500 Series Motorola R56 Approved Surge Protective Device Submittal Specification General Specifications Maximum Continuous Operating Voltage Short Circuit Current Rating (SCCR) Operating Frequency Range Connection Type EMI/RFI Noise Rejection Maximum Surge Current Capacity Motorola R56 Unit Type UL1449 Location Type (UL) UL1449 Nominal Discharge Current (In) Standard Status Indication Certifications Standard Enclosure Weight Warranty 125% 65kAIC 47-63Hz Wire Compression Lugs 63dB Max 570: 20kA Per Mode (SAD) & 160kA Per Mode (MOV) 560: 160kA Per Mode (MOV) 570: Type 1 (SAD/MOV Hybrid) 560: Type 2 (MOV only) Type 1 20kA Status LED’s, Module LED’s, Relay Alarm Contacts ANSI/UL 1449 Third Edition, Motorola R56 UL 1283, cUL(Type 2 locations) NEMA 4X Single Phase = 28 lbs. [12.7 kg] 3 Phase = 32 lbs. [14.5 kg] 10 Years Parts, 5 Years Labor Model Number Information Motorola R56 Location Type Source Configuration SPD Model Number R56 Type 1 Hybrid SAD/MOV 120/240VAC, 120/208VAC Single “Split” Phase, 3W+G 570SA16FNRJ1S 20kA Per Mode (SAD) & 160kA Per Mode (MOV) 120/208VAC, 127/220VAC 3 Phase, WYE, 4W+G 570YA16FNRJ1S 120/240VAC, 120/208VAC Single “Split” Phase, 3W+G 560SA16FNRJ1S 120/208VAC, 127/220VAC 3 Phase, WYE, 4W+G 560YA16FNRJ1S R56 Type 2 MOV Only 160kA Per Mode (MOV) Model Number 570SA16FNRJ1S 570YA16FNRJ1S 560SA16FNRJ1S 560YA16FNRJ1S UL 1449 Third Edition Type 1 VPRs 700Vpk (L-N) 1000Vpk (L-L) CUL Approvals For all applications requiring CUL approvals, change the SPD model number from a UL Type 1 (5xxxxxxxxxx1x) to a UL Type 2 (5xxxxxxxxxx2x) Dimensional Information 13.34” [338.8] 14.75” [374.7] 100 Emerson Parkway Binghamton, NY 13905 P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E [email protected] 15.49” [393.4] 7.96” [202.2] 0.32” [8.1] 10.00” [254.0] SS-70102 Rev 0 1-15