Emerson Network Power Rack PDU Systems Product Selection Guide; (R02/11); (SL-20828)

AC Power
For Business-Critical Continuity™
Emerson Network Power Rack PDU Systems
Product Selection Guide - North American Models
TABLE OF CONTENTS
1.0
EMERSON NETWORK POWER RACK PDU SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Safety and Agency Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0
DETERMINING THE RIGHT EMERSON PDU FOR YOUR APPLICATION . . . . . . . . . . . . . . . . . . .2
3.0
KNURR DI-STRIP PRODUCT SELECTION GUIDE - BASIC RACK PDUS . . . . . . . . . . . . . . . . .3
3.1
Overview - Basic Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2
Basic Rack PDU Optional Cord Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3
Dimensional Drawings - Basic Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.0
LIEBERT MPH PRODUCT SELECTION GUIDE - MANAGED RACK PDUS . . . . . . . . . . . . . . . 27
4.1
Overview - Managed Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2
Specifications - Liebert MPH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3
Model Number Configuration - Liebert MPH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.4
Managed Rack PDU Optional Cord Sets and Cable Restraints . . . . . . . . . . . . . . . . . . . . . . 30
4.5
Dimensional Drawings - Managed Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.0
LIEBERT MPX - ADAPTIVE RACK PDUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1
Overview - Adaptive Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2
MPX PRC (Power Rail Chassis). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3
MPX PEM (Power Entry Module) and MPX IPC (Input Power Cord) . . . . . . . . . . . . . . . . . 36
5.4
MPX BRM (Branch Receptacle Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.5
Adaptive Rack PDU Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5.1
5.5.2
5.5.3
5.5.4
5.5.5
5.5.6
5.5.7
Cord Sets and Cable Restraints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert RPC™ (RPC-1000) and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part Numbers for Liebert RPC and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ports on the Liebert RPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert RPC Capabilities and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RPC BDM—Basic Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature/Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
37
38
38
39
40
40
6.0
LIEBERT MPX SYSTEM PRODUCT SELECTION GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.1
STEP 1 - Select an MPX PRC (Quantity x 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.2
STEP 2 - Select an MPX PEM / MPX IPC (Quantity x 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3
STEP 3 - Select an MPX BRM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4
STEP 4 - Select Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.5
System Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.6
Specifications for Liebert MPX Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.7
Dimensional Drawings - Adaptive Rack PDUs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
i
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Figure 29
Figure 30
Figure 31
Knurr DI-STRIP 35351011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Knurr DI-STRIP 35351021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Knurr DI-STRIP 35351031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Knurr DI-STRIP 35351041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Knurr DI-STRIP 35351051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Knurr DI-STRIP 35351061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Knurr DI-STRIP 35351081 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Knurr DI-STRIP 35352011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Knurr DI-STRIP 35352021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Knurr DI-STRIP 35352031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Knurr DI-STRIP 35352041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Knurr DI-STRIP 35352051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Knurr DI-STRIP 35352061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Knurr DI-STRIP 35352078 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Knurr DI-STRIP 35353011 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Knurr DI-STRIP 35353021 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Knurr DI-STRIP 35353031 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Knurr DI-STRIP 35353041 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Knurr DI-STRIP 35353051 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Knurr DI-STRIP 35353061 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Knurr DI-STRIP 35353078 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Knurr DI-STRIP 35353088 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Liebert MPH rack mount power strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Liebert MPH vertical power strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Liebert MPX 1880 and 1035 models and components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
MPX PRC (Power Rail Chassis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Liebert RPC ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
RPC BDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Temperature/humidity sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Liebert MPX MPXPRC-1035mm mixed modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Liebert MPX MPXPRC-1880mm mixed modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Specifications - Knurr DI-STRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Cord sets - Knurr DI-STRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specifications - Liebert MPH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Cord sets and cable restraints - Liebert MPH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Selections for Power Entry Module MPXPEM-NVAXXAXX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Selections for Power Entry Module MPXPEM-NHBXXV30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Selections for Power Entry Module MPXPEM-NHBXXX30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Selections for Power Entry Module MPXPEM-NHBXXW30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Specifications - MPX BRM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ii
Emerson Network Power Rack PDU Systems
1.0
EMERSON NETWORK POWER RACK PDU SYSTEMS
Emerson Network Power’s Rack PDU Systems is a family of products that delivers power and management to connected IT equipment through a global and comprehensive offering including Basic,
Managed and Adaptive Rack PDU systems.
Each PDU type offers simplified installation and easy operation. Each type is compatible with
standard rack enclosures. These Emerson Rack PDUs provide easy low-cost installation, simple
relocation, security and proven design and performance.
Emerson Rack PDUs can be set up with varying degrees of power-monitoring and management.
When power or management requirements grow, the adaptive PDUs are scalable, enabling them to
grow with the installation.
Emerson PDUs are available for the entire spectrum of power needs of every type of rack equipment.
• Knurr® DI-STRIP - Basic Rack PDU systems, provide a broad range of power distribution capacities and connectivity solutions in a robust package.
• Liebert MPH™ - Managed Rack PDUs with single-phase or three-phase capability for fixed power
input/output with remote management support; one-piece unit with monitoring at the branch
level and control at the receptacle level; available in rack-mount and zero U configurations.
• Liebert MPX™ - Adaptive Rack PDUs built with modular and scalable components that can be
installed and reconfigured on-site to meet changing input and output power connectivity needs;
with remote monitoring at the branch level and receptacle management and control at the receptacle level.
1.1
Safety and Agency Compliance
Where a conflict arises between the following documents and statements made herein, the statements
in this specification will govern.
North American Units - 120V and 208V (Single-Phase and Three-Phase)
•
•
•
•
•
UL 60950-1 Information Technology Equipment
CAN/CSA-C22.2 No. 60950-1-03 Information Technology Equipment
FCC, Title 47, Part 15 Subpart B for Class A operation as defined by ANSI Standard C63.4
ISTA Procedure 1A and 2A
RoHS Compliant
1
Determining the Right Emerson PDU for Your Application
2.0
DETERMINING THE RIGHT EMERSON PDU FOR YOUR APPLICATION
Each of the Rack PDU systems Emerson offers is well-suited for delivering power to sensitive, highcapacity, rack-mounted equipment. Determining which is best for a particular installation requires
knowing the basic power requirements of the equipment in the rack, deciding on the acceptable or
preferable level of monitoring and control and then balancing those considerations against site
requirements.
The Emerson Rack PDU product line includes models to fit all types of installations: new or established; stable or rapidly changing; contracting or expanding. Each type of installation may require
any or all types of Emerson Rack PDUs.
After determining your requirements, refer to the data and specifications for each product.
2
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
3.0
KNURR DI-STRIP PRODUCT SELECTION GUIDE - BASIC RACK PDUS
3.1
Overview - Basic Rack PDUs
The Knurr DI-STRIP, a Basic Rack PDU system, provides a broad range of power distribution capacities and connectivity solutions in a robust package.
The Knurr DI-STRIP includes an input power cord with appropriate input plug connection and
hydraulic-magnetic branch rated overload protection as appropriate; basic rack mounting provisions
are also provided. Knurr DI-STRIP Rack PDUs are available in rack mount and vertical zero-U form
factors.
The Knurr DI-STRIP fits most standard 600mm width network equipment rack enclosures. Product
fit should be confirmed for each application.
Table 1
Specifications - Knurr DI-STRIP
INPUT
OUTPUT
Voltage
Rated
Amps
Max
Continuous
Amps
kW*
Phase
Plug
Receptacle/Socket
Configuration
035351011
120
15
12
1.4
1
NEMA 5-15P
(9) NEMA 5-15R
035351021
035351031
035351041
035351051
035351061
035351081
035352011
120
120
120
120
120
120
208-240
15
15
20
20
20
30
20
12
12
16
16
16
24
16
1.4
1.4
1.9
1.9
1.9
2.8
3.3
1
1
1
1
1
1
1
NEMA 5-15P
NEMA 5-15P
NEMA L5-20P
NEMA 5-20P
NEMA L5-20P
NEMA L5-30P
NEMA L6-20P
(12) NEMA 5-15R
(18) NEMA 5-15R
(9) NEMA 5-20 T-Slot
(12) NEMA 5-20 T-Slot
(12) NEMA 5-20 T-Slot
(24) NEMA 5-20 T-Slot
(9) IEC-C13 sockets
035352021**
208-240
20
16
3.3
1
IEC-C20 inlet
(9) IEC-C13 sockets
035352031
035352041**
035352051
035352061
208-240
208-240
208-240
208-240
20
20
30
30
16
16
24
24
3.3
3.3
4.9
4.9
1
1
1
1
NEMA L6-20P
IEC-C20 inlet
NEMA L6-30P
NEMA L6-30P
035352078
208-240
30
24
4.9
1
NEMA L6-30P
035353021
120/208
20
16
5.7
3
NEMA L21-20P
035353031
120/208
20
16
5.7
3
NEMA L21-20P
035353041
035353011
120/208
120/208
20
30
16
24
5.7
8.6
3
3
NEMA L21-20P
NEMA L21-30P
035353051
120/208
30
24
8.6
3
NEMA L21-30P
035353061
120/208
30
24
8.6
3
NEMA L21-30P
(12) IEC-C13 sockets
(12) IEC-C13 sockets
(4) IEC-C19 sockets
(24) IEC-C13 sockets
(20) IEC-C13 +
(4) IEC-C19 sockets
(18) IEC-C13 +
(6) IEC-C19 sockets
(27) IEC-C13 +
(6) IEC-C19 sockets
(27) 5-20 T-Slot
(6) IEC-C19 sockets
(18) IEC-C13 +
(6) IEC-C19 sockets
(27) IEC-C13 +
(6) IEC-C19 sockets
035353078
208-240
60
48
17.3
3
035353088
208-240
42
34
24.4
3
Part
Number
IEC60309
(3 pole, 4 wire,
250VAC, blue)
(2) IEC60309
(3 pole, 4 wire,
250VAC, blue)
All input cords are 10 ft. (3m) in length.
* Formulas used to calculate the kW:
For single-phase: input voltage x max continuous amps = watts
For three-phase: input voltage x max continuous amps x 1.73 = watts
** Knurr DI-STRIP output expansion modules require the use of a cord set for input power.
3
Form
Factor
Rack mount
or Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rack mount
or Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
(42) IEC-C13 +
(6) IEC-C19 sockets
Vertical
(42) IEC-C13 +
(6) IEC-C19 sockets
Vertical
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
3.2
Basic Rack PDU Optional Cord Sets
Output Cord Sets
Output cord sets are available to support conversion of Rack PDU power output receptacles to alternative power output connections and to support Rack PDU output expansion capabilities.
Conversion of power output connections can be provided on Rack PDUs with IEC-C19 receptacles.
The output cord set for these systems includes an IEC-C20 plug to connect to the IEC-C19 receptacle,
a 3 ft. (1m) power cord and receptacle to connect to user equipment. Available receptacles include:
IEC-C13 to connect to IEC-C14 equipment plugs and IEC-C19 to connect to NEMA L6-20P equipment
plugs.
Knurr DI-STRIP output expansion modules are powered via an IEC-C20 input connection. These
systems provide output expansion capabilities when connected to a receptacle on a separate Rack
PDU. The output cord set for these systems includes an IEC-C19 receptacle to connect to the IEC-C20
plug on the output expansion Knurr DI-STRIP, a 3 ft. (1m) power cord and plug to connect to the
Rack PDU receptacle providing power. Available plugs include: IEC-C20 to connect to an IEC-C19
Rack PDU receptacle.
Input Cord Sets
Input cord sets are available to support conversion of Rack PDU power input connections to
alternative power input connections. Conversion of power input can be provided on Rack PDUs with
L5-20P plug connections. The input cord set includes an L5-20R receptacle to connect to the L5-20P
Rack PDU plug, a 1 ft. (0.3m) power cord and a 5-20P plug.
Table 2
Cord sets - Knurr DI-STRIP
Cord Sets
Output Cord Sets - Power Output Conversion
539031G5
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 3 ft. (1m)
539031G6
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 10 ft. (3m)
539031G9
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 3 ft. (1m)
539031G10
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 10 ft. (3m)
Output Cord Sets - Power Output Expansion
539031G7
Output Cord Set - Power Output Expansion - IEC-C20 to IEC-C19, 3 ft. (1m)
539031G8
Output Cord Set - Power Output Expansion - IEC-C20 to IEC-C19, 10 ft. (3m)
539031G3
Output Cord Set - Power Output Expansion - IEC-C14 to IEC-C19, 3 ft. (1m)
539031G4
Output Cord Set - Power Output Expansion - IEC-C14 to IEC-C19, 10 ft. (3m)
Input Cord Sets - Power Input Conversion
539031G12
Input Cord Set - Power Input Conversion - L5-20R to 5-20P, 1 ft. (0.3m)
4
www.knuerr.com
5
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
1
5-15R (9)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
5-15P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
12.2" (311mm)
17.6" (447mm)
FRONT VIEW
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 2.5 lb. (1.1kg)
3. Shipping dimensions:
18.9" (480mm) L x 2.8" (71mm) W x 3.3" (84mm) D
4. Shipping weight: 2.8 lb. (1.3kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351011
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2.5"
(63mm)
Figure 1
2.9"
(73mm)
03.535.101.1
00/00 000000
3.3
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Dimensional Drawings - Basic Rack PDUs
Knurr DI-STRIP 35351011
www.knuerr.com
6
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
1
5-15R (9)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
5-15P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
12.2" (311mm)
19.6" (497mm)
FRONT VIEW
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 2.7 lb. (1.2kg)
3. Shipping dimensions:
22.2" (565mm) L x 2.8" (70mm) W x 3.3" (85mm) D
4. Shipping weight: 3.1 lb. (1.4kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351021
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2.5"
(63mm)
Figure 2
4.8"
(123mm)
03.535.102.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351021
NA B AS IC
DI S TR IP
www.knuerr.com
7
5-15P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
15
Rated
Amps
12
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
5-15R (18)
1
120
12
12
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
5-15P
(2-pole, 3-wire)
12.7" (323mm)
27.4" (697mm)
FRONT VIEW
2"
(50mm)
2.5"
(63mm)
Rev. 3
NOTES:
1. Unit dimensions:
27.4" (697mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.3 lb. (1.5kg)
3. Shipping dimensions:
42" (1065mm) L x 2.4" (60mm) W x 3" (75mm) D
4. Shipping weight: 3.8 lb. (1.72kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351031
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
1.7"
(44mm)
Figure 3
INPUT POWER
03.535.103.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351031
8
L5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
L5-20P
(2 pole, 3 wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
17.6" (447mm)
FRONT VIEW
1
5-20R (9)
1
120
16
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
www.knuerr.com
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3 lb. (1.35kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.4 lb. (1.54kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351041
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2"
(50mm)
1.7"
(44mm)
Figure 4
03.535.104.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351041
NA B AS IC
DI S TR IP
9
5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
5-20P
(2-pole, 3-wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
5-20R (9)
1
120
16
16
2.5"
(63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.5 lb. (1.57kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.9 lb. (1.76kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351051
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
19.6" (497mm)
FRONT VIEW
12.2" (311mm)
Receptacle Type
Max. Cont. Amps
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
4.8"
(123mm)
www.knuerr.com
Figure 5
03.535.105.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351051
www.knuerr.com
10
L5-20P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
1
5-20R (12)
1
120
16
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
L5-20P
(2-pole, 3-wire)
SIDE VIEW
REAR VIEW
2.5"
(63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.2 lb. (1.47kg)
3. Shipping dimensions:
24.6" (625mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.5 lb. (1.6kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351061
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
19.6" (497mm)
FRONT VIEW
Figure 6
4.8"
(123mm)
03.535.106.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351061
1.8"
(46mm)
NA B AS IC
www.knuerr.com
11
L5-30P
10 ft.
(3m)
1
Phase
120
Voltage
(VAC)
30
Rated
Amps
24
Max. Cont.
Amps
5-20R (12)
5-20R (12)
1
2
1
1
120
120
16
16
20
20
24.5" (622mm)
Branch 2
Rev. 4
NOTES:
1. Unit dimensions:
43.2" (447mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit weight: 7.51 lb. (3.4kg)
3. Shipping dimensions:
44.9" (1140mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping weight: 8.4 lb. (3.8kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35351081
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
SIDE VIEW
REAR VIEW
43.2" (1097mm)
FRONT VIEW
Max. Cont. Amps
Receptacle Type
Receptacle
Branch Type (Qty) Phase Voltage (VAC) Per Receptacle Per Branch
OUTPUT POWER
Input
Plug
L5-30P
(2-pole, 3-wire)
16.6" (422mm)
Input
Cord
INPUT POWER
03.535.108.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
Branch 1
20A branch circuit breakers
3.3"
(85mm)
2.1"
(53mm)
1.7"
(44mm)
Figure 7
DI S TR IP
20A branch
circuit breakers
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35351081
12
L6-20P
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
L6-20P
(2-pole, 3-wire)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
FRONT VIEW
17.6" (447mm)
1
IEC-C13 (9)
1
208-240
12
16
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
www.knuerr.com
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.2 lb. (1.4kg)
3. Shipping dimensions:
24.6" (625mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.4 lb. (1.5kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352011
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
2"
(50mm)
1.7"
(44mm)
Figure 8
03.535.201.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352011
NA B AS IC
DI S TR IP
13
IEC-C20
Inlet *
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
17.6" (447mm)
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
12.2" (311mm)
FRONT VIEW
1
IEC-C13 (9)
1
208-240
12
16
Receptacle Type
Max. Cont. Amps
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
* Requires a cordset
Input
Input
Cord
INPUT POWER
2.5" (63mm)
www.knuerr.com
2.9" (73mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
17.6" (447mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 1.5 lb. (0.7kg)
3. Shipping dimensions:
19" (483mm) L x 3" (75mm) W x 2.4" (60mm) D
4. Shipping weight: 1.7 lb. (0.8kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352021
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
IEC-C20 inlet
Figure 9
03.535.202.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352021
www.knuerr.com
14
L6-20P
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
IEC-C13 (12)
1
208-240
12
16
2.5" (63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 3.4 lb. (1.5kg)
3. Shipping dimensions:
26.8" (680mm) L x 2.4" (60mm) W x 3.9" (100mm) D
4. Shipping weight: 3.7 lb. (1.68kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352031
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
FRONT VIEW
19.6" (497mm)
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
L6-20P
(2-pole, 3-wire)
4.8" (123mm)
03.535.203.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 10 Knurr DI-STRIP 35352031
www.knuerr.com
15
IEC-C20
inlet *
10 ft.
(3m)
1
Phase
208-240
Voltage
(VAC)
20
Rated
Amps
16
Max. Cont.
Amps
SIDE VIEW
REAR VIEW
1
IEC-C13 (12)
1
208-240
12
16
2.5" (63mm)
2"
(50mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
19.6" (497mm) L x 1.7" (44mm) W x 2" (50mm) D
2. Unit weight: 1.8 lb. (0.8kg)
3. Shipping dimensions:
22.6" (575mm) L x 2.4" (60mm) W x 3" (75mm) D
4. Shipping weight: 2.1 lb. (0.9kg)
5. All wiring is to be in compliance with national
and local electric codes.
6. Mounting provisions provided.
35352041
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
12.2" (311mm)
Max. Cont. Amps
Receptacle Type
Receptacle
Bank Type (Qty) Phase Voltage (VAC) Per Receptacle Per Bank
OUTPUT POWER
* Requires a cordset
Input
Plug
Input
Cord
INPUT POWER
03.535.204.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
4.8" (123mm)
IEC-C20 INLET
19.6" (497mm)
Figure 11
FRONT VIEW
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Knurr DI-STRIP 35352041
16
L6-30P
10 ft. (3m)
1
2
Branch
1
IEC-C19 (2)
IEC-C19 (2)
30
Rated
Amps
Per Receptacle Type
208-240
Voltage
L6-30P
(2-pole, 3-wire)
Max. Continuous Amps
24
Max. Cont.
Amps
1
1
208-240
208-240
20
20
16
16
Branch 2
03.535.205.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
20A branch circuit breaker
www.knuerr.com
3.3"
(85mm)
1.7"
(44mm)
35352051
Rev. 3
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
ENVIRONMENTAL:
Operating:
32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
NOTES:
1. Unit Dimensions: 17.6" (447mm) L x 1.7" (44mm) W x 2.0" (50mm) D
2. Unit Weight: 4.8lb. (2.2kg)
3. Shipping Dimensions: 29.0" (740mm) L x 6.3" (160mm) W x 2.7" (70mm) D
4. Shipping Weight: 5.5lbs (2.5kg)
5. All wiring is to be in compliance with national and local
electric codes.
6. Mounting provisions provided.
SIDE VIEW
REAR VIEW
FRONT VIEW
17.6" (447mm)
Branch 1
Phase Voltage (VAC) Per Receptacle Per Branch
Phase
Receptacle Type
(Quantity)
OUTPUT POWER
Input
Plug
Input
Cord
INPUT POWER
1.8"
(46mm)
20A branch
circuit breaker
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 12 Knurr DI-STRIP 35352051
1.8"
(46mm)
www.knuerr.com
17
L6-30P
1
1
IEC-C13 (12)
1
2
Phase
IEC-C13 (12)
Branch
208-240
208-240
Voltage (VAC)
43.2" (1097mm)
Max Cont. Amps
30
24
Rated Amps Max Cont. Amps
SIDE VIEW
REAR VIEW
FRONT VIEW
20
20
12
12
Per Receptacle Per Branch
208-240
Per Receptacle Type
Voltage (VAC)
1
BRANCH 1
Phase
Receptacle Type
(Quantity)
OUTPUT POWER
Input Plug
10 ft/3.0m
L6-30P
(2 Pole, 3 Wire)
16.6" (422mm)
Input Cord
INPUT POWER
03.535.206.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
20A Branch
Circuit Breaker
BRANCH 2
Rev. 3
NOTES:
1. Unit Dimensions:
43.2" (1097mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit Weight: 6.8lbs (3.1kg)
3. Shipping Dimensions:
44.9" (1140mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping Weight: 7.7lbs (3.5kg)
5. All wiring is to be in compliance with national
and local electric codes.
035352061
6. Mounting provisions provided.
AGENCY:
CSA Tested to UL 60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32° F-131° F (0° C-55° C ) non-condensing,
non-corrosive, 5% - 95% RH
Storage Temperature: -4° F-140° F (-20° C - 60° C )
24.5" (622mm)
20A Branch
Circuit Breaker
3.3"
(85mm)
2.1
(53mm)
1.7"
(44mm)
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 13 Knurr DI-STRIP 35352061
18
1
L6-30P
10 ft. (3m)
IEC-C13 (10) / IEC-C19 (2)
IEC-C13 (10) / IEC-C19 (2)
1
2
Branch Receptacle Type (Qty)
OUTPUT POWER
Phase
Input Plug
Input Cord
INPUT POWER
L6-30P
(2-pole, 3-wire)
20A branch circuit breaker
30
1/1
1/1
208-240 / 208-240
208-240 / 208-240
Receptacle Type
Phase Voltage (VAC)
208-240
12 / 16
12 / 16
20
20
Max. Cont. Amps
Per Receptacle Per Branch
24
1.9"
(47mm)
Rev. 3
NOTES:
1. Unit dimensions:
21.3" (540mm) L x 6.7" (170mm) W x 1.9" (47mm) D
2. Unit weight: 15 lb. (6.8kg)
3. Shipping dimensions:
22.4" (570mm) L x 11.6" (295mm) W x 6.3" (160mm) D
4. Shipping weight: 18.3 lb. (8.3kg)
5. All wiring is to be in compliance with national
and local electric codes.
35352078
6. Mounting provisions provided.
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
20A branch circuit breaker
Voltage (VAC) Rated Amps Max. Cont. Amps
BOTTOM VIEW
TOP VIEW
FRONT VIEW
21.3" (540mm)
6.7"
(170mm)
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 14 Knurr DI-STRIP 35352078
1.8"
[46mm
www.knuerr.com
19
L21-30P
(4 pole, 5 wire)
Branch 1
27.4" (697mm)
SIDE VIEW
REAR VIEW
24.5" (622mm)
FRONT VIEW
L21-30P
3
120/208
30
24
IEC-C19 (2)
IEC-C19 (2)
IEC-C19 (2)
1
1
1
1
1
1
208-240
208-240
208-240
16
16
16
20
20
20
Max Cont. Amps
Per Receptacle Type
Receptacle Type
Branch
(Quantity)
Phase Voltage (VAC) Per Receptacle Per Branch
OUTPUT POWER
10 ft. (3m)
0.9" (23mm)
Branch 3
20A Branch
Circuit Breaker
3.3"
(85mm)
1.7"
(44mm)
Rev. 3
NOTES:
1. Unit dimensions:
27.4" (697mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit weight:
8 lb. (3.6kg)
3. Shipping dimensions:
64.6" (1640mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping weight: 9.4 lb. (4.3kg)
5. All wiring is to be in compliance with national
and local electric codes.
035353011
6. Mounting provisions provided.
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive,
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
Branch 2
20A Branch
Circuit Breaker
Input Cord Input Plug Phase Voltage (VAC) Rated Amps Max Cont. Amps
INPUT POWER
03.535.301.1
00/00 000000
120 VAC, 60Hz
Input: max. 15A
Outlets: max. 15A
NA BASIC
DI STRIP
20A Branch
Circuit Breaker
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 15 Knurr DI-STRIP 35353011
www.knuerr.com
20
L21-20P
(4 pole, 5 wire)
12.7" (322mm)
L21-20P
20
12 / 16
12 / 16
12 / 16
IEC-C13 (6)/IEC-C19 (2) 1 / 1 208-240/208-240
IEC-C13 (6)/IEC-C19 (2) 1 / 1 208-240/208-240
3
16
16
16
Branch 3
2.0"
(50mm)
2.1"
(53mm)
1.7"
(44mm)
035353021
Rev. 3
NOTES:
1. Unit Dimensions: 39.3" (997mm) L x 1.7" (44mm) W x 2.0" (50mm) D
2. Unit Weight: 5.8 lb. (2.63kg)
3. Shipping Dimensions: 40.4" (1027mm) L x 2.3" (60mm) W x 3.9" (100mm) D
4. Shipping Weight: 6.2 lb. (2.8kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Mounting provisions provided.
AGENCY:
CSA Tested to UL 60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F-131°F (0°C to 55°C ) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C )
24.5" (622mm)
Per Receptacle Per Branch
IEC-C13 (6)/IEC-C19 (2) 1 / 1 208-240/208-240
Voltage (VAC)
Max Cont. Amps
16
Max Cont. Amps
SIDE VIEW
REAR VIEW
Branch 2
2
Phase
Per Receptacle Type
120/208
39.3" (997mm)
FRONT VIEW
1
Branch
3
Receptacle Type
(Quantity)
OUTPUT POWER
10 ft/3.0m
Input Cord Input Plug Phase Voltage (VAC) Rated Amps
INPUT POWER
03.535.302.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA BASIC
DI ST RIP
Branch 1
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 16 Knurr DI-STRIP 35353021
www.knuerr.com
11.9" (301mm)
21
L21-20P
(4 Pole, 5 Wire)
L21-20P
20
12 / 16
12 / 16
12 / 16
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
3
16
16
16
Per Receptacle Per Bank
2.0"
(50mm)
2.5
(63mm)
1.7"
(44mm)
035353031
Rev. 3
NOTES:
1. Unit Dimensions: 51.1" (1297mm) L x 1.7" (44mm) W x 2.0" (50mm) D
2. Unit Weight: 7.0 lb. (3.2kg)
3. Shipping Dimensions: 72.0" (1830mm) L x 2.4" (60mm) W x 3.5" (90mm) D
4. Shipping Weight: 7.5 lb. (3.4kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Mounting provisions provided.
AGENCY:
CSA Tested to UL 60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C ) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C )
SIDE VIEW
Max Cont. Amps
16
36.8" (934mm)
REAR VIEW
Max Cont. Amps
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
Phase Voltage (VAC)
Per Receptacle Type
120/208
2
Receptacle Type
(Quantity)
3
Branch 2
FRONT VIEW
51.1" (1297mm)
Branch 1
1
Bank
OUTPUT POWER
10 ft/3.0m
Input Cord Input Plug Phase Voltage (VAC) Rated Amps
INPUT POWER
03.535.303.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA BASIC
DI STRIP
Branch 3
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 17 Knurr DI-STRIP 35353031
NA BASIC
DI ST RIP
www.knuerr.com
12.3" (312mm)
22
L21-20P
(4 Pole, 5 Wire)
L21-20P
120/208
20
1
1
1
5/20R (9)
5/20R (9)
5/20R (9)
2
3
Max Cont. Amps
16
Max Cont. Amps
16
16
120
16
120
120
16
16
16
24.5" (622mm)
39.3" [997mm
2.5
(63mm)
2.0"
(50mm)
1.7"
(44mm)
035353041
Rev. 3
NOTES:
1. Unit Dimensions: 39.3" (997mm) L x 1.7" (44mm) W x 2.0" (50mm) D
2. Unit Weight: 5.7lb. (2.6kg)
3. Shipping Dimensions: 40.4" (1027mm) L x 2.3" (60mm) W x 4.0" (100mm) D
4. Shipping Weight: 6.3lb. (2.85kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Mounting provisions provided.
AGENCY:
CSA Tested to UL 60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C ) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C )
SIDE VIEW
REAR VIEW
24.5" [622mm]
Branch 2
FRONT VIEW
39.3" [997mm]
Phase Voltage (VAC) Per Receptacle Per Bank
1
Per Receptacle Type
Receptacle Type
(Quantity)
3
Bank
OUTPUT POWER
10 ft/3.0m
Input Cord Input Plug Phase Voltage (VAC) Rated Amps
INPUT POWER
03.535.304.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
Branch 1
Branch 3
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 18 Knurr DI-STRIP 35353041
www.knuerr.com
23
L21-30P
3
Phase
SIDE VIEW
REAR VIEW
FRONT VIEW
51.1" (1297mm)
120 / 208
30
1/1
1/1
1/1
IEC-C13 (6) / IEC-C19 (2)
IEC-C13 (6) / IEC-C19 (2)
IEC-C13 (6) / IEC-C19 (2)
1
2
3
208-240/208-240
208-240/208-240
208-240/208-240
Branch 2
20A branch
circuit breaker
12 / 16
12 / 16
12 / 16
20
20
20
Max. Cont. Amps
Per Receptacle Per Branch
24
Voltage (VAC) Rated Amps Max. Cont. Amps
L21-30P
(4-pole, 5-wire)
25.7" (652mm)
Receptacle Type
Branch Receptacle Type (Qty) Phase Voltage (VAC)
OUTPUT POWER
10 ft. (3m)
Input Cord Input Plug
INPUT POWER
1.8"
(46mm)
03.535.305.1
00/00 000000
120 V AC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA B AS IC
DI S TR IP
Branch 1
20A branch
circuit breaker
0.9"
(23mm)
1.7"
(44mm)
3.3"
(85mm)
Rev. 3
NOTES:
1. Unit dimensions:
51.1" (1297mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit weight: 10.1 lb. (4.6kg)
3. Shipping dimensions:
64.6" (1640mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping weight: 11.6 lb. (5.25kg)
5. All wiring is to be in compliance with national
and local electric codes.
35353051
6. Mounting provisions provided.
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C), 5% - 95% RH
non-condensing, non-corrosive
Storage temperature: -4°F to 140°F (-20°C to 60°C)
AGENCY:
CSA tested to UL 60950-1
RoHS compliant (reduction of hazardous substances)
24.5" (622mm)
Branch 3
20A branch
circuit breaker
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 19 Knurr DI-STRIP 35353051
24
L21-30P
10ft/3.0m
30
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
IEC-C13 (9) / IEC-C19 (2) 1 / 1 208-240/208-240
3
Voltage (VAC)
2
Phase
12 / 16
12 / 16
12 / 16
20
20
20
Per Receptacle Per Branch
Max Cont. Amps
24
Max Cont. Amps
Branch 3
20A Branch
Circuit Breaker
0.9"
(22mm)
1.7"
(44mm)
035353061
Rev. 3
NOTES:
1. Unit Dimensions: 62.9" (997mm) L x 1.7" (44mm) W x 3.3" (85mm) D
2. Unit Weight: 11.0lb. (5.0kg)
3. Shipping Dimensions: 72.4" (1840mm) L x 2.8" (70mm) W x 6.3" (160mm) D
4. Shipping Weight: 12.7lb. (5.75kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Mounting provisions provided.
AGENCY:
CSA Tested to UL 60950-1
3.3"
RoHS Compliant (Reduction of Hazardous Substances)
(85mm)
ENVIRONMENTAL:
Operating: 32°F to 131°F (0°C to 55°C ) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C )
Rear View
49.0" (1245mm)
Front View
62.9" (1597mm)
Branch 2
20A Branch
Circuit Breaker
L21-30P
(4 Pole, 5 Wire)
Rated Amps
Per Receptacle Type
120/208
Voltage (VAC)
1
Branch
3
Phase
Receptacle Type
(Quantity)
OUTPUT POWER
Input Plug
Input Cord
13.0" (330mm)
www.knuerr.com
INPUT POWER
1.8"
(46mm)
03.535.306.1
00/00 000000
120 VAC , 60Hz
Input: max. 15A
Outlets : max. 15A
NA BASIC
DI STRIP
Branch 1
20A Branch
Circuit Breaker
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 20 Knurr DI-STRIP 35353061
25
IEC 60309
IEC-C13 (7) / IEC-C19 (1)
IEC-C13 (7) / IEC-C19 (1)
IEC-C13 (7) / IEC-C19 (1)
IEC-C13 (7) / IEC-C19 (1)
IEC-C13 (7) / IEC-C19 (1)
IEC-C13 (7) / IEC-C19 (1)
2
3
4
5
6
3
Phase
1
Branch
20A Branch
Circuit Breaker
60
1/1
1/1
1/1
1/1
1/1
1/1
Phase
12 / 16
12 / 16
12 / 16
12 / 16
12 / 16
12 / 16
208-240/208-240
208-240/208-240
208-240/208-240
208-240/208-240
208-240/208-240
20
20
20
20
20
20
Per Receptacle Per Branch
Max. Cont. Amps
48
208-240/208-240
Voltage (VAC)
Per Receptacle Type
208-240
Voltage (VAC) Rated Amps Max. Cont. Amps
SIDE VIEW
20A Branch
Circuit Breaker
20A Branch
Circuit Breaker
1.9"
(47mm)
Rev. 5
NOTES:
1. Unit dimensions: 63.0" (1600mm) L x 6.7" (170mm) W x 1.9" (47mm) D
2. Unit Weight: 32.8lbs (14.9kg)
3. Shipping Dimensions: 74.0" (1880mm) L x 16.3" (415mm) W x 6.3" (160mm) D
4. Shipping Weight: 38.4lb. (17.4kg)
5. All wiring is to be in compliance with national and local
electric codes.
035353078
6. Mounting provisions provided.
AGENCY:
UL 60950-1, cUL
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F-131°F (0°C to 55°C) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
20A Branch
Circuit Breaker
REAR VIEW
FRONT VIEW
IEC 60309
(3 POLE, 4 WIRE, 250VAC, BLUE)
Receptacle Type
(Quantity)
OUTPUT POWER
10ft/3.0m
INPUT POWER
Input Cord Input Plug
20A Branch
20A Branch
Circuit Breaker Circuit Breaker
63.0" (1600mm)
6.7"
(170mm)
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 21 Knurr DI-STRIP 35353078
26
50
12 / 16
12 / 16
12 / 16
12 / 16
12 / 16
12 / 16
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
1/3
2/4
2/5
2/6
20
20
20
20
20
20
Per Receptacle Per Branch
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
Voltage (VAC)
40
Max. Cont. Amps
IEC-C13 (7) / IEC-C19 (1) 1 / 1 208-240/208-240
Phase
Per Receptacle Type
208-240
Voltage (VAC) Rated Amps Max. Cont. Amps
1/2
Receptacle Type
(Quantity)
3
Phase
1/1
Input/
Branch
OUTPUT POWER
Input Plug
IEC 60309
Input Cord
10ft/3.0m
INPUT POWER
SIDE VIEW
20A Branch
20A Branch
Circuit Breaker Circuit Breaker
1.9"
(47mm)
035353088
Rev. 5
NOTES:
1. Unit dimensions: 63.0" (1600mm) L x 6.7" (170mm) W x 1.9" (47mm) D
2. Unit Weight: 44.5lb. (20.2kg)
3. Shipping Dimensions: 74.0" (1880mm) L x 16.3" (415mm) W x 6.3" (160mm) D
4. Shipping Weight: 50lb. (22.7kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Mounting provisions provided.
AGENCY:
UL 60950-1, cUL
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F-131°F (0°C to 55°C) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
20A Branch
Circuit Breaker
REAR VIEW
IEC 60309
(3 POLE, 4 WIRE, 250VAC, BLUE)
20A Branch
20A Branch
20A Branch
Circuit Breaker Circuit Breaker Circuit Breaker
63" (1600mm)
FRONT VIEW
6.7"
(170mm)
Knurr DI-STRIP Product Selection Guide - Basic Rack PDUs
Figure 22 Knurr DI-STRIP 35353088
Liebert MPH Product Selection Guide - Managed Rack PDUs
4.0
LIEBERT MPH PRODUCT SELECTION GUIDE - MANAGED RACK PDUS
4.1
Overview - Managed Rack PDUs
The Liebert MPH Managed Rack PDU system delivers power distribution, branch monitoring and
receptacle control for IT devices. Liebert MPH Rack PDUs, with remote monitoring and/or control
capabilities for power distribution at the load/equipment level, are designed to support the growth in
rack electrical needs while meeting the new demands for remote power management.
The Liebert MPH monitors electrical attributes of an individual Rack PDU, including real-time
remote and (optional) local display of monitoring of aggregate and branch electrical parameters
(status, thresholds, alarms) including voltage, amps, kW, and kW-hr. Liebert MPH features include
branch load monitoring and control for continuous uptime and minimum disruptions; expandable
monitoring interface providing simplified growth management; rugged construction; and the
convenience of being factory-installed in the Knurr rack enclosure system.
The Liebert MPH includes an input power cord with appropriate input plug connection and
hydraulic-magnetic branch rated overload protection as appropriate; basic rack mounting provisions
are also provided. Liebert MPH Managed Rack PDUs are available in rack mount and vertical zero-U
form factors and are painted black.
Liebert MPH – Managed Rack PDUs / Liebert MPH-NB Systems (Branch Monitoring Only)
Liebert MPH-NB series Rack PDUs provide local and remote monitoring of individual PDU volts,
amps, watts, and kilowatt-hours.
Liebert MPH – Managed Rack PDUs / Liebert MPH-NC (Monitoring & Receptacle Control)
Liebert MPH-NC series power strips provide the same features and functionality as the Liebert
MPH-NB series with the additional capability of remote on/off control of individual receptacles.
Local receptacle power on-off status is provided through an LED display.
Liebert MPH – Managed Rack PDUs – ALL Liebert MPH Systems
All Liebert MPH systems are provided with a factory-integrated Liebert RPC (Rack PDU Card
RPC-1000) that provides Web-based remote monitoring via a direct IP network connection, Rack
PDU Array™ interface connection to three additional Liebert MPH or Liebert MPX systems to
allow viewing of up to four Rack PDUs on a single IP connection, an environmental sensor port,
and a port for connection to the optional local display. Local display monitoring is provided via the
optional RPC BDM (Basic Display Module) and integrated audible alarm. See 5.5 - Adaptive
Rack PDU Optional Accessories for further details. Each Liebert MPH unit is provided with
basic rack mounting provisions to meet a range of installation needs.
The Liebert MPH fits most standard 600mm width network equipment rack enclosures. Product fit
should be confirmed for each application.
27
Liebert MPH Product Selection Guide - Managed Rack PDUs
4.2
Specifications - Liebert MPH
Table 3
Specifications - Liebert MPH
INPUT
Part Number
Branch Monitoring
MPH-NBR09AXXC30
MPH-NBV27AXXC30
MPH-NBR09AXXD30
MPH-NBV27AXXD30
MPH-NBR09NXXE30
MPH-NBV27NXXE30
MPH-NBR09NXXF30
MPH-NBV27NXXF30
OUTPUT
Max.
Voltage Rated Continuous
Amps
kW* Phase
(VAC) Amps
Plug
Receptacle/Socket
Configuration
Form
Factor
(9) NEMA 5-20R T-Slot
(27) NEMA 5-20R T-Slot
(9) NEMA 5-20R T-Slot
(27) NEMA 5-20R T-Slot
(9) IEC-C13
(27) IEC-C13
(9) IEC-C13
(27) IEC-C13
(21) IEC-C13 &
(6) IEC-C19
(27) IEC-C13
(21) IEC-C13 &
(6) IEC-C19
(15) IEC-C13,
(6) NEMA 5-20 T-slot &
(6) IEC-C19
(27) NEMA 5-20R T-Slot
Rack mount
Vertical
Rack mount
Vertical
Rack mount
Vertical
Rack mount
Vertical
120
120
120
120
208-240
208-240
208-240
208-240
20
20
30
30
20
20
30
30
16
16
24
24
16
16
24
24
1.9
1.9
2.8
2.8
3.3
3.3
4.9
4.9
1
1
1
1
1
1
1
1
NEMA L5-20P
NEMA L5-20P
NEMA L5-30P
NEMA L5-30P
NEMA L6-20P
NEMA L6-20P
NEMA L6-30P
NEMA L6-30P
MPH-NBV27NOXF30 208-240
30
24
4.9
1
NEMA L6-30P
MPH-NBV27NXXJ30
208-240
30
24
8.6
3
NEMA L15-30P
MPH-NBV27NOXJ30 208-240
30
24
8.6
3
NEMA L15-30P
MPH-NBV27AMXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NBV27AXXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NBV27ANXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NBV27NXXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NBV27NOXH30 120/208
30
24
8.6
3
NEMA L21-30P
Receptacle Control
MPH-NCR09AXXC30
MPH-NCV27AXXC30
MPH-NCR09AXXD30
MPH-NCV27AXXD30
MPH-NCR09NXXE30
MPH-NCV27NXXE30
MPH-NCR09NXXF30
MPH-NCV27NXXF30
120
120
120
120
208-240
208-240
208-240
208-240
20
20
30
30
20
20
30
30
16
16
24
24
16
16
24
24
1.9
1.9
2.8
2.8
3.3
3.3
4.9
4.9
1
1
1
1
1
1
1
1
MPH-NCV27NOXF30 208-240
30
24
4.9
1
MPH-NCV27NXXJ30
208-240
30
24
8.6
3
MPH-NCV27NOXJ30 208-240
30
24
8.6
3
MPH-NCV27AMXH30 120/208
30
24
8.6
3
MPH-NCV27AXXH30 120/208
30
24
8.6
3
NEMA L5-20P (9) NEMA 5-20R T-Slot
NEMA L5-20P (27) NEMA 5-20R T-Slot
NEMA L5-30P (9) NEMA 5-20R T-Slot
NEMA L5-30P (27) NEMA 5-20R T-Slot
NEMA L6-20P
(9) IEC-C13
NEMA L6-20P
(27) IEC-C13
NEMA L6-30P
(9) IEC-C13
NEMA L6-30P
(27) IEC-C13
(21) IEC-C13 &
NEMA L6-30P
(6) IEC-C19
NEMA L15-30P
(27) IEC-C13
(21) IEC-C13 &
NEMA L15-30P
(6) IEC-C19
(15) IEC-C13,
NEMA L21-30P (6) NEMA 5-20 T-slot &
(6) IEC-C19
NEMA L21-30P (27) NEMA 5-20R T-Slot
MPH-NCV27ANXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NCV27NXXH30 120/208
30
24
8.6
3
NEMA L21-30P
MPH-NCV27NOXH30 120/208
30
24
8.6
3
NEMA L21-30P
All input cords are 10 ft. (3m) in length.
* Formulas used to calculate the kW:
For single-phase: input voltage x max continuous amps = watts
For three-phase: input voltage x max continuous amps x 1.73 = watts
28
(21) IEC-C13 &
(6) NEMA 5-20R T-Slot
(27) IEC-C13
(21) IEC-C13 &
(6) IEC-C19
(21) IEC-C13 &
(6) NEMA 5-20R T-Slot
(27) IEC-C13
(21) IEC-C13 &
(6) IEC-C19
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Rack mount
Vertical
Rack mount
Vertical
Rack mount
Vertical
Rack mount
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Liebert MPH Product Selection Guide - Managed Rack PDUs
4.3
Model Number Configuration - Liebert MPH
Example: MPH N B R 09 AX XC 30
• Prefix:
• Region:
• Type:
MPH
N = North American
B = Branch Monitoring
C = Controlled Receptacles
• Mounting: V = Vertical
R = Rack mount
• Output Power:
• Quantity Receptacles (Total):
09 or 27
• Receptacle Type(s)—2 characters (each set):
A = 5-20R T-Slot
N = IEC-C13
O = IEC-C19
Note: Second character indicates a second receptacle type (X if no additional type chosen)
• Input Power:
• Plug Type:
• First character = X
• Second character:
C = L5-20P
D = L5-30P
E = L6-20P
F = L6-30P
H = L21-30P
J = L15-30P
• Cord Length:
30 = 3.0m (10 ft.)
29
Liebert MPH Product Selection Guide - Managed Rack PDUs
4.4
Managed Rack PDU Optional Cord Sets and Cable Restraints
Output Cord Sets
Output cord sets are available to support conversion of Rack PDU power output receptacles to alternative power output connections and to support Rack PDU output expansion capabilities.
Conversion of power output connections can be provided on Rack PDUs with IEC-C19 receptacles.
The output cord set for these systems includes an IEC-C20 plug to connect to the IEC-C19 receptacle,
a 3 ft. (1m) power cord and receptacle to connect to user equipment. Available receptacles include:
IEC-C13 to connect to IEC-C14 equipment plugs and IEC-C19 to connect to NEMA L6-20P equipment
plugs.
Input Cord Sets
Input cord sets are available to support conversion of Rack PDU power input connections to alternative power input connections. Conversion of power input can be provided on Rack PDUs with L5-20P
plug connections. The input cord set includes an L5-20R receptacle to connect to the L5-20P Rack
PDU plug, a 1 ft. (0.3m) power cord and a 5-20P plug.
Cable Restraints (Liebert MPH - Vertical Systems)
Cable restraints are available to secure user equipment power cord connections to IEC-C13 receptacles. The Liebert MPH supports all vertical-mount models with IEC-C13 receptacles or a combination
of IEC-C13 plus IEC-C19 receptacles. The cable restraint system includes three tie-down brackets for
receptacle groups along with cable ties to secure individual input user equipment power cables.
Table 4
Cord sets and cable restraints - Liebert MPH
Cord Sets and Cable Restraints
Output Cord Sets - Power Output Conversion
539031G5
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 3.3 ft. (1m)
539031G6
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 10 ft. (3m)
539031G9
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 3.3 ft. (1m)
539031G10
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 10 ft. (3m)
Input Cord Sets - Power Input Conversion
539031G12
Input Cord Set - Power Input Conversion - L5-20P to 5-20P, 1 ft. (0.3m)
Cable Restraints IEC-C13 (Liebert MPH - Vertical Systems)
11858KIT
Cable Restraints - MPH Vertical Systems with IEC-C13 receptacles
30
31
2
Input Plug
1
5
REAR VIEW
4
TOP VIEW
17.2" (438mm)
3
18.3" (465mm)
FRONT VIEW
6
7
L5-20P
1
5-20R (9)
Receptacle Type
Branch
(Quantity)
OUTPUT POWER
10ft/3.0m
1
1
Phase
120
16
20
Per Branch
Max Cont. Amps
16
Per Receptacle
20
MPH-NCR09AXXC30
Rev. 3
Voltage (VAC)
Per Receptacle Type
120
8
HID16
1.7" [44mm
7.0"
(178mm)
0.2" (6mm)
L5-20P
(2 Pole, 3 Wire)
1.2"
(32mm)
NOTES:
1. Unit Dimensions: 1.7" H x 7.0" D x 17.2" W (44mm x 178mm x 438mm)
2. Unit Weight: 7.5lb. (3.4kg)
3. Shipping Dimensions: 22.0" H x 9.0" D x 24.1" W (559mm x 228mm x 612mm)
4. Shipping Weight: 8.5lb. (3.9kg)
5. All wiring is to be in compliance with national and local electric codes.
AGENCY:
UL/C-UL Listed to UL60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIROMENTAL:
Operating: 32°F-131°F (0°C-55°C) non-condensing, non-corrosive, 5% - 95% RH
Storage Temperature: -4°F-140°F (-20°C to 60°C)
9
RPC Communication Card
Output
Receptacles
PN: RPC-1000
Input Cord Input Plug Phase Voltage (VAC) Rated Amps Max Cont. Amps
INPUT POWER
20A
Input Breaker
Circ ui t Br eaker
20 Amp
Audible Alarm
Silence
MPH
Power Distribution
4.5
Li ebert
Liebert MPH Product Selection Guide - Managed Rack PDUs
Dimensional Drawings - Managed Rack PDUs
Figure 23 Liebert MPH rack mount power strip
B ranc h 1
C irc uit B reaker
20 Ampere
32
L5-20P
10 ft/3.0m
5-20R (9)
5-20R (9)
5-20R (9)
1
2
3
Receptacle Type
(Quantity)
Branch
OUTPUT POWER
Input Plug
Input Cord
INPUT POWER
B ranc h 3
2
3
4
5
7
8
9
1
B ranc h 2
2
5
7
120
16
16
16
16
120
120
120
1
1
20
20
20
Phase Voltage (VAC) Per Receptacle Per Branch
1
9
SIDE VIEW
Max Cont. Amps
20
8
1
B ranc h 1
2
3
4
5
6
7
Branch 3
(9) 5-20R
8
9
MPH
P N: R PC -1000
3.4 (86mm)
Toolless Mounting
Button (See Note 6)
12.3 (312mm)
P ower Dis tribution
L iebert
RPC
Communication
Card
1.2" (32mm)
0.2" (6mm)
1.9"
(50mm)
Vertical Mounting
Bracket (See Note 6)
HID16
MPH-NCV27AXXC30
Rev. 2
AGENCY:
UL/C-UL Listed to UL60950-1
RoHS Compliant (Reduction of Hazardous Substances)
ENVIRONMENTAL:
Operating: 32°F to 131° F (0°C to 55° C) non-condensing, non-corrosive,
5% - 95% RH
Storage Temperature: -4°F to 140°F (-20° C to 60° C)
NOTES:
1. Unit Dimensions: 68.1" (1730mm) H x 3.1" (80mm) D x 1.9" (50mm) W
2. Unit Weight: 18lb. (8.2kg)
3. Shipping Dimensions: 72.2" (1962mm) H x 6.2" (159mm) D x 10.7" (273mm) W
4. Shipping Weight: 20lb. (9.1kg)
5. All wiring is to be in compliance with national and local electric codes.
6. Only one mounting option required to be used at a time. Vertical mounting
brackets and toolless buttons shown together for reference only.
FRONT VIEW
6
68.1" (1730mm)
4
REAR VIEW
3
Branch 3
(9) 5-20R
Voltage (VAC) Rated Amps Max Cont. Amps
L5-20P
(2 Pole, 3 Wire)
Per Receptacle Type
1
6
2.2" (57mm)
20A Branch
Circuit Breakers
1
Phase
9.2" (235mm)
3.1" (80mm)
0.99 (25mm)
B ranc h 2
C irc uit B reaker
20 Ampere
3.4 (86mm)
12.3 (312mm)
B ranc h 3
C irc uit B reaker
20 Ampere
Branch 3
(9) 5-20R
Liebert MPH Product Selection Guide - Managed Rack PDUs
Figure 24 Liebert MPH vertical power strip
Liebert MPX - Adaptive Rack PDUs
5.0
LIEBERT MPX - ADAPTIVE RACK PDUS
5.1
Overview - Adaptive Rack PDUs
The Liebert MPX Adaptive Rack PDU system delivers break-through flexibility, availability and total
cost of ownership. The Liebert MPX enables users to respond to and manage changing rack power and
management environments. The Liebert MPX provides users the ability to size their Rack PDU system to support initial requirements and then adapt as connectivity, capacity and/or functionality
needs change. The Liebert MPX is based on a patent-pending design built on a power / communication
bus and input/output power module strategy.
The Liebert MPX Adaptive Rack PDU is composed of several key building blocks and support modules. The Liebert MPX is built on the MPX PRC (Power Rail Chassis) that distributes power and communications to all support modules, acts as a backplane to mount support modules and offers
provisions to physically mount the Liebert MPX in a network rack. Input power is connected and
delivered to the Liebert MPX system via the MPX PEM (Power Entry Module). Output power connectivity and communications management level is defined by the MPX BRM (Branch Receptacle Modules). MPX BRM power connectivity includes NEMA receptacles and IEC sockets. MPX BRM
communications include Branch Monitoring and Receptacle Management versions. Network communications, sensor and/or local display interface are provided by the Liebert RPC (Rack PDU Card) that
mounts in the MPX PEM. The Liebert RPC provides connection to an optional RPC BDM (Basic Display Module) for local status / alarm viewing. Module versions for North American and European
applications are available.
The Liebert MPX is provided as separate ship-loose modules for user on-site configuration. The Liebert MPX is designed for simple and quick configuration and reconfiguration. Preconfigured systems
are available as an Special Feature Authorization (SFA) when ordered as factory installed in Knurr
rack enclosure systems.
The major Liebert MPX system components are described in the following sections:
• 5.2 - MPX PRC (Power Rail Chassis)
• 5.3 - MPX PEM (Power Entry Module) and MPX IPC (Input Power Cord)
• 5.4 - MPX BRM (Branch Receptacle Module)
33
Liebert MPX - Adaptive Rack PDUs
Figure 25 Liebert MPX 1880 and 1035 models and components
MPX BRM
Liebert RPC
MPX PEM,
Variable Capacity
Liebert MPX,
1035mm
Liebert PRC chassis
MPX PEM,
Fixed Capacity
Liebert MPX,
1880mm
Liebert PRC chassis
MPX IPC
RPC BDM
34
Liebert MPX - Adaptive Rack PDUs
5.2
MPX PRC (Power Rail Chassis)
The MPX PRC distributes power and communications to the installed Liebert MPX modules. The
MPX PRC supports both single-phase power input up to 20A and three-phase up to 60A. It includes
provisions to mount and secure an input power module (MPX PEM) and output receptacle modules
(MPX BRM). It is available in lengths to accommodate typical 23U or 42U network racks: 1035mm
(40.75 in.) for 23U and 1880mm (74 in.) for 42U. The MPX PRC includes zero-U mounting provisions
that accommodate most rack designs. The MPX PRC is provided with cover / spacers to assist users
with positioning for future MPX BRM module additions.
Figure 26 MPX PRC (Power Rail Chassis)
FRONT SIDE
Section of MPX PRC
Power Bus
REAR SIDE
Section of MPX PRC
Communication
Bus
T-slots in the
back of the
MPX PRC
(Power Rail
Chassis)
accept spring
nuts for easy
mounting
Module
Connector Slot
35
Liebert MPX - Adaptive Rack PDUs
5.3
MPX PEM (Power Entry Module) and MPX IPC (Input Power Cord)
The MPX PEM provides input power to the Liebert MPX system and includes provisions for addition
of the Liebert RPC (Rack PDU Card) to support remote and local communications. The MPX PEM is
available in two versions: Variable Capacity and Fixed Capacity.
The MPX PEM Variable Capacity version allows the user to select and change power input via different MPX IPCs. The MPX IPC includes cord, MPX PEM connector, and input plug. The MPX IPC is
available in multiple versions supporting up to 30 amps including single-phase North American
120VAC and 208VAC and three-phase North American 208/120VAC connections.
The MPX PEM Fixed Capacity version supports rated input capacities from 40 up to 60 amps with
fixed cord and plug connections. All MPX PEMs include an audible over current alarm with local
reset. One MPX PEM is required per Liebert MPX Rack PDU.
• Variable Capacity MPX PEMs are 220mm in length for application on both short (1035mm) and
standard (1880mm) MPX PRC systems.
• Fixed Capacity systems are 266mm in length for application on standard (1880mm) MPX PRCs.
5.4
MPX BRM (Branch Receptacle Module)
The MPX BRM provides output power distribution to user load equipment and remote management /
monitoring of that equipment. The MPX BRM includes output receptacles (NEMA and IEC) and is
overload-protected. The MPX BRM is available in two versions: Branch Monitoring and Receptacle
Management. The MPX BRM Branch Monitoring version supports monitoring of its aggregate branch
electrical and energy parameters (status, thresholds, and alarms) including voltage, amps, kW, and
kW-hr. The MPX BRM Receptacle Management version supports monitoring of individual receptacle
electrical and energy parameters (status, thresholds, and alarms)—including voltage, amps, kW and
kW-hr—and supports on-off power control of individual receptacles, along with the aggregate branch
monitoring provided on MPX BRM Branch Monitoring systems.
MPX BRMs are hot-swappable to allow user installation without powering down the Liebert MPX
system. Each MPX BRM includes a display that automatically assigns and displays a Branch identification number to the MPX BRM when added to an active Liebert MPX system. Each MPX BRM is
overload-protected by 20 Amp branch-rated hydraulic magnetic circuit breakers that support
UL60950 requirements. The breakers are protected from inadvertent tripping by requiring tool insertion to manually open and from accidental impact damage by a protection body/cover.
MPX BRMs are offered in line-to-line and line-to-neutral power configurations. These configurations
support different power input requirements and provide support for load balancing for three-phase
input power systems.
Up to three (3) MPX BRMs can be deployed on a Liebert MPX system utilizing the 1035mm MPX PRC
for typical 23U racks and up to six (6) MPX BRMs for systems utilizing the 1880mm MPX PRC for
typical 42U racks. All MPX BRMs are 266mm in length.
36
Liebert MPX - Adaptive Rack PDUs
5.5
Adaptive Rack PDU Optional Accessories
5.5.1
Cord Sets and Cable Restraints
Output Cord Sets
Output cord sets are available to support conversion of Rack PDU power output receptacles to alternative power output connections and to support Rack PDU output expansion capabilities.
Conversion of power output connections can be provided on Rack PDUs with IEC-C19 receptacles.
The output cord set for these systems includes an IEC-C20 plug to connect to the IEC-C19 receptacle,
a 3 ft. (1m) power cord and receptacle to connect to user equipment. Available receptacles include:
IEC-C13 to connect to IEC-C14 equipment plugs and IEC-C19 to connect to NEMA L6-20P equipment
plugs.
Cable Restraints (Liebert MPX Systems)
Cable restraints are available to secure user equipment power cord connections to IEC-C13 receptacles. The Liebert MPX supports all models of the MPX BRM with IEC-C13 receptacles and includes
individual cable restraint clips to support individual receptacles. Twelve restraint clips are provided
per option. The Liebert MPX cable restraint supports most IEC-C14 plugs that connect to the
IEC-C13 receptacles.
Cord Sets and Cable Restraints
Output Cord Sets - Power Output Conversion
539031G5
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 3 ft. (1m)
539031G6
Output Cord Set - Power Output Conversion - IEC-C20 to IEC-C13, 10 ft. (3m)
539031G9
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 3 ft. (1m)
539031G10
Output Cord Set - Power Output Conversion - IEC-C20 to NEMA L6-20R, 10 ft. (3m)
Cable Restraints IEC-C13 (Liebert MPX Systems)
039102169
5.5.2
Cable Restraints - MPX BRM with IEC-C13 receptacles (Set of 12)
Liebert RPC™ (RPC-1000) and Accessories
The Liebert RPC (Rack PDU Card) is a network interface card that provides network connectivity to
the Liebert Rack PDU family of products.
The Liebert RPC can be installed in Adaptive and Managed versions of Liebert Rack PDUs to provide
network monitoring and control capabilities. The Liebert RPC is a factory-installed standard feature
of the Liebert MPH; it is an option for the Liebert MPX.
In addition, the Liebert RPC serves as the integration point for several rack accessory products.
Available options that connect to the card include the RPC BDM (Basic Display Module) and a temperature/humidity sensor.
37
Liebert MPX - Adaptive Rack PDUs
5.5.3
Part Numbers for Liebert RPC and Accessories
• Liebert RPC (Rack PDU Card):
• RPC-1000
• RPC BDM (Basic Display Module):
• RPC-BDM-1000
• Liebert SN Integrated Environmental Sensors:
• SN-Z01 - Single Temperature Probe; 12 ft. (3.66m) length cable
• SN-Z02 - Three Temperature Probes; 17 ft. (5.18m) length cable
• SN-Z03 - Three Temperature Probes and Single Humidity Probe; 17 ft. (5.18m) length cable
Liebert SN Modular Environmental Sensors:
• SN-T - Single Temperature Probe (1 probe)
• SN-TH - Single Temperature Probe and Single Humidity Probe (2 probes)
• SN-2D - Door Switch, 2 inputs (1 probe)
• SN-3C - Digital Input, 3 inputs (1 probe)
5.5.4
Ports on the Liebert RPC
Figure 27 shows the four individual ports on the Liebert RPC.
Each port is designed for only one type of connection. See the Liebert RPC user manual, SL-20825, for
details on using these ports.
Figure 27 Liebert RPC ports
External Sensor port
Display port
Expansion/Management port
LAN port
38
Liebert MPX - Adaptive Rack PDUs
5.5.5
Liebert RPC Capabilities and Benefits
The Liebert RPC offers the following capabilities and benefits:
Web Support
The Liebert RPC delivers Web management and control to Liebert Rack PDU equipment. All authorized users will be able to view status information on their network.
SNMP Support
The Liebert RPC enables SNMP management of Liebert Rack PDU equipment. To integrate the card
into an SNMP implementation, compile the Liebert Global Products MIB on your Network Management System (NMS).
The Liebert Global Products MIB can be downloaded from:
www.liebert.com
Liebert Nform™
Utilizing the SNMP and Web technologies built into the Liebert RPC, Liebert Nform will centrally
manage event notifications, access critical system information and manage the power delivered to
your critical devices.
A downloadable edition is available online at:
nform.liebert.com
Liebert SiteScan® Web
The Liebert RPC integrates with Liebert SiteScan Web software to monitor and analyze trends to
ensure high-availability operation of critical facilities.
For more information on Liebert SiteScan Web, visit the Web page at:
sitescan.liebert.com
39
Liebert MPX - Adaptive Rack PDUs
5.5.6
RPC BDM—Basic Display Module
The RPC BDM is an optional device with an LCD for local viewing of status and alarms of up to four
Liebert MPX or Liebert MPH PDUs. It connects to Liebert RPC with a factory-supplied cable that is
6.5 ft. (2m) long. The portable unit can be mounted on a wall for viewing particular units. The
RPC BDM provides local display of electrical status for all connected Liebert MPX (and Liebert MPH)
systems, MPX BRMs and individual receptacles, if the PDU version permits it. Information is
accessed via a navigation switch on the RPC BDM.
For model number and other details, refer to 5.5.3 - Part Numbers for Liebert RPC and Accessories and the Liebert RPC user manual, SL-20825, available at the Liebert Web site: www.liebert.com
Figure 28 RPC BDM
Jog Wheel on Top of Unit
to Navigate Display
Communication Port on Side
of Unit Connects to Liebert RPC
RPC BDM
5.5.7
Temperature/Humidity Sensor
A temperature/humidity sensor is available to monitor conditions in the rack. The sensor mounts
without tools. It connects to the Liebert RPC with a factory-supplied Ethernet cable and can be monitored over a network.
Figure 29 Temperature/humidity sensor
Sensor
support
Tool-less
fastener
Sensor
Sensor
Knurr frame
member
Support
base
Sensor installed in rack
40
Liebert MPX System Product Selection Guide
6.0
LIEBERT MPX SYSTEM PRODUCT SELECTION GUIDE
6.1
STEP 1 - Select an MPX PRC (Quantity x 1)
To select an MPX PRC (Power Rail Chassis), refer to:
Specifications - MPX PRC
MPXPRC-V1035XXX:
Input:
Rack Fit:
MPXPRC-V1880XXX:
Input:
Rack Fit:
Max 8.6 kW, limited to 3 MPX BRM modules
Single-Phase and Three-Phase 5-wire / 20-30 Amp /
120/208VAC
Typical 23U, most 600mm wide
Max 17.2 kW, limited to 6 MPX BRM modules
Single-Phase and Three-Phase 5-wire / 20-60 Amp /
120/208VAC
Typical 42U, most 600mm wide
Model Number Configuration - MPX PRC
Example: MPXPRC-V1035XXX
• Prefix:
• Mounting:
• Length:
MPXPRC
V = Vertical
1035 = Short (40.75"; 1035mm)
1880 = Standard (74"; 1880mm)
• Placeholder: XXX
Liebert MPX
with 1035mm
Liebert PRC
chassis
Liebert MPX
with 1880mm
Liebert PRC
chassis
41
Liebert MPX System Product Selection Guide
6.2
STEP 2 - Select an MPX PEM / MPX IPC (Quantity x 1)
To select an MPX PEM (Power Entry Module)—and an MPX IPC (Input Power Cord) for a Variable
Capacity MPX PEM system—refer to:
• The appropriate table in 6.5 - System Selection Guide for the MPX PEM (Power Entry Module):
• Table 5 - Selections for Power Entry Module MPXPEM-NVAXXAXX
• Table 6 - Selections for Power Entry Module MPXPEM-NHBXXV30
• Table 7 - Selections for Power Entry Module MPXPEM-NHBXXX30
• Table 8 - Selections for Power Entry Module MPXPEM-NHBXXW30
• The following information:
Input Power
MPX PEM Selection
MPX IPC
Input Plug
120VAC / 1-Phase / 30 Amp
MPXPEM-NVAXXAXX
MPXIPC-NXD30XXX
L5-30P
208VAC / 1-Phase / 30 Amp
MPXPEM-NVAXXAXX
MPXIPC-NXF30XXX
L6-30P
208VAC / 3-Phase / 30 AMP
MPXPEM-NVAXXAXX
MPXIPC-NXJ30XXX
L15-30P
120/208VAC / 3-Phase / 20 Amp
MPXPEM-NVAXXAXX
MPXIPC-NXG30XXX
L21-20P
120/208VAC / 3-Phase / 30 Amp
MPXPEM-NVAXXAXX
MPXIPC-NXH30XXX
L21-30P
Specifications - MPX PEM
MPX PEM (Power Entry Module)
MPXPEM-NVAXXAXX
Power Entry Module - Variable Capacity, North American, 120 or 208VAC single-phase
and/or 208-240VAC three-phase input up to 30Amp
MPXPEM-NHBXXV30
Power Entry Module - Fixed Capacity, North American, 208-240VAC, three-phase 4-wire
(L-L-L-G), 50Amp input, CS8365C plug, 10 ft. (3m) cord
MPXPEM-NHBXXX30
Power Entry Module - Fixed Capacity, North American, 208-240VAC, three-phase 4-wire
(L-L-L-G), 60Amp input, IEC60309 Pin-Sleeve plug, 10 ft. (3m) cord
MPXPEM-NHBXXW30
Power Entry Module - Fixed Capacity, North American, 120/208VAC, three-phase 5-wire
(L-L-L-N-G), 60Amp input, IEC60309 Pin-Sleeve plug, 10 ft. (3m) cord
Model Number Configuration - MPX PEM
Example: MPXPEM-NVAXXAXX
• Prefix:
• Region:
• Type:
MPXPEM
N = North American
V = Variable Capacity
H = Fixed Capacity
• Size:
A = Base (220mm) – Variable Capacity version
B = Standard (266mm) – Fixed Capacity version
• Communications:
X = Future Use
• Input Power:
• Available Capacity or Plug Type:
XA = 30 amps
XV = 50 amps, 4-wire (CS8365C)
XX = 60 amps, 4-wire (IEC60309)
XW = 60 amps, 5-wire (IEC60309)
• Cord Length:
XX = No integrated cord (Requires MPX IPC)
30 = 3.0m (10 ft.)
42
MPX PEM,
Variable Capacity
MPX PEM,
Fixed Capacity
Liebert MPX System Product Selection Guide
Specifications - MPX IPC (MPX PEM Variable Capacity Systems ONLY)
MPX IPC (Input Power Cord)
120VAC – Single-Phase Input / Output
MPXIPC-NXD30XXX
Input Power Cord - North American, 30Amp - 120VAC - Single-Phase;
NEMA L5-30P Locking plug; 10 ft. (3m) length cord
208VAC – Single-Phase Input / Output
MPXIPC-NXF30XXX
Input Power Cord - North American, 30Amp - 208-240VAC - Single-Phase;
NEMA L6-30P Locking plug; 10 ft. (3m) length cord
208VAC – Three-Phase Input / 208VAC Single-Phase Output
MPXIPC-NXJ30XXX
Input Power Cord - North American, 30Amp - 208-240VAC - Three-Phase, 4-wire;
NEMA L15-30P Locking plug; 10 ft. (3m) length cord
208VAC – Three-Phase Input / 120/208VAC Single-Phase Output
MPXIPC-NXG30XXX
Input Power Cord - North American, 20Amp - 120/208VAC - Three-Phase;
NEMA L21-20P Locking plug; 10 ft. (3m) length cord
MPXIPC-NXH30XXX
Input Power Cord - North American, 30Amp - 120/208VAC - Three-Phase;
NEMA L21-30P Locking plug; 10 ft. (3m) length cord
Model Number Configuration - MPX IPC (MPX PEM Variable Capacity Systems ONLY)
Example: MPXIPC-NXG30XXX
• Prefix:
MPXIPC
• Region: N = North American
• Input Power and Connection:
• Plug Type:
XD = L5-30P
XF = L6-30P
XJ = L15-30P
XG = L21-20P
XH = L21-30P
• Cord Length:
30 = 3.0m (10 ft.)
• Placeholder:
XXX
MPX PEM,
Variable Capacity
MPX IPC
43
Liebert MPX System Product Selection Guide
6.3
STEP 3 - Select an MPX BRM
To select an MPX BRM (Branch Receptacle Module), refer to:
• The appropriate table in 6.5 - System Selection Guide for the MPX PEM (Power Entry Module):
• Table 5 - Selections for Power Entry Module MPXPEM-NVAXXAXX
• Table 6 - Selections for Power Entry Module MPXPEM-NHBXXV30
• Table 7 - Selections for Power Entry Module MPXPEM-NHBXXX30
• Table 8 - Selections for Power Entry Module MPXPEM-NHBXXW30
• The following MPX BRM quantity definitions:
MPX PRC selected
Single-Phase Input
Three-Phase Input
MPXPRC-V1035XXX
3 MPX BRM modules maximum
1 x BRM per Lx-Lx* (total 3 max)
MPXPRC-V1035XXX
6 MPX BRM modules maximum
2 x BRM per Lx-Lx* (total 6 max)
* Required for phase load balancing
• If needed, refer to the MPX BRM specifications in Table 9
Model Number Configuration - MPX BRM
Example: MPXBRM-NRBD4O31
• Prefix:
• Region:
• Type:
MPXBRM
N = North American
B = Branch Monitoring
R = Receptacle Management
• Size and OL Protection:
• Size: B = Standard (266mm)
• Voltage Rating and OL Protection:
A = 120V/20A
D = 208-240V/20A
• Output Power:
• Quantity Receptacles:
4, 6
• Receptacle Type:
A = 5-20R T-slot
N = IEC-C13
O = IEC-C19
• Phase Configuration:
1N = L1-N
2N = L2-N
3N = L3-N
12 = L1-L2
23 = L2-L3
31 = L3-L1
44
MPX BRM
Liebert MPX System Product Selection Guide
6.4
STEP 4 - Select Communication Options
Choose from the following options for the Liebert MPX:
• Liebert RPC (Rack PDU Card) part number:
• RPC-1000
• RPC BDM (Basic Display Module) part number:
• RPC-BDM-1000
• Liebert SN Integrated and Modular
Environmental Sensor part numbers:
Integrated Sensors
• SN-Z01 - Single Temperature Probe;
12 ft. (3.66m) length cable
• SN-Z02 - Three Temperature Probes;
17 ft. (5.18m) length cable
• SN-Z03 - Three Temperature Probes
and Single Humidity Probe;
17 ft. (5.18m) length cable
Modular Sensors
• SN-T - Single Temperature Probe (1 probe)
• SN-TH - Single Temperature Probe and
Single Humidity Probe (2 probes)
• SN-2D - Door Switch, 2 inputs (1 probe)
• SN-3C - Digital Input, 3 inputs (1 probe)
Liebert RPC
RPC BDM
The Liebert RPC is required for the other two options,
the RPC BDM and Liebert SN integrated sensor.
Liebert SN
(Integrated Sensor)
Liebert SN
(Modular Sensor)
45
Liebert MPX System Product Selection Guide
6.5
System Selection Guide
Use the appropriate table as a guide to select components that are compatible with each MPX PEM:
•
•
•
•
Table 5
Table 5 - Selections for Power Entry Module MPXPEM-NVAXXAXX
Table 6 - Selections for Power Entry Module MPXPEM-NHBXXV30
Table 7 - Selections for Power Entry Module MPXPEM-NHBXXX30
Table 8 - Selections for Power Entry Module MPXPEM-NHBXXW30
Selections for Power Entry Module MPXPEM-NVAXXAXX
MPX PEM
Part Number
Module
Voltage
Rated
Amps
Max.
Continuous
Amps
Input
Connection
Input
Phases
Module
Length
(mm)
MPXPEM-NVAXXAXX*
120/208
or 208-240
30
24
Variable
Single-Phase
or Three-Phase
depending on the
MPX IPC selection
220
Max. #
MPX BRMs
Supported
Phase
Configuration
Overall
Length
1035mm, 23U
6
Single-Phase
& Three-Phase
1880mm, 42U
Cord
Length
ft. (m)
* No fixed cord (requires MPX IPC)
Compatible MPX PRC
for given MPX PEM:
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
MPXPRC-V1035XXX
120/208
or 208-240
60
48
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
Input Plug
Phase
Configuration
120
30
24
NEMA L5-30P
L1-N-G
10 (3.0)
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
120V
20
16
(6) NEMA 5-20R
L1-N
266
120V
20
16
(6) NEMA 5-20R
L1-N
266
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
Input Plug
Phase
Configuration
Cord
Length
ft. (m)
MPXIPC-NXF30XXX
208-240
30
24
NEMA L6-30P
L1-L2-G
10 (3.0)
Compatible MPX BRM
for given MPX IPC:
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXPRC-V1880XXX
Compatible MPX IPC
for given MPX PEM:
MPXIPC-NXD30XXX
Compatible MPX BRM
for given MPX IPC:
3
Branch Monitoring
MPXBRM-NBBA6A1N
Receptacle Management
MPXBRM-NRBA6A1N
Compatible MPX IPC
for given MPX PEM:
Branch Monitoring
Receptacle Management
46
Liebert MPX System Product Selection Guide
Table 5
Selections for Power Entry Module MPXPEM-NVAXXAXX (continued)
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
Input
Plug
Phase
Configuration
Cord
Length
ft. (m)
MPXIPC-NXJ30XXX
208-240
30
24
NEMA L15-30P
L1-L2-L3-G
10 (3.0)
Compatible MPX BRM
for given MPX IPC:
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
Compatible MPX IPC
for given MPX PEM:
Branch Monitoring
Receptacle Management
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
Input Plug
Phase
Configuration
Cord Length
ft. (m)
Compatible MPX IPC
for given MPX PEM:
MPXIPC-NXG30XXX
120/208
20
16
NEMA L21-20P
L1-L2-L3-N-G
10 (3.0)
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBA6A1N
120V
20
16
(6) NEMA 5-20R
L1-N
266
MPXBRM-NBBA6A2N
120V
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NBBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBA6A1N
120V
20
16
(6) NEMA 5-20R
L1-N
266
MPXBRM-NRBA6A2N
120V
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NRBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
Compatible MPX BRM
for given MPX IPC:
Branch Monitoring
Receptacle Management
47
Liebert MPX System Product Selection Guide
Table 5
Selections for Power Entry Module MPXPEM-NVAXXAXX (continued)
Voltages
Supported
Rated
Amps
Max.
Continuous
Amps
Input Plug
Phase
Configuration
Cord
Length
ft. (m)
MPXIPC-NXH30XXX
120/208
30
24
NEMA L21-30P
L1-L2-L3-N-G
10 (3.0)
Compatible MPX BRM
for given MPX IPC:
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBA6A1N
120V
MPXBRM-NBBA6A2N
120V
20
16
(6) NEMA 5-20R
L1-N
266
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NBBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBA6A1N
120V
20
16
(6) NEMA 5-20R
L1-N
266
MPXBRM-NRBA6A2N
120V
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NRBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
Compatible MPX IPC
for given MPX PEM:
Branch Monitoring
Receptacle Management
48
Liebert MPX System Product Selection Guide
Table 6
Selections for Power Entry Module MPXPEM-NHBXXV30
Input
Connection
Input
Phases
Module
Length
(mm)
40
CS83665C
3-PH, 4-Wire
L1-L2-L3-G
266
Rated
Amps
Max.
Continuous
Amps
Max. #
MPX BRMs
Supported
Phase
Configuration
Overall
Length
60
48
1035mm, 23U
6
Single-Phase
& Three-Phase
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPX PEM
Part Number
MPXPEM-NHBXXV30
Compatible MPX PRC
for given MPX PEM:
MPXPRC-V1035XXX
MPXPRC-V1880XXX
Compatible MPX BRM
for given MPX PEM:
Module
Voltage
Rated
Amps
Max.
Continuous
Amps
208-240V
50
Voltages
Supported
120/208
or 208-240
3
1880mm, 42U
Branch Monitoring
Receptacle Management
49
Liebert MPX System Product Selection Guide
Table 7
Selections for Power Entry Module MPXPEM-NHBXXX30
Input
Connection
Input
Phases
Module
Length
(mm)
48
IEC60309
3-PH, 4-Wire
L1-L2-L3-G
266
Rated
Amps
Max.
Continuous
Amps
Max. #
MPX BRMs
Supported
Phase
Configuration
Overall
Length
60
48
1035mm, 23U
6
Single-Phase
& Three-Phase
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPX PEM
Part Number
MPXPEM-NHBXXX30
Compatible MPX PRC
for given MPX PEM:
MPXPRC-V1035XXX
MPXPRC-V1880XXX
Compatible MPX BRM
for given MPX PEM:
Module
Voltage
Rated
Amps
Max.
Continuous
Amps
208-240V
60
Voltages
Supported
120/208
or 208-240
3
1880mm, 42U
Branch Monitoring
Receptacle Management
50
Liebert MPX System Product Selection Guide
Table 8
Selections for Power Entry Module MPXPEM-NHBXXW30
Input
Connection
Input
Phases
Module
Length
(mm)
48
IEC60309
3-PH, 5-Wire
L1-L2-L3-N-G
266
Rated
Amps
Max.
Continuous
Amps
Max. #
MPX BRMs
Supported
Input
Phases
Overall
Length
60
48
1035mm, 23U
6
Single-Phase
& Three-Phase
Module
Voltage
Branch
Rated
Amps
Max.
Continuous
Amps
Quantity
& Receptacle
Type
Output
Phase
Configuration
Module
Length
(mm)
MPXBRM-NBBA6A1N
120V
20
16
(6) NEMA 5-20R
L1-N
266
MPXBRM-NBBA6A2N
120V
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NBBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NBBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NBBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NBBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NBBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NBBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NBBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPXBRM-NRBA6A1N
120V
20
16
(6) NEMA 5-20R
L1-N
266
MPXBRM-NRBA6A2N
120V
20
16
(6) NEMA 5-20R
L2-N
266
MPXBRM-NRBA6A3N
120V
20
16
(6) NEMA 5-20R
L3-N
266
MPXBRM-NRBD6N12
208-240V
20
16
(6) IEC-C13
L1-L2
266
MPXBRM-NRBD6N23
208-240V
20
16
(6) IEC-C13
L2-L3
266
MPXBRM-NRBD6N31
208-240V
20
16
(6) IEC-C13
L3-L1
266
MPXBRM-NRBD4O12
208-240V
20
16
(4) IEC-C19
L1-L2
266
MPXBRM-NRBD4O23
208-240V
20
16
(4) IEC-C19
L2-L3
266
MPXBRM-NRBD4O31
208-240V
20
16
(4) IEC-C19
L3-L1
266
MPX PEM
Part Number
MPXPEM-NHBXXW30
Compatible MPX PRC
for given MPX PEM:
MPXPRC-V1035XXX
MPXPRC-V1880XXX
Compatible MPX BRM
for given MPX PEM:
Module
Voltage
Rated
Amps
Max.
Continuous
Amps
208-240V
60
Voltages
Supported
120/208
or 208-240V
3
1880mm, 42U
Branch Monitoring
Receptacle Management
51
Liebert MPX System Product Selection Guide
6.6
Table 9
Specifications for Liebert MPX Components
Specifications - MPX BRM
MPX BRM (Branch Receptacle Module)
Single-Phase Liebert MPX System (MPX PEM) Input Selections
Phase L1 to Neutral (120VAC) Output
Branch Monitoring Support
MPXBRM-NBBA6A1N
Branch Monitoring, (6) NEMA 5-20R (T-slot) receptacles; Line L1 to Neutral (120VAC)
Receptacle Management Support
MPXBRM-NRBA6A1N
Receptacle Management, (6) NEMA 5-20R (T-slot) receptacles; Line L1 to Neutral (120VAC)
Line L1 to L2 (208VAC) Output
Branch Monitoring Support
MPXBRM-NBBD6N12
Branch Monitoring, (6) IEC-C13 receptacles; Line L1 to L2 (208-240VAC)
MPXBRM-NBBD4O12
Branch Monitoring, (4) IEC-C19 receptacles; Line L1 to L2 (208-240VAC)
Receptacle Management Support
MPXBRM-NRBD6N12
Receptacle Management, (6) IEC-C13 receptacles; Line L1 to L2 (208-240VAC)
MPXBRM-NRBD4O12
Receptacle Management, (4) IEC-C19 receptacles; Line L1 to L2 (208-240VAC)
Three-Phase Liebert MPX System (MPX PEM) Input Selections
Line L1 to L2 (208VAC) or Phase L1 to Neutral (120VAC) Output
Branch Monitoring Support
MPXBRM-NBBA6A1N
Branch Monitoring, (6) NEMA 5-20R (T-slot) receptacles; Phase L1 to Neutral (120VAC)
MPXBRM-NBBD6N12
Branch Monitoring, (6) IEC-C13 receptacles; Line L1 to L2 (208-240VAC)
MPXBRM-NBBD4O12
Branch Monitoring, (4) IEC-C19 receptacles Line L1 to L2 (208-240VAC)
Receptacle Management Support
MPXBRM-NRBA6A1N
Receptacle Management, (6) NEMA 5-20R (T-slot) receptacles; Phase L1 to Neutral (120VAC)
MPXBRM-NRBD6N12
Receptacle Management, (6) IEC-C13 receptacles; Line L1 to L2 (208-240VAC)
MPXBRM-NRBD4O12
Receptacle Management, (4) IEC-C19 receptacles Line L1 to L2 (208-240VAC)
Line L2 to L3 (208VAC) or Phase L2 to Neutral (120VAC) Output
Branch Monitoring Support
MPXBRM-NBBA6A2N
Branch Monitoring, (6) NEMA 5-20R (T-slot) receptacles; Phase L2 to Neutral (120VAC)
MPXBRM-NBBD6N23
Branch Monitoring, (6) IEC-C13 receptacles; Line L2 to L3 (208-240VAC)
MPXBRM-NBBD4O23
Branch Monitoring, (4) IEC-C19 receptacles Line L2 to L3 (208-240VAC)
Receptacle Management Support
MPXBRM-NRBA6A2N
Receptacle Management, (6) NEMA 5-20R (T-slot) receptacles; Phase L2 to Neutral (120VAC)
MPXBRM-NRBD6N23
Receptacle Management, (6) IEC-C13 receptacles Line L2 to L3 (208-240VAC)
MPXBRM-NRBD4O23
Receptacle Management, (4) IEC-C19 receptacles Line L2 to L3 (208-240VAC)
Line L3 to L1 (208VAC) or Phase L3 to Neutral (120VAC) Output
Branch Monitoring Support
MPXBRM-NBBA6A3N
Branch Monitoring, (6) NEMA 5-20R (T-slot) receptacles; Phase L3 to Neutral (120VAC)
MPXBRM-NBBD6N31
Branch Monitoring, (6) IEC-C13 receptacles; Line L3 to L1 (208-240VAC)
MPXBRM-NBBD4O31
Branch Monitoring, (4) IEC-C19 receptacles Line L3 to L1 (208-240VAC)
Receptacle Management Support
MPXBRM-NRBA6A3N
Receptacle Management, (6) NEMA 5-20R (T-slot) receptacles; Phase L3 to Neutral (120VAC)
MPXBRM-NRBD6N31
Receptacle Management, (6) IEC-C13 receptacles Line L3 to L1 (208-240VAC)
MPXBRM-NRBD4O31
Receptacle Management, (4) IEC-C19 receptacles Line L3 to L1 (208-240VAC)
52
2.9"
(75mm)
53
2.9"
(75mm)
4.1"
(104mm)
MPX-PRC
cover/spacer
MPX-BRM
circuit breaker
protection body
MPX-PRC
(Power Rail
Chassis)
SIDE VIEW
MPX-BRM
(Branch Receptacle
Modules)
TOP VIEW
40.6" (1035mm)
10.5"
(266mm)
8.7"
(220mm)
4.1"
(104mm)
Input power
cord (variable)
MPX-MIXMOD1035
Rev. 0
NOTES:
1. Dimensional view of 1035mm MPX-PRC application.
2. Representative module mix may not reflect user selection.
3. Operating temperature: 41°F to 131°F (5°C to 55°C)
4. Storage temperature: -13°F to 185°F (-25°C to 85°C )
MPX-PEM
(Power Entry
Module)
10.5"
(266mm)
6.7
10.5"
(266mm)
Liebert MPX System Product Selection Guide
Dimensional Drawings - Adaptive Rack PDUs
Figure 30 Liebert MPX MPXPRC-1035mm mixed modules
54
2.9"
(75mm)
END VIEW
2.9"
(75mm)
4.1"
(104mm)
MPX-PRC
cover/spacer
10.5"
(266mm)
MPX-PRC
(Power Rail
Chassis)
4.1"
(104mm)
10.5"
(266mm)
TOP VIEW
74" (1880mm)
10.5"
(266mm)
SIDE VIEW
MPX-BRM
(Branch Receptacle
Modules)
10.5"
(266mm)
MPX-MIXMOD1880
Rev. 1
NOTES:
1. Dimensional view of 1880mm MPX-PRC application.
2. Representative module mix may not reflect user selection.
3. Operating temperature: 41°F to 131°F (5°C to 55°C)
4. Storage temperature: -13°F to 185°F (-25°C to 85°C )
4.1"
(104mm)
MPX-PEM
(Power Entry
Module)
10.5"
(266mm)
Input power
cord (fixed)
10.5"
(266mm)
MPX-BRM
circuit breaker
protection body
10.5"
(266mm)
Liebert MPX System Product Selection Guide
Figure 31 Liebert MPX MPXPRC-1880mm mixed modules
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2009 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
SL-20828_REV1_02-11
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
AC Power
Connectivity
Embedded Computing
Embedded Power
DC Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.