ACU+ Controller Data Sheet

DC Power for
Business-Critical Continuity™
ACU+ Controller
M820B, M821B, M820D, M821D, M820N
Key Features
nFlexible and scalable to satisfy your
present and future needs with
configurable IB (interface boards)
nEasily configurable file
upload/download minimizes
installation time
nLong battery life-span –
sophisticated boost charge
management
nUnattended battery test –
advanced scheduled test/constant
test/fast test
nHigh quality failure information –
programmable logic controller
provides intelligent alarm setup
Designed for global use, the ACU+ Controller
withstands high telecom standards, providing
outstanding reliability and availability.
Description
The ACU+ is an advanced control unit designed for DC power applications. It can
provide remote monitoring of the telecom site's AC mains supply, DC power plant,
battery backup, diesel generator and site environment etc.
Featuring advanced battery management such as sophisticated boost charge
control, remaining time and capacity prediction, constant current test, scheduled
test and short test, and Battery Low Voltage Disconnection (BLVD), the ACU+
realizes easy and predictive battery maintenance. Furthermore, with basic energy
saving and power split function, the ACU+ is a highly cost-efficient product.
The information and alarms from a specific site can be monitored or checked with
a simple web browser or special monitoring software. When using a web browser,
no additional software is needed, and the web browser login is password
protected.
nLower operating cost –
energy-saving standby function
for rectifier
M820B
M821B
2012.09
M820D
M821D
M820N
1
ACU+ Controller
Technical Specifications
Diagram
General
Power Supply
Power Consumption
Operating Temperature Range
Relative Humidity
EMC
Safety
Approvals
Network Operation Center
Net Management
Centre
19 to 60VDC
5W
- 40°C to + 75°C/- 40°F to + 167°F
0 to 90%
EN 300 386, 2001 class B, FCC part 15 class B
IEC 60950-1, EN 60950-1, UL 60950-1
CE, UL and NEBS level 3
SNMP
ENEC
IE
TCP
HTTP
TCP/IP
PSTN,GSM
MODEM
DC POWER
RS232
Mechanical Data
Dimensions (H x W x D)
Standard Installation Methods
Weight
Inputs/Outputs
Model
Display
Communication
Protocol
M820B and M821B: 42 x 86.6 x 211.5mm
1.65 x 3.41 x 8.33inch
M820D, M821D and M820N:86.6 x 86.8 x 211.5mm
3.41 x 3.42 x 8.33inch
Hot pluggable in stand-alone or embedded power plants
< 1 kg / 2.2 Ibs
M820B
M821B
LCD with 8 x 16 characters
M820D
M821D
M820N
LCD with 4 x 16 characters
RS232, 10/100M
RS232, RS485, Ethernet, USB
ethernet, TCP/IP,
SNMP, web server
HTTP, SNMP, EEM, SocTpe, Rsoc
Inputs
2 battery
2 battery
currents, 1 load
currents, 1 load
current, 1 bus
current, 1 bus
Analog voltage, 2 battery
voltage, 2 battery
voltages,
voltages, 2
3 temperatures,
temperatures
3 AC voltages
1 input for status
of SPD auxiliary
1 input for status
contacts, 10 load
of SPD auxiliary
Digital
fuses, 4 battery
contacts
fuses, bi-stable
contactor status
2 LVD mono &
Outputs
bistable
None
contactors
3 DC systen
voltages, 3 DC
system currents, 3
temperatures, 3
AC voltages
Refer to
M820B
Refer to
M821B
1 input for status
of SPD auxiliary
contacts
10 load fuses,
4 battery fuses
2 LVD mono &
bistable
contactors
Examples of Alarms
DC Power Plant Alarms
AC mains failure, Rectifier failure, DC/DC converter failure, High
voltage shutdown, Fan failure, Thermal derating (of rectifier
output due to high temperature)
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
ACU+
CAN
PSU
PSU
PSU
SM
DU
USB memory
stick
I2C
conv
IB1 or
IB2
RS485
EIB
SM
Modules
Large
DU
ABBREVIATIONS
PSTNPublic Switched Telephone
Network, an ordinary
telephone line
IE Internet Explorer
ENEC EnergyMaster™ Emerson Network
Energy Center, multi-platform,
multi-user, distributed multilanguage web environment for
monitoring of Emerson Network
Power DC, HPAC and UPS
equipment
PSU Power Supply Unit (AC/DC
converter/rectifier)
SM DU Supervision Module for additional
alarms in extension cabinets
EIB Extension Interface Board
IB Interface Board
Ordering Information
Model
Part Number / Description
M820B
1M820BAXX / ACU+ controller
M821B
1M821BAXX / ACU+ controller
M820D
1M820DAXX / ACU+ controller
M821D
1M821DAXX / ACU+ controller
M820N
1M820NXX / ACU+ controller
Optional Interface Board
IB1
4 relay outputs, 4 digital inputs
8 relay outputs, 8 digital inputs,
IB2
2 temperatures
5 relay outputs, 8DC voltages,
EIB
3DC currents, 2 temperatures
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
2012.09