NX-series Digital Mixed I/O Units
NX-MD
CSM_NX-MD_DS_E_2_2
Digital Mixed I/O Units for High speed
Synchronous Control
• DC Input/Transistor Output Units for the NX-series modular
I/O system.
• Connect to other NX-series I/O Units and EtherCAT
Coupler units using the high-speed NX-bus.
• One Unit enables synchronous Units to update the status of
input devices to the controller and the output status of
synchronous Units according to the controller's instructions
every EtherCAT cycle.
Features
• High-speed I/O refreshing is possible by connecting with the NX-series EtherCAT Coupler.
• Output refreshing can be synchronized with the control cycle of the Controller. (Synchronous refreshing)
• Connector Types significantly reduces wiring work.
System Configuration
Sysmac Studio
Support Software
Connection to peripheral USB port
or built-in EtherNet/IPTM port on
NJ/NX-series CPU Unit
EtherCAT master*
NJ/NX-series CPU Unit or master from
another manufacturer
Built-in EtherCAT port
Sysmac Studio
Support Software
●EtherCAT Slave Terminal
Communications cable
Ethernet cables
Peripheral USB port.
NX Series
EtherCAT Coupler Unit
NX-ECC@@@
Connection to peripheral USB
port on EtherCAT Coupler Unit
.xml
ESI files
NX Units
End Cover
* Refer to Versions information on the unit versions of CPU Units when you connect an EtherCAT Slave Terminal to the built-in EtherCAT port on
an OMRON NJ/NX-series CPU Unit. OMRON CJ1W-NC@81/@82 Position Control Units cannot be connected to the EtherCAT Slave Terminal
even though they support EtherCAT.
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
EtherCAT® is a registered trademark of Beckhoff Automation GmbH for their patented technology. EtherNet/IPTM is the trademarks of ODVA.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
1
NX-MD
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1:
cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, CE: EC Directives,and KC: KC Registration.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Digital Mixed I/O Unit
● DC Input/Transistor Output Units (MIL Connector, 30 mm Width)
Specification
Product
Name
Unit type
Number of
points
Outputs:
16 points
Inputs:
16 points
Rated
voltage
I/O refreshing
method
UC1, CE,
KC
Outputs:
0.5 ms max./
1.0 ms max.
Inputs:
20 μs max./
400 μs max.
Outputs:
24 VDC
Inputs:
24 VDC
Standards
NX-MD6121-5
Switching
Synchronous
I/O refreshing and
Free-Run
refreshing
0.5 A/point,
2 A/Unit
Outputs: PNP
Inputs: For both
NPN/PNP
Model
ON/OFF
response time
Outputs:
0.1 ms max./
0.8 ms max.
Inputs:
20 μs max./
400 μs max.
Outputs:
12 to 24 VDC
Inputs:
24 VDC
Outputs: NPN
Inputs: For both
NPN/PNP
DC Input/
Transistor
Output Units
NX Series
Digital
Mixed I/O
Units
Internal I/O
common
Maximum
value of load
current
NX-MD6256-5
● DC Input/Transistor Output Units (Fujitsu Connector, 30 mm Width)
Specification
Product
Name
Unit type
Number of
points
Internal I/O
common
Maximum
value of load
current
Rated
voltage
I/O refreshing
method
ON/OFF
response time
Model
Standards
Transistor
Output Units
NX Series
Digital
Output
Units
Outputs:
16 points
Inputs:
16 points
Outputs: NPN
Inputs: For both
NPN/PNP
0.5 A/point,
2 A/Unit
Switching
Outputs:
Synchronous
12 to 24 VDC
I/O refreshing and
Inputs:
Free-Run
24 VDC
refreshing
Outputs:
0.1 ms max./
0.8 ms max.
Inputs:
20 μs max./
400 μs max.
NX-MD6121-6
UC1, CE,
KC
Accessories
Not included.
2
NX-MD
General Specification
Item
Grounding method
Operating
environment
Specification
Mounted in a panel
Enclosure
Ground to 100 Ω or less
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage temperature
−25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise immunity
2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage category
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity level
Zone B
Vibration resistance *1
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each
in X, Y, and Z directions
(10 sweeps of 10 min each = 100 min total)
Shock resistance *1
Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
cULus: Listed UL508 and ANSI/ISA 12.12.01
EC: EN 61131-2 and C-Tick, KC: KC Registration, NK, LR
*1 For the Relay Output Unit, refer to the Digital Input Unit Specifications.
*2 Refer to the OMRON website (http://www.ia.omron.com/) or consult your OMRON representative for the most recent applicable standards for
each model.
Applicable standards *2
3
NX-MD
Digital Mixed I/O Unit Specifications
● DC Input/Transistor Output Units (MIL Connector, 30 mm Width)
NX-MD6121-5
Unit name
DC Input/Transistor Output Unit
Model
NX-MD6121-5
Number of points
16 inputs/16 outputs
External connection
terminals
2 MIL connectors (20 terminals)
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Output
section
(CN1)
Internal I/O
common
NPN
Internal I/O
common
For both NPN/PNP
Rated voltage
12 to 24 VDC
Rated input
voltage
24 VDC (15 to 28.8 VDC)
Operating load
voltage range
10.2 to 28.8 VDC
Input current
7 mA typical (at 24 VDC)
Maximum value
of load current
0.5 A/point, 2 A/Unit
ON voltage/ON
current
15 VDC min./3 mA min. (between COM and
each signal)
Maximum inrush
current
4.0 A/point, 10 ms max.
OFF voltage/OFF
current
5 VDC max./1 mA max. (between COM and
each signal)
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
Input
section
(CN2)
ON/OFF response
20 μs max./400 μs max.
time
Input filter time
ON/OFF response
0.1 ms max./0.8 ms max.
time
TS indicator, I/O indicators
Indicators
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms,
4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms
Dimensions
30 (W) x 100 (H) x 71 (D)
Isolation method
Photocoupler isolation
Insulation resistance
20 MΩ min. between isolated circuits
(at 100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1 minute
at a leakage current of 5 mA max.
I/O power supply method
Supply from external source
Current capacity of I/O power
supply terminal
Without I/O power supply terminals
NX Unit power consumption
0.70 W max.
Current consumption from
I/O power supply
30 mA max.
Weight
105 g max.
CN1 (left) output circuit
Internal circuits
+V0
+V0
Connector
COM0
COM0
I/O power
supply + NX bus
connector
I/O power (right)
supply −
I/O power
NX bus
connector supply +
I/O power
(left)
supply −
CN2 (right) input circuit
Input indicator
Connector
IN0
to
IN15
COM1
COM1
I/O power
NX bus
connector supply +
I/O power
(left)
supply −
3.3 kΩ
Internal circuits
Circuit layout
OUT0
to OUT15
I/O power
supply + NX bus
connector
I/O power (right)
supply −
4
NX-MD
Installation orientation: Possible in 6 orientations.
Restrictions: As shown in the following.
Installation orientation and
restrictions
Number of simultaneously ON input points
• For upright installation
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 35°C
16 points at 45°C
16
13 points at 55°C
12
9 points at 55°C
8
I/O power supply voltage
24 V
4
28.8 V
0
0
10
20
30
40 45 50 55 60
Ambient temperature
(°C)
Number of simultaneously ON input points
• For any installation other than upright
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 40°C
16 points at 25°C
16
12
8
4
0
I/O power supply
voltage
24 V
5 points at 55°C
28.8 V
3 points at 55°C
0
10
20
30
40 45 50 55 60
Ambient temperature
(°C)
CN1 (left) output terminal
Signal Connector Signal
name
pin
name
OUT0 20 19 OUT8
L
OUT1 18 17 OUT9
L
OUT2 16 15 OUT10
L
OUT3 14 13 OUT11
L
OUT4 12 11 OUT12
L
OUT5 10 9 OUT13
L
OUT6 8 7 OUT14
L
OUT7 6 5 OUT15
L
COM0 4 3 COM0
+V0 2 1 +V0
L
L
L
L
L
L
L
L
12 to 24 VDC
Terminal connection
diagram
• Be sure to wire both pins 3 and 4 (COM0) of CN1.
• Be sure to wire both pins 1 and 2 (+V0) of CN1.
CN2 (right) input terminal
24 VDC
Signal Connector Signal
name
pin
name
NC 1 2 NC
COM1 3 4 COM1
IN15 5 6 IN07
IN14 7 8 IN06
IN13 9 10 IN05
IN12 11 12 IN04
IN11 13 14 IN03
IN10 15 16 IN02
IN09 17 18 IN01
IN08 19 20 IN00
• The polarity of the input power supply of CN2 can be connected in either direction.
• Be sure to wire both pins 3 and 4 (COM1) of CN2, and set the same polarity for both pins.
Disconnection/Short-circuit
detection
Not supported.
Protective function
Not supported.
5
NX-MD
NX-MD6256-5
Unit name
DC Input/Transistor Output Unit
Model
NX-MD6256-5
Number of points
16 inputs/16 outputs
External connection
terminals
2 MIL connectors (20 terminals)
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Output
section
(CN1)
Internal I/O
common
PNP
Internal I/O
common
For both NPN/PNP
Rated voltage
24 VDC
Rated input
voltage
24 VDC (15 to 28.8 VDC)
Operating load
voltage range
20.4 to 28.8 VDC
Input current
7 mA typical (at 24 VDC)
Maximum value
of load current
0.5 A/point, 2 A/Unit
ON voltage/ON
current
15 VDC min./3 mA min. (between COM and
each signal)
Maximum inrush
current
4.0 A/point, 10 ms max.
OFF voltage/OFF
current
5 VDC max./1 mA max. (between COM and
each signal)
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
Input
section
(CN2)
ON/OFF response
20 μs max./400 μs max.
time
Input filter time
ON/OFF response
0.5 ms max./1.0 ms max.
time
TS indicator, I/O indicators
Indicators
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms,
4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms
Dimensions
30 (W) x 100 (H) x 71 (D)
Isolation method
Photocoupler isolation
Insulation resistance
20 MΩ min. between isolated circuits
(at 100 VDC)
Dielectric strength
510 VAC between isolated circuits for 1 minute
at a leakage current of 5 mA max.
I/O power supply method
Supply from external source
Current capacity of I/O power
supply terminal
Without I/O power supply terminals
NX Unit power consumption
0.75 W max.
Current consumption from I/
O power supply
40 mA max.
Weight
110 g max.
Connector
OUT0
to OUT15
0V0
0V0
I/O power
supply + NX bus
connector
I/O power (right)
supply −
I/O power
NX bus
connector supply +
I/O power
(left)
supply −
CN2 (right) input circuit
Input indicator
Connector
IN0
to
IN15
COM1
COM1
I/O power
NX bus
connector supply +
I/O power
(left)
supply −
3.3 kΩ
Internal circuits
Circuit layout
COM0 (+V)
COM0 (+V)
Short-circuit
protection
Internal circuits
CN1 (left) output circuit
I/O power
supply + NX bus
connector
I/O power (right)
supply −
6
NX-MD
Installation orientation: Possible in 6 orientations.
Restrictions: As shown in the following.
Installation orientation and
restrictions
Number of simultaneously ON input points
• For upright installation
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 35°C
16 points at 45°C
16
13 points at 55°C
12
9 points at 55°C
8
I/O power supply voltage
24 V
4
28.8 V
0
0
10
20
30
40 45 50 55 60
Ambient temperature
(°C)
Number of simultaneously ON input points
• For any installation other than upright
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 40°C
16 points at 25°C
16
12
8
4
0
0
I/O power supply
voltage
24 V
5 points at 55°C
28.8 V
3 points at 55°C
10
20
30
40 45 50 55 60
Ambient temperature
(°C)
CN1 (left) output terminal
Signal Connector Signal
name
pin
name
OUT0 20 19 OUT8
L
OUT1 18 17 OUT9
L
OUT2 16 15 OUT10
L
OUT3 14 13 OUT11
L
OUT4 12 11 OUT12
L
OUT5 10 9 OUT13
L
OUT6 8 7 OUT14
L
OUT7 6 5 OUT15
L
COM0 (+V) 4 3 COM0 (+V)
0V0 2 1 0V0
L
L
L
L
L
L
L
L
24 VDC
Terminal connection
diagram
• Be sure to wire both pins 3 and 4 (COM0 (+V)) of CN1.
• Be sure to wire both pins 1 and 2 (0V0) of CN1.
CN2 (right) input terminal
24
VDC
Signal Connector Signal
name
pin
name
NC 1 2
NC
COM1 3 4
COM1
IN15 5 6
IN07
IN14 7 8
IN06
IN13 9 10 IN05
IN12 11 12 IN04
IN11 13 14 IN03
IN10 15 16 IN02
IN09 17 18 IN01
IN08 19 20 IN00
• The polarity of the input power supply of CN2 can be connected in either direction.
• Be sure to wire both pins 3 and 4 (COM1) of CN2, and set the same polarity for both pins.
Disconnection/Short-circuit
detection
Not supported.
Protective function
With load short-circuit protection.
7
NX-MD
● DC Input/Transistor Output Units (Fujitsu Connector, 30 mm Width)
NX-MD6121-6
Unit name
DC Input/Transistor Output Unit
Model
NX-MD6121-6
Number of points
16 inputs/16 outputs
External connection
terminals
2 Fujitsu connectors (24 terminals)
I/O refreshing method
Switching Synchronous I/O refreshing and Free-Run refreshing
Output
section
(CN1)
Internal I/O
common
NPN
Internal I/O
common
For both NPN/PNP
Rated voltage
12 to 24 VDC
Rated input
voltage
24 VDC (15 to 28.8 VDC)
Operating load
voltage range
10.2 to 28.8 VDC
Input current
7 mA typical (at 24 VDC)
Maximum value
of load current
0.5 A/point, 2 A/Unit
ON voltage/ON
current
15 VDC min./3 mA min. (between COM and each
signal)
Maximum inrush
current
4.0 A/point, 10 ms max.
OFF voltage/OFF
current
5 VDC max./1 mA max. (between COM and each
signal)
Leakage current
0.1 mA max.
ON/OFF
response time
20 μs max./400 μs max.
Input filter time
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms,
4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256 ms
Input
section
(CN2)
Residual voltage 1.5 V max.
ON/OFF
response time
0.1 ms max./0.8 ms max.
TS indicator, I/O indicators
Indicators
Dimensions
30 (W) x 100 (H) x 71 (D)
Isolation method
Photocoupler isolation
Insulation resistance
20 MΩ min. between isolated circuits (at 100
VDC)
Dielectric strength
510 VAC between isolated circuits for 1 minute at
a leakage current of 5 mA max.
I/O power supply method
Supply from external source
Current capacity of I/O
power supply terminal
Without I/O power supply terminals
NX Unit power consumption 0.70 W max.
Current consumption from
I/O power supply
30 mA max.
Weight
95 g max.
CN1 (left) output circuit
+V0
Internal circuits
+V0
Connector
COM0
COM0
I/O power
supply +
I/O power
supply −
I/O power
supply +
I/O power
supply −
NX bus
connector
(right)
CN2 (right) input circuit
Input indicator
3.3 kΩ
IN0
to
IN15
Connector
COM1
NX bus
connector
(left)
COM1
I/O power
supply +
I/O power
supply −
Internal circuits
Circuit layout
NX bus
connector
(left)
OUT0
to OUT15
I/O power
supply +
I/O power
supply −
NX bus
connector
(right)
8
NX-MD
Installation orientation: Possible in 6 orientations.
Restrictions: As shown in the following.
• For upright installation
16 points at 35°C
16 points at 45°C
16
13 points at 55°C
12
9 points at 55°C
8
I/O power supply voltage
24 V
4
28.8 V
0
0
10
20
30
40 45 50 55 60
Ambient temperature
(°C)
• For any installation other than upright
Number of simultaneously ON input points vs.
Ambient temperature characteristic
Number of simultaneously ON input points
Installation orientation and
restrictions
Number of simultaneously ON input points
Number of simultaneously ON input points vs.
Ambient temperature characteristic
16 points at 40°C
16 points at 25°C
16
12
I/O power supply
voltage
8
5 points at 55°C
24 V
4
28.8 V
0
0
10
3 points at 55°C
20
30
40 45 50 55 60
Ambient temperature
(°C)
9
NX-MD
CN1 (left) output terminal
Signal name
Connector
Signal name
pin
B
A
NC B12 A12 NC
NC B11 A11 NC
+V0 B10 A10 +V0
L
L
L
L
L
L
L
L
COM0
B9
A9
COM0
OUT15
B8
A8
OUT7
OUT14
B7
A7
OUT6
OUT13
B6
A6
OUT5
OUT12
B5
A5
OUT4
OUT11
B4
A4
OUT3
OUT10
B3
A3
OUT2
OUT9
B2
A2
OUT1
OUT8
B1
A1
OUT0
L
L
L
L
L
L
L
L
12 to 24 VDC
Terminal connection
diagram
• Be sure to wire both pins A9 and B9 (COM0) of CN1.
• Be sure to wire both pins A10 and B10 (+V0) of CN1.
CN2 (right) input terminal
Signal name
Connector
Signal name
pin
A
B
IN0
A1
B1
IN8
IN1
A2
B2
IN9
IN2
A3
B3
IN10
IN3
A4
B4
IN11
IN4
A5
B5
IN12
IN5
A6
B6
IN13
IN6
A7
B7
IN14
IN7
A8
B8
IN15
COM1
A9
B9
COM1
NC A10 B10 NC
NC A11 B11 NC
24 VDC
NC A12 B12 NC
• The polarity of the input power supply of CN2 can be connected in either direction.
• Be sure to wire both pins A9 and B9 (COM1) of CN2, and set the same polarity for both pins.
Disconnection/Short-circuit
detection
Not supported.
Protective function
Not supported.
10
NX-MD
Version Information
NX Units
Corresponding Unit Versions/Versions *
EtherCAT
Model
NX-MD6121-5
Unit version
Ver.1.0
Communications
Coupler Units
NX-ECC20@
Ver.1.0
NJ/NX series
CPU Units
Ver.1.05
EtherNet/IP
Sysmac Studio
Ver.1.10
Communications
Coupler Units
NX-EIC202
Ver.1.0
Sysmac Studio
Ver.1.10
NX-MD6121-6
Ver.1.13
Ver.1.13
NX-MD6256-5
Ver.1.10
Ver.1.10
* Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the
oldest available version after the specified version. Refer to the user’s manuals for the specific Units for the relation between models and
versions.
11
NX-MD
External Interface
Connector Types
NX Units (30 mm Width)
● Units with MIL Connectors (2 Connectors with 20 Terminals)
(A)
(B)
(C)
Letter
Name
Function
(A)
NX bus connector
This connector is used to connect each Unit.
(B)
Indicators
The indicators show the current operating status of the Unit.
(C)
Connectors
The connectors are used to connect to external devices.
The number of terminals depends on the type of Unit.
● Units with Fujitsu Connectors (2 Connectors with 24 Terminals)
(A)
(B)
(C)
Letter
(A)
Name
Function
NX bus connector
This connector is used to connect each Unit.
(B)
Indicators
The indicators show the current operating status of the Unit.
(C)
Connectors
The connectors are used to connect to external devices.
12
NX-MD
Dimensions
(Unit/mm)
Connector Types
30 mm Width
● Units with MIL Connectors (2 Connectors with 20 Terminals)
16.1
1.5
104.5
100
58.3
27.85
8.9
1.5
65.2
19.1
71
30
89.52
32.1
● Units with Fujitsu Connectors (2 Connectors with 24 Terminals)
16.1
1.5
104.5
100
27.85
1.5
8.6
65.2
19.4
71
30
72.5
(118.5)
32.1
Related Manuals
Cat. No.
W521
Model number
NX-IA@@@@
NX-ID@@@@
NX-OD@@@@
NX-OC@@@@
NX-MD@@@@
Manual name
NX-series Digital I/O
Units User’s Manual
Application
Description
Learning how to use NX-series The hardware, setup methods, and functions of the NXDigital I/O Units
series Digital I/O Units are described.
13
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2016.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2016 All Right Reserved.