Datasheet
Electronic Circuit Protection
ESX10-TC 12VDC
status indication are provided by a multicolor LED
and an integral short-circuit-proof status output or
a relay signal contact. Remote operation is possible by
means of a remote reset signal or a remote ON/OFF
control signal. The manual ON/OFF button allows
separate actuation of individual load circuits.
The ESX10-TC, with a width of only 12.5 mm, can be
snapped onto symmetrical rails for easy installation and
control cabinet space savings.
Upon detection of overload or short circuit in the
load circuit, the MOSFET of the load output will be
blocked to interrupt the current flow. The load circuit
can be re-activated via the remote electronic reset
input, control input ormanually bymeans of the
ON/OFF button.
Zone 2
Electronic circuit protection type ESX10-TC is designed to
ensure selective disconnection of 12VDC load systems.
12VDC power supplies, which are widely used in
industry today, will shut down the output in the event
of an overload with the result that one faulty load in the
system can lead to complete disconnection of all loads.
Through selective disconnection the ESX10-TC responds
much faster to overload or short circuit conditions than
the switch-mode power supply. This is achieved by
active current limitation. The ESX10-TC limits the highest
possible current to 1.3 to 1.8 times the selected rated
current of the circuit protector. Thus it is possible to
switch on capacitive loads of up to 20,000 μF, but they
are disconnected only in the event of an overload or
short circuit.
For optimal alignment with the characteristics of the
application the current rating of the ESX10-TC can be
selected in fixed values from 1.0 A...10 A. Failure and
Features
• Selective load protection, electronic trip characteristics
• Active current limitation for safe connection of capacitive
loads up to 20,000 μF and on overload/short circuit
• Current ratings 1 A...10 A at 12VDC
• Reliable overload disconnection with 1.1 x In plus,
even with long load lines or small cable cross sections
(see table 3)
• Manual ON/OFF button (S1)
• Control input IN+ for remote ON/OFF signal (option)
• Electronic reset input RE (option)
• Clear status and failure indication through LED,
status output SF
• Integral fail-safe element adjusted to current rating
• Width per unit only 12.5 mm
• Rail mounting
• Ease of wiring through busbar LINE+ and 0 V
• Hazardous area approved– Class1 Div 2,
Zone 2 (ATEX)
Canada
Mexico
United States
Weidmuller, Canada
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (905) 475-2798
Email: [email protected]
Website: www.weidmuller.ca
Weidmuller, Mexico
Blvd. Hermanos Serdán 698
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
Weidmuller
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
Electronic Circuit Protection
Technical data
(Tambient = 25°C, operating voltage US = 12VDC)
Operating data
Operating voltage Ub
Current rating In
Closed current I0
Status indication
by means of
Load circuit
Load output
Overload disconnection
Short-circuit current IK
Trip time
for electronic disconnection
Temperature disconnection
Low voltage monitoring
load output
12VDC (9...18 V)
fixed current ratings: 1 A, 2 A, 3 A, 4 A, 6 A, 10 A
ON condition: typically 20...30 mA
depending on signal output
• multicolor LED:
GREEN: unit is ON, power-MOSFET
is switched on
- status output SF ON,
supplies + 12VDC
ORANGE: in the event of overload or
short circuit until electronic
disconnection
RED:
- unit electronically disconnected
- load circuit/Power-MOSFET
OFF
- low voltage (< 3.25 V)
- after switch-on till the end of
switch-on delay
OFF:
- manually switched off
(S1 = OFF)
or device is dead
- undervoltage
• status output SF (option)
• ON/OFF/ condition of switch S1
Power-MOSFET switching output
(high side switch)
typically 1.1 x In (1.05...1.35 x In)
active current limitation (see table 1)
see time/current characteristics
typically 3 s at ILoad > 1.1 x In
typically 3 s...50 ms at ILoad > 1.8 x In
(or 1.5 x In/1.3 x In)
internal temperature monitoring with
electronic disconnection
with hysteresis at voltage dips < 500 ms,
no reset required: load “OFF” at UB < 3.2 V
Starting delay tstart
typically 10 ms
Disconnection of load circuit
electronic disconnection
Free-wheeling circuit
external free-wheeling diode
recommended with inductive load
Several load outputs must not be connected in parallel
2
E S X 10 - T C 1 2 V D C
Technical data
Status output SF
Electrical data
(Tambient = 25°C, operating voltage Us = 12VDC)
ESX10-TC-114/-124/
plus-switching signal output,
connects Us to terminal 12 of module 17plus
nominal data: 12VDC / max. 0.2 A (short circuit proof)
status output is internally connected to
GND with a 10 kM resistor
Status OUT
ESX10-TC-114/-124 (signal status OUT),
+12 V = S1 is ON, load output connected through
0V = S1 is ON, load output blocked and/or
switch S1 is OFF
red LED lit
OFF condition
0 V level at status output when:
• switch S1 is in ON position, but device is
still in switch-on delay
Reset input RE
Electrical data
• switch S1 is OFF, or control signal OFF,
device is switched off
• no operating voltage Us
ESX10-TC-124
voltage: max. +32VDC
high > 4.5VDC ≤ 18VDC
low ≤ 2.5VDC > 0 V
power consumption typically 1.4 mA
Reset signal RE
(terminal 22)
(+12VDC)
min. pulse duration typically 10 ms
The electronically blocked ESX10-TC-124
may remotely be reset via an external
momentary switch due to the falling edge of
a +12 V pulse.
Control input IN+
Electrical data
Control signal IN+
(terminal 21)
Switch S1 ON/OFF
A common reset signal can be applied to
several devices simultaneously.
Switched on devices remain unaffected.
ESX10-TC-114
see reset input RE
+12V level (HIGH): device will be switched
on by a remote ON/OFF signal
0 V level (LOW): device will be switched
off by a remote ON/OFF signal
unit can only be switched on with S1 if a
HIGH level is applied to IN+
E S X 10 - T C 1 2 V D C
Technical data
Electronic Circuit Protection
(Tambient = 25°C, operating voltage Us = 12VDC)
General data
Fail-safe element:
Terminals
screw terminals
backup fuse for ESX10-T not required
Mounting
Ambient temperature
because of the integral
redundant fail-safe element
LINE+ / LOAD+ / 0V
Storage temperature
Humidity
symmetrical rail to EN 50022-35x7.5
-20...+60 °C (without condensation, see EN 60204-1)
(with condensation upon request)
-20...+70 °C
96 hrs/95 % RH/40 °C to IEC 60068-2-78-Cab
climate class 3K3 to EN 60721
3 g, test to IEC 68-2-6 test Fc
housing: IP20 DIN 40050
terminals: IP20 DIN 40050
emission: EN 61000-6-3
susceptibility: EN 61000-6-2
0.5 kV/2 pollution degree 2
re-inforced insulation in operating area
max. 18VDC (load circuit)
M4
max. cable cross section
flexible with wire end ferrule w/wo plastic sleeve
multi-lead connection
20-6 AWG (0.5 - 10 mm2)
(2 identical cables)
20-11 AWG (0.5 - 4 mm2)
20-13 AWG (0.5 - 2.5 mm2)
20-9 AWG (0.5 - 6 mm2)
10 mm
1.2 Nm
rigid/flexible
flexible with wire end ferrule without plastic sleeve
flexible with TWIN wire end ferrule with plastic sleeve
wire stripping length
tightening torque (EN 60934)
Terminals
aux. contacts
screw terminals M3
max. cable cross section
flexible with wire end ferrule w/wo plastic sleeve
wire stripping length
tightening torque (EN 60934)
Housing material
moulded
Vibration
Degree of protection
EMC
(EMC directive, CE logo)
Insulation co-ordination
(IEC 60934)
dielectric strength
Insulation resistance
(OFF condition)
Dimensions (W x H x D)
Mass
n/a, only electronic disconnection
12.5 x 80 x 83 mm
approx. 65 g
23-13 AWG (0.25 – 2.5 mm2)
8 mm
0.5 Nm
Table 1:
voltage drop, current limitation, max. load current
current rating
In
1A
2A
3A
4A
6A
10 A
typically voltage drop
Uon at In
80 mV
130 mV
80 mV
100 mV
130 mV
150 mV
active current
limitation (typically)
1.8 x In
1.8 x In
1.8 x In
1.8 x In
1.8 x In
1.5 x In
max. load current at 100% ON duty
Tu = 40 °C
Tu = 50 °C
1A
1A
2A
2A
3A
3A
4A
4A
6A
5A
10 A
9A
Attention: when mounted side-by-side without convection the ESX10-TC should not carry more
than 80% of its rated load with 100% ON duty due to thermal effects.
Please note:
•
The user should ensure that the cable cross sections of the relevant load
•
Automatic start-up of machinery after shut down must be prevented
circuit are suitable for the current rating of the ESX10-TC used.
(Machinery Directive 98/37/EG and EN 60204-1). In the event of a short
circuit or overload the load circuit will be disconnected electronically by
the ESX10-TC.
•
Refer to UL file for proper wiring and installation techniques.
Table 2: ESX10-TC - Ordering Information
Version
Signal input
Control input
Remote
ON/OFF Reset
ESX10-TC-114
Reset
Signal output
Status OUT
Positive 12V
= OK
x
ESX10-TC-124
x
EMC
Insulation co-ordination
CE logo
UL
ATEX
ESX10-TC-124**
Current Rating
(amps)
Control Input
Part Number
Current Rating
(amps)
Reset Input
Part Number
1
6720005351
1
6720005331
x
2
6720005352
2
6720005471
x
3
6720005353
3
6720005333
4
6720005354
4
6720005334
6
6720005356
6
6720005472
10
6720005357
10
6720005473
Table 3: Specifications
Protection
ESX10-TC-114*
to EN6052
housing IP30, terminals IP00
emitted interference to EN 61000-6-3
noise immunity to EN 61000-6-2
0.5 kV / pollution degree 2, re-inforced
insulation in operating area to
IEC60934 / IEC60664
to 2004/108/EG and 94/9/EG
UL2367, File No E306740
UL508, File No E322549
UL 1604, File No E320024
* Control force input on/off
** Reset input only to reset under fault conditions
IEC/EN60079-0 /-14/-15
II 3G Ex nA II B T4 Gc X
3
Electronic Circuit Protection
ESX10-TC 12VDC
ESX10-TC Signal inputs / outputs (wiring diagram)
Schematic diagram
(Example)
Schematic diagram ESX10-TC-124-DC 12 V (Example)
1
LINE+
IN 21
RE 22
LINE (+)
24VDC
1
Rsense
SF 23
SF 23
ESX10-TC-124-…
electronic control unit
LINE+
ESX10-TC-124
with reset input RE
(+12VDC ↓)
with status output SF
(+12 V = load output ON)
Failsafe
ESX10-TC-114
with control input IN+
(+12VDC)
with status output SF
(+12 V = load output ON)
2
LOAD+
2
S1
ON/OFF
status indication
green/orange/red
RE
reset input
SF
status output
LOAD+
LOAD (+)
load output
0V
Terminal wiring diagram
0V
3
operating condition: SF +12 V = OK
fault condition:
SF 0 V
0V
3
(Example)
Terminal wiring diagram ESX10-TC-124-DC 12 V (Example)
operating condition: SF +12 V = OK
fault condition:
SF 0 V
DC12V
xxA
ok
r
e
s
e
t
on
off
2 LOAD+
Dimensions
Dimensions
83
3.27
12.5
.492
80
3.15
DC12V
xxA
ok
on
r
e
s
e
t
2 LOAD+
80
3.15
Label
4
snap-on socket for
symmetrical rail EN 50022-35x7.5
ESX10-TC 12VDC
Electronic Circuit Protection
Time/Current characteristic curve (Ta = 25 °C)
• The trip time is typically 3 seconds in the range between
1.1 and 1.8 x In†.
disconnection
typically 1.1 x In 1.8 x In †
10000
1000
• Electronic current limitation occurs at typically 1.8 x In†
which means that under all overload conditions
(independent of the power supply and the resistance of
the load circuit) the max. overload before disconnection
will not exceed 1.8 x In† times the current rating. Trip
time is between 100 ms and 3 sec (depending on
overload or at short circuit).
trip time in seconds
100
current limitation †
typically 1.8 x In
10
5
1
0.1
0.01
0
1
2
3
...times rated current
4
5 IK
• Without this current limitation a considerably higher
overload current would flow in the event of an overload
or short circuit.
† current
limitation typically 1.8 x In times rated current at In = 1.0 A...6 A
current limitation typically 1.5 x In times rated current at In = 10 A
5
Electronic Circuit Protection
ESX10-TC 12VDC
The ESX10-TC-DC 12 V features an integral power distribution system.
Accessories for ESX10-TC
LINE+ busbar
6720005315
remove protection against
brush contact from bottom side
continuous busbar
500 mm length, cut
(12.5 x n)-3 = length of busbars ± 0.5
e. g. (12.5 x 5)-3 = 59.5 ± 0.5
insert protection against
brush contact
0 V busbar
6720005315
12.5 x n = width of
protector block
e. g. 12.5 x 5 = 62.5
insert busbars
and protection slides
to be flush with housing sides
5 ESX10-TC
with busbars
Mounting procedure:
Before wiring, insert busbars into protection block.
Max. 10 insertion/removal cycles for busbars.
Recommendation:
Every 10 units busbars should be interrupted and fed in anew.
Table of lengths for busbars:
(see accessories)
No. of Units
2
3
4
5
6
7
8
9
10
Length of busbar
[mm] + 0.5 mm
22
34.5
47
59.5
72
84.5
97
10.95
122
6
ESX10-TC 12VDC
Electronic Circuit Protection
Accessories for ESX10-TC
Description
The ESX10-TC features an integral power distribution
system. The following wiring modes are possible with
various pluggable current and signal busbars:
• LINE +(12VDC)
• 0V
Caution: The electronic devices ESX10-TC require a
0 V connection
Description
Busbars for LINE+ and 0 V
Part No.
6720005315
max. load with one line entry
(recommended: center line entry)
Imax
50 A
max. load with two line entries
Imax
63 A
length:
500 mm
TS32 rail adapter
9102100000
(Remove protection walls/barriers before using adapter.)
For detailed installation instructions and approvals contact
Weidmuller at 1-800-849-9343 or go to www.weidmuller.com
7
Electronic Circuit Protection
ESX10-TC 12VDC
Accessories
Busbars for LINE+ and 0 V
max. load with one line entry
(recommended: centre line entry)
max. load with two line entries
grey insulation, length: 500 mm
6720005315
Supply module for LINE+ and 0 V
suitable for ESX10-T... versions
ampacity Imax 50 A
AD-TX-EM01
Imax
50A
AD-TXEM01
Busbars for LINE+ and 0 V
grey insulation
max. number of plug-on operations 10:
6720005335, (3-unit-block ESX10-T), length: 34.5 mm
6720005336, (4-unit-block ESX10-T), length: 47 mm
6720005337, (5-unit-block ESX10-T), length: 59.5 mm
packing unit: 10 pcs
6720005474, (8-unit-block ESX10-T), length: 97 mm
6720005475, (10-unit-block ESX10-T), length: 122 mm
packing unit: 4 pcs
ø2.5
.099
50 pin lugs to
DIN 46230
tinned copper
~70
~2.76
Connector bus link – K10
suitable for auxiliary contacts (series connection)
6720005476 (1.5 mm2, brown),
50 pin lugs to
DIN 46230
tinned copper
50 pin lugs to
DIN 46230
tinned copper
ø2.5
.099
~70
~2.76
~70
~2.76
ø2.5
.099
8
Subject to technical changes • 05/12-LIT1118E