CJ1W-INT01

CJ-series Interrupt Input Units
CJ1W-INT01
CSM_CJ1W-INT01_DS_E_2_1
High-speed Starting of I/O Interrupt
Tasks. Use Up to Two Units for a
Total of Up to 32 Interrupt Inputs.
• Receive inputs to start I/O interrupt tasks. When the
Interrupt Input Unit receives an input, the CPU Unit will
interrupt execution of the cyclic tasks in the normal
program and execute an I/O interrupt task.
CJ1W-INT01
Features
• High-speed ON response of 0.05 ms
• Use up to 32 interrupt inputs with up to two Units per CPU Unit.
• Applicable with both NPN and PNP output devices. Polarity selection is not required. *
* The same polarity is used for the same common.
1
CJ1W-INT01
Ordering Information
International Standards
• The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2
Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Contact your OMRON representative for further details and applicable conditions for these standards.
Interrupt Input Units
Specifications
Product
name
Unit type
I/O
points
Input
voltage
current
Commons
Input pulse
width
conditions
16
inputs
24 VDC,
7 mA
16 points,
1 common
ON time:
0.05 ms max.
OFF time:
0.5 ms max.
Max. Units
mountable
per Unit
External
connection
2
Removable
terminal
block
No. of words
allocated
Current
consumption
(A)
5V
24 V
0.08
−
Model
Standards
CJ1W-INT01
UC1, N, L,
CE
Interrupt
Input Unit
CJ1
Basic
I/O Units
1 word
Note: 1. Can be used only on CPU Racks, and not on Expansion Racks.
2. The locations where the Units can be mounted depend on the CPU Rack and the CPU Unit model.
CJ2H-CPU6@-EIP: From the slot next to the CPU Unit until the fourth slot.
CJ1G, CJ1H: From the slot next to the CPU Unit until the fifth slot.
CJ1M: From the slot next to the CPU Unit until the third slot.
3. With the SYSMAC NJ-series Controllers,Interrupt Input Units can be used as normal Basic Input Units. They cannot be used to start I/O
interrupt tasks.
Accessories
There is no accessory for the CJ series Interrupt Input Units.
Mountable Racks
NJ system
Molde
CJ1W-INT01
CJ system (CJ1, CJ2)
CP1H system
NSJ system
CPU Rack
Expansion
Rack
CJ1-CPU
Rack
CPU Units
other than left
Expansion
Backplane
CP1H PLC
NSJ Controller
Expansion
Backplane
2 Units *1*4
Not supported
*3
Not supported
2 Units *2
Not supported
*3
Not supported
Not supported
Not supported
*3
*1. The Interrupt Input Unit can be mounted in slots 0 to 4 on the CJ1-CPU Rack. An Incorrect Unit/Expansion Rack Connection error will occur if
an Interrupt Input Unit is mounted to slot 5 or higher.
*2. Connectable slot position changes with the CPU Unit.
• CJ1M-CPU@@: Slot No.0 to 2
• CJ2H-CPU@@-EIP: Slot No.0 to 3
• CPU Unit other than abobe: Slot No.0 to 4
If the Unit is mounted to the slot other than abobe, I/O setting error will occur.
*3. An I/O setting error will occur if an Interrupt Input Unit is mounted to an Expansion Rack.
*4. Interrupt Input Units can be used as normal Basic Input Units. They cannot be used to start I/O interrupt tasks.
2
CJ1W-INT01
Specifications
CJ1W-INT01 Interrupt Input Unit (16 Points)
Name
16-point Interrupt Input Unit with Terminal Block
Model
CJ1W-INT01
Rated Input Voltage
24 VDC
Rated Input Voltage Range
20.4 to 26.4 VDC
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage/ON Current
14.4 VDC min./3 mA min.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
0.05 ms max.
OFF Response Time
0.5 ms max.
Number of Circuits
16 (16 points/common, 1 circuit)
Number of Simultaneously
ON Points
100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance
20 MΩ between external terminals and GR terminal (at 100 VDC)
DielectrQic Strength
1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption 80 mA max.
Weight
110 g max.
Accessories
None
Signal
name
3.3 kΩ
COM
Input indicator
COM
Internal circuits
1000 pF
to
Jxx_Ch1_In15
470 Ω
Jxx_Ch1_In00
Circuit Configuration
Number of simultaneously ON points
Temperature characteristics for
simultaneously ON points
16 points at 45°C
• Up to two Interrupt Input Units can be mounted to the CPU
Rack. They must be connected as one of the five Units
immediately next to the CPU Unit. If an Interrupt Input Unit is
connected in any other position, an Incorrect Unit/Expansion
Rack Connection error will occur.
• Set the pulse width of signals input to the Interrupt Input Unit so
they satisfy the following conditions.
• The signal names of the terminals are the device variable
names.
The device variable names are the names that use "Jxx" as the
device name.
18
16
14
OFF
12 points at 55°C
Input voltage: 26.4 VDC
12
0.5 ms min.
ON
10
0.05 ms min.
8
6
4
2
0
0
10
20
30
40
50
60
(°C)
Ambient Temperature
\
Signal
name
Jxx_Ch1_In00
Jxx_Ch1_In02
External connection and
terminal-device variable
diagram
Connector pin *
A0
B0
A1
B1
Jxx_Ch1_In04
A2
Jxx_Ch1_In06
A3
Jxx_Ch1_In08
A4
B2
B3
B4
Jxx_Ch1_In10
A5
Jxx_Ch1_In12
A6
Jxx_Ch1_In14
A7
COM
B5
B6
B7
A8
Signal
name
Jxx_Ch1_In01
Jxx_Ch1_In03
Jxx_Ch1_In05
24 VDC
Jxx_Ch1_In07
Jxx_Ch1_In09
Jxx_Ch1_In11
Jxx_Ch1_In13
Jxx_Ch1_In15
COM
B8
• The polarity can be connected in either direction.
• The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the
device name.
Note: With NJ-series Controllers, Interrupt Input Units can be used as normal Basic Input Units.
They cannot be used to start I/O interrupt tasks.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units.
3
CJ1W-INT01
External Interface
Model number label
Input indicators
Connector
Connect to the connector on the next Unit.
Terminal block for
Input wiring, 18P × 1
ERR
0
1
8
9 10 11 12 13 14 15
2 3
4 5
6
7
Wiring Terminal Blocks
Electric Wires
The following wire gauges are recommended.
Terminal Block Connector
18-terminal
Wire Size
AWG 22 to 18 (0.32 to 0.82 mm2)
Crimp terminals
Use crimp terminals (M3) having the dimensions shown below.
6.2 mm max.
6.2 mm max.
4
CJ1W-INT01
Dimensions
(Unit: mm)
2.7
89
65
ID211
0
1
2
8
9
10 11 12 13 14 15
3
4
5
6
7
0
1
2
3
4
5
90
6
7
8
9
10
11
12
13
14
15
COM
COM
2.7
DC24V
7mA
31
Related Manuals
Name
Cat. No.
Contents
CJ-series
CJ2H-CPU6@-EIP, CJ2H-CPU6@, CJ2M-CPU@@
CJ2 CPU Unit Hardware User's Manual
W472
Describes the following for CJ2 CPU Units:
• Overview and features
• Basic system configuration
• Part nomenclature and functions
• Mounting and setting procedure
• Remedies for errors
• Also refer to the Software User's Manual (W473).
CJ Series
CJ1H-CPU@@H-R, CJ1G/H-CPU@@H, CJ1G-CPU@@P,
CJ1G-CPU@@, CJ1M-CPU@@
Programmable Controllers Operation Manual
W393
Provides an outlines of and describes the design, installation, maintenance, and
other basic operations for the CJ-series PLCs.
W500
An introduction to the entire NJ-series system is provided along with the following
information on a Controller built with an NJ501 CPU Unit.
• Features and system configuration
• Introduction
• Part names and functions
• General specifications
• Installation and wiring
• Maintenance and inspection
Use this manual together with the NJ-series CPU Unit Software User's Manual
(Cat. No. W501).
NJ-series CPU Unit Hardware User's Manual
NJ501-@@@@
5
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
 Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
 Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
 Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2011 All Right Reserved.