SITRANS P MPS Catalog sheet

© Siemens AG 2015
Pressure Measurement
Transmitters for basic requirements
SITRANS P MPS Transmitter for hydrostatic level
■ Overview
■ Function
SITRANS P MPS pressure transmitters are for measuring the liquid levels in wells, tanks, channels and dams.
Sensor
U
const.
Diaphragm
U
p
I
EM
+2 (brown)
I0, UB
-1 (blue)
Vent pipe
Screen
SITRANS P MPS pressure transmitters are submersible sensors
for hydrostatic level measurements.
The SITRANS P MPS pressure transmitters are available for various measuring ranges and with explosion protection as an option.
A junction box and a cable hanger are available as accessories
for simple installation.
■ Benefits
•
•
•
•
Compact design
Simple installation
Small error in measurement (0.3 %)
Degree of protection IP68
■ Application
SITRANS P MPS pressure transmitters are used in the following
branches for example:
• Oil and gas industries
• Shipbuilding
• Water supply
• For use in pressureless/open tanks and wells
SITRANS P MPS pressure transmitter, mode of operation and wiring diagram
On one side of the sensor, the diaphragm is exposed to the hydrostatic pressure which is proportional to the submersion
depth. This pressure is compared with atmospheric pressure.
Pressure compensation is carried out using the vent pipe in the
connection cable.
The hydrostatic pressure of the liquid column acts on the sensor
diaphragm, and transmits the pressure to the piezo-resistive
bridge in the sensor.
The output voltage of the sensor is applied to the electronic circuit where it is converted into an output current of 4 to 20 mA.
The cable of the 7MF1570 transmitter must always be connected
in the supplied junction box. The junction box has to be installed
near the measuring point.
If the medium is anything other than water, it is also necessary to
check compatibility with the specified materials of the transmitter.
■ Integration
Venting pipe
■ Design
SITRANS P MPS pressure transmitters have a front-flush piezoresistive sensor with stainless steel diaphragm.
These pressure transmitters are equipped with an electronic circuit fitted together with the sensor in a stainless steel housing.
The cable also contains a strength cord and vent pipe.
The diaphragm is protected against external influences by a
protective cap.
The sensor, electronic circuit and cable are sealed in a common
housing of small dimensions.
The pressure transmitter is temperature-compensated for a wide
temperature range.
To transmitter
7MF1570
To measuredvalue
processing
Junction box 7MF1570-8AA, opened
Siemens FI 01 · 2015 US Edition
1/31
1
© Siemens AG 2015
Pressure Measurement
Transmitters for basic requirements
1
SITRANS P MPS Transmitter for hydrostatic level
Long-term stability
Zero and span
• 1 ... 6 mH2O (3 ...18 ftH2O)
0.25 % of full-scale value/year
•  6 mH2O ( 18 ftH2O)
0.2 % of full-scale value/year
Rated conditions
Ambient conditions
• Process temperature
-10 ... +80 °C (14 ... 176 °F)
• Storage temperature
-40 ... +100 °C (-40 ... +212 °F)
Degree of prot. to DIN EN 60529
IP68
Design
Weight
• Pressure transmitter
 0.4 kg ( 0.88 lb)
• Cable
0.08 kg/m ( 0.054 lb/ft)
Electrical connection
Cable with 2 conductors with
screen and vent pipe, strength
cord (max. 300 N (67.44 lbf)
Material
• Seal diaphragm
Stainl. steel, mat. no. 1.4571/316Ti
• Enclosure
Stainl. steel, mat. no. 1.4571/316Ti
• Gasket
Viton
• Connecting cable
Either PE/HFFR sheath (non-halogen) or FEP sheath
Power supply
Terminal voltage on pressure transmitter UB
10 ... 36 V DC
0 ... 30 V DC for transmitter with
intrinsic safety explosion protection
Certificates and approvals
Measuring point setup, in principle
■ Technical specifications
SITRANS P MPS pressure measurement transmitter
(submersible sensor)
Mode of operation
Measuring principle
Germanischer Lloyd (GL)
GL 75360-09 HH
Bureau Veritas (BV)
BV 27101/A0 BV
Det Norske Veritas (DNV)
DNV A-12553
Drinking water approval (ACS)
ACS 11 ACC NY 014
Drinking water approval (WRAS)
WRAS 1111055
GOST
GOST-R, GOST FR.C.30.004.A/
42376/1 und PPC 00-04 1505
piezo-resistive
Measured variable
Hydrostatic level
The transmitter is not subject to the
pressure equipment directive
(PED 97/23/EC)
Measuring range
Maximum operating pressure
Explosion protection
• 0 ... 2 mH2O (0 ... 6 ftH2O)
• 1.4 bar (20.3 psi) (corresponds
to 14 mH2O (42 ftH2O))
• Intrinsic safety "i"
• 0 ... 4 mH2O (0 ... 12 ftH2O)
• 1.4 bar (20.3 psi) (corresponds
to 14 mH2O (42 ftH2O))
Junction box
• 0 ... 5 mH2O (0 ... 15 ftH2O)
• 1.4 bar (20.3 psi) (corresponds
to 14 mH2O (42 ftH2O))
• 0 ... 6 mH2O (0 ... 18 ftH2O)
• 3.0 bar (43.5 psi) (corresponds
to 30 mH2O (90 ftH2O))
Input
• 0 ... 10 mH2O (0 ... 30 ftH2O)
• 3.0 bar (43.5 psi) (corresponds
to 30 mH2O (90 ftH2O))
• 0 ... 20 mH2O (0 ... 60 ftH2O)
• 6.0 bar (87psi) (corresponds to
50 mH2O (150 ftH2O))
Output
- Marking
Application
II 1 G Ex ia IIC T4 Ga
for connecting the transmitter
cable
Design
Weight
0.2 kg (0.44 lb)
Electrical connection
2 x 3-way (28 to 18 AWG)
Cable entry
2 x M20 x 1.5
Enclosure material
polycarbonate
Vent pipe for atmospheric pressure
Output signal
4 ... 20 mA
Screw for cable strength cord
Measuring accuracy
Acc. to IEC 60770-1
Rated conditions
Error in measurement at limit setting
incl. hysteresis and reproducibility
0.3 % of full-scale value (typical)
Degree of prot. to DIN EN 60529
IP65
Cable hanger
Influence of ambient temperature
Application
Zero and span
• 1 ... 6 mH2O (3 ... 18 ftH2O)
0.45 %/10 K of full-scale value
•  6 mH2O ( 18 ftH2O)
0.3 %/10 K of full-scale value
1/32
SEV 10 ATEX 0149
Siemens FI 01 · 2015 US Edition
for mounting the transmitter
Design
Weight
0.16 kg (0.35 lb)
Material
Galvanized steel, polyamide
© Siemens AG 2015
Pressure Measurement
Transmitters for basic requirements
SITRANS P MPS Transmitter for hydrostatic level
Selection and Ordering data
Article No.
Order code
SITRANS P MPS pressure transmitter for gauge pressure (submersible sensor)
7 MF 1 5 7 0 - 77A 0 7 777
Selection and Ordering data
Article No.
SITRANS P MPS pressure transmitter for gauge pressure (submersible sensor)
7 MF 1 5 7 0 - 77A 0 7 777
2-wire system
2-wire system
Note: Junction box and cable hanger
included in delivery
Note: Junction box and cable hanger
included in delivery
Click on the Article No. for the
online configuration in the PIA Life
Cycle Portal.
With FEP cable
With PE cable
Measuring range
0 ... 2 mH2O
0 ... 4 mH2O
0 ... 5 mH2O
0 ... 6 mH2O
0 ... 10 mH2O
0 ... 20 mH2O
Cable length L
10 m
10 m
25 m
25 m
25 m
25 m
1C
1D
1B
1E
1F
1G
0 ... 6 ftH2O
0 ... 12 ftH2O
0 ... 18 ftH2O
0 ... 30 ftH2O
0 ... 60 ftH2O
32 ft
32 ft
82 ft
82 ft
82 ft
1K
1L
1M
1N
1P
Special cable lenght/Special measuring range1)
Please add „-Z“ to Article No. and
specify Order code and plain text.
Note: Indication of measuring range
Y01 is always necessary.
Order code
9A
H. .
+
Y01
3m
5m
7m
10 m
15 m
H1A
H1B
H1C
H1D
H1E
20 m
25 m
30 m
40 m
50 m
H1F
H1G
H1H
H1 J
H1K
60 m
70 m
80 m
90 m
100 m
H1L
H1M
H1N
H1P
H1Q
125 m
150 m
175 m
200 m
225 m
H1R
H1S
H1T
H1U
H1V
250 m
275 m
300 m
350 m
400 m
H 1W
H1X
H2A
H2B
H2C
450 m
500 m
550 m
600 m
650 m
H2D
H2E
H2F
H2G
H2H
700 m
750 m
800 m
850 m
900 m
H2 J
H2K
H2L
H2M
H2N
950 m
1000 m
H2P
H2Q
Measuring range
0 ... 2 mH2O
0 ... 4 mH2O
0 ... 5 mH2O
0 ... 6 mH2O
0 ... 10 mH2O
0 ... 20 mH2O
Cable length L
10 m
10 m
25 m
25 m
25 m
25 m
5C
5D
5B
5E
5F
5G
0 ... 6 ftH2O
0 ... 12 ftH2O
0 ... 18 ftH2O
0 ... 30 ftH2O
0 ... 60 ftH2O
32 ft
32 ft
82 ft
82 ft
82 ft
5K
5L
5M
5N
5P
Special cable lenght/Special measuring range1)
Please add „-Z“ to Article No. and
specify Order code and plain text.
Note: Indication of measuring range
Y01 is always necessary.
9A
H. .
+
Y01
3m
5m
7m
10 m
15 m
H5A
H5B
H5C
H5D
H5E
20 m
25 m
30 m
40 m
50 m
H5F
H5G
H5H
H5J
H5K
60 m
70 m
80 m
90 m
100 m
H5L
H5M
H5N
H5P
H5Q
125 m
150 m
175 m
200 m
225 m
H5R
H5S
H5T
H5U
H5V
250 m
275 m
300 m
350 m
400 m
H 5W
H5X
H6A
H6B
H6C
450 m
500 m
550 m
600 m
650 m
H6D
H6E
H6F
H6G
H6H
700 m
750 m
800 m
850 m
900 m
H6J
H2K
H6L
H6M
H6N
950 m
1000 m
H6P
H6Q
Siemens FI 01 · 2015 US Edition
1/33
1
© Siemens AG 2015
Pressure Measurement
Transmitters for basic requirements
SITRANS P MPS Transmitter for hydrostatic level
Selection and Ordering data
SITRANS P MPS pressure transmitter for gauge pressure (submersible sensor)
Article No.
Order code
7 MF 1 5 7 0 - 77A 0 7 777
■ Dimensional drawings
Protective cap
Cable sheath + (brown)
2-wire system
Vent pipe
Ø 27
(1.1
diam.)
Note: Junction box and cable hanger
included in delivery
Strength
cord (white)
Explosion protection
1
2
Cable sheath 8.3 (0.33) diam. (black, PE/HFFR)
Flexible cable with 0.5 mm2 (0.00078 inch2) cross-section
Vent pipe 1 (0.04) diam. (inner diameter)
Protective cap with 4 x 3 diam. (4 x 0.12 diam.) holes (black, PA)
C11
Indication of measuring range (only at
special cable lengths) in „... to ...
mH2O“ or „... to ... ftH2O“
Y01
Accessories (as spare part)
Article No.
Junction box
for connecting the transmitter cable
7MF1570-8AA
Cable hanger
7MF1570-8AB
for attachment of transmitter
Power supply units see Chap. 7 "Supplementary Components".
Special measuring ranges of between 0 ... 1 mH2O (0 ... 3 ftH2O)
and 0 ... 200 mH2O (0 ... 656 ftH2O) and special cable lengths of up to
1000 m (3281 ft) are possible.
For evaluation of the maximum possible cable length following data have
to be regarded:
Transmitter: Ci = 0 µF, Li = 0 µH
Cable: Ck = 0.19 nF per meter cable, Lk = 1.5 µH per meter cable
The maximum permitted data of the transmitter’s power supply have to be
considered!
The length of free hanging cable should not exceed 375 m (1230 ft).
Note: Due to mounting reasons it has to be considered that the cable
always must be longer than the height of the liquid column to be measured.
SITRANS P MPS pressure transmitters, dimensions in mm (inch)
50 (1.97)
57 (2.25)
22
(0.87)
M20x1,5
30
(1.2)
Order code
Quality inspection certificate (factory
calibration) to IEC 60770-2, add „-Z“
to Article No. and add Order code.
Mounting
hole
Venting
valve
M20x1,5
22
(0.87)
65 (2.56)
Junction box, dimensions in mm (inch)
19
(0.75)
175 (6.9)
1)
Screen
6
Further designs
- (blue)
L
94 (3.7)
Approvals
• with drinking water approval to
WRAS and ACS (with EPDM gasket)
158 (6.2)
30
(1.2)
• None
• with type of protection "intrinsic
safety" (Ex II 1 G Ex ia IIC T4)
79 (3.1)
1
48 (1.9)
Cable hanger, dimensions in mm (inch)
1/34
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for basic requirements
SITRANS P MPS Transmitter for hydrostatic level
■ More information
Determination of the measuring range in case of media with
a density  1000 kg/m3 (medium  water)
H
r
Calculation of the measuring range:
p=xgxH
with:
 = density of medium
g = local acceleration due to gravity
H = maximum level
Example:
Medium: Diesel fuel,  = 850 kg/m3
Acceleration due to gravity: 9.81 m/s2
Start-of-scale: 0 m
Maximum level: 6.2 m
Cable length: 7 m, FEP cable
Calculation:
p = 850 kg/m3 x 9.81 m/s2 x 6.2 m
p = 51698.7 N/m2
p = 517 mbar
Transmitter to be ordered:
7MF1570-9AA02-Z, H5C + Y01
Y01: 0 ... 517 mbar
Siemens FI 01 · 2015 US Edition
1/35