460L Surge Protective Device; (Discrete 10-Mode) Technical Specification (SS-70113)

400 Series
460 Surge Protective Device – Discrete 10-Mode
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Maximum Surge Current Rating
Connection Types
Operating Frequency Range
EMI/RFI Noise Rejection
UL 1449 Location Type
UL1449 Nominal Discharge Current (In)
Status Indication
Certifications
Discrete 10-Mode Option
The 460 offers a Discrete “10-Mode” protection option, (up to
200kA/mode, 600kA/phase when adding L-N+L-G+L-L modes).
This may be a requirement on some commercial projects based
on performance advantage claims; including increased operational
life, enhanced durability due to lower component stress, improved
transient response and increased surge current sharing. We have
a long history of achieving those same results with our standard
mode/connection methods and configurations. However, for those
projects that are specified with this requirement, the 460 is
available in a Discrete 10-Mode construction format.
IEC Class
Standard Enclosure
Warranty
120VAC 150%, all others 115%
200kAIC
(“05”)
50kA Per Mode/150kA Per Phase
(“10”) 100kA Per Mode/300kA Per Phase
(“20”) 200kA Per Mode/600kA Per Phase
Compression Lug/Terminal Block
Rotary Disconnect Switch
47-63Hz
40dB Max (Type 1), 60dB Max (Type 2)
Type 1 / Type 2
20kA
Green/Red LED, Audible Alarm, Alarm Test/Silence
Feature, Relay Alarm Contacts, N-G LED,
Surge Event LED Surge Counter, ATDS
ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL
CE, IEC61643-11
Class I/II
NEMA Type 12/4
10 Years
ANSI/UL 1449 Third Edition, Type 1 VPR’s
Source Configuration
SA, YA
YC
YD
DB / DF / DG
L-N
800V
1200V
1500V
N/A
L-G
800V
1200V
1500V
1200V / 1800V / 2000V
Model Number Configurator
0
L
N-G
800V
1200V
1500V
N/A
CUL Approvals
_____________
4 6
L-L
1200V
2000V
2500V
1200V / 2000V / 3000V
For all applications requiring CUL approvals,
change the SPD model number from a UL Type 1
(460xxxxxxxx1x) to a UL Type 2 (460xxxxxxxx2x)
1 S
Advanced Transient
Detection System
Configuration & Voltage
SA
Single Phase,
3W+G
(L1, L2, N, G)
YA
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
Three Phase
WYE, 4W+G
(L1, L2, L3, N, G)
YC
YD
DB
DF
DG
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
Three Phase
Delta, 3W+G
(L1, L2, L3, G)
120/240 VAC
120/208 VAC,
127/220 VAC
05
10
20
277/480 VAC,
254/440 VAC
346/600 VAC
220 VAC, 230
VAC, 240 VAC
N
R
Additional Accessories
Surge Rating
50kA Per Mode
150kA Per Phase
100kA Per Mode
300kA Per Phase
200kA Per Mode
600kA Per Phase
Connection Type
Compression
Lug/Terminal Block
Rotary Disconnect
Switch
480 VAC
600 VAC
E
LL
CL
TG
A Web-Based Power Quality Monitor
Integrated within a Surge Protection Device
S
Standard
X
Consult Factory for additional source
configurations, Surge Ratings,
Monitoring Options, Enclosure
Ratings, Etc.
Monitoring Option
Red & Green LEDs, Relay Alarm Contacts
Audible Alarm, N-G LED & Surge Event
LED
Red & Green LEDs, Relay Alarm Contacts
Audible Alarm, N-G LED & Surge Counter
Advanced Transient
Detection System
See publication SL-70109, TS-70109
1.34
[34]
C




Real-Time Measurements
Event Logging with Time/Date Stamp
Embedded Web Page
Ethernet, MODBUS, RS-485
Communications
 SPD Health Status - % Protection remaining
 LCD Display
Dimensional Information
Dimensional Information
Surge
A
B
C
D
E
Weight
Rating
50kA-150kA 12
12
6
10.75 10.88 21.0 lbs
Per Mode [305] [305] [152] [273] [276] (9.5 kg)
A
100 Emerson Parkway
Binghamton, NY 13905
P (607) 721 8840
P (800) 288 6169
F (607) 722 8713
E [email protected]
D
200kA
Per Mode
16
14
8
16.75 12
35.0 lbs
[406] [356] [203] [425] [305] (15.9 kg)
Units with Advanced Transient Detection System monitoring option.
Surge
Rating
0.31
[8]
B
All
A
B
C
D
E
16
16
8
16.75 12
[406] [406] [203] [425] [305]
Weight
see
weights
above
SS-70113 Rev 2 1-15