データシート

For more information, please visit the product page.
date
05/07/2015
page
1 of 4
SERIES: PSE-1800 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
FEATURES
up to 1800 W continuous power
1U package
I2C communication for monitoring and control
redundant (N+1) operation
blind mate connections for hot-swap
power factor correction
3.3 Vdc (0.5A) standby voltage
DROOP current sharing
single I/O connector for AC input, DC output & signals
remote on/off control, power good signal
o
of N
C
rt
.
T
Rheinla
nd
UV
, I
nc
•
•
•
•
•
•
•
•
•
•
h A
ca
meri
US
MODEL
output
voltage
output
current
output
power1,2
ripple
and noise
efficiency3
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
48
37.5
1800
480
85
PSE-1800-48
Notes:
1. At 90~180 Vac input, maximum of 1000 W.
2. At 180~264 Vac input, maximum of 1800 W.
3. At 90 Vac input.
PART NUMBER KEY
PSE-1800 - 48 - CXX
Base Number
Output Voltage
cui.com
Reserved for Custom
Configurations
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1800 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/07/2015 │ page 2 of 4
INPUT
parameter
conditions/description
min
voltage
frequency
max
units
90
typ
264
Vac
50
60
Hz
current
at 90 Vac, full load
11
A
inrush current
half cycle, cold start, 25°C
at 115 Vac, 60 Hz
at 230 Vac, 50 Hz
20
40
A
A
1.5
mArms
max
units
leakage current
power factor correction
0.95
0.98
min
typ
OUTPUT - V1 (MAIN OUTPUT)
parameter
conditions/description
regulation
±3
transient response
25% step load, recovery to 1% within 1 ms, slew
rate 1 A/µs
hold-up time
at full load
in redundant operation
%
3
12
20
%
ms
ms
OUTPUT - V2 (STANDBY OUTPUT)
parameter
conditions/description
min
output voltage
typ
max
3.3
output current
0
ripple and noise
regulation
units
Vdc
0.5
A
50
mVp-p
±5
%
STATUS & CONTROL
parameter
conditions/description
I2C interface
SCL 1000 kHz clock rate SDA data line
remote sense
main oputput
remote enable
“active low” enables main output, last-mate / firstbreak enable pin
current share
droop share
status
AC OK, DC OK and OTP_OK (open collector, active
“low”=ok); and PS_Present
LED indicator
AC OK & DC OK indicators
min
typ
max
units
typ
max
units
60
120
Vdc
%
120
%
max
units
PROTECTIONS
parameter
conditions/description
min
over voltage protection
V1
V2
110
over current protection
followed by latching shutdown after 2 s
over temperature protection
output shut down, auto recovery
SAFETY & COMPLIANCE
parameter
conditions/description
min
safety approvals
cTUVus EN60950-1, CE (LVD)
emissions
FCC 15 Sub Part J, Class A, EN55022 Class A, VCCI Class A
harmonic compliance
EN61000-3-2 Class A
surges (mains)
IEC/EN 61000-4-5
voltage dips/interruptions
IEC/EN 61000-4-11
cui.com
typ
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1800 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/07/2015 │ page 3 of 4
SAFETY & COMPLIANCE (CONTINUED)
parameter
conditions/description
MTBF
as per Telcordia SR332, 40°C, full load
min
RoHS
2011/65/EU
typ
max
500,000
units
hours
ENVIRONMENTAL
parameter
conditions/description
min
operating temperature
storage temperature
max
units
0
typ
55
°C
-40
85
°C
max
units
MECHANICAL
parameter
conditions/description
min
dimensions
11.00 x 4.00 x 1.60 (279.4 x 101.6 x 40.6 mm)
cooling / airflow
internal high performance 38 mm fan, air inlet at
face; exhaust at connector
input / output connector
FCI P/N 51939-531LF
mates with FCI 51915-299LF
hot-swap capability
fully hot-swappable, blind mate connector
typ
inches
MECHANICAL DRAWING
units: inches [mm]
tolerance:
X.XX ±0.02 [0.50]
X.XXX ±0.010 [0.25]
INPUT / OUTPUT CONNECTOR
Pins
Function
Pins
Function
Pins
Function
Pins
Function
Pins
Function
P1
No Blade
A1
+V Sense
B1
ISHARE
C1
-V Sense
D1
Reserved
P2
+48 V
A2
V Pgm
B2
I2C Address A0
C2
I2C Address A1
D2
I2C Address A2
P3
+48 V
A3
Reserved
B3
Reserved
C3
Reserved
D3
Reserved
P4
No Blade
A4
AC_OK_L
B4
DC_OK_L
C4
PS_Present_L
D4
OTP_OK_L
P5
-48 V
A5
Signal Return
B5
I C SCL
C5
I C SDA
D5
+3.3 VSB
2
2
P6
-48 V
A6
-3.3 VSB
B6
Reserved
C6
Reserved
D6
Remote_On _L
(short pin)
P7
Earth
--
--
--
--
--
--
--
--
P8
Neutral
--
--
--
--
--
--
--
--
P9
Line
--
--
--
--
--
--
--
--
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-1800 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/07/2015 │ page 4 of 4
REVISION HISTORY
rev.
1.0
description
date
initial release
05/07/2015
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.