Download

Data Sheet •
Mann Series
U n i ve r s a l A u t o/ M a n u a l S t a t i o n
AMS400A
The AMS400A is an interface device
used between controlling equipment and
field devices to allow manual takeover of
automatically controlled processes. Typical
applications are:
• manual start-up of sensitive processes
before handover to automatic control
• manual over-ride in case of controller
failure or malfunction.
A fully configured AMS400A can be installed
in three I/O configurations, which interface
between:
• Analogue control equipment and analogue
control devices
• Digital control equipment and analogue
control devices
• Digital control equipment and digital
control devices
For analogue to analogue operation there
are digital outputs available to force a
change to automatic or manual mode.
You can also set ramp rates and handover
settings to ensure a smooth transfer of
control.
% \
Australia
Weidmüller Pty Ltd.
43 Huntingwood Drive, Huntingwood
NSW 2148
Phone +61 (0) 2 9671 9999
Fax
+61 (0) 2 9671 9900
[email protected]
www.mannseries.com
United Kingdom
Other countries
Weidmüller Ltd.
1 Abbey Wood Road, Kings Hill
West Malling, Kent ME19 4YT
Phone +44 1732-877032
Fax
+44 1732-873873
[email protected]
www.weidmueller.com
Weidmüller Interface GmbH & Co.
Postfach 3030
32720 Detmold
Phone +495231-14-0
Fax
+495231-14-2083
[email protected]
www.weidmueller.com
PMX400 Series
AMS400A
Auto/Manual
DisplaysStation
Auto/Manual Station configurations
137.00mm
Digital Input
Analogue Input
Analogue Output
Relay outputs
Solid state Output
Up/Down signals from PLC/DCS
Feedback input from field device
Not used
Up/Down outputs to field device
AMS400A Mode signal to PLC/DCS
96.6mm
143.5mm
44.4mm
Description
48.8 mm
Signal
!54/
GASKET
18.0mm
PANEL THICKNESS Max 18.0mm
%.4
15.5mm
CUTOUT
60.0.mm
Up/Down signals from PLC/DCS
Feedback input from field device
Proportional output to field device
Not used
AMS400A Mode signal to PLC/DCS
96.6mm
Description
Digital Input
Analogue Input
Analogue Output
Relay outputs
Solid state Output
-!.
92.0mm (+0.8/-0.0mm)
‘dA’-Digital control equipment to analogue field device
Signal
-2700
45.0mm (+0.6/-0.0mm)
‘dd’ - Digital control equipment to digital field device
%
\
Signal
Description
Digital Input
Analogue Input
Analogue Output
Relay outputs
Solid state Output
Force shifts between modes
Automatic signal from PLC/DCS
Proportional output to field device
Not used
AMS400A Mode signal to PLC/DCS
15.5mm
‘AA’-Analogue control equipment to analogue field device
General
Accuracy
General Technical Data
Typically ±0.1% of span
Linearity
Better than 0.05%
Full 4 digit, red 14.2 mm LED
Repeatability
±0.02% of span
Scaling
To display in % or engineering units
Temperature drift
Less than 0.02% span/°C
Display range
–9999 to 9999
Long term drift
0.1% per 10,000 hours
Status indicators
Operating mode (Automatic or Manual)
Frequency response
–3dB point = 5Hz
Response time
300 mS for 10–90% output change
Display
Type
Analogue output (optional)
Type (selected by internal jumper)
Analogue current/voltage
Insulation Co-ordination
Range (determined by calibration)
Any range inside the limits 0–24 mA / 0–18 V
Ports
Input / Output / Case
Current drive
Up to 900Ω load (at 20mA)
Rated Insulation Voltage
300Veff
Voltage drive
True voltage source (up to 20mA)
Overvoltage Category
III
Output ripple
Less than 20mV P/P
Impulse Withstand
4kV (1.2 / 50)
Isolation
2 kV (between ports)
Analogue input
Type
Analogue current/voltage (as ordered)
Environmental Conditions
Range
Any range inside the limits ±24mA or ±12 V
(determined by calibration)
Operating temperature
0 to 60 °C
Storage temperature
–25 to +70 °C
Input impedance
50Ω (current) or 1MΩ (voltage)
Pollution Degree
2
Noise immunity
120dB CMRR (1.5kVrms limit)
Relative humidity
10–90% (non–condensing)
Sampling rate
5 samples per second
Digital Inputs
Type (jumper selectable)
Voltage pulse or volt-free contact
Minimum pulse width
64mS
Ordering information
Type (Model 1/2/3/4 - See key below)
Cat. No.
AMS400A 4-20mA/CC/24Vdc/AO
7940011895
AMS400A 4-20mA/CC/24Vdc/AORO
7940015937
Status outputs
Type
2 opto-isolated O/C transistor outputs with
common negative return
Rating
200mA on-state current or
50Vdc off state voltage
Note: back EMF protection required
Relay outputs
Type
SPDT relay contacts
Rating (resistive)
3A @ 240Vac or 24Vdc
Isolation
1.5kVrms between channels
For other ranges please specify AMS400A
1/2/3/4 where:
1 = Analogue input format
2 = Digital input type (VP for voltage pulse or
CC for contact closure)
3 = Power supply voltage
4 = Output type (AO for analogue output, RO
for relay outputs or AORO for both types)
Housing
Type
Panel mount, IP65 rated (from front of panel)
Front bezel
1/8 DIN format
Power supply
Connections
Terminal
Signal
Terminal
Signal
1
Neutral / −
11
Signal +
Live / +
12
Signal −
Power supply
Type
AC or DC powered
2
AC (selectable)
110Vac (47-63Hz) ±15%
240Vac (47-63Hz) ±15%
3
Signal +
4
Signal −
DC
24Vdc ±10%
5
0V
Power usage
AC 6VA or 6W @ 24Vdc
6
AUTO/MAN
7
Handover Status
Approvals
Mark
AM400A Series
\
AMS400A - DC
Powered only
Page 2
%
Standard
E256486
LV Directive EMC
CAN/CSA C22.2 No. 1010.1:92
UL61010-1: 2004
EN50178:1998
BS EN 61326:1998 + A2
8
Common
9
Increment
10
Decrement
Analogue
output
Status
Outputs
13
Normally Closed
14
Common
15
Normally Open
16
Normally Closed
17
Common
18
Normally Open
Analogue
Input
Increment
Relay Output
Decrement
Relay Output
Digital Input
Subject to technical alterations without notice • Printed in Australia • 7940015663 • 25/10/2007