560 Surge Protective Device; Technical Specification; Motorola R56 (SS-70102)

500 Series
Motorola R56 Approved Surge Protective Device
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Operating Frequency Range
Connection Type
EMI/RFI Noise Rejection
Maximum Surge Current Capacity
Motorola R56 Unit Type
UL1449 Location Type (UL)
UL1449 Nominal Discharge Current (In)
Standard Status Indication
Certifications
Standard Enclosure
Weight
Warranty
125%
65kAIC
47-63Hz
Wire Compression Lugs
63dB Max
570: 20kA Per Mode (SAD) & 160kA Per Mode (MOV)
560: 160kA Per Mode (MOV)
570: Type 1 (SAD/MOV Hybrid)
560: Type 2 (MOV only)
Type 1
20kA
Status LED’s, Module LED’s, Relay Alarm Contacts
ANSI/UL 1449 Third Edition, Motorola R56
UL 1283, cUL(Type 2 locations)
NEMA 4X
Single Phase = 28 lbs. [12.7 kg]
3 Phase = 32 lbs. [14.5 kg]
10 Years Parts, 5 Years Labor
Model Number Information
Motorola R56
Location Type
Source Configuration
SPD Model Number
R56 Type 1
Hybrid SAD/MOV
120/240VAC, 120/208VAC
Single “Split” Phase, 3W+G
570SA16FNRJ1S
20kA Per Mode (SAD) &
160kA Per Mode (MOV)
120/208VAC, 127/220VAC
3 Phase, WYE, 4W+G
570YA16FNRJ1S
120/240VAC, 120/208VAC
Single “Split” Phase, 3W+G
560SA16FNRJ1S
120/208VAC, 127/220VAC
3 Phase, WYE, 4W+G
560YA16FNRJ1S
R56 Type 2
MOV Only
160kA Per Mode (MOV)
Model Number
570SA16FNRJ1S
570YA16FNRJ1S
560SA16FNRJ1S
560YA16FNRJ1S
UL 1449 Third Edition
Type 1 VPRs
700Vpk
(L-N)
1000Vpk
(L-L)
CUL Approvals
For all applications requiring CUL approvals,
change the SPD model number from a UL Type 1
(5xxxxxxxxxx1x) to a UL Type 2 (5xxxxxxxxxx2x)
Dimensional Information
13.34”
[338.8]
14.75”
[374.7]
100 Emerson Parkway
Binghamton, NY 13905
P (607) 721 8840
P (800) 288 6169
F (607) 722 8713
E [email protected]
15.49”
[393.4]
7.96”
[202.2]
0.32”
[8.1]
10.00”
[254.0]
SS-70102 Rev 0 1-15