M i c r o m a n n U n i ve r s a l , A u x i l i a r y Powe r e d , A l a r m s
U C V R C u r re n t / Vo l t a g e I n p u t s
U RT R R e s i s t i v e Te m p e r a t u re D e t e c t o r I n p u t s
UTCR Thermocouple Inputs
U H Z R F re q u e n c y I n p u t s
CNDR Conductivity sensor Inputs
X FA R E x t e n d e d F u n c t i o n A l a r m
Micromann universal alarms monitor and
display process measurements. Each model
covers a range of similar signal and sensor
types
• Two versatile alarm channels with LED
status indication
• Dual SPDT relay outputs
• Display in Engineering units
• Complete isolation
• AC or DC powered
• Removable, screw-type, terminal blocks
• Compact metal housing
% \
Australia
Weidmüller Pty Ltd.
43 Huntingwood Drive, Huntingwood
NSW 2148
Phone +61 (0) 2 9671 9999
Fax
+61 (0) 2 9671 9900
[email protected]
www.mannseries.com
United Kingdom
Other countries
Weidmüller Ltd.
1 Abbey Wood Road, Kings Hill
West Malling, Kent ME19 4YT
Phone +44 1732-877032
Fax
+44 1732-873873
[email protected]
www.weidmueller.com
Weidmüller Interface GmbH & Co.
Postfach 3030
32720 Detmold
Phone +495231-14-0
Fax
+495231-14-2083
[email protected]
www.weidmueller.com
Universal Alarm Modules
Description
The Micromann series are fully isolated,
microprocessor based, alarm modules
for use with most common process
measurement signals and sensors.
You can program all features of Micromann
operation through the front panel keypad.
When the set-up is complete, you simply
remove the security link to protect the
setup.
You can tailor each alarm’s operation
individually during setup. If necessary, you
can also allow setpoint adjustment (from the
front panel) during normal operation.
Alarm operation can be set to ‘manual reset’
so that active alarms will remain tripped until
manually cleared.
%
General Technical Data
\
Display
Type
Full 4 digit, red 7mm LED
Scaling
to display in % or engineering units
Display range
-999 to 9999
Status indicators
Trip1 /Trip 2 / Processor status
Alarm ouputs
Type
Two SPDT relay contact outputs
Rating
3A at 250Vac/30Vdc
Setpoints
Any value within the display range
Deadband
From 1 display count
Alarm action
High alarm or Low alarm
Output sense
Normally de-energised or energised
Alarm reset
Automatic or manual
Alarm timer delay
From 0 to 4200 seconds
RIGHT HAND SIDE VIEW
97 mm
Power Supply
Type
AC or DC powered
AC
110Vac (100-132Vac) at 47-63Hz or
240Vac (200-264Vac) at 47-63Hz
DC
12 to 50Vdc (other voltages on request)
Power Usage
AC 6VA or 6W at 24Vdc
TOP VIEW
46 mm
Housing
Type
Dual DIN rail mount, Anodised Aluminium Enclosure
Dimensions
See diagram
Weight
0.5kg
Connection type
Plug in terminal blocks with screw connections
Effective depth :
120mm (Top Hat 35mm +/- 0.3, DIN 46277-3, EN 50022)
125mm (G - Rail 32mm +/- 0.3, DIN 46277-1, EN 50035)
To surface (including rail/mounting plate)
Performance
Repeatability
±0.05% of span
Temperature drift
Less than 0.02% span per °C
Long term drift
0.1% per 10,000 hours
Reponse time
320ms for 10-90% output change
Input step response
Programmable (from 250mS to 32s)
Sampling rate
5 samples per second
Setup retention
100 years minimum
Connections
Terminal
Insulation Co-ordination
2
Ports
Input / Relay One / Relay Two / Power Supply / Case
Rated Insulation Voltage
300Veff
Overvoltage Category
III
Impulse Withstand
4kV (1.2 / 50)
Isolation
2 kV (between ports)
Input signals
Link to change the
set-up
Security Link
8
9
Neutral (−)
10
Live (+)
11
Normally Closed
12
Common
Custom transducer power supply
13
Normally Open
Standard
14
Normally Closed
CAN/CSA C22.2 No. 1010.1:92
UL61010-1: 2004
15
Common
16
Normally Open
Case
Earthing is via a stud on lower side of case
0 to 60 °C
Storage temperature
–25 to +70 °C
Pollution Degree
2
Relative humidity
10–90% (non–condensing)
Options
FPS
Mark
\
%
Page 2
4
5
6
7
Operating temperature
Micromann Series
3
See individual
models
Environmental Conditions
Approvals
Signal
1
E256486
LV Directive
EMC
EN50178:1998
BS EN 61326:1998 + A2
Power supply
Alarm Channel One
Alarm Channel Two
Subject to technical alterations without notice • Printed in Australia • 7940015667 • 04/03/2008
Universal Alarm Modules
%
%
%
\
\
\
UCVR Current/Voltage
• Convert, filter and Isolate
current and voltage signals
• Power for active input devices
• Linearises square law signals
• Bipolar inputs
UTCR Temperature (T/C)
• Select J, K, N, T, E, B, S, R
or mV inputs
• Temperature Display in °C/°F
• Burn-out alarm
• CJC Temperature display
URTR Temperature (RTD)
• Accepts 2-wire and 3-wire
PT100 RTD inputs
• Temperature Display in °C/°F
• Automatic lead length
compensation
Technical Data
Inputs
Input Type
Analogue current/voltage signals
Standard range limits
–55.00mA to +55.00mA or
–55.00V to +55.00V
(without recalibration)
Input impedance
22Ω (current inputs)
1MΩ (voltage inputs)
Resolution
1μA/1mV per bit for small ranges
Minimum recommended span
1mA or 1V
Linearisation
Linear or square root
Transducer supply
24Vdc (to 25mA) output
Maximum input impedance
Thermocouple (type J, K, N, T, E, B, S, R)
or millivolt signals
2-wire or 3-wire, PT100 RTD
(to BS1904:1984/IEC751:1983)
Display Limits
Display Limits
Input
Type
Upper
J
Resolution
Upper
Lower
870°C (1598°F)
700°C
-200°C
K
1372°C (2502°F)
1292°F
-328°F
1°F
N
1300°C (2372°F)
200.0°C
-99.9°C
0.1°C
400.0°F
-99.9°F
0.1°F
T
400°C (752°F)
E
700°C (1292°F)
B
1800°C (3272°F)
S
1768°C (3214°F)
R
1768°C (3214°F)
mV
60.00mV
Lower
–50°C (–58°F)
1°C
0°C (32°F)
–50°C (–58°F)
-9.99mV
1kΩ (e.g., IS barrier resistance)
30Ω (lead resistance)
Display
Scaling
to display in % or engineering units
to display temperature (in °C or °F) or mV
to display temperature (in °C or °F)
Display range
-999 to 9999
See table above
See table above
Resolution
0.001 engineering units
1°C/°F or 0.01mV
1°C/°F or 0.1°C/°F
Performance
CJC tracking error
Less than 0.02% per °C ambient change
Lead length compensation
Better than 0.05% error for equal changes
in lead resistance
Input Connections
Terminal
Signal
Terminal
mV Signal
1
24Vdc (out)
1
mV +
2
Current +
2
mV −
3
Common −
3
4
Voltage +
4
T/C Signal
CJC Board
(white dot to
terminal 2)
5
5
Terminal
Signal
1
Not used
2
A
3
B
4
B sense
5
Not used
6
Not used
Not used
6
6
Not used
Ordering Information
Specify as
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Where
UCVR 12-50Vdc
7940010174
UTCR 12-50Vdc
7760000017
URTR 12-50Vdc
7940011087
Note: For other ranges please specify as
UCVR 1 where 1 = Power Supply Voltage
Note: For other ranges please specify as
UTCR 1 where 1 = Power Supply Voltage
Note: For other ranges please specify as
URTR 1 where 1 = Power Supply Voltage
Default Burnout Action is Upscale. For
Downscale please specify on order.
Notes
Page 3
Subject to technical alterations without notice • Printed in Australia • 7940015667 • 04/03/2008
Universal Alarm Modules
%
%
%
\
\
\
UHZR Frequency
• Connects directly to a wide
range of frequency sources
• Power for active input
devices
CNDR Conductivity
• Suits any conductivity probe
• Autoranging
• Probe temperature
compensation
• Programmable cell constant
• linearises probe characteristic
XFAR Extended function
current/voltage alarm
• Rate of change alarms
(increase, decrease or both)
• Deviation alarms
(deviation from setpoint)
• Alarm inhibit inputs
(for each channel)
• Loss of signal alarms
(for elevated zero signals)
Technical Data
Inputs
Input Type
Programmable frequency
(includes debouncing for voltfree contacts)
Conductivity cell, conductance and Pt100
RTD (probe temperature compensation)
Process current or voltage signals
Standard range limits
Any range inside the limits 0 to 10kHz
(or 0-10Hz for debounced volt-free
contacts)
Any range inside the limits 0 to 20,000μS
using 4 selectable ranges: 0-200μS;
0-1,000μS; 0-5,000μS; or 0-20mS.
Any range inside the limits
-22.00mA to +22.00mA or
-11V to +11V
Minimum recommended span
0.001Hz
20% of selected range
2mA or 1V
Input voltage range
50mV to 250V (ac and dc)
others on request
Sensor supply output
Nominally 12Vdc to 25mA
others on request (see /FPS option)
Nominally 24Vdc to 25mA
others on request (see /FPS option)
Temperature range
0-200°C (for RTD)
Cell Constants
0-01 to 99.99/cm
Type
Excitation voltage
Less than 6V p/p @ 400Hz
Lead length compensation
< 2% of change for equal changes in lead
resistance (up to 30Ω)
Temperature Compensation
Linear or user defi ned up to 5 points
Input impedance
Opto isolated voltage
Sense
Active high
High Voltage
4V to 40V
Low Voltage
<3V
Isolation
50V (ac and dc)
22Ω (Current) or 1mΩ (Voltage)
Display
Scaling
to display in % or engineering units
μS, mS, μS/cm, mS/cm or °C
to display in % or engineering units
Display range
-999 to 9999
-999 to 9999
Resolution
0.001 engineering units
0-200.0μS (0.1μS resolution)
0-1,000μS (1μS resolution)
0-5,000μS (1μS resolution)
0-20.00mS (0.01mS resolution)
0-200.0°C (0.1°C resolution)
0.001 engineering units
Performance
Repeatability
±0.02% of span
±0.05% of span
Noise immunity
40dB CMRR (1.5kVrms limit)
Notes
Input Connections
Terminal
Signal
Terminal
Cell
Terminal
Signal
1
12Vdc (out)
1
Not used
1
24Vdc (out)
2
Pull Up/Down
2
A
2
Current +
3
Input −
4
Voltage +
3
3
0V
Pt100 RTD
B
4
Low Voltage (<24Vdc) Signal +
4
A
5
Signal −
5
6
High Voltage (>24Vdc) Signal +
6
5
Inhibit input common
B
6
Channel one Inhibit +
B sense
7
Channel Two Inhibit +
Notes
Ordering Information
Specify as
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Type (Model Supply)
Cat. No.
Where
UHZR 12-50Vdc
7940015213
CNDR 12-50Vdc
7940017921
XFAR 12-50Vdc
7940014450
Note: For other ranges please specify as
UHZR 1 where 1 = Power Supply Voltage
Page 4
Note: For other ranges please specify as
CNDR 1 where 1 = Power Supply Voltage
Note: For other ranges please specify as
XFAR 1 where 1 = Power Supply Voltage
Subject to technical alterations without notice • Printed in Australia • 7940015667 • 04/03/2008