Datenblatt

For more information, please visit the product page.
date
05/06/2015
page
1 of 4
SERIES: PSE-1200 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
FEATURES
up to 1200 W continuous power
low profile sub-1U package
I2C communication for monitoring and control
redundant (N+1) operation
blind mate connections for hot-swap
power factor correction
active current sharing
remote on/off control, power good
efficiency up to 90%
T
o
of N
C
rt
Rheinla
nd
UV
, I
nc.
•
•
•
•
•
•
•
•
•
h A
ca
meri
US
MODEL
PSE-1200-12
Notes:
output
voltage
output
current
output
power1,2
ripple
and noise
efficiency3
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
12
100
1200
120
90
1. At 115 Vac input, maximum of 1000 W
2. At 230 Vac input, maximum of 1200 W
3. At 230 Vac input, 50% load.
PART NUMBER KEY
PSE-1200 - 12 - CXX
Base Number
Output Voltage
cui.com
Reserved for Custom
Configurations
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1200 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 2 of 4
INPUT
parameter
conditions/description
min
voltage
typ
90
frequency
50
current
at 115 Vac, 1000 W
at 230 Vac, 1200 W
inrush current
half cycle, cold start, 25°C
at 115 Vac, 60 Hz
at 230 Vac, 50 Hz
leakage current
power factor correction
0.95
0.99
min
typ
max
units
264
Vac
60
Hz
10.2
6.2
A
A
25
30
A
A
1.5
mArms
max
units
OUTPUT - V1 (MAIN OUTPUT)
parameter
conditions/description
regulation
transient response
±2
25% step load, recovery to 1% within 1 ms
%
2
%
max
units
OUTPUT - VSB (STANDBY OUTPUT)
parameter
conditions/description
output voltage
VSB1
VSB2
min
typ
output current
VSB1
VSB2
500
250
mA
mA
ripple and noise
VSB1
VSB2
240
150
mVp-p
mVp-p
regulation
VSB1
VSB2
10.5
14.5
Vdc
%
parameter
conditions/description
min
typ
max
units
I C interface
I C (SCL/SDA); addresses (A0, A1, A2)
remote sense
main only, compensates for VDrop
current share
signal wire active current share
parallel operation
parallel non-redundant or N+1
typ
max
units
12
5
±5
Vdc
Vdc
STATUS & CONTROL
2
2
PROTECTIONS
parameter
conditions/description
min
over voltage protection
inception point shutdown
120
%
over current protection
V1: hiccup mode after 100 ms auto recovery
120
%
over temperature protection
output shut down, auto recovery
SAFETY & COMPLIANCE
parameter
conditions/description
safety approvals
cTUVus UL60950-1, CE (LVD)
min
emissions
FCC 15 Sub Part J, Class A, EN55022 Class A
harmonic compliance
EN61000-3-2 Class A
surges (mains)
IEC/EN 61000-4-5
voltage dips/interruptions
IEC/EN 61000-4-11
RoHS
2011/65/EU
cui.com
typ
max
units
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1200 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 3 of 4
ENVIRONMENTAL
parameter
conditions/description
min
operating temperature
storage temperature
max
units
0
typ
50
°C
-40
85
°C
MECHANICAL
parameter
conditions/description
dimensions
10.00 x 4.00 x 1.60 (254.0 x 102.4 x 40.6 mm)
min
cooling / airflow
integral high performance 38 mm fan, air inlet at
face; exhaust at connector
input / output connector
FCI P/N 51939-103LF
mates with FCI P/N 51866-025LF
hot-swap capability
fully hot-swappable, blind mate connector
typ
max
units
inches
MECHANICAL DRAWING
units: inches [mm]
tolerance:
X.XX ±0.02 [0.50]
X.XXX ±0.010 [0.25]
P1
P2
P3
P4
P5
P6
P7
P8
P9
D
1
2
3
4
5
6
C
B
A
INPUT / OUTPUT CONNECTOR
Pins
Function
Pins
Function
Pins
Function
Pins
Function
Pins
P1
Line
P2
Neutural
A1
ISHARE
A2
I2C clock (SCL)
P3
Earth/Ground
A3
P4
-12 V
A4
P5
-12 V
P6
-12 V
P7
P8
P9
B1
- Sense
C1
Secondary Return
D1
+ Sense
B2
Reserved
C2
V Margin
D2
Short Pin
A1 address (I2C)
B3
A0 Address (I2C)
C3
12 VSB
D3
EEPROM DAT (SDA)
--
B4
Reserved
C4
5 VSB
D4
A2 Address (I2C)
A5
AC Fail
B5
Module Present (out)
C5
Module Present (in)
D5
--
A6
Signal Return
B6
Module Alarm
C6
Module Disable
D6
Temp Alarm
+12 V
--
--
--
--
--
--
--
--
+12 V
--
--
--
--
--
--
--
--
+12 V
--
--
--
--
--
--
--
--
cui.com
Function
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1200 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 4 of 4
REVISION HISTORY
rev.
1.0
description
date
initial release
05/06/2015
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.