NX-series Analog Output Unit
NX-DA
CSM_NX-DA_DS_E_2_5
Analog Outputs to meet all
machine control needs; from
general-purpose outputs to highspeed synchronous, highresolution control outputs
• Analog Output Units for the NX-series modular I/O
system.
• Connect to other NX-series I/O Units and EtherCAT
Coupler units using the high-speed NX-bus.
• Separate modules for voltage- and current outputs.
Features
• Up to four analog outputs per unit.
• Free-Run refreshing or Synchronous I/O refreshing, Task Period Prioritized refreshing *, can be selected for refreshing with the NX-series
EtherCAT Coupler.
• Output update cycles of 10 μs per channel, and resolution of 1/30000, ideal for high-speed, high-precision control.
• The screwless terminal block is detachable for easy commissioning and maintenance.
• Screwless push-in terminal block significantly reduces wiring work.
• All models are just 12 mm wide, saving space in your cabinet.
* Task Period Prioritized refreshing is available when the NX-ECC203 is used together.
System Configuration
Sysmac Studio
Support Software
EtherCAT master*
NJ/NX-series CPU Unit
Connection to peripheral USB port
or built-in EtherNet/IPTM port on
NJ/NX-series CPU Unit
Built-in EtherCAT port
Sysmac Studio
Support Software
●EtherCAT Slave Terminal
Communications cable
Ethernet cables
Peripheral USB port.
NX Series
EtherCAT Coupler Unit
NX-ECC@@@
Connection to peripheral USB
port on EtherCAT Coupler Unit
NX Units
End Cover
* OMRON CJ1W-NC@81/@82 Position Control Units cannot be connected to the EtherCAT Slave Terminal even though they support EtherCAT.
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
EtherCAT® is a registered trademark of Beckhoff Automation GmbH for their patented technology. Other company names and product names in this document are the
trademarks or registered trademarks of their respective companies.
1
NX-DA
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1:
cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, CE: EC Directives,and KC: KC Registration.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Analog Output Unit
Specification
Unit
type
Product
Name
Voltage
Output
Unit
Capacity
Input
range
Resolution
Over all
accuracy
(25°C)
1/8000
-4000 to 4000
±0.3%
250 μs/point
(full scale)
Free-Run
refreshing
1.10W max.
NX-DA2603
1.10W max.
NX-DA2605
Current
Output
Unit
Model
Standards
-15000 to
15000
±0.1%
10 μs/point
(full scale)
1/8000
-4000 to 4000
±0.3%
250 μs/point
(full scale)
Free-Run
refreshing
1.25W max.
NX-DA3603
1/30000
-15000 to
15000
±0.1%
10 μs/point
(full scale)
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
1.25W max.
NX-DA3605
1/8000
0 to 8000
±0.3%
250 μs/point
(full scale)
Free-Run
refreshing
1.75W max.
NX-DA2203
1/30000
0 to 30000
±0.1%
10 μs/point
(full scale)
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
1.75W max.
NX-DA2205
1/8000
0 to 8000
±0.3%
250 μs/point
(full scale)
Free-Run
refreshing
1.80W max.
NX-DA3203
0 to 30000
±0.1%
10 μs/point
(full scale)
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
1.80W max.
NX-DA3205
2 points
4 to
20mA
I/O
refreshing
method
1/30000
4 points
NX
Series
Analog
Output
Unit
Conversion
time
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
2 points
-10 to
+10V
NX Unit
power
consumption
Output setting
value, decimal
number
(0 to 100%)
4 points
1/30000
UC1,N, L,
CE,KC
Option
Product Name
Unit/Terminal Block Coding Pins
Specification
Model
For 10 Units
(Terminal Block: 30 pins, Unit: 30 pins)
NX-AUX02
Standards
---
Specification
Product Name
Terminal Block
No. of
terminals
8
12
Terminal
number
indications
A/B
Ground
terminal
mark
None
Terminal
current
capacity
10 A
Model
NX-TBA082
NX-TBA122
Standards
---
Accessories
Not included.
2
NX-DA
General Specification
Item
Enclosure
Specification
Mounted in a panel
Grounding method
Ground to 100 Ω or less
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage temperature
−25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
Operating
Noise immunity
environment
Overvoltage category
2 or less: Conforms to JIS B3502 and IEC 61131-2.
2 kV on power supply line (Conforms to IEC61000-4-4.)
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity level
Zone B
Vibration resistance
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each
in X, Y, and Z directions
(10 sweeps of 10 min each = 100 min total)
Shock resistance
IConforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
Applicable standards
cULus: Listed UL508 and ANSI/ISA 12.12.01
EC: EN 61131-2 and C-Tick, KC Registration, NK, LR
3
NX-DA
Analog Output Unit Specifications
Analog Output Unit (voltage output type) 2points NX-DA2603
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA2603
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.5% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.10 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output V1+ to V2+
IOG
Circuit layout
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
Terminal block
B1
Voltage Output Unit
NX-DA2603
A1
B1
IOV
IOV
V1+
V2+
Voltage output +
IOG
IOG
IOV
IOV
Voltage output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
4
NX-DA
Analog Output Unit (voltage output type) 2points NX-DA2605
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA2605
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.10 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output V1+ to V2+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
Terminal block
B1
Voltage Output Unit
NX-DA2605
A1
B1
IOV
IOV
V1+
V2+
Voltage output +
IOG
IOG
IOV
IOV
Voltage output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
5
NX-DA
Analog Output Unit (voltage output type) 4points NX-DA3603
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA3603
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.5% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.25 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output V1+ to V4+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
Terminal block
IOG
Voltage Output Unit
NX-DA3603
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
V1+
V2+
IOV
IOV
IOG
IOG
V3+
V4+
IOV
IOV
IOG
IOG
Voltage output +
Voltage output −
IOG
B8
A8
B8
6
NX-DA
Analog Output Unit (voltage output type) 4points NX-DA3605
Unit name
Analog Output Unit (voltage output type)
Model
NX-DA3605
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
-10 to +10 V
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
5 kΩ min.
Output impedance
0.5 Ω max.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.25 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output V1+ to V4+
Circuit layout
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
Installation orientation
and restrictions
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
Terminal block
IOG
Voltage Output Unit
NX-DA3605
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
V1+
V2+
IOV
IOV
IOG
IOG
V3+
V4+
IOV
IOV
IOG
IOG
Voltage output +
Voltage output −
IOG
B8
A8
B8
7
NX-DA
Analog Output Unit (current output type) 2points NX-DA2203
Unit name
Analog Output Unit (current output type)
Model
NX-DA2203
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
600 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.6% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.75 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output I1+ to I2+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
600
350
Use it within this range.
0
55 (°C)
40
Ambient operating temperature
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
B1
Current Output Unit
NX-DA2203
A1
B1
IOV
IOV
I1+
I2+
Current output +
IOG
IOG
IOV
IOV
Current output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
8
NX-DA
Analog Output Unit (current output type) 2points NX-DA2205
Unit name
Analog Output Unit (current output type)
Model
NX-DA2205
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
600 Ω min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.75 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output I1+ to I2+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
600
350
Use it within this range.
0
55 (°C)
40
Ambient operating temperature
Additional I/O
Power Supply Unit
A1
Terminal connection
diagram
B1
Current Output Unit
NX-DA2205
A1
B1
IOV
IOV
I1+
I2+
Current output +
IOG
IOG
IOV
IOV
Current output −
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
24 VDC
A8
B8
A8
B8
9
NX-DA
Analog Output Unit (current output type) 4points NX-DA3203
Unit name
Analog Output Unit (current output type)
Model
NX-DA3203
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
350 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.3% (full scale)
Conversion time
250 μs/point
±0.6% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.80 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output I1+ to I4+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
350
250
Use it within this range.
0
55 (°C)
40
Ambient operating temperature
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
IOG
Current Output Unit
NX-DA3203
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
I1+
I2+
IOV
IOV
IOG
IOG
I3+
I4+
IOV
IOV
IOG
IOG
Current output +
Current output −
IOG
B8
A8
B8
10
NX-DA
Analog Output Unit (current output type) 4points NX-DA3205
Unit name
Analog Output Unit (current output type)
Model
NX-DA3205
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Output range
4 to 20 mA
Output conversion
range
-5 to 105% (full scale)
Allowable load
resistance
350 Ω min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.3% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.80 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
AMP
Output I1+ to I4+
Circuit layout
Terminal block
IOG
AG: Analog circuit internal GND
NX bus
connector
(left)
AG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions:
For upright installation: No restrictions
For any installation other than upright: Restricted as shown in the graph below.
Installation orientation
and restrictions
Load resistance (per point)
(Ω)
350
250
Use it within this range.
0
55 (°C)
40
Ambient operating temperature
Additional I/O
Power Supply Unit
A1
B1
IOV
Terminal connection
diagram
IOG
Current Output Unit
NX-DA3205
A1
IOV
IOG
24 VDC
IOV
IOG
A8
IOV
B1
I1+
I2+
IOV
IOV
IOG
IOG
I3+
I4+
IOV
IOV
IOG
IOG
Current output +
Current output −
IOG
B8
A8
B8
11
NX-DA
Version Information
NX Unit
Corresponding unit versions/versions *
EtherCAT Coupler Units
Model
Unit Version
NJ/NX-series CPU Units
Sysmac Studio
NX-ECC20@
NX-DA@@@@
Ver.1.0
Version 1.0 or later
Version 1.05 or later
Version 1.06 or higher
* Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the
oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and
versions.
External Interface
Analog Output Unit
NX-DA@@@@
12mm Width
(B)
(C)
(A)
Symbol
(A)
(B)
(C)
Name
NX bus connector
Indicators
Terminal block
Function
This connector is used to connect each Unit.
The indicators show the current operating status of the Unit.
The terminal block is used to connect external devices.
The number of terminals depends on the type of Unit.
Terminal Blocks
(A)
(B)
A1
B1
A1
B1
A2
B2
A2
B2
A3
B3
A3
B3
A4
B4
A4
B4
A5
B5
A5
B5
A6
B6
A6
B6
A7
B7
A7
B7
A8
B8
A8
B8
(C)
12 mm width
8-terminal type
Symbol
Name
(A)
Terminal number
indications
(B)
(C)
Release holes
Terminal holes
12 mm width
12-terminal type
Function
Terminal numbers for which A to D indicate the column, and 1 to 8 indicate the line are displayed.
The terminal number is a combination of column and line, so A1 to A8 and B1 to B8 are displayed.
The terminal number indications are the same regardless of the number of terminals on the terminal block.
Insert a flat-blade screwdriver into these holes to connect and remove the wires.
The wires are inserted into these holes.
12
NX-DA
Applicable Terminal Blocks for Each Unit Model
Unit model
Model
NX-DA2@@@
NX-DA3@@@
NX-TBA082
NX-TBA122
No. of terminals
8
12
Terminal Blocks
Terminal number
indications
A/B
A/B
Ground terminal
mark
None
None
Terminal current
capacity
10 A
10 A
Applicable Wires
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tool are given in the following table.
Terminal types
Manufacturer
Terminals other
than ground
terminals
Phoenix Contact
Ground terminals
Terminals other
than ground
terminals
Weidmuller
Ferrule model
number
AI0,34-8
AI0,5-8
AI0,5-10
AI0,75-8
AI0,75-10
AI1,0-8
AI1,0-10
AI1,5-8
AI1,5-10
AI2,5-10
H0.14/12
H0.25/12
H0.34/12
H0.5/14
H0.5/16
H0.75/14
H0.75/16
H1.0/14
H1.0/16
H1.5/14
H1.5/16
Applicable wire
(mm2 (AWG))
Crimping tool
0.34 (#22)
0.5 (#20)
Phoenix Contact (The figure in parentheses is the applicable wire size.)
CRIMPFOX 6 (0.25 to 6 mm2, AWG24 to 10)
0.75 (#18)
1.0 (#18)
1.5 (#16)
2.0 *
0.14 (#26)
0.25 (#24)
0.34 (#22)
0.5 (#20)
Weidmuller (The figure in parentheses is the applicable wire size.)
PZ6 Roto (0.14 to 6 mm2, AWG 26 to 10)
0.75 (#18)
1.0 (#18)
1.5 (#16)
* Some AWG 14 wires exceed 2.0 mm2 and cannot be used in the screwless clamping terminal block.
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are achieved.
Finished Dimensions of Ferrules
8 to 10 mm
1.6 mm max. (except ground terminals)
2.4 mm max. (except ground terminals)
2.0 mm max. (ground terminals)
2.7 mm max. (ground terminals)
Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications.
Terminals
Classification
Current capacity
Wire type
Twisted wires
Plated
2 A max.
All terminals except
ground terminals
Ground terminals
Greater than
2 A and 4 A or less
Possible
Greater than 4 A
Possible *1
---
Possible
Solid wire
Unplated
Plated
Unplated
Possible
Possible
Possible
Not
Possible
Possible
Possible
*1
Not Possible
Possible
*2
Not
Possible
Possible
*2
Wire size
Conductor length
(stripping length)
0.08 to 1.5 mm2
AWG28 to 16
8 to 10 mm
2.0 mm2
9 to 10 mm
*1 Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires.
*2 With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire.
Conductor length (stripping length)
<Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules.
13
NX-DA
Dimensions
(Unit/mm)
Analog Output Unit
NX-DA@@@@
12 mm Width
14.1
12.0
0.55
1.5
100
1.5
104.5
65.2
71
80.1
Related Manuals
Cat. No.
W522
Model
number
Manual name
NX-AD@@@@
NX-series Analog I/O
NX-DA@@@@
Units User’s Manual
NX-TS@@@@
Application
Description
Learning how to use NX-series The hardware, setup methods, and functions of the NXAnalog I/O Units and
series Analog I/O Units and Temperature Input Units
Temperature Input Units
are described.
14
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is