminals and RS-485/transistor/relay outputs
Between the power supply terminals and current/voltage/earth leakage inputs
Between current/voltage/earth leakage inputs and RS-485/relay/transistor outputs
KE1-PVS1C-FLK: Between the power supply terminals and RS-485/transistor/relay outputs
Between the power supply terminals and current/voltage input
Between current/voltage inputs and RS-485/relay/transistor outputs
KE1-VSU1B-FLK: Between power supply terminals and RS-485/relay outputs
Between the power supply terminals and voltage inputs
Between voltage inputs and RS-485/relay outputs
KE1-VAU1B-FLK: Between power supply terminals and RS-485/relay outputs
Between the power supply terminals and current/voltage input
Between current/voltage inputs and RS-485/relay outputs
KE1-CTD8E:
Between current inputs and relay outputs
KE1-ZCT8E:
Between earth leakage inputs and relay outputs
---
0.1% to 19.9% of rated input in
0.1% increments
---
--Variable in 0.1mA increments
between 0.1
and 30.0 mA
KE1
Model
Item
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
Vibration resistance
Single-amplitude: 0.35 mm, Acceleration: 50 m/s2
Vibration: 10 to 55 Hz, 10 sweeps of 5 minutes each along 3 axes
Shock resistance
150 m/s2, 3 times each in 6 directions (up/down, left/right, forward/backward)
Weight
Approx. 230 g
Memory backup
No. of writes to non-volatile memory: 1,000,000 times
KE1-ZCT8E
(ZCT
Expansion)
*1. Based on JISC1111, without special CT error, at ambient temperature of 23°C, rated input, and rated frequency. Applicable to 2nd, 3rd, 5th,
7th, 9th, 11th, and 13th harmonics.
*2. Power factor formula: Power factor = Active power/Apparent power
Apparent power =
Model
Item
Event
inputs
KE1-PGR1CFLK (Power/
Earth Leakage)
(Active power)2 + (Reactive power)2
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
Number of inputs
---
No-voltage inputs
---
Voltage input
---
Tempera- Thermistor inputs
ture inApplicable
puts
thermistor
---
---
Number of outputs
One open-collector output (OUT2)
---
Output capacity
30 VDC, 30 mA
---
ON residual voltage
1.2 V max.
---
OFF leakage current 100 μA max.
Relay
outputs
KE1-ZCT8E
(ZCT
Expansion)
---
Capable of supporting 7 event
inputs and 1 temperature input
when connected with the KM1EMU8A-FLK.
Combinations
Transistor outputs
KE1-CTD8E
(CT
Expansion)
---
Total power
consumption pulse
output
Outputs one pulse when the power
consumption reaches the set pulse
output unit (1, 10, 100, 1k, 2k, 5k,
10k, 20k, 50k, 100k W/h).
---
Alarm output
Outputs an alarm based on the set
alarm output threshold.
---
Alarm recovery
method
Automatic recovery only
---
Number of outputs
One NO contact
output (OUT1)
---
Two NO contact
One NO contact
outputs (OUT1 One NO contact output (OUT1)
output (OUT1)
and OUT2)
Rated load
Resistance
load, 250 VAC,
3 A; 30 VDC, 3 A
Inductive load
(cosφ = 0.4, L/R
= 7 ms): 250
VAC, 1 A;
30 VDC, 1 A
---
Resistance load, 250 VAC, 3 A;
30 VDC, 3 A
Inductive load (cosφ = 0.4, L/R = 7
ms): 250 VAC, 1 A; 30 VDC,
1A
Resistance load, 125 VAC, 3 A;
30 VDC, 3 A
Mechanical life
expectancy
10,000,000
operations
---
10,000,000 operations
5,000,000 operations min.
Electrical life
expectancy
50,000
operations min.
(rated load
switching
frequency:
1,800 times/h)
---
50,000 operations min. (rated load 200,000 times min. (rated load
switching frequency: 1,800 times/ switching frequency: 1,800 times/
h)
h)
Failure rate P level
5 VDC, 10 mA
(at a switching
frequency of
120 times/min)
---
5 VDC, 10 mA (at a switching frequency of 120 times/min)
Alarm output
Turns output
ON or OFF
based on the
alarm set value.
---
Turns output ON or OFF based on the alarm set value.
Recovery method
Automatic
recovery only
---
Automatic recovery only
7
KE1
Model
Item
Semicon
ductor
relay
outputs
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
One MOS FET
output (OUT2)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
Number of outputs
---
One MOS FET
output (OUT1)
Maximum load
voltage
---
Peak: 24 VAC/DC
---
Continuous load
current
---
Peak: 80 mA AC/DC
---
ON resistance
---
15 Ω max.
---
Open-circuit leakage
current
---
1 nA max.
---
Alarm output
---
Turns output ON or OFF based on
the alarm set value.
---
Recovery method
---
Automatic recovery only
---
Protocols
KE1-ZCT8E
(ZCT
Expansion)
---
Communications protocol setting OFF: CompoWay/F, ON: Modbus
Commun Unit number setting
ications
RS-485
KE1-PGR1CFLK (Power/
Earth Leakage)
CompoWay/F: 0 to 99, Modbus:1 to 99
When a switch operation is performed to set the protocol to Modbus when the node number is set to 0, the
node number is automatically changed to 1.
Communication
items
Refer to the KM1/KE1 Communications Manual.
Sync method
Start-stop
---
Baud rate
9,600 bps, 19,200 bps, or 38,400 bps
---
Transmission code
CompoWay/F: ASCII, Modbus: Binary
---
Data length
CompoWay/F: 7 bits, 8 bits; Modbus: 8 bits
---
Stop bits
CompoWay/F: 1 bits or 2 bits
Modbus: 1 bit with priority, 2 bits without priority
---
Parity
Even, odd, or none
---
Maximum
transmission
distance
500 m
---
Maximum number of
CompoWay/F: 31, Modbus: 99
nodes
---
USB
USB 1.1 compliant
Memory retention for power
interruptions
Parameter data,
alarm history,
logged data,
and backup
data
Number of connect connector
insertions/removals
25 times
Parameter data,
alarm history,
logged data,
backup data,
and momentary
voltage sag
history
Parameter data,
alarm history,
Parameter data,
Parameter data,
Parameter data
logged data,
alarm history,
alarm history,
and alarm
and momentary
and backup
and logged data
history
voltage sag
data
history
Protection
Model
Item
Voltage
monitoring
8
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
Alarm threshold
(overvoltage/
undervoltage)
0.0 to 12,100.0 V
---
Operation
characteristic
±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under
the same conditions.
---
Alarm ON delay
(overvoltage/
undervoltage)
0.1 to 10.0 s
---
Operating time
characteristic
±0.2 s
---
Alarm hysteresis
(overvoltage/
undervoltage)
0.0 to 2,200.0 V
---
Resetting time
0.5 s (Cannot be changed.)
---
Resetting time
characteristic
±0.2 s
---
KE1
Model
Item
Current
monitoring
Active
power
monitoring
Reactive
power
monitoring
Power
factor
monitoring
KE1-PGR1CFLK (Power/
Earth Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
---
0.0 to 6,000.0 A
---
---
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
Alarm threshold
(overcurrent/
undercurrent)
0.0 to 6,000.0 A
Operation
characteristic
±1.0% FS ±1 digit
However, the accuracy is ±2.0%
FS ±1 digit for the phase-S current
for a three-phase, three-wire
circuit and the phase-N current for
a single-phase, three-wire circuit
under the same conditions.
---
±1.0% FS ±1 digit
However, the accuracy is ±2.0%
FS ±1 digit for the phase-S current
for a three-phase, three-wire
circuit and the phase-N current for
a single-phase, three-wire circuit
under the same conditions.
Alarm ON delay
(overcurrent/
undercurrent)
0.1 to 10.0 s
---
0.1 to 10.0 s
---
Operation
characteristic
±0.2 s
---
±0.2 s
---
Alarm hysteresis
(overcurrent/
undercurrent)
0.0 to 1,000.0 A
---
0.0 to 1,000.0 A
---
Resetting time
0.5 s (Cannot be changed.)
---
0.5 s (Cannot be changed.)
---
Resetting time
characteristic
±0.2 s
---
±0.2 s
---
Alarm thresholds
(upper limit/lower
limit)
• 120,000,000 to 120,000,000 W
---
• 120,000,000 to
120,000,000 W
---
Operation
characteristic
±2.0% FS ±1 digit
---
±2.0% FS ±1
digit
---
Alarm ON delay
(upper limit/lower
limit)
0.5 to 10.0 s
---
0.5 to 10.0 s
---
Operation
characteristic
±0.2 s
---
±0.2 s
---
Alarm hysteresis
(upper limit/lower
limit)
0 to 24,000,000 W
---
0 to 24,000,000
W
---
Resetting time
0.5 s (Cannot be changed.)
---
0.5 s (Cannot be
changed.)
---
Resetting time
characteristic
±0.2 s
---
±0.2 s
---
Alarm thresholds
(upper limit/lower
limit)
−120,000,000 to 120,000,000 W
---
−120,000,000 to
120,000,000 W
---
Operation
characteristic
±2.0% FS ±1 digit
---
±2.0% FS ±1
digit
---
Alarm ON delay
(upper limit/lower
limit)
0.5 to 10.0 s
---
0.5 to 10.0 s
---
Operation
characteristic
±0.2 s
---
±0.2 s
---
Alarm hysteresis
(upper limit/lower
limit)
0 to 24,000,000 W
---
0 to 24,000,000
W
---
Resetting time
0.5 s (Cannot be changed.)
---
0.5 s (Cannot be
changed.)
---
Resetting time
characteristic
±0.2 s
---
±0.2 s
---
Alarm threshold
−1.00 to 1.00
---
−1.00 to 1.00
-----
Operation
characteristic
±5.0% FS (Power factor = 0.5 to 1
to 0.5)
---
±5.0% FS
(Power factor =
0.5 to 1 to 0.5)
Alarm ON delay
0.5 to 10.0 s
---
0.5 to 10.0 s
---
Operation
characteristic
±0.2 s
---
±0.2 s
---
Alarm hysteresis
0.00 to 1.00
---
0.00 to 1.00
---
9
KE1
Model
Item
Earth
leakage
monitoring
Momentary voltage sag
monitoring
Open
phase
monitoring
Reversed
phase
monitoring
10
KE1-PGR1CFLK (Power/
Earth Leakage)
Earth leakage
comparison value
30 to 1,000 mA
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
---
30 to 1,000 mA
Operation
characteristic
±5% rdg ±1 digit
for 30 to 200
mA, ±1% FS ±1
digit for 200 to
1,000 mA
---
±5% rdg ±1 digit
for 30 to 200
mA, ±1% FS ±1
digit for 200 to
1,000 mA
Earth leakage
operating time
0.1 to 20.0 s
---
0.1 to 20.0 s
Operation
characteristic
±0.2 s
---
±0.2 s
Resetting condition
95% of
operating value
---
95% of
operating value
Resetting time
0.5 s (Cannot be
changed.)
---
0.5 s (Cannot be
changed.)
Momentary voltage
sag detection
voltage
---
0 to 480.0 V
---
Allowable error in
detection voltage
---
±2.5% FS ±1 digit
---
Continuation time
for momentary
voltage sag
---
Relay output
operating time
accuracy
---
Without backup: 0.02 to 0.2 s
With backup: 0.02 to 1.00 s
±5 ms
---
---
Open phase
detection condition
(Largest error between any phase voltage and average voltage) ÷
Average voltage × 100 ≤ 85%
---
Operation
characteristic
±1.0% FS ±1 digit
The accuracy of the voltage across the Vtr is ±2.0% FS ±1 digit under
the same conditions.
---
Operating time
0.1 s
---
Operation
characteristic
±0.2 s
---
Resetting condition
Non-balance ratio: Less than 13%
---
Resetting time
0.5 s (Cannot be changed.)
---
Resetting time
characteristic
±0.2 s
---
Reversed phase
detection condition
Change in voltage phase sequence lasts for 0.1 second or longer.
---
Operating time
0.1 s
---
Operation
characteristic
±0.2 s
---
Resetting condition
Phase offset within ±45°
---
Resetting time
0.5 s (Cannot be changed.)
---
Resetting time
characteristic
±0.2 s
---
KE1
Special CTs
Current Transformers (CTs)
Structure
Model
Split-type
KM20-CTF-5A
KM20-CTF5AU
Item
Rated primary
current
Secondary
winding
Applicable
frequency
Insulation
resistance
Dielectric
strength
Protective
element
Allowable
number of
connections/
disconnections
Mountable wire
diameter
Operating
temperature
and humidity
ranges
Storage
temperature
and humidity
ranges
5A
KM20-CTF50A
KM20-CTF50AU
KM20-CTF100A
KM20-CTF100AU
50 A
100 A
Through-hole
KM20-CTF200A
KM20-CTF200AU
200 A
3,000 turns
KM20-CTF400A
KM20-CTF400AU
KM20-CTF600A
KM20-CTF600AU
KM20-CTB-5A/
50A
400 A
600 A
5A/50 A
6,000 turns
9,000 turns
3,000 turns
10 Hz to 5 kHz
Between output terminals and case: 50 MΩ min. (at 500 VDC)
Between output terminals and case: 2,000 VAC for 1 minute
7.5-V clamp element
100 times
7.4 mm max.
8.5 mm max.
11 mm max.
24 mm max.
35.5 mm max.
8.4 mm max.
−20 to 60°C, 85% max. (with no condensation)
−30 to 65°C, 85% max. (with no condensation)
Note: Operate the Special CTs at a low voltage of 600 V or less.
General Specifications
Item
Specification
Rated power supply voltage
100 to 240 VAC, 50/60 Hz
Allowable voltage range
85% to 110% of rated power supply voltage
Power consumption (at
6 VA max.
maximum load)
Current consumption (DeviceNet
45 mA max. (24 VDC)
power supply)
Vibration resistance
Shock resistance
Dielectric strength
10 to 55 Hz, 10 m/s2 for 2 hours along 3 axes
Single-amplitude: 0.35 mm, Acceleration: 50 m/s2 Vibration: 10 to 55 Hz, 10 sweeps of 5 minutes each
along 3 axes
2,000 V for 1 min between all terminals and case, and between power supply terminals and temperature
input/RS-485 output/USB output/DeviceNet output/transistor output
Insulation resistance
20 MΩ min. (at 500 VDC)
Ambient operating temperature
−10 to 55°C (with no condensation or icing)
Ambient operating humidity
25% to 85%
Ambient storage temperature
−25 to 65°C (with no condensation or icing)
Dimensions
45 × 90 × 110 mm (W×H×D) (excluding protrusions)
Memory backup
EEPROM (non-volatile memory), No. of writes: 1,000,000
Weight
Approx. 170 g
Current Transformer (CT) Cable
Model
Cable length
KM20-CTF-CB3
3m
Note: Use only the CT Cable specified by OMRON.
11
KE1
Special ZCTs
Zero-phase Current Transformers (Compatible ZCTs)
Structure
Item
Model
Rated current
Through-hole
diameter
Rated load
Output terminal
polarity
Secondary
connection
Insulation
resistance
Dielectric strength
Ambient operating
temperature
Ambient operating
humidity
Weight
OTG-L21
50 A
OTG-L30
100 A
Indoor, through-hole
OTG-L42
OTG-L68
200 A
400 A
OTG-L82
600 A
OTG-L156
1,000 A
21
30
42
82
156
68
600 VAC max, 50/60 Hz, Single-phase/three-phase
Polarity (Connect CT output terminal k to terminal 5 or 7 and terminal I to terminal 6 or 8.)
Terminals (with test terminals kt and lt)
100 MΩ min. (between charged metal parts and ground)
2,200 VAC at 50/60 Hz for 1min (between charged metal parts and ground)
−10 to 60°C (with no icing)
45% to 85%
Approx. 90 g
Approx. 130 g
Structure
Approx. 230 g
Approx. 480 g
Indoor, split-type
Approx. 700 g
Outdoor, throughhole
OTG-LA30W
100 A
Item
Model
OTG-CN52
OTG-CN77
OTGCN112
Rated current
200 A
400 A
600 A
Through-hole
52
77
112
30
diameter
Rated load
600 VAC max, 50/60 Hz, Single-phase/three-phase
Output terminal
Polarity (Connect CT output terminal k to terminal 5 or 7 and terminal I to terminal 6 or 8.)
polarity
Secondary
Terminals (with test terminals kt and lt)
Lead wire I = 500
connection
Insulation
100 MΩ min. (between charged metal parts and ground)
resistance
Dielectric strength 2,200 VAC at 50/60 Hz for 1min (between charged metal parts and ground)
Ambient operating
−10 to 60°C (with no icing)
temperature
Ambient operating
45% to 85%
humidity
Weight
Approx. 1.3 kg
Approx. 2.5 kg
Approx. 3.5 kg
Approx. 140 g
Note: Operate the Special ZCTs at a low voltage of 600 V or less.
Current Transformer for Ground Wires
Structure
Item
Model
Rated current
Through-hole
diameter
Rated load
Output terminal
polarity
Secondary
connection
Insulation
resistance
Dielectric strength
Ambient operating
temperature
Ambient operating
humidity
Weight
12
Indoor, split-type
K6ER-CN22
2A
22
600 VAC max, 50/60 Hz, Single-phase/three-phase
Polarity (Connect CT output terminal k to terminal 5 or 7 and terminal I to terminal 6 or 8.)
Lead wire I: 150, Enclosed cable: 3,000 mm
100 MΩ min. (between core and output lead wire)
1,000 VAC at 50/60 Hz for 1 min (between core and output lead wire)
−10 to 60°C (with no icing)
80% max.
Approx. 65 g
Approx. 6.6 kg
Outdoor, split-type
OTG-CN36W
150 A
36
Lead wire I = 450
Approx. 650 g
KE1
Nomenclature
Measurement Masters, Function Slaves, and CT
Expansion Slaves
Horizontal connection hook
DIN hook
Setting switch
Setting Switches
There are two setting switches, one for the slave ID and one for the
communications protocol.
Before you make the initial settings, always set the slave ID and
communications protocol.
• Slave ID (Rotary Switch)
901
78
23
Link connector
456
Display
Set the switch to between 1 and 4. (Do not set it to 0 or to between 5
and 9.)
Do not set the same ID more than once within the same system.
Only the Function Slaves and CT Expansion Slaves have a rotary
switch.
Display cover
• Communications Protocol Switch (DIP Switch)
USB port
ON
Link connector
Communications Slave
DIN hook
Setting switch
• Simple Assignment/Communications Protocol Switch (DIP Switch)
ON
Horizontal
connection hook
Pin 1: Not used.
Pin 2 ON: Modbus
OFF: CompoWay/F
Link connector
Display
Display cover
USB port
Link connector
Node address
Pin 1 ON: Manual assignment
OFF: Simple assignment
Pin 2 ON: Modbus
OFF: CompoWay/F
• Simple Assignment Setting
Turn OFF DIP switch pin 1 to set simple assignment.
The setting is read only once when the power supply is turned ON.
Any changes while power is ON are ignored. To change the setting,
turn OFF the power supply, set the switch, and then turn ON the
power supply.
• Node Address Setting
Set the address of the Unit as a slave on the DeviceNet network to a
decimal number between 00 and 63. (Do not set addresses 64 to 99.)
Set the 1s digit on the bottom rotary switch (×100) and set the 10s digit
on the top rotary switch (×101). You can set any node address that is
within the specified range as long as the same address is not set for
another node (Master, Slave, or Configurator) on the same network.
Node Address
456
901
23
78
×101
DeviceNet connector
DeviceNet
Node Address Setting
456
×100
901
23
78
* The Link Connector is provided with the Slave Units only and is not
provided with the Master Unit.
13
KE1
Display
KE1-PGR1CFLK (Power/
Earth
Leakage)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag)
KE1-VSU1BFLK
(Momentary
Voltage Sag)
KE1-VAU1BFLK (Voltage/
Current)
PWR
ALM
CT1
CT2
CONN
COMM
OUT1
OUT2
PWR
ALM
CT1
CT2
CONN
COMM
OUT1
OUT2
PWR
ALM
CONN
COMM
OUT1
OUT2
PWR
ALM
CT1
CT2
CONN
COMM
OUT1
OUT2
Indicator
Name
Color
CT3
CT3
ZCT
KE1-CTD8E
(CT
Expansion)
KE1-ZCT8E
(ZCT
Expansion)
KE1-DRTFLK
(DeviceNet)
PWR
ALM
CT1
CT2
CT3
CT4
CONN
CONN
CT5
CT6
CT7
CT8
PWR
ALM
ZCT1
ZCT2
ZCT3
ZCT4
CONN
CONN
ZCT5
ZCT6
ZCT7
ZCT8
PWR
CONN
MS
COMM
NS
CT3
Indication
Status
Power is ON.
PWR
Power Supply
Green
An error has occurred.
Power is not supplied.
CONN
Internal Bus
Communications
ALM
Alarm
COMM
RS-485
Communications
Yellow
Red
Yellow
Internal bus is connected (multiple Units are connected).
Internal bus is not connected (multiple Units are not connected).
An alarm was detected.
RS-485/USB communications are in progress.
RS-485/USB communications are not in progress.
CT
CT Input
Yellow
The indicator for the relevant input lights if the current measurement value for a
CT input is 2% of the rated current or higher for 10 seconds or longer.
• The indicator lights for the above condition even if the current measurement
value is forced to 0 by the low-cut function.
ZCT
ZCT Input
Yellow
The indicator for the relevant input lights if the earth leakage measurement value
for a ZCT input is 2% of the rated current or higher for 10 seconds or longer.
• The indicator lights for the above condition even if the current measurement
value is forced to 0 by the low-cut function.
OUT
Output
Yellow
The indicators light according to the alarm settings for individual output
terminals.
Normal (DeviceNet Communications Unit is normal.)
Green
MS
Module Status
Red
---
Green
Network Status
(DeviceNet)
NS
Red
Not set (when I/O assignments are made with the Configurator).
• Connected configuration is not set.
• I/O assignments are not set.
Fatal Error
• Watchdog timer error
• RAM error
EEPROM Failure
• Non-volatile memory checksum error
• Non-volatile memory hardware error
There is no network power supply (24 VDC).
• There is no power supply to the DeviceNet Communications Unit.
• A reset is in progress.
• Waiting for initialization to start.
The Unit is online and communications settings were completed. (The network
is normal.)
The Unit is online but communications settings have not been completed
(waiting for connection from host).
Communications error
(The Unit has detected an error that indicates network communications are not
possible.)
• Node address duplication
• Busoff was detected.
Minor communications error
• Communications timeout
---
: Lit.
14
: Flashing.
: Not lit.
The Unit is offline and the power supply is OFF.
• Waiting for the host to complete a node address duplication check.
• There is no power supply to the DeviceNet Communications Unit.
KE1
Connections
Power/Earth Leakage Monitor Unit
KE1-PGR1C-FLK
Terminal Arrangement and I/O Configuration
11
12
9
10
P3
P0
23
24
P1
P2
21
22
Voltage inputs
KE1-PGR1C-FLK
7
RS-485
communications
A(−)
OUT1 and OUT2: Total
power consumption pulse
output alarm outputs
B(+)
5
6
17
3
4
15
2
13
1
Power supply voltage
19
8
RS-485
PWR
ZCT
K L
CT3
S L
CT2
S L
CT1
S L
20
ZCT input
18
16
CT inputs 1 to 3
14
Terminal Functions
1
2
3
Power supply voltage
(100 to 240 VAC)
SPST-NO relay output
4
9
NC
17
CT-3S
10
NC
18
CT-3L
11
NC
19
ZCT-K
12
NC
20
ZCT-L
5
Transistor outputs
13
CT-1S
21
Measurement voltage input P1
6
Transistor output COM
14
CT-1L
22
Measurement voltage input P2
7
RS-485 A (−)
15
CT-2S
23
Measurement voltage input P3
8
RS-485 B (+)
16
CT-2L
24
Measurement voltage input P0
15
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
Power supply (K)
L
N
• Single-phase, Three-wire
Power supply (K)
RNT
Load (L)
P2
P1
ZCT
Input
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
P3
P2
P1
KE1-PGR1C-FLK
KE1-PGR1C-FLK
ZCT input
RS-485 communications
7
8
19
20
Transistor outputs
5
6
17
18
SPST-NO relay output
3
4
15
16
RS-485 communications
7
8
19
20
Transistor outputs
5
6
17
18
SPST-NO relay output 3
4
15
16
1
2
13
14
CT3 input
CT3 input
CT2 input
CT1 input
1
2
13
14
Load (L)
Power supply voltage
• Three-phase, Three-wire
CT1 input
Load (L)
Power supply voltage
• Three-phase, Four-wire
Power supply (K)
RSTN
Power supply (K)
RST
11
12
9
10
23
24
21
22
P3
P2
P1
11
12
9
10
23
24
21
22
KE1-PGR1C-FLK
KE1-PGR1C-FLK
ZCT input
ZCT input
RS-485 communications
7
8
19
20
18
Transistor outputs
5
6
17
18
15
16
SPST-NO relay output
3
4
15
16
13
14
1
2
13
14
RS-485 communications
7
8
19
20
Transistor outputs
5
6
17
SPST-NO relay output
3
4
1
2
CT3 input
CT3 input
CT1 input
Power supply voltage
16
P0
P3
P2
P1
Load (L)
CT2 input
CT1 input
Power supply voltage
Load (L)
KE1
Power/Momentary Voltage Sag Monitor Unit
KE1-PVS1C-FLK
Terminal Arrangement and I/O Configuration
11
12
9
10
P3
P0
23
24
P1
P2
21
22
Voltage inputs
KE1-PVS1C-FLK
7
RS-485 communications
A(−)
19
8
RS-485
20
B(+)
OUT2: Total power
consumption pulse
output alarm output
5
6
17
OUT1: Momentary
voltage sag alarm output
3
4
15
Power supply voltage
1
2
13
PWR
CT3
S L
CT2
S L
CT1
S L
18
CT inputs
1 to 3
16
14
Terminal Functions
1
2
3
Power supply voltage
(100 to 240 VAC)
Semiconductor relay outputs
4
9
NC
17
CT-3S
10
NC
18
CT-3L
11
NC
19
NC
12
NC
20
NC
5
Transistor outputs
13
CT-1S
21
Measurement voltage input P1
6
Transistor output COM
14
CT-1L
22
Measurement voltage input P2
7
RS-485 A (−)
15
CT-2S
23
Measurement voltage input P3
8
RS-485 B (+)
16
CT-2L
24
Measurement voltage input P0
17
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
• Single-phase, Three-wire
Power supply (K)
L
N
Power supply (K)
RNT
Load (L)
P1
P2
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
KE1-PVS1C-FLK
KE1-PVS1C-FLK
8
19
20
RS-485 communications
7
Transistor outputs
5
6
17
18
Semiconductor relay outputs
3
4
15
16
CT3 input
CT2 input
CT1 input
1
2
13
P3
P2
P1
RS-485 communications
7
8
19
20
Transistor outputs
5
6
17
18
Semiconductor relay outputs
3
4
15
16
1
2
13
14
14
Load (L)
Power supply voltage
• Three-phase, Three-wire
CT3 input
CT1 input
Load (L)
Power supply voltage
• Three-phase, Four-wire
Power supply (K)
RST
11
12
9
10
23
24
21
22
Power supply (K)
RSTN
P3
P2
P1
11
12
23
24
9
10
21
22
KE1-PVS1C-FLK
KE1-PVS1C-FLK
RS-485 communications
7
8
19
20
RS-485 communications
7
8
19
20
CT3 input
CT3 input
Transistor outputs
5
6
17
18
Transistor outputs
5
6
17
18
Semiconductor relay outputs
3
4
15
16
Semiconductor relay outputs
3
4
15
16
1
2
13
14
1
2
13
14
CT2 input
CT1 input
CT1 input
Power supply voltage
18
P0
P3
P2
P1
Load (L)
Power supply voltage
Load (L)
KE1
Momentary Voltage Sag Monitor Unit
KE1-VSU1B-FLK
Terminal Arrangement and I/O Configuration
11
12
9
10
P3
P0
23
24
P1
P2
21
22
Voltage
inputs
KE1-VSU1B-FLK
RS-485
communications
7
A(−)
8
RS-485
19
20
B(+)
OUT2:
Momentary
voltage sag
alarm output
5
6
17
18
OUT1:
Alarm output
3
4
15
16
2
13
14
1
Power supply
voltage
PWR
Terminal Functions
1
2
3
Power supply voltage
(100 to 240 VAC)
SPST-NO relay output
4
5
Semiconductor relay outputs
6
9
NC
17
NC
10
NC
18
NC
11
NC
19
NC
12
NC
20
NC
13
NC
21
Measurement voltage input P1
14
NC
22
Measurement voltage input P2
7
RS-485 A (−)
15
NC
23
Measurement voltage input P3
8
RS-485 B (+)
16
NC
24
Measurement voltage input P0
19
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
• Single-phase, Three-wire
Power supply (K)
RNT
Power supply (K)
11
9
12
10
23
21
24
22
P2
P1
11
12
23
24
9
10
21
22
P3
P2
P1
KE1-VSU1B-FLK
KE1-VSU1B-FLK
RS-485 communications
7
8
19
20
RS-485 communications
7
8
19
20
Semiconductor relay outputs
5
6
17
18
Semiconductor relay outputs
5
6
17
18
SPST-NO relay output
3
4
15
16
SPST-NO relay output
3
4
15
16
1
2
13
14
1
2
13
14
Load (L)
Power supply voltage
• Three-phase, Three-wire
Load (L)
Power supply voltage
• Three-phase, Four-wire
Power supply (K)
RSTN
Power supply (K)
RST
11
9
12
10
23
21
24
22
P3
P2
P1
11
12
9
10
24
P0
P3
21
22
P2
P1
KE1-VSU1B-FLK
KE1-VSU1B-FLK
RS-485 communications
7
8
19
20
RS-485 communications
7
8
19
20
Semiconductor relay outputs
5
6
17
18
Semiconductor relay outputs
5
6
17
18
SPST-NO relay output
3
4
15
16
SPST-NO relay output
3
4
15
16
1
2
13
14
1
2
13
14
Power supply voltage
20
23
Load (L)
Power supply voltage
Load (L)
KE1
Voltage/Current Monitor Unit
KE1-VAU1B-FLK
Terminal Arrangement and I/O Configuration
11
12
9
10
P3
P0
23
24
P1
P2
21
22
Voltage
inputs
KE1-VAU1B-FLK
7
RS-485
communications
A(−)
19
8
RS-485
20
B(+)
5
6
17
3
4
15
2
13
CT3
S L
18
OUT1 and OUT2:
Alarm outputs
1
Power supply
voltage
PWR
CT2
S L
CT1
S L
CT inputs
1 to 3
16
14
Terminal Functions
1
2
3
Power supply voltage
(100 to 240 VAC)
SPST-NO relay output 1
4
5
SPST-NO relay output 2
6
9
NC
17
CT-3S
10
NC
18
CT-3L
11
NC
19
NC
12
NC
20
NC
13
CT-1S
21
Measurement voltage input P1
14
CT-1L
22
Measurement voltage input P2
7
RS-485 A (−)
15
CT-2S
23
Measurement voltage input P3
8
RS-485 B (+)
16
CT-2L
24
Measurement voltage input P0
21
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
Power supply (K)
L
N
• Single-phase, Three-wire
Power supply (K)
RNT
Load (L)
P1
P2
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
KE1-VAU1B-FLK
KE1-VAU1B-FLK
RS-485 communications
7
8
19
20
RS-485 communications
7
8
19
20
SPST-NO relay output
5
6
17
18
SPST-NO relay output
3
4
15
16
1
2
13
14
CT3 input
SPST-NO relay output
5
6
17
18
SPST-NO relay output
3
4
15
16
P3
P2
P1
CT3 input
CT2 input
CT1 input
CT1 input
1
2
13
14
Load (L)
Power supply voltage
• Three-phase, Three-wire
Load (L)
Power supply voltage
• Three-phase, Four-wire
Power supply (K)
RST
11
9
12
10
23
21
Power supply (K)
RSTN
24
22
P3
P2
P1
11
12
23
24
P0
P3
9
10
21
22
P2
P1
KE1-VAU1B-FLK
RS-485 communications
7
8
19
KE1-VAU1B-FLK
20
RS-485 communications
7
8
19
20
CT3 input
CT3 input
SPST-NO relay output
5
6
17
18
SPST-NO relay output
5
6
17
18
SPST-NO relay output
3
4
15
16
SPST-NO relay output
3
4
15
16
1
2
13
14
1
2
13
14
CT2 input
CT1 input
Power supply voltage
22
CT1 input
Load (L)
Power supply voltage
Load (L)
KE1
CT Expansion Unit
KE1-CTD8E
Terminal Arrangement and I/O Configuration
11
9
CT8
S L
CT7
S L
12
10
23
21
CT6
S L
CT5
S L
24
Measurement block 2
CT inputs
5 to 8
22
KE1-CTD8E
OUT1:
Alarm output
7
8
19
5
6
17
3
4
15
1
2
13
CT4
S L
CT3
S L
CT2
S L
CT1
S L
20
Measurement block 1
18
CT inputs
1 to 4
16
14
Terminal Functions
1
NC
9
CT-7S
17
CT-3S
2
NC
10
CT-7L
18
CT-3L
11
CT-8S
19
CT-4S
12
CT-8L
20
CT-4L
3
SPST-NO relay output
4
5
NC
13
CT-1S
21
CT-5S
6
NC
14
CT-1L
22
CT-5L
7
NC
15
CT-2S
23
CT-6S
8
NC
16
CT-2L
24
CT-6L
23
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
P1
P1
Load
CT7 input
23
12
9
24
21
10
11
22
23
12
9
24
21
10
KE1-@@@1@-FLK
P3
Measurement
Master Unit
CT6 input Load
11
Power
supply (K)
RN T
Example for Power Measurement on Four Lines
CT8 input
P2
Measurement
Master Unit
• Single-phase, Three-wire
Power
supply (K)
LN
Example for Power Measurement on Eight Lines
P2
CT7 input
CT8 input
CT6 input
CT5 input Load
22
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
Load
KE1-CTD8E
KE1-@@@1@-FLK
Load
CT5 input
KE1-CTD8E
Load
CT4 input
SPST-NO relay output
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
CT3 input Load
CT2 input Load
CT1 input Load
SPST-NO relay output
Load
Power supply voltage
Load (L)
* The KE1-CTD8E will not operate alone.
It must be used together with a Measurement Master Unit.
* The required number of CT inputs depends on the wiring method.
Single-phase, two-wire: 1 input
* The number of circuits that one KE1-CTD8E Unit can
measure is as follows:
Single-phase, two-wire: 8 circuits max.
• Three-phase, Three-wire
Power
supply (K)
RS T
Example for Power Measurement on Four Lines
Measurement
Master Unit
9
12
10
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
CT4 input
Load
CT3 input
CT2 input Load
CT1 input
Power supply voltage
Load (L)
* The KE1-CTD8E will not operate alone.
It must be used together with a Measurement Master Unit.
* The required number of CT inputs depends on the wiring method.
Single-phase, three-wire: 2 inputs
* The number of circuits that one KE1-CTD8E Unit can
measure is as follows:
Single-phase, three-wire: 4 circuits max.
• Three-phase, Four-wire
Example for Power Measurement on Two Lines
Measurement
Master Unit
P2
Power
supply (K)
RS T N
P3
P2
P0
CT7 input
CT8 input
CT6 input
11
8
P1
CT7 input
P1
P3
7
23
21
24
22
11
9
12
10
KM1-PMU@A-FLK
23
21
24
CT6 input
Load
CT5 input
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
22
KM1-PMU1A-FLK
KE1-CTD8E
CT5 input
Load
KE1-CTD8E
Load
7
5
SPST-NO relay output 3
1
8
6
4
2
19
17
15
13
20
18
16
14
7
5
3
1
8
6
4
2
19
17
15
13
20
18
16
14
CT4 input
Load
CT3 input
CT2 input
Load
CT1 input
SPST-NO relay output
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
Power supply voltage
Power supply voltage
Load (L)
* The KE1-CTD8E will not operate alone.
It must be used together with a Measurement Master Unit.
* The required number of CT inputs depends on the wiring method.
Three-phase, three-wire: 2 inputs
* The number of circuits that one KE1-CTD8E Unit can
measure is as follows:
Three-phase, three-wire: 4 circuits max.
24
CT3 input
CT2 input
CT1 input
Load
* The KE1-CTD8E will not operate alone.
Load (L)
It must be used together with a Measurement Master Unit.
* The required number of CT inputs depends on the wiring method.
Three-phase, four-wire: 3 inputs
* The number of circuits that one KE1-CTD8E Unit can
measure is as follows:
Three-phase, four-wire: 2 circuits max.
KE1
ZCT Expansion Unit
KE1-ZCT8E
Terminal Arrangement and I/O Configuration
ZCT inputs
7 and 8
11 ZCT8 12
23 ZCT6 24
9
21 ZCT5 22
K
L
ZCT7
K L
10
K
K
ZCT inputs
5 and 6
L
L
KE1-ZCT8E
7
8
19 ZCT4 20
K
5
6
17 ZCT3 18
K
OUT1:
Alarm output
3
4
2
L
ZCT inputs
1 to 4
15 ZCT2 16
K
1
L
L
13 ZCT1 14
K
L
Terminal Functions
1
NC
9
ZCT-7K
17
ZCT-3K
2
NC
10
ZCT-7L
18
ZCT-3L
11
ZCT-8K
19
ZCT-4K
12
ZCT-8L
20
ZCT-4L
3
SPST-NO relay output
4
5
NC
13
ZCT-1K
21
ZCT-5K
6
NC
14
ZCT-1L
22
ZCT-5L
7
NC
15
ZCT-2K
23
ZCT-6K
8
NC
16
ZCT-2L
24
ZCT-6L
25
KE1
Wiring Diagram Examples
• Single-phase, Two-wire
Power
supply (K)
LN
P1
Power/Earth
Leakage
Measurement
Master Unit
P2
ZCT7 input
• Single-phase, Three-wire
Power/Earth
Leakage
P1
Measurement P3
Master Unit
Load
ZCT8 input
Power
supply (K)
RN T
ZCT7 input
Load
ZCT8 input
P2
Load
Load
ZCT6 input
ZCT6 input
11
23
12
24
11
12
23
11
Load
24
12
23
24
11
12
23
24
9
21
10
22
9
10
KE1-PGR1C-FLK
21
9
22
10
Load
KE1-ZCT8E
Load
ZCT5 input
ZCT5 input
21
22
9
10
KE1-PGR1C-FLK
21
22
Load
KE1-ZCT8E
Load
Load
ZCT4 input
ZCT4 input
Load
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
Load
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
ZCT3 input
ZCT3 input
SPST-NO relay output
ZCT2 input
Load
Load
SPST-NO relay output
ZCT1 input
ZCT2 input
ZCT1 input
Load
Load
Power supply voltage
Load (L)
* The KE1-ZCT8E will not operate alone.
It must be used together with a Measurement Master Unit.
* One input is required for each circuit regardless of the wiring method.
* The number of circuits that one KE1-ZCT8E Unit can
measure is as follows:
Single-phase, two-wire: 8 circuits max.
• Single-phase, Three-wire
Power/Earth
Leakage
Measurement
Master Unit
Power
supply (K)
RS T
Load
P3
Load (L)
* The KE1-ZCT8E will not operate alone.
It must be used together with a Measurement Master Unit.
* One input is required for each circuit regardless of the wiring method.
* The number of circuits that one KE1-ZCT8E Unit can
measure is as follows:
Single-phase, three-wire: 8 circuits max.
• Three-phase, Four-wire
Power/Earth
Leakage P1
Measurement
Master Unit
ZCT7 input
P1
Power supply voltage
ZCT8 input
P2
Power
supply (K)
RS T N
ZCT7 input
Load
P3
ZCT8 input
P2
P0
Load
Load
ZCT6 input
ZCT6 input
23
24
11
12
23
24
Load
11
12
23
24
11
12
23
24
9
10
21
22
9
10
21
22
21
22
9
10
KE1-PGR1C-FLK
21
22
Load
KE1-ZCT8E
Load
ZCT5 input
ZCT5 input
KE1-PGR1C-FLK
Load
KE1-ZCT8E
Load
ZCT4 input
Load
ZCT4 input
Load
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
Load
7
8
19
20
7
8
19
20
5
6
17
18
5
6
17
18
3
4
15
16
3
4
15
16
1
2
13
14
1
2
13
14
ZCT3 input
ZCT3 input
Load
Load
SPST-NO relay output
Power supply voltage
ZCT2 input
ZCT1 input
SPST-NO relay output
Load
ZCT1 input
Load
Load (L)
* The KE1-ZCT8E will not operate alone.
It must be used together with a Measurement Master Unit.
* One input is required for each circuit regardless of the wiring method.
* The number of circuits that one KE1-ZCT8E Unit can
handle is as follows:
Three-phase, three-wire: 8 circuits max.
26
ZCT2 input
Power supply voltage
Load (L)
* The KE1-ZCT8E will not operate alone.
It must be used together with a Measurement Master Unit.
* One input is required for each circuit regardless of the wiring method.
* The number of circuits that one KE1-ZCT8E Unit can
handle is as follows:
Three-phase, four-wire: 8 circuits max.
KE1
DeviceNet Communications Unit
KE1-DRT-FLK
Terminal Arrangement and I/O Configuration
KE1-DRT-FLK
Terminal Functions
RS-485
communications
8
7
−
RS-485
1
Power supply
voltage
+
2
PWR
Communications Connections
Host
B (+)
A (−) B (+)
Maximum transmission distance: 500 m
Terminating
resistance
7
8
KE1
1
KE1
A (−) B (+)
7
8
2
KE1
A (−) B (+)
7
8
Terminating resistance
Power supply voltage
2
Power supply voltage
3
NC
4
NC
5
NC
6
NC
7
RS-485 B (+)
8
RS-485 A (−)
Special CT Connections
• Separate RS-485 cables and power lines to prevent the influence
of noise.
• Use a twisted-pair cable of AWG24 (cross-sectional area: 0.205
mm2) to AWG14 (cross-sectional area: 2.081 mm2). (The stripping
length is 5 to 6 mm)
• Do not ground the RS-485 communications cable. Failure may
occur.
• Connect terminating resistance (120 Ω (1/2 W)) between the
positive and negative RS-485 pins on the host device and the last
device (normally a KE1). When connecting terminating resistance
to the host device, check the manual provided with the host device.
A (−)
1
Last
device
• One Special CT is required to measure a single-phase, two-wire
circuit. Two CTs are required to measure a single-phase, threewire circuit or three-phase, three-wire circuit. Three CTs are
required to measure a three-phase, four-wire circuit.
• Make sure that the ratings of the Special CTs and the Special CT
setting in the KE1 are the same.
• Check the directions of the power supply (K) and load (L) before
making the connections. Correct measurements will not be
possible if they are connected in the wrong directions.
• Release the locking hook and clamp the CT on the line. Do this for
each phase. Then, press the hook firmly until you hear it lock into
place.
• Make sure that the terminal cover on the secondary side of the CT
is closed securely.
• Do not ground the
Load (L)
Special CTs.
Failure may occur.
• The Special CTs have
polarity.
Power
Locking hook
supply (K)
Correctly wire the K
Used to secure
terminal on the Special
the CT
with a band.
CT to the S side of the
KE1 Unit and the L
CT secondary
side terminal cover
terminal on the Special
CT to the L side on the
KE1 Unit.
• Use the Special CT Cable (KM20-CTFCB3: 3 m) to connect the
Special CT. Connect the Special CT to the end with the shrinking
tube.
• Electric shock may occasionally occur.
Always use a sheathed cable with basic insulation of 600 V or
higher for the primary cable clamped by the CT.
If you clamp onto a busbar or other conductive item, cover it with
insulation or otherwise provide at least the required basic
insulation.
L
K
27
KE1
Dimensions
(Unit: mm)
Main Units
KE1-PGR1C-FLK/PVS1C-FLK/VSU1B-FLK/
VAU1B-FLK/CTD8E/ZCT8E
Two, 4.3 dia.
45
19.2
102
96 110
90
KE1-DRT-FLK
Two, 4.3 dia.
45
19.2
102
96 110
90
Split-type Current Transformers (CTs)
KM20-CTF-50A
KM20-CTF-50AU
KM20-CTF-5A
KM20-CTF-5AU
33
22.9
28.9
39
CT Through-hole Dimensions
CT Through-hole Dimensions
25.3
25.5
10
3
7.4
3
10
8.5
R5
7.9
R7.5
R8
41.3
5.57
48
40
40.5
28
R5
9.5
7.5
KE1
KM20-CTF-200A
KM20-CTF-200AU
KM20-CTF-100A
KM20-CTF-100AU
44.9
55.9
29.4
37.4
CT Through-hole Dimensions
CT Through-hole Dimensions
3
30.5
16
35.5
R8
24
6
14.5 11
R10
24
14.2 R9
R8
53.7
75.7
46
52.5
KM20-CTF-400A/600A
KM20-CTF-400A/600AU
62.5
73.5
CT Through-hole Dimensions
37
R18.5
35.5
6
35.5
R13
92.5
54
CT Through-hole Dimensions
27.6
KM20-CTB-5A/50A
38.6
49
8.4
52.8
9.05
12.95
CT Cable
KM20-CTF-CB3 (Special CT cable)
3000±100
V1.25-B3A
Unit end
CT end
VCTF 0.3×2
V1.25-N3A
30±5
50±5
29
KE1
Zero-phase Current Transformers (Compatible ZCTs)
Indoor, through-hole
OTG-L21 (50A)
9.3
M4 terminal screws
13.5
11
50
20
17
Installation Hole
Dimensions
Terminal symbols
(protrude 0.3 mm)
kt
k
l
lt
Nameplate
Label and caution
68.5
6
Two, 5.5-dia. holes or
two, M5 screw holes
64
74
21 dia.
5.2
20
64
Indoor, through-hole
OTG-L30 (100A)
9.3
M4 terminal screws
11
63
54
50
20
13.5
Installation Hole
Dimensions
Terminal symbols
(protrude 0.3 mm)
17
kt
k
l
lt
Nameplate
Two, 5.5-dia. holes or
two, M5 screw holes
81.5
76
6
86
30 dia.
5.2 20
76
Indoor, through-hole
OTG-L42 (200A)
11
9.3
5.2
Installation Hole
Dimensions
17
88
42 dia.
Two, 5-dia. holes or
Two, M4 screw holes
109
97
97 (installation pitch)
107
Indoor, through-hole
OTG-L68 (400A)
25
11
9.3
6.1
17
118
Installation Hole
Dimensions
68 dia.
Two, 5-dia. holes or
Two, M4 screw holes
136
131
131 (installation pitch)
143
30
31
KE1
Indoor, through-hole
OTG-L82 (600A)
11
9.3
6.2
138
Installation Hole
Dimensions
17
82 dia.
Two, 5-dia. holes or
Two, M4 screw holes
158
160
28
160 (installation pitch)
172
Indoor, through-hole
OTG-L156 (1,000A)
33
156 dia.
L
M5 terminal screws
Installation Hole
Dimensions
263
Four, 8.5-dia. holes or
Four, M8 screw holes
138
90
230
270
3.2
60
230
9
90 130
20
40
Indoor, split-type
OTG-CN52 (200A)
52 dia.
K
M4 terminal screws
Installation Hole
Dimensions
141
79
Two, 6.5-dia. holes or
Two, M6 screw holes
K
170
170
30
7
200
Indoor, split-type
OTG-CN77 (400A)
77 dia.
K
M4 terminal screws
Installation Hole
Dimensions
157
84
Four, 6.5-dia. holes or
Four, M6 screw holes
K
53
195
195
70 53
7
230
31
KE1
Indoor, split-type
OTG-CN112 (600A)
112 dia.
K
M4 terminal screws
Installation Hole
Dimensions
200
Four, 6.5-dia. holes or
Four, M6 screw holes
107
K
53
225
225
70 53
7
260
Outdoor, through-hole
OTG-LA30W (100A)
62
Installation Hole
Dimensions
73.5
30 dia.
42.5
3.5
Two, 5.5-dia. holes or
Two, M5 screw holes
10.5
500
2
2
20
24
5.5
68
1.25mm VCTFK
(JIS C 3306)
5
5.5 dia.
68
84
Outdoor, split-type
OTG-CN36W (150A)
150
135
35
5
30
Installation Hole
Dimensions
5.5 dia.
130
Two, 5.5-dia. holes or
Two, M5 screw holes
45
91±1
135
36 dia.
46
5±
2
20
±
2
45
0±
20
4
1.25mm2 VCTFK
Largest Applicable Wire Sizes for CTs
Power cable
Model
OTG-L21
OTG-L30
OTG-L42
OTG-L68
OTG-L82
OTG-L156
OTG-CN52
OTG-CN77
OTG-CN112
OTG-LA30W
OTG-CN36W
32
600-V vinyl-insulated cable (IV)
VVR cable
Rated
current
Throughhole
diameter
50 A
21 mm
22 mm2
14 mm2
8 mm2
5.5 mm2
30 mm
2
2
2
38 mm2
2
60 mm2
2
250 mm2
2
400 mm2
2
1,000 mm2
2
100 mm2
2
325 mm2
2
1,000 mm2
2
38 mm2
2
38 mm2
100 A
200 A
400 A
600 A
1,000 A
200 A
400 A
600 A
100 A
150 A
42 mm
68 mm
82 mm
156 mm
52 mm
77 mm
112 mm
30 mm
36 mm
2 wires
3 wires
60 mm
2
100 mm
2
400 mm
2
500 mm
2
500 mm
2
200 mm
2
500 mm
2
500 mm
60 mm
2
60 mm
2
2 wires
38 mm
2
100 mm
2
325 mm
2
500 mm
2
500 mm
2
200 mm
2
400 mm
2
500 mm
2
38 mm
2
38 mm
3 wires
38 mm
100 mm
325 mm
400 mm
1,000 mm
150 mm
400 mm
1,000 mm
38 mm
60 mm
KE1
Current Transformer for Ground Wires
Indoor, split-type
K6ER-CN22 (2A)
22 dia.
20
VVC-0.18 × 7 cores × 2C
39
BK(l)
W(k)
21
51.5
(53.65)
150
The following connection cable is included.
W(k)
BK(l)
5±1
3,000±30
Communications Interface Converter
K3SC-10
7
Mounting Hole Dimensions
for Direct Mounting
Two, M4 screw holes
or two 4.3 dia. holes
75
72±0.3
80
30
3
23.5
51.5
78
Note: DIN Track mounting is also possible.
DIN Track
PFP-100N
PFP-50N
Model
7.3±0.15
PFP-100N
35±0.3
4.5
15
25
10
25
25
10
15(5)*
25
27±0.15
PFP-50N
1
1000(500)*
*The dimensions for the PFP-50N DIN Track are given in parenthesis.
Clamp (End Plate)
PFP-M
Model
10
6.2
M4 × 8 pan
head screws
50
1.8
PFP-M
1
1.8
35.5 35.5
11.5
1.3
10
M4 spring washer
4.8
33
KE1
Operating Procedure
Workflow to Prepare for Application
Initial Settings
• Communications protocol and slave ID settings . . . . . . . . . . . . . . Refer to Nomenclature on page 13
• Initializing settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Implement initialization with USB communications.
• Initial settings with the Setup Software . . . . . . . . . . . . . . . . . . . . . Implement the settings with USB communications or RS-485
communications.
Note: 1. Apply the specified power supply voltage if you use RS-485 communications to make the settings.
2. There are no RS-485 communications terminals on CT Expansion Units or ZCT Expansion Units. Use USB communications or make
the settings through the Measurement Master Unit.
Connections
• Use the horizontal connection hooks to connect the Unit cases to each other.
• Connect the Units to each other with the link connectors.
Installation
• Mount the KE1 Units to a DIN Track or on a wall.
Note: If you connect more than one Unit together, install them on a DIN Track.
Wiring
• Wire the Units starting from the bottom of the terminal block.
34
KE1
Main Functions
Functions
Yes: Function is supported. ---: Function is not supported.
Alarm output functions Measurement functions
Measurement Master Units
(1 Unit max.)
CT Expansion Slaves
(4 Units max.)
Communications Slaves
(1 Unit max.)
KE1-PGR1CFLK (Power/
Earth Leakage
Monitor Unit)
KE1-PVS1CFLK (Power/
Momentary
Voltage Sag
Monitor Unit)
KE1-VSU1BFLK (Momentary Voltage
Sag Monitor
Unit)
KE1-VAU1BFLK (Voltage/
Current Monitor Unit)
KE1-CTD8E
(CT Expansion Unit)
KE1-CTD8E
(ZCT Expansion Unit)
KE1-DRT-FLK
(DeviceNet
Communications Unit)
Active power
Yes
Yes
---
---
Yes
---
---
Reactive power
Yes
Yes
---
---
Yes
---
---
Power factor
Yes
Yes
---
---
Yes
---
---
Current
Yes
Yes
---
Yes
Yes
---
---
Voltage
Yes
Yes
Yes
Yes
---
---
---
Frequency
Yes
Yes
Yes
Yes
---
---
---
Total power consumption
Yes
Yes
---
---
Yes
---
---
---
Yes
Yes
---
---
---
-----
Momentary voltage sag
Earth leakage
Yes
---
---
---
---
Yes
Overcurrent/undercurrent
Yes
Yes
---
Yes
Yes
---
---
Overvoltage/undervoltage
Yes
Yes
Yes
Yes
---
---
---
Open phase
Yes
Yes
Yes
Yes
---
---
---
Reversed phases
Yes
Yes
Yes
Yes
---
---
---
Data logging
Other functions
Function Slaves
(4 Units max.)
Yes
Yes
Yes
Yes
---
---
---
Setting Special CTs
Yes
Yes
---
Yes
Yes
---
---
Setting CT ratios
Yes
Yes
---
Yes
Yes
---
---
Setting VT ratios
Yes
Yes
Yes
Yes
---
---
---
Low-cut function
Yes
Yes
---
Yes
Yes
Yes
---
Average count
Yes
Yes
Yes
Yes
Yes
Yes
---
CT signal detection
Yes
Yes
---
Yes
Yes
---
---
ZCT signal detection
Yes
---
---
---
---
Yes
---
---
---
---
---
---
---
Yes
DeviceNet communications
Power Measurement Functions
Earth Leakage Monitoring
KE1-PGR1C-FLK/-PVS1C-FLK/-CTD8E
The active power, reactive power, power factor, and total power
consumption are measured on the circuits to measure.
By combining the Units with KE1-CTD8E CT Expansion Units, you
can measure up to 35 circuits.
(The number of circuits that can be measured depends on the wiring
methods of the circuits that are measured.)
Just set the detection values in advance to detect upper and lower
limits and save alarms in an alarm history in the Unit.
Also, the KE1-PGR1C-FLK (Power/Earth Leakage Monitor Unit) and
KE1-PVS1C-FLK (Power/Momentary Voltage Sag Monitor Unit)
Measurement Masters can log various types of measurement data.
(The number of days for which data can be logged depends on the
logging period.)
The measured power values and alarm records can be sent via
communications to a computer or other host system.
KE1-PGR1C-FLK/-ZCT8E
Earth leakage from insulation deterioration of the circuits to monitor
can be detected.
By combining with KE1-ZCT8E ZCT Expansion Units, you can
monitor earth leakage on up to 33 circuits.
If the detected earth leakage current reaches or exceeds the preset
value, the detection time and alarm type are stored in the alarm
history.
Alarm settings can also be made to output alarms.
The measured earth leakage currents and alarm records can be sent
via communications to a computer or other host system.
Note: You can connect a computer on which OMRON’s EasyKM
Manager is installed to constantly monitor earth leakage and
earth leakage trends.
Note: Do not use this function for the secondary side of an inverter.
Note: You can connect a computer on which OMRON’s EasyKM
Manager is installed to constantly monitor power and calculate
the total demand.
35
KE1
Momentary Voltage Sag Detection
KE1-PVS1C-FLK/-VSU1B-FLK
If a voltage sag that conforms to SEMI-F47 continues for the specified
time or longer, it is detected as a momentary voltage sag, the actual
voltages before and after it are recorded in memory, and an alarm is
recorded in the alarm history.
Alarm settings can also be made to output alarms.
If you connect a UPS or other backup power supply that is not
affected by momentary voltage sags, you can output an alarm for up
to 1 second after the momentary voltage sag occurs.
Example: If the momentary voltage sag detection function is set to Vrs, the momentary voltage sag detection voltage is set to 170 V, and the
momentary voltage sag time is set to 0.02 seconds, a momentary voltage sag is detected when the voltage between the R and S lines
of the three-phase, three-wire system if the voltage drops below 170 V for the momentary voltage sag detection time or longer. The
output turns ON within 5 ms of when the momentary voltage sag is detected.
Normal voltage
recovered.
Momentary voltage
sag detected.
220 V
170 V
0.02 s
50 V
0V
Alarm output*1
Voltage sag level
Momentary voltage
sag occurs.
1s
Alarm output*2
5 ms
5 ms
Before momentary voltage sag
A/D values (effective value conversion for 2.5 cycles) (80 values)
At 60 Hz: Approx.
0.52-ms interval (0.04 s)
At 50 Hz: Approx.
0.63-ms interval (0.05 s)
(
3)
At 60 Hz: Approx.
0.52-ms interval (0.04 s)
At 50 Hz: Approx.
0.63-ms interval (0.05 s)
150.1 V
149.7 V
150.3 V
149.5 V
Effective values (64 values per cycle)
Effective values (64 values per cycle)
At 60 Hz: Approx.
16.7-ms interval (1.06 s)
At 50 Hz: Approx. 20-ms
interval (1.28 s)
After momentary voltage sag
A/D values (effective value conversion for 2.5 cycles) (80 values)
At 60 Hz: Approx.
16.7-ms interval (1.06 s)
At 50 Hz: Approx. 20-ms
interval (1.28 s)
150.0 V
149.9 V
150.2 V
149.7 V
Effective values (120 values averaged across 10 cycles)
At 50 Hz: Approx. 200-ms
interval (24 s)
At 60 Hz: Approx. 166-ms
interval (20 s)
150.0 V
*1. With a backup power supply.
*2. Without a backup power supply.
*3. Data extraction from a PLC.
150.1 V
Voltage/Current Monitoring
Overcurrents/Undercurrents
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK/-CTD8E
Note: 1. The KE1-VSU1B-FLK can monitor only voltages.
2. The KE1-CTD8E can monitor only currents.
The circuit is monitored for overvoltages, undervoltages,
overcurrents, and undercurrents.
With single-phase circuits with three wires or more, you can detect if
the voltage or current for any of the phases exceeds a set value.
Detection dates and alarm types are recorded in the alarm history.
Alarm settings can also be made to output alarms.
Overvoltages/Undervoltages
Overvoltage alarm threshold
Overvoltage reset value
Voltage 1
Input Voltage 2
Voltage 3
Undervoltage alarm threshold
Alarm indicator
36
Overcurrent alarm threshold
Overcurrent reset value
Current 1
Input Current 2
Current 3
Undercurrent alarm threshold
Alarm indicator
Undercurrent reset value
Lit.
Lit.
Open Phase Detection
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK
The voltage balance on three-phase, three-wire circuits or threephase, four-wire circuits is monitored to detect open phases.
An open phase is detected if the following open phase detection
condition is met for any of the phases.
Alarm settings can also be made to output alarms.
Undervoltage reset value
(Largest error between any phase voltage and the average voltage)
Lit.
Lit.
Average voltage
× 100 ≤ 85%
KE1
Three-phase Reverse Phase Detection
Alarm Output Time Charts
1.
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK
The phase sequence on three-phase, three-wire circuits or threephase, four-wire circuits is monitored to detect reversed phases.
Alarm settings can also be made to output alarms.
Upper limit
threshold
Hysteresis
Alarm Outputs
Hysteresis
Lower limit
threshold
Alarm output support depends on the Unit.
Refer to Functions on page 35.
You can set alarm outputs for the detection functions.
You can assign alarm outputs to relay or transistor outputs to output
signals.
For a momentary voltage sag alarm, you can assign the alarm to a
semiconductor relay output to output an alarm. You can set an ON
delay to delay the alarm output signal.
You can set hysteresis to help prevent chattering.
You can set alarm outputs for the detection functions that are given in
the following table.
Detection function
Alarm type
Momentary voltage sag
Momentary voltage sag alarm
Earth leakage
Earth leakage alarm
Active/reactive power
Power factor
Voltage monitoring
Current monitoring
Hysteresis Setting
Upper limit alarm detection
Lower limit alarm detection
Upper limit alarm output
Lower limit alarm output
2.
ON Delay Setting
Upper limit
threshold
Lower limit
threshold
Upper limit alarm
Upper limit alarm detection
Lower limit alarm
Lower limit alarm detection
Power factor alarm
ON delay status
Overvoltage alarm
Upper limit alarm output
Undervoltage alarm
Lower limit alarm output
*1
*1
Overcurrent alarm
Undercurrent alarm
Open phase
Open phase alarm
Reversed phases
Reverse phase alarm
Saving Data
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK/-CTD8E/-ZCT8E
Four types of data is saved in the Unit’s memory: backup data, logging data, a momentary voltage sag detection history, and an alarm history.
The following table gives the measurement data that is saved, when the data is saved, and how long the data is saved.
Name
Measurement data
Saved when
Number of records/save
period
Reading method
Backup data
Total active power
consumption
Total regenerated energy
Total reactive power
consumption
5 min
Logging data
Various types of total power
consumption
Voltages
Currents
Earth leakage currents
Power
Power factor
2 days, 4 days, 12 days,
5 min, 10 min, 30 min, 1 h, 2
24 days, 49 days, 147 days,
h, 6 h, 12 h, or 24 h
294 days, or 588 days
RS-485 communications (*1)
Momentary voltage
sag detection history
Momentary voltage sag
occurrence date and time
Voltage measurement
values before and after
occurrence
At momentary voltage sag
detection
8 occurrences per condition
(4 conditions max.)
Provided tool
(KM1_KE1-Setting) (*3)
RS-485 communications (*1)
Alarm history
Date and time of occurrence
5 min (*2)
for alarms for trip factors
20 alarms
Provided tool
(KM1_KE1-Setting) (*3)
RS-485 communications (*1)
---
RS-485 communications (*1)
*1. Separate software must be created to read the data. For details, refer to the Model KM1/KE1 Smart Power Monitor Communication Manual
for Smart Measurement and Monitoring Instrument.
*2. After the alarms are reset, alarms are saved every 5 minutes starting from 0 hours on the Unit’s clock.
*3. For details, refer to KM1/KE1- Setting Tool.
37
KE1
Special CTs
KE1PGR1CFLK
(Power/
Earth
Leakage)
KE1KE1KE1PVS1CKE1KE1VSU1BVAU1BFLK
CTD8E
ZCT8E
FLK (MoFLK
(Power/
(CT Ex- (ZCT Exmentary
(Voltage/
Momenpansion) pansion)
Voltage
Current)
tary VoltSag)
age Sag)
Yes
Yes
Yes
Yes
Yes
No
Yes: Setting, No: No setting
Set the Special CT to use.
The Special CTs are listed below.
(KE1-PGR1C-FLK, KE1-PVS1C-FLK, KE1-VAU1B-FLK, or KE1CTD8E)
Set the CT ratio if you use a commercially available standard CT.
You can combine one of the following CTs with a standard CT to
measure currents that are 600 A or higher.
KM20-CTF-5A
KM20-CTF-5AU
KM20-CTF-50A
KM20-CTF-50AU
KM20-CTF-5/50A
Setting VT Ratios
Split-type CTs
CT model
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK
Set the VT ratio if you use a commercially available VT.
You can use commercially available VTs to measure voltages that are
higher than the voltage ratings.
Rating
KM20-CTF-5A
5A
KM20-CTF-50A
50 A
KM20-CTF-100A
100 A
KM20-CTF-200A
200 A
KM20-CTF-400A
400 A
KM20-CTF-600A
600 A
Low-cut Current and Earth Leakage Lowcut Current
KE1-PGR1C-FLK/-PVS1C-FLK/-VAU1B-FLK/-CTD8E/-ZCT8E
You can force the measurement value to 0 A if the current flow is
lower than the set value.
The effective value is used for detection, so inputs with high crest
values, such as for noise, can be cut.
Split-type CTs (UL-compliant)
CT model
Rating
KM20-CTF-5AU
5A
Average Count
KM20-CTF-50AU
50 A
KM20-CTF-100AU
100 A
KM20-CTF-200AU
200 A
KM20-CTF-400AU
400 A
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/
-VAU1B-FLK/-CTD8E/-ZCT8E
You can average measurement values to stabilize them.
You can average active power values, reactive power values, power
factors, currents, and voltages.
KM20-CTF-600AU
600 A
CT and ZCT Signal Detection
Through-hole (panel-installed) CTs
CT model
KE1-PGR1C-FLK/-PVS1C-FLK/-VAU1B-FLK/-CTD8E/-ZCT8E
An indicator is lit then a signal from a CT or ZCT is detected so that
you can confirm connection status and signal status.
An indicator lights for the following condition.
• When the signal input is 2% or higher of the rated current for 10
seconds or longer.
Rating
KM20-CTB-5A/50A
5 A/50 A
CT Ratios
KE1PGR1CFLK
(Power/
Earth
Leakage)
KE1KE1KE1PVS1CKE1KE1VSU1BVAU1BFLK
CTD8E
ZCT8E
FLK (MoFLK
(Power/
(CT Ex- (ZCT Exmentary
(Voltage/
Momenpansion) pansion)
Voltage
Current)
tary VoltSag)
age Sag)
Yes
Yes
No
Yes
Yes
No
Yes: Setting, No: No setting
Standard CT
with 5-A secondary output
5A
Special CT
Use one of the following.
KM20-CTF-5A
KM20-CTF-5AU
KM20-CTF-50A
KM20-CTF-50AU
KM20-CTB-5A/50A
1000 A
Time
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/-VAU1B-FLK
The time is used for timestamps for measurement data and the alarm
history. You can set a year between 2012 and 2099 (adjusted for leap
years) and the data is backed up for power interruptions lasting up to
7 days.
Initialization
You can set the CT ratio for a standard CT to measure currents that
are higher than the ratings of the Special CTs.
If you combine Special CTs with previous installed standard CTs, set
the CT ratio of the standard CTs.
To use a Special CT with a previously installed standard CT, combine
it with the KM20-CTF5A or KM20-CTF-5AU, or combine it with the
KM20-CTB-5A/50A (5 A on primary side).
38
Setting CT Ratios
KE1-PGR1C-FLK/-PVS1C-FLK/-VSU1B-FLK/
-VAU1B-FLK/-DRT-FLK/-CTD8E/-ZCT8E
The following table gives the types of initialization that you can
perform.
The previous data cannot be recovered after initialization.
Initialized item
Initialized data
Initialize maximum/
minimum values
Initializes the maximum and minimum
values.
Initialize total power
consumptions
Initializes the backup data.
Initialize
measurement log
Initializes the items that are to be
logged
Initialize alarm
history
Initializes the alarm history.
Initialize settings
Initializes all parameters except for the
Time Setting parameter.
Initialize all
Initializes all parameters except for the
Time Setting parameter.
KE1
KE1
Safety Precautions
● Be sure to read the precautions for all E5CC/E5EC/E5AC/E5DC models in the website at:
http://www.ia.omron.com/.
Warning Indications
CAUTION
Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury or in
property damage.
Precautions for
Safe Use
Supplementary comments on what to
do or avoid doing, to use the product
safely.
Precautions for
Correct Use
Supplementary comments on what to
do or avoid doing, to prevent failure to
operate, malfunction or undesirable
effect on product performance.
Meaning of Product Safety Symbols
Used for general CAUTION, WARNING, or
DANGER precautions for which there is no
specified symbol. (This symbol is also used as the
alerting symbol, but shall not be used in this
meaning on the product.)
Used for general mandatory action precautions
for which there is no specified symbol.
Used to warn of the risk of explosion under
specific conditions.
Used to warn of the risk of electric shock under
specific conditions.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source
if the product is disassembled.
CAUTION
Property damage may occasionally occur due to fire.
Tighten terminal screws to the specified tightening
torque.
The recommended tightening torque is 0.69 to 0.88
N·m. Confirm that the screws are straight (i.e., not at an angle)
after tightening them.
Minor or moderate bodily harm or property damage
may occasionally occur due to explosion.
Do not use the Units near inflammable or explosive
gas.
Destruction or rupture may occasionally occur.
Make sure that the power supply voltages and loads
are within specifications and ratings.
Destruction or rupture may occasionally occur.
The voltage input circuit and CT secondary circuit are
not isolated. If a Special CT is grounded, incorrect
wiring will short-circuit the voltage input and the
secondary circuit of the CT. To prevent failure, do not
ground a Special CT or ZCT.
The Power Monitor uses a Special CT or ZCT.
Therefore, correct measurements can be made even if
the CT or ZCT is not grounded.
Electric shock may occasionally occur.
Always turn OFF the power supply before connecting
CTs.
Electric shock may occasionally occur.
Do not touch any of the terminals while the power is
being supplied.
Electric shock may occasionally occur.
Always use a sheathed cable with basic insulation or
better for the primary cable clamped by the CT.
If you clamp onto a busbar or other conductive item,
cover it with insulation or otherwise provide at least
the required basic insulation.
Electrical shock, minor injury, fire, or equipment
malfunction may occasionally occur.
Do not attempt to disassemble, modify, or repair any
Unit.
Precautions for Safe Use
The following items must be observed to prevent failure to operate
and malfunctions of the Units and to prevent adverse effects on
performance and functions of the Units.
1. Do not use, store, or transport the Units in the following locations.
• Locations that are greatly affected by vibration or shock
• Unstable locations
• Locations where the specified range of temperature or humidity
would be exceeded
• Locations that are subject to rapid changes in temperature or
humidity where condensation or icing may occur
• Locations that are subject to direct sunlight.
• Outdoors or locations that are subject to wind or rain
• Locations that are affected by static electricity or noise
• Locations that are subject to water, oil or saltwater.
• Locations that are subject to corrosive gas (particularly sulfide or
ammonia gas)
• Locations that are subject to dust or iron powder
• Locations that are affected by electric or magnetic fields
2. When you install DIN tracks, make sure that the screws are
tightened securely. Mount the Units securely to the DIN Track. If
any Units are loose, vibration or shock can cause the DIN Track,
Units, or wires to become disconnected.
3. Use DIN Tracks with a width of 35 mm (OMRON PFP-50N/-100N).
4. Use crimp terminals that are suitable for M3.5 screws to wire the
Units.
5. Check the specifications and wiring to be sure there are no
mistakes before you turn ON the power supply.
6. Read and understand the Unit manuals before attempting to
install, use, or maintain the Units. Electric shock, injury, accidents,
failure, or malfunction may occur.
7. Install and suitably label a switch or circuit breaker that complies
with relevant requirements of IEC 60947-1 and IEC 60947-3 so
that the operator can immediately turn OFF the power supply.
8. Understand the manuals when you set the Units.
9. Install the Units separated as far as possible from devices with
strong high-frequency noise or devices that generate surge.
10.Touch grounded metal to discharge any static electricity before
touching the Units.
11.To prevent inductive noise, wire the lines connected to the Units
separately from power lines carrying high voltages or currents. Do
not wire in parallel with or on the same cable as power lines. Other
measures for reducing noise include running lines in separate
ducts and using shields.
12.Do not install the Units near sources of heat, such as devices with
coils or windings.
13.Do not allow metal objects, conductors, or cuttings from
39
KE1
installation work to enter the Units.
14.Do not use solvents, such as paint thinners, to clean the Units. Use
commercially available alcohol instead.
15.Use a power supply voltage and wires with suitable specifications
for the control power supply and the power supply for inputs and
other parts of the system. Failure, burning, or electrical shock may
result.
16.If you install a Unit on a wall, install it so that the screws are not
loose. If any Units are loose, vibration or shock may cause the Unit
or wires to become disconnected.
17.If you use more than one Unit together, slide them together until
the horizontal connection hooks audibly lock in place.
18.If you mount the Units on DIN Track, slide them until the DIN hooks
audibly lock in place.
19.Use only the Special CTs, Special ZCTs, and Special CT Cable
specified by OMRON.
Special CTs
Split-type
KM20-CTF-5A
KM20-CTF-50A
KM20-CTF-100A
KM20-CTF-200A
KM20-CTF-400A
KM20-CTF-600A
Throughhole
KM20-CTB-5A/50A
For ground
line
K6ER-CN22 (with cable)
Special ZCTs
Split-type
Throughhole
OTG-CN52
OTG-CN77
OTG-CN112
OTG-L21
OTG-L30
OTG-L42
OTG-L68
OTG-L82
OTG-L156
OTG-CN36W
OTG-LA30W
Special CT Cable: KM20-CTF-CB3 (3 m) (This Cable can also be
used with the Special ZCTs.)
20.Do not use the Units for measurement on the secondary side of an
inverter.
21.Do not block the ventilation holes in or the areas around the Units
to ensure proper dissipation of heat.
22.Check all terminal numbers before wiring. Do not connect anything
to unused terminals.
23.The Units are a Class A products (for use in industrial
environments). In residential environment areas, they may cause
radio interference. If they cause radio interference, the user may
be required to take adequate measures to reduce interference.
24.Use the Special CTs and Special ZCTs at a low voltage of 600 V
or less.
Installation Precautions
Maintaining Product Life
Use the KE1 within the following temperature and humidity ranges.
Temperature: −10 to 55°C (with no icing or condensation)
Humidity: 25% to 85%
Do not let the ambient temperature around the Units exceed 55°C.
(This is not the ambient temperature around the panel.)
Some of the electronic components used in the Units have limited
service lives. The life of these components depends on the ambient
temperature. The service lives will be shorter at higher temperatures
and longer at lower temperatures. The life of the Units can thus be
extended by lowering the internal temperature. If more than one KE1
Unit is mounted side by side or top to bottom, you must consider using
forced cooling, such as fans that circulate air around the Units.
Noise Countermeasures
To prevent inductive noise, wire the lines connected to the terminal
block on the Units separately from power lines carrying high voltages
or currents. Do not wire in parallel with or on the same cable as power
lines. Other measures for reducing noise include running lines in
separate ducts and using shields.
Attach surge absorbers or noise filters to nearby equipment that
generates noise (particularly equipment with a high inductance
component, such as motors, transformers, or magnetic coils).
Install the Units as far as possible away from devices with strong highfrequency noise (such a high-frequency welders or sewing machines)
or devices that generate surge.
40
Precautions for Correct Use
1. Make sure that all parameters are set suitably for the monitor
targets.
2. Do not pull on the cables.
3. When discarding the Units, dispose of them according to all local
laws and ordinances as they apply. Dispose of the Units as
industrial waste.
4. When using the Units in an Overvoltage Category III environment,
externally install varistors between the power supply and voltage
measurement inputs to the Units.
MEMO
41
MEMO
42
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2013 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_5_3_0316
Printed in Japan
Cat. No. N173-E1-01
0813 (0813)