NX-series Analog Input Unit
NX-AD
CSM_NX-AD_DS_E_2_5
Analog Inputs to meet all machine
control needs; from generalpurpose inputs to high-speed
synchronous, high-resolution units
• Analog Input Units for the NX-series modular I/O system.
• Connect to other NX-series I/O Units and EtherCAT
Coupler units using the high-speed NX-bus.
• Separate modules for voltage- and current inputs.
Features
•
•
•
•
•
•
•
Up to eight analog inputs per unit.
Free-Run refreshing or Synchronous I/O refreshing, can be selected for refreshing with the NX-series EtherCAT Coupler.
Input update cycles of 10μs per channel, and a resolution of 1/30000, ideal for high-speed measurement and, high-precision control.
All basic models are available as single-ended and differential-input types.
The screwless terminal block is detachable for easy commissioning and maintenance.
Screwless push-in terminal block significantly reduces wiring work.
All models are just 12 mm wide, saving space in your cabinet.
System Configuration
Sysmac Studio
Support Software
EtherCAT master*
NJ/NX-series CPU Unit
Connection to peripheral USB port
or built-in EtherNet/IPTM port on
NJ/NX-series CPU Unit
Built-in EtherCAT port
Sysmac Studio
Support Software
●EtherCAT Slave Terminal
Communications cable
Ethernet cables
Peripheral USB port.
NX Series
EtherCAT Coupler Unit
NX-ECC@@@
Connection to peripheral USB
port on EtherCAT Coupler Unit
NX Units
End Cover
* OMRON CJ1W-NC@81/@82 Position Control Units cannot be connected to the EtherCAT Slave Terminal even though they support EtherCAT.
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
EtherCAT® is a registered trademark of Beckhoff Automation GmbH for their patented technology. Other company names and product names in
this document are the trademarks or registered trademarks of their respective companies.
1
NX-AD
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1:
cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, CE: EC Directives,and KC: KC Registration.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Analog Input Unit
Specification
Unit
type
Product
Name
Capacity
Input
range
Resolution
Conversion
value,
decimal
number
(0 to 100%)
Over all
accuracy
(25°C)
1/8000
-4000 to
4000
Singleended input
±0.2%
(full scale) Differential
Input
250 μs/
point
Free-Run
refreshing
1/30000
-15000 to
15000
±0.1%
Differential
(full scale) Input
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
1/8000
-4000 to
4000
Singleended input
±0.2%
(full scale) Differential
Input
250 μs/
point
Free-Run
refreshing
Input
method
Conversion
Input
time
impedance
2 points
Voltage
Input
Unit
4 points
-10 to
+10V
1MΩ min.
1/30000
-15000 to
15000
±0.1%
Differential
(full scale) Input
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
1/8000
-4000 to
4000
Singleended input
±0.2%
(full scale) Differential
Input
250 μs/
point
Free-Run
refreshing
-15000 to
15000
±0.1%
Differential
(full scale) Input
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
0 to 8000
Singleended input
±0.2%
(full scale) Differential
Input
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
8 points
1/30000
NX
Series
Analog
Input
Unit
1/8000
2 points
1/30000
Current
Input
Unit
1/8000
4 points
I/O
refreshing
method
±0.1%
Differential
0 to 30000
(full scale) Input
0 to 8000
4 to
20mA
1/30000
1/8000
Singleended input
±0.2%
(full scale) Differential
Input
±0.1%
Differential
0 to 30000
(full scale) Input
0 to 8000
Singleended input
±0.2%
(full scale) Differential
Input
250Ω
250 μs/
point
Free-Run
refreshing
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
250 μs/
point
Free-Run
refreshing
8 points
85Ω
1/30000
±0.1%
Differential
0 to 30000
(full scale) Input
10 μs/
point
Selectable
Synchronous
I/O refreshing
or Free-Run
refreshing
NX Unit
power
consum
ption
Model
1.05W
max.
NX-AD2603
1.05W
max.
NX-AD2604
1.05W
max.
NX-AD2608
1.10W
max.
NX-AD3603
1.10W
max.
NX-AD3604
1.10W
max.
NX-AD3608
1.15W
max.
NX-AD4603
1.15W
max.
NX-AD4604
1.15W
max.
NX-AD4608
0.90W
max.
NX-AD2203
0.90W
max.
NX-AD2204
0.90W
max.
NX-AD2208
0.90W
max.
NX-AD3203
0.90W
max.
NX-AD3204
0.95W
max.
NX-AD3208
1.05W
max.
NX-AD4203
1.05W
max.
NX-AD4204
1.10W
max.
NX-AD4208
Stand
ards
UC1,
N, L,
CE,
KC
2
NX-AD
Option
Product Name
Unit/Terminal Block Coding Pins
Specification
Model
For 10 Units
(Terminal Block: 30 pins, Unit: 30 pins)
Standards
NX-AUX02
---
Specification
Product Name
No. of
terminals
Terminal
number
indications
Ground
terminal
mark
Terminal
current
capacity
8
Terminal Block
12
Model
Standards
NX-TBA082
A/B
None
10 A
16
NX-TBA122
---
NX-TBA162
Accessories
Not included.
General Specification
Item
Specification
Enclosure
Mounted in a panel
Grounding method
Ground to 100 Ω or less
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage temperature
−25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Operating
Noise immunity
environment
Overvoltage category
2 kV on power supply line (Conforms to IEC61000-4-4.)
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity level
Zone B
Vibration resistance
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each
in X, Y, and Z directions
(10 sweeps of 10 min each = 100 min total)
Shock resistance
IConforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
Applicable standards
cULus: Listed UL508 and ANSI/ISA 12.12.01
EC: EN 61131-2 and C-Tick, KC Registration, NK, LR
3
NX-AD
Analog Input Unit Specifications
Analog Input Unit (voltage input type) 2 points NX-AD2603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2603
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.05 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
Terminal block
Input1+ to 2+
AMP
1 MΩ
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
IOV
IOV
IOG
IOG
Voltage Input Unit
NX-AD2603
A1
B1
Input1+ Input2+
Input +
24 V (Sensor power supply +)
Terminal connection
diagram
0 V (Sensor power supply − / Input −)
IOV
24 VDC
Three-wire sensor
A8
Input disconnection
detection
IOV
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
B8
A8
B8
The NC terminal is not connected to the internal circuit.
Not supported.
4
NX-AD
Analog Input Unit (voltage input type) 2 points NX-AD2604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2604
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.05 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 2+
AMP
Terminal block
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD2604
A1
B1
Input1+ Input2+
Input +
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
5
NX-AD
Analog Input Unit (voltage input type) 2 points NX-AD2608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD2608
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.05 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 2+
AMP
Terminal block
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD2608
A1
B1
Input +
Input1+ Input2+
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
B8
AG terminal is connected to 0 V of analog circuit inside the Unit.
It is not necessary to wire AG terminal normally.
Not supported.
6
NX-AD
Analog Input Unit (voltage input type) 4 points NX-AD3603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3603
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.10 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
Terminal block
Input1+ to 4+
AMP
1MΩ
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
IOG
Voltage Input Unit
NX-AD3603
A1
IOV
B1
Input1+ Input2+
IOG
24 VDC
IOV
IOV
IOG
IOG
Input +
24 V (Sensor power supply +)
0 V (Sensor power supply − / Input −)
Input3+ Input4+
IOV
IOG
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
IOV
IOV
IOV
IOG
IOG
Three-wire sensor
IOG
B8
A8
B8
Not supported.
7
NX-AD
Analog Input Unit (voltage input type) 4 points NX-AD3604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3604
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.10 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 4+
AMP
Terminal block
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD3604
A1
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Terminal connection
diagram
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
8
NX-AD
Analog Input Unit (voltage input type) 4 points NX-AD3608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD3608
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.10 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 4+
AMP
Terminal block
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD3608
A1
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Terminal connection
diagram
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Not supported.
9
NX-AD
Analog Input Unit (voltage input type) 8 points NX-AD4603
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4603
Capacity
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOG: 0.1 A/terminal max.
NX Unit power
consumption
1.15 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 8+
AMP
1 MΩ
Terminal block
IOG
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
I/O Power Supply
Connection Unit
A1
IOV
IOG
IOG
IOV
IOV
IOG
IOG
24 VDC
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
B8
A8
B1
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
IOV
Voltage Input Unit
NX-AD4603
A1
B1
Input1+ Input2+
IOG
Input +
IOG
24 V (Sensor power supply +)
0 V (Sensor power supply − / I
Input3+ Input4+
IOG
IOG
Three-wire sensor
Input5+ Input6+
IOG
IOG
Input7+ Input8+
IOG
B8
A8
IOG
B8
Not supported.
10
NX-AD
Analog Input Unit (voltage input type) 8 points NX-AD4604
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4604
Capacity
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.15 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 8+
Terminal block
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD4604
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Not supported.
11
NX-AD
Analog Input Unit (voltage input type) 8 points NX-AD4608
Unit name
Analog Input Unit (voltage input type)
Model
NX-AD4608
Capacity
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
-10 to +10 V
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±15 V
Input impedance
1 MΩ min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.15 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 8+
Terminal block
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Voltage Input Unit
NX-AD4604
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Not supported.
12
NX-AD
Analog Input Unit (current input type) 2 points NX-AD2203
Unit name
Analog Input Unit (current input type)
Model
NX-AD2203
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
0.90 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
Terminal block
Input1+ to 2+
AMP
250 Ω
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG: Analog circuit internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
A1
B1
Current Input Unit
NX-AD2203
A1
B1
IOV
IOV
IOG
IOG
IOV
IOV
IOV
IOV
IOG
IOG
IOG
IOG
NC
NC
Input1+ Input2+
Input +
24 V (Sensor power supply +)
Terminal connection
diagram
Three-wire sensor
A8
Input disconnection
detection
0 V (Sensor power supply − / Input −)
24 VDC
B8
A8
B8
The NC terminal is not connected to the internal circuit.
Supported.
13
NX-AD
Analog Input Unit (current input type) 2 points NX-AD2204
Unit name
Analog Input Unit (current input type)
Model
NX-AD2204
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
0.90 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 2+
250 Ω
Terminal block
AMP
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD2204
A1
B1
Input1+ Input2+
Input +
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
14
NX-AD
Analog Input Unit (current input type) 2 points NX-AD2208
Unit name
Analog Input Unit (current input type)
Model
NX-AD2208
Capacity
2 points
External connection
terminals
Screwless clamping terminal block (8
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
0.90 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 2+
250 Ω
Terminal block
AMP
Input1− to 2−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD2208
A1
B1
Input1+ Input2+
Input +
Input −
Input1− Input2−
Terminal connection
diagram
AG
AG
NC
NC
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
15
NX-AD
Analog Input Unit (current input type) 4 points NX-AD3203
Unit name
Analog Input Unit (current input type)
Model
NX-AD3203
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.,
IOG: 0.1 A/terminal max.
NX Unit power
consumption
0.90 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
Terminal block
Input1+ to 4+
AMP
250 Ω
Circuit layout
IOG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
IOG
Current Input Unit
NX-AD3203
A1
IOV
B1
Input1+ Input2+
IOG
24 VDC
Input +
IOV
IOV
24 V (Sensor power supply +)
IOG
IOG
0 V (Sensor power supply − / Input −)
Input3+ Input4+
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG: Analog circuit internal GND
I/O power supply +
IOV
IOV
IOG
IOG
B8
A8
IOV
IOV
IOG
IOG
Three-wire sensor
B8
Supported.
16
NX-AD
Analog Input Unit (current input type) 4 points NX-AD3204
Unit name
Analog Input Unit (current input type)
Model
NX-AD3204
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω min.
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
0.90 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 4+
250 Ω
Terminal block
AMP
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG: Analog circuit
internal GND
AG
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD3204
A1
Terminal connection
diagram
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
AG terminal is connected to 0 V of analog circuit inside the Unit.
B8 It is not necessary to wire AG terminal normally.
Supported.
17
NX-AD
Analog Input Unit (current input type) 4 points NX-AD3208
Unit name
Analog Input Unit (current input type)
Model
NX-AD3208
Capacity
4 points
External connection
terminals
Screwless clamping terminal block (12
terminals)
I/O refreshing method
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Indicator
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
250 Ω min.
Resolution
1/30000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.1% (full scale)
Conversion time
10 μs/point
±0.2% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
0.95 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 4+
250 Ω
Terminal block
AMP
Input1− to 4−
510 KΩ
Circuit layout
510 KΩ
AG
AG: Analog circuit
internal GND
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD3208
A1
B1
Input1+ Input2+
Input +
Input1− Input2−
Input −
Input3+ Input4+
Terminal connection
diagram
Input3− Input4−
AG
AG
AG
AG
A8
Input disconnection
detection
B8
AG terminal is connected to 0 V of analog circuit inside the Unit.
It is not necessary to wire AG terminal normally.
Supported.
18
NX-AD
Analog Input Unit (current input type) 8 points NX-AD4203
Unit name
Analog Input Unit (current input type)
Model
NX-AD4203
Capacity
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Single-ended input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
85 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
Supply from the NX bus
Current capacity of I/O
power supply terminal
IOV: 0.1 A/terminal max.
NX Unit power
consumption
1.05 W max.
I/O current consumption No consumption
Weight
70 g max.
IOV
Terminal block
Input1+ to 8+
AMP
AG: Analog circuit internal GND
85 Ω
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
I/O power supply +
I/O power supply −
I/O power supply −
A1
B1
IOV
I/O Power Supply
Connection Unit
A1
IOV
IOG
IOG
IOV
IOV
IOG
IOG
24 VDC
A8
Input disconnection
detection
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Additional I/O
Power Supply Unit
Terminal connection
diagram
AG
I/O power supply +
B8
A8
B1
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
IOG
Voltage Input Unit
NX-AD4203
A1
B1
Input1+ Input2+
IOV
Input +
IOV
24 V (Sensor power supply +)
0 V (Sensor power supply − / Input −)
Input3+ Input4+
IOV
IOV
Three-wire Sensor
Input5+ Input6+
IOV
IOV
Input7+ Input8+
IOV
B8
A8
IOV
B8
Supported.
19
NX-AD
Analog Input Unit (current input type) 8 points NX-AD4204
Unit name
Analog Input Unit (current input type)
Model
NX-AD4204
Capacity
8 points
External connection
terminals
Screwless clamping terminal block (16
terminals)
I/O refreshing method
Free-Run refreshing
Input method
Differential Input
Input range
4 to 20 mA
Input conversion range
-5 to 105% (full scale)
Absolute maximum
rating
±30 mA
Input impedance
85 Ω
TS indicator
Indicator
Resolution
1/8000 (full scale)
25°C
Overall
accuracy 0 to 55°C
±0.2% (full scale)
Conversion time
250 μs/point
±0.4% (full scale)
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
I/O power supply
method
No supply
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power
consumption
1.05 W max.
I/O current consumption No consumption
Weight
70 g max.
Input1+ to 8+
Terminal block
85 Ω
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit
internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD4204
A1
B1
Input1+ Input2+
Input1− Input2−
Terminal connection
diagram
Input +
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Supported.
20
NX-AD
Analog Input Unit (current input type) 8 points NX-AD4208
Unit name
Analog Input Unit (current input type)
Capacity
I/O refreshing method
Indicator
Model
External connection
8 points
terminals
Selectable Synchronous I/O refreshing or Free-Run refreshing
TS indicator
Input method
Input range
Input conversion range
Absolute maximum
rating
Input impedance
Resolution
25°C
Overall
accuracy 0 to 55°C
Conversion time
NX-AD4208
Screwless clamping terminal block (16
terminals)
Differential Input
4 to 20 mA
-5 to 105% (full scale)
±30 mA
85 Ω
1/30000 (full scale)
±0.1% (full scale)
±0.2% (full scale)
10 μs/point
Between the input and the NX bus: Power
= Transformer, Signal = Digital isolator (no
isolation between inputs)
510 VAC between isolated circuits for 1
minute at a leakage current of 5 mA max.
Dimensions
12 (W) x 100 (H) x 71 (D)
Isolation method
Insulation resistance
20 MΩ min. between isolated circuits (at
100 VDC)
Dielectric strength
No supply
Current capacity of I/O
power supply terminal
1.10 W max.
I/O current consumption No consumption
I/O power supply
method
NX Unit power
consumption
Weight
Without I/O power supply terminals
70 g max.
Input1+ to 8+
Terminal block
85 Ω
AMP
Input1− to 8−
510 KΩ
510 KΩ
Circuit layout
AG
NX bus
connector
(left)
Installation orientation
and restrictions
AG
AG: Analog circuit
internal GND
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
NX bus
connector
(right)
Installation orientation: Possible in 6 orientations.
Restrictions: No restrictions
Current Input Unit
NX-AD4208
A1
B1
Input1+ Input2+
Input1− Input2−
Terminal connection
diagram
Input +
Input −
Input3+ Input4+
Input3− Input4−
Input5+ Input6+
Input5− Input6−
Input7+ Input8+
Input7− Input8−
A8
Input disconnection
detection
B8
Supported.
Version Information
NX Unit
Corresponding unit versions/versions *
EtherCAT Coupler Units
Model
Unit Version
NJ/NX-series CPU Units
Sysmac Studio
NX-ECC20@
NX-AD@@@@
Ver.1.0
Version 1.0 or later
Version 1.05 or later
Version 1.06 or higher
* Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the
oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and
versions.
21
NX-AD
External Interface
Analog Input Unit
NX-AD@@@@
12mm Width
(B)
(C)
(A)
Symbol
Name
Function
(A)
NX bus connector
(B)
Indicators
The indicators show the current operating status of the Unit.
Terminal block
The terminal block is used to connect external devices.
The number of terminals depends on the type of Unit.
(C)
This connector is used to connect each Unit.
Terminal Blocks
(A)
(B)
A1
B1
A1
B1
A1
B1
A2
B2
A2
B2
A2
B2
A3
B3
A3
B3
A3
B3
A4
B4
A4
B4
A4
B4
A5
B5
A5
B5
A5
B5
A6
B6
A6
B6
A6
B6
A7
B7
A7
B7
A7
B7
A8
B8
A8
B8
A8
B8
(C)
12 mm width
8-terminal type
Symbol
(A)
12 mm width
12-terminal type
12 mm width
16-terminal type
Name
Function
Terminal number
indications
Terminal numbers for which A to D indicate the column, and 1 to 8 indicate the line are displayed.
The terminal number is a combination of column and line, so A1 to A8 and B1 to B8 are displayed.
The terminal number indications are the same regardless of the number of terminals on the terminal block.
(B)
Release holes
Insert a flat-blade screwdriver into these holes to connect and remove the wires.
(C)
Terminal holes
The wires are inserted into these holes.
Applicable Terminal Blocks for Each Unit Model
Terminal Blocks
Unit model
Model
No. of terminals
Terminal number
indications
Ground terminal
mark
Terminal current
capacity
NX-AD2@@@
NX-TBA082
8
A/B
None
NX-AD3@@@
NX-TBA122
12
A/B
None
10 A
10 A
NX-AD4@@@
NX-TBA162
16
A/B
None
10 A
22
NX-AD
Applicable Wires
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tool are given in the following table.
Terminal types
Manufacturer
Terminals other
than ground
terminals
Phoenix Contact
Ferrule model
number
Applicable wire
(mm2 (AWG))
AI0,34-8
0.34 (#22)
AI0,5-8
0.5 (#20)
Crimping tool
Phoenix Contact (The figure in parentheses is the applicable wire size.)
CRIMPFOX 6 (0.25 to 6 mm2, AWG24 to 10)
AI0,5-10
AI0,75-8
0.75 (#18)
AI0,75-10
AI1,0-8
1.0 (#18)
AI1,0-10
AI1,5-8
1.5 (#16)
AI1,5-10
Ground terminals
Terminals other
than ground
terminals
Weidmuller
AI2,5-10
2.0 *
H0.14/12
0.14 (#26)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
Weidmuller (The figure in parentheses is the applicable wire size.)
PZ6 Roto (0.14 to 6 mm2, AWG 26 to 10)
H0.5/16
H0.75/14
0.75 (#18)
H0.75/16
H1.0/14
1.0 (#18)
H1.0/16
H1.5/14
1.5 (#16)
H1.5/16
* Some AWG 14 wires exceed 2.0 mm2 and cannot be used in the screwless clamping terminal block.
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that the following processed dimensions are
achieved.
Finished Dimensions of Ferrules
8 to 10 mm
1.6 mm max. (except ground terminals)
2.4 mm max. (except ground terminals)
2.0 mm max. (ground terminals)
2.7 mm max. (ground terminals)
Using Twisted Wires/Solid Wires
If you use the twisted wires or the solid wires, use the following table to determine the correct wire specifications.
Terminals
Classification
Current capacity
Wire type
Twisted wires
Plated
2 A max.
All terminals except
ground terminals
Ground terminals
Greater than
2 A and 4 A or less
Possible
Greater than
4A
Possible
*1
---
Possible
Solid wire
Unplated
Plated
Unplated
Possible
Possible
Possible
Not
Possible
Possible
Possible
*1
Not
Possible
Possible
*2
Not
Possible
Possible
*2
Wire size
Conductor length
(stripping length)
0.08 to 1.5 mm2
AWG28 to 16
8 to 10 mm
2.0 mm2
9 to 10 mm
*1 Secure wires to the screwless clamping terminal block. Refer to the Securing Wires in the USER'S MANUAL for how to secure wires.
*2 With the NX-TB@@@1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid wire.
Conductor length (stripping length)
<Additional Information> If more than 2 A will flow on the wires, use plated wires or use ferrules.
23
NX-AD
Dimensions
(Unit/mm)
Analog Input Unit
NX-AD@@@@
12 mm Width
14.1
12.0
0.55
1.5
100
1.5
104.5
65.2
71
80.1
Related Manuals
Cat. No.
W522
Model
number
Manual name
NX-AD@@@@
NX-series Analog I/O
NX-DA@@@@
Units User’s Manual
NX-TS@@@@
Application
Description
Learning how to use NX-series The hardware, setup methods, and functions of the NXAnalog I/O Units and
series Analog I/O Units and Temperature Input Units
Temperature Input Units
are described.
24
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.