Power Switching & Controls For Business-Critical ContinuityTM Edco SLAC Series AC Power/Signal The Edco SLAC Series suppressor was specifically designed to protect electronic instruments used by the water/wastewater industries. It combines hybrid AC power protection and signal line protection in a NEMA-4X polycarbonate case. The AC power suppressor can supply up to 1875 Watts and has a 15 Amp replaceable fuse to prevent overloading of the protective elements. A “Power ON” LED provides visual indication that power is applied to instruments. Signal line protection is accomplished by the Edco PC642 Series available in a variety of voltage clamps. Signal current can be monitored by reading the voltage across the 10 ohm, 1% resistors (TP1 & TP2 or TP3 & TP4). All leads going to the Edco SLAC board are terminated by quick disconnect or barrier block connectors to facilitate easy removal for service or replacement. Features General Technical Specifications AC Power Technology Three-Stage Series Hybrid Voltage Clamp 325 VAC Input Voltage 120 VAC 50/60 Hz Output Current 15 Amps Max. Response Time <5 Nanoseconds Maximum Surge Current (8x20 µs) 39 kA Occurrences at 500 Amps >50 Parameter Normal Mode (L-N) Common Mode (L-G) (N-G) IEEE 587 CAT A Ring* 172 V 280 V IEEE 587 CAT B Ring* 205 V 280 V IEEE 587 CAT B Impulse* 330 V 360 V Lightning and surge suppression for AC power and low-voltage signal lines Series hybrid AC suppressor/filter Plug-in protection module 15 Amp replaceable fuse Test jacks for signal line monitoring “Power ON” indicator Optional stainless steel or fiberglass enclosure 5 year warranty *Measured from zero volts, 90° Phase angle Signal Line Technology Three-Stage Series Hybrid Peak Surge Current (8x20 µs) 10 kA Response Time <5 Nanoseconds Voltage Clamp (customer selected) 8–200 Volts Series Resistance 5 ohm (Typical) Certification UL 1449 3rd Edition (2009), Type 2 Optional Enclosure NEMA-4X Stainless Steel or Fiberglass Continuous Hinge Nominal Outside Dimensions (Inches) Standard Enclosure NEMA-4X Corrosion Resistant Polycarbonate Base Resists Temperatures up to 250 deg. F Smoked Grey Transparent Cover Flammability Rating UL94-5V Knockouts for 20mm and 32mm Nominal Outside Dimensions (inches): H=7.1, W=7.1, D=3.0 Bosses for 6-32 x 3/8 self-tapping screws Maximum Protection-Total Insulation H=10, W=8, D=4 UNPROTECTED (FIELD) SIDE PROTECTED (EQUIP) SIDE 4/20 mA SIGNAL 4/20 mA SIGNAL UNPROTECTED (FIELD) SIDE PROTECTED (EQUIP) SIDE 120 VAC POWER 120 VAC POWER Installation Ordering Information Signal Line Connections: *For Standard Unit order part # SLAC-12036 • Connect GND Terminal to Local Ground using #12 AWG wire minimum SLAC — 1 2 3 LC • L1 and L2 – Connect for Signal Pair #1 1 0 No Enclosure • L3 and L4 – Connect for Signal Pair #2 1 Polycarbonate Case (Standard) • Terminals accept #24-#14 AWG wire, torque to 4kg-cm 2 Stainless Steel (Optional) 3 Fiberglass (Special) 0 Without PC642 Signal Protector 2 With PC642 036 PC642 Voltage Clamp Selection • “S” Connection for Cable Shield ( If Applicable ) CAUTION: Do not place this product in service on any signal line capable of suppying more than 150 milliamperes continuously. 2 3 = = = 043 AC Power Connections: • Connect AC Power as Marked on Case using #12 AWG wire minimum • Keep 120 VAC Power feed separate from Low Voltage 4/20 mA feed Emerson Network Power. The global leader in enabling Business-Critical ContinuityTM. AC Power Embedded Computing Infrastructure Management & Monitoring Connectivity Embedded Power Outside Plant Racks and Integrated Cabinets DC Power Industrial Power Power Switching & Controls Services Emerson Network Power Contact information Thermal Management www.emersonnetworkpower.com/surge Headquarters Surge Protection 100 Emerson Parkway Binghamton, NY 13905 T: (607) 721-8840 T: (800) 288-6169 F: (607) 722-8713 E: [email protected] IO-50124 10/13 Rev. 3 Printed in USA Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2013 Emerson Electric Co.