420 Surge Protective Device Technical Specification (SS-70104)

400 Series
420 Surge Protective Device
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Maximum Surge Current Rating
Operating Frequency Range
Location Type
Nominal Discharge Current (In)
Status Indication
Certifications
Standard Enclosure
Weights
Warranty
120VAC 150%, all others 115%
200kAIC
50kA per Mode/50kA per Phase
47-63Hz
Type 1 / Type 2
20kA
Green/Red LED, Relay Alarm Contacts
ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL
(ROHS Compliant)
NEMA Type 4X
1.2 lbs (.54 kg)
5 Year Replacement
ANSI/UL 1449 Third Edition, Type 1 VPR’s
Source
Configuration
SA, YA
YC
YD
DB
DF
DG
Model Number
420SA05BWRJ1S
420YA05BWRJ1S
420YC05BWRJ1S
420YD05BWRJ2S
420DB05EWRJ1S
420DF05EWRJ1S
420DG05EWRJ2S
Surge
Rating
50kA Mode
50kA Phase
L-N
L-G
L-L
N-G
700V
1200V
1500V
N/A
N/A
N/A
1200V
2500V
3000V
N/A
N/A
N/A
1200V
2500V
2500V
1200V
2500V
2500V
700V
1200V
1500V
N/A
N/A
N/A
Source Configuration
(Consult Factory for additional source configurations)
“SA” - 120/240VAC, 120/208VAC, Single Split Phase, 3W+G
Modes Of
Protection
L-N, N-G
“YA” - 120/208VAC, 127/220VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 1
“YC” - 277/480VAC, 254/440VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 1
“YD” - 346/600VAC, Three Phase WYE, 4W+G
L-N, N-G
Type 2
“DB” - 240VAC, Three Phase DELTA, 3W+G
L-L
Type 1
UL Location Type
Type 1
“DF” - 480VAC, Three Phase DELTA, 3W+G
L-L
Type 1
“DG” - 600VAC, Three Phase DELTA, 3W+G
L-L
Type 2
For applications requiring CUL approval, change the SPD model number from a UL Type 1 (420xxxxxxxx1x) to a UL Type 2 (420xxxxxxxx2x)
Dimensions:
Top View
Side View