400 Series 425 Surge Protective Device Submittal Specification General Specifications Maximum Continuous Operating Voltage 120VAC 150%, all others 115% Short Circuit Current Rating (SCCR) 200kAIC Maximum Surge Current Rating 50kA per Mode/100kA per Phase Operating Frequency Range 47-63Hz Location Type Type 1 / Type 2 Nominal Discharge Current (In) 20kA Status Indication Green/Red LED, Relay Alarm Contacts, Alarm Certifications ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL (ROHS Compliant) Standard Enclosure NEMA Type 4X Weights 1.9 lbs (.86 kg), Warranty 10 Year Replacement ANSI/UL 1449 Third Edition, Type 1 VPR’s Source Configuration SA, YA YC YD DB DF DG Model Number 425SA05AWAJ1S 425YA05AWAJ1S 425YC05AWAJ1S 425YD05AWAJ2S 425DB05AWAJ1S 425DF05AWAJ1S 425DG05AWAJ2S Surge Rating 50kA/ Mode 100kA/ Phase L-N L-G L-L N-G 700V 1200V 1500V N/A N/A N/A 700V 1200V 1500V 1200V 1800V 2000V 1200V 2000V 2500V 1200V 2500V 2500V 700V 1200V 1500V N/A N/A N/A Source Configuration (Consult Factory for additional source configurations) “SA” - 120/240VAC, 120/208VAC, Single Split Phase, 3W+G Modes Of Protection L-N, L-G, N-G, L-L UL Location Type Type 1 “YA” - 120/208VAC, 127/220VAC, Three Phase WYE, 4W+G L-N, L-G, N-G, L-L Type 1 “YC” - 277/480VAC, 254/440VAC, Three Phase WYE, 4W+G L-N, L-G, N-G, L-L Type 1 “YD” - 346/600VAC, Three Phase WYE, 4W+G L-N, L-G, N-G, L-L Type 2 “DB” - 240VAC, Three Phase DELTA, 3W+G L-G, L-L Type 1 “DF” - 480VAC, Three Phase DELTA, 3W+G L-G, L-L Type 1 “DG” - 600VAC, Three Phase DELTA, 3W+G L-G, L-L Type 2 For applications requiring CUL approval, change the SPD model number from a UL Type 1 (425xxxxxxxx1x) to a UL Type 2 (425xxxxxxxx2x) Dimensions: Top View Side View 100 Emerson Parkway Binghamton, NY 13905 P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E [email protected] SS-70109 Rev 0 8-14