AC Power For Business-Critical Continuity™ Liebert® MPX™ User Manual–Global Applications TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Save These Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 LIEBERT® MPX™ INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.0 LIEBERT® MPX™ SYSTEM MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 2.1 MPX PRC™—Power Rail Chassis/Power and Communication Bus . . . . . . . . . . . . . . . . . . . . 4 2.2 2.1.1 Mounting Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 MPX™ PEM™—Power Entry Module/ Power Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.2.1 MPX™ IPC™—Input Power Cord/Communication (North American Models Only) . . . . . . . . 7 2.3 MPX BRM™—Branch Receptacle Module (Power Output) . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.4 Liebert® RPC™—Rack PDU Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.0 RPCBDM™—RPC Basic Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 LIEBERT® MPX™ INSTALLATION AND ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.1 Installation in a Knurr® Miracel Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.4.1 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.2 Mounting Hardware Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Tools Required—Field-Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Prepare the Liebert® MPX™ for Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Attach Brackets to a Knurr® Miracel™ Horizontal Frame Member . . . . . . . . . . . . . . . . . . . . 12 Attach L-Shaped Brackets to an Upright Frame Member of the Knurr® Miracel™ . . . . . . . . . . .13 Liebert® MPX™ System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 3.2.1 3.2.2 3.2.3 Attach an MPX PEM™ or MPX BRM™ to the MPX PRC™ . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Attach an MPX™ IPC™ to an MPX PEM™—Variable-Capacity MPX PEM Only (North American Models Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Install an Optional Liebert RPC in the MPX PEM—North American Models Only . . . . . . . 17 3.3 Temperature/Humidity Sensor Installation—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.4 Install an Optional RPCBDM™ in the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3.4.1 3.4.2 Mounting Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 RPCBDM Installation on Knurr® Miracel™ Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 4.0 SYSTEM FUNCTIONAL TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 4.1 Checklist for Liebert® MPX™ Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 4.2 Test the Liebert MPX’s Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5.0 OPERATION AND CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 5.1 Configure the Liebert RPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 5.1.1 5.2 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Operation With the Liebert RPC™ 5.2.1 5.2.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Connect to the Liebert RPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Viewing PDU and Receptacle Status: PDU Explorer and Device Explorer . . . . . . . . . . . . . . 24 5.3 Operation Without the Liebert RPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.1 Maintenance Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 7.1 MPX™ PRC™—Model Number Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 i 7.2 MPX™ PEM™—Model Number Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 7.3 MPX™ BRM™—Model Number Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.4 MPX™ IPC™—Model Number Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 7.5 Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 8.0 DIMENSIONAL DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 9.0 RECYCLING INFORMATION, FCC COMPLIANCE, MODIFICATIONS . . . . . . . . . . . . . . . . . . . . .34 FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Liebert MPX assembly diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 MPX PRC™ (Power Rail Chassis) components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 MPX PRC (Power Rail Chassis) T-slots for mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 MPX PEM™ (Power Entry Module) features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 MPX IPC connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 MPX BRM™ (Branch Receptacle Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Liebert® RPC™ (rack PDU card) in an MPX™ PEM™ (Power Entry Module) . . . . . . . . . . . . . . . . . 9 RPCBDM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Inserting a spring nut into a T-slot and attaching an MPX™ mounting screw. . . . . . . . . . . . . . . 12 Attaching brackets to a horizontal frame member . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Attaching brackets to an upright frame member . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Hang Liebert MPX on a bracket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Attach a module to the MPX PRC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Liebert® MPX™ assembled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Quick-connect couplings on MPX IPC (input power cord) and MPX PEM (Power Entry Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Temperature/humidity sensor mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 RPCBDM installation in rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 RPCBDM™ cable connection port on Liebert® RPC™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Liebert® RPC™ PDU Explorer view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Liebert RPC Device Explorer view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Liebert® MPX™ assembly dimensions, 1880mm (74") versions . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Liebert MPX assembly dimensions, 1035mm (40.6") versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 RPCBDM™ dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 MPX PRC (Power Rail Chassis) specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPX PEM (Power Entry Module) specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPX BRM (Branch Receptacle Module) specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPX IPC (Input Power Cord) specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical and environmental specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Metering performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii 26 27 28 30 31 31 IMPORTANT SAFETY INSTRUCTIONS MPX™ PRC™: Power Rail Chassis MPX PEM™: Power Entry Module MPX BRM™: Branch Receptacle Module MPX IPC™: Input Power Cord MPX RPC™: Rack PDU Card SAVE THESE INSTRUCTIONS ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. The Liebert® MPX contains hazardous voltage. Follow the warnings and cautions in this document to avoid serious injury or death from electric shock. Read This Manual This manual contains important safety instructions. Read all safety, installation and operating instructions before installing a Liebert MPX. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Observe all cautions and warnings in this manual. Install in Appropriate Location The Liebert MPX must be installed in a restricted-access location. A restricted-access location is an area where access is possible only through the use of a tool or lock and key or other means of security, and is controlled by the authority responsible for the location. Operate the Liebert MPX in an indoor environment only within an ambient temperature range of 41°F to 131°F (5°C to 55°C) with a relative humidity of 0% ~ 95%, non-condensing. Install it in a clean environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances. Qualified Personnel Only Emerson strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work. Only personnel who understand the precautions in this manual should be permitted in the Liebert MPX’s restricted access location. Not for Use in Safety-Critical Applications The Liebert MPX is designed to deliver power to information technology and telecommunication equipment. The Liebert MPX is not intended for use with life support or other designated critical devices. If uncertain about its application, consult your local dealer or your Emerson representative. Install MPX PEM Before Connecting Power Whenever the MPX PEM is connected to power, the connectors on the bottom are energized with hazardous voltage. Connect input power only after: • the MPX PEM (Power Entry Module) is properly installed on the MPX PRC (Power Rail Chassis) • the MPX IPC (Input Power Cord) is properly connected to the MPX PEM Disconnect power before unlocking the connector screws that attach the PEM to the PRC. Never remove a PEM from the power distribution unit while input power is connected. The PEM is not hot swappable. Only one MPX PEM (Power Entry Module) should be connected to an MPX PRC (Power Rail Chassis). Failure to comply could result in serious injury or equipment damage. 1 Do Not Open Covers or Insert Objects Never open or remove the cover of any Liebert® MPX™ module, with exception of the Liebert RPC™ cover on the MPX PEM module. Never insert any foreign object into a Liebert MPX, particularly into the power bus. Never insert any foreign object into an MPX PEM™. An exception is that the MPX RPC provides a small hole between the display and sensor RJ-45 connectors to reset the card. See Figure 4 to find the hole location. Do Not Service Liebert MPX modules contain no user-serviceable parts. If you need support or have questions about your Liebert MPX, contact Emerson® Network Power Distributed Processing Applications or your local Emerson representative. Do not attempt to service this product yourself. 2 Liebert® MPX™ Introduction 1.0 LIEBERT® MPX™ INTRODUCTION The Liebert MPX is an Adaptive Rack PDU (power distribution unit) built with modular and scalable components that can be installed and reconfigured on-site to meet varying input and output power connectivity needs. The flexibility of the modules requires that the installer ensure that the modules match the power requirements of the application. Failure to do so could result in damage to the Liebert MPX and connected components. The Liebert MPX Adaptive Rack PDU family consists of the following components: • MPX PRC™—(Power Rail Chassis) distributes intermodule power, communications and serves as the mounting base for all Liebert MPX components. • MPX PEM™—(Power Entry Module) delivers power to the Liebert MPX and includes provisions for remote and local communication options. Detachable and non-detachable cord versions are available. • MPX IPC™—(Input Power Cord) is a detachable input power cord required for some versions of MPX PEM. A variety of single- and three-phase plug types are available. • MPX BRM™—(Branch Receptacle Module) distributes overload-protected output power to user loads. Hot swappable design allows for reconfiguration with choice of receptacle type, quantities, and monitoring / control to the receptacle level. • Liebert RPC™—(Rack PDU Card) optional network interface card to manage and monitor power distribution to connected equipment; installs in the MPX PEM communication card slot. Allows for multiple Liebert MPXs to be interconnected and managed from a single network connection. • RPCBDM™—(Basic Display Module) optional display for local monitoring of Liebert MPX units. Cord-connected, allowing user to select rack mounting location. Figure 1 Liebert MPX assembly diagram Liebert PRC (runs full length of unit; obscured by modules) MPX BRM modules Liebert RPC Quick-Connect Input MPX PEM module 3 Liebert® MPX™ System Modules 2.0 LIEBERT® MPX™ SYSTEM MODULES 2.1 MPX PRC™—Power Rail Chassis/Power and Communication Bus The MPX PRC acts as the fundamental building block of the Liebert MPX. Power and Communications buses are integrated into the full length of the MPX PRC. The MPX BRM™ (Branch Receptacle Modules) and MPX PEM™ (Power Entry Module) lock onto the MPX PRC, adding power input, power output, monitoring and management, depending on the type of module. The MPX PRC is available in two lengths: Part # Length, mm (in) Typical Cabinet Size MPXPRC-V1880XXX 1880 (74.07) 42U MPXPRC-V1035XXX 1035 (40.78) 23U The MPXPRC-V1880XXX will accommodate up to six standard size (266 mm) MPX BRMs (Branch Receptacle Modules); the MPXPRC-V1035XXX will accept up to three MPX BRMs. Each size of MPX PRC also accepts a single MPX PEM. The MPX PRC has five power bus slots that allow the connection of the MPX PEM and MPX BRM modules to three phases of power, neutral and protective earth. A communication bus provides the path through which the Liebert RPC, MPX PEM and MPX BRM modules communicate. The MPX PRC also has a module connector slot that permits secure attachment of MPX PEM and MPX BRM modules via their integral connectors. Spacer covers are available to cap off unused sections of the MPX PRC’s surface. The spacer covers reserve positions to insert MPX BRMs for future expansion. ! WARNING Risk of connecting two MPX PEMs to one MPX PRC. Can cause equipment damage, injury or death. Connect only one MPX PEM (Power Entry Module) to an MPX PRC (Power Rail Chassis). Connecting more than one MPX PEM could cause cross-conduction. A cross-conduction can cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit current may exceed the OCPD A.I.C. ratings. 4 Liebert® MPX™ System Modules Figure 2 MPX PRC™ (Power Rail Chassis) components Section of MPX PRC (Power Rail Chassis) Power Bus Communication Bus Module Connector Slot 2.1.1 PRC1880 installed in Knurr® Miracel™ Mounting Features The back of the MPX PRC features T-slots running the length of the unit. These may be used for mounting the assembled units in racks, such as the Knurr® Miracel™ rack. Figure 3 MPX PRC (Power Rail Chassis) T-slots for mounting This T-slot in the back of the MPX PRC (Power Rail Chassis) accepts spring nuts for easy mounting 5 Liebert® MPX™ System Modules 2.2 MPX™ PEM™—Power Entry Module/ Power Input ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. The MPX PEM contains hazardous voltage. This unit must be properly and securely installed on the MPX PRC (Power Rail Chassis). The power conductors on the bottom of the MPX PEM are energized with hazardous voltage whenever the MPX PEM is attached to power. If the MPX PEM is not installed on the MPX PRC, these conductors will be exposed. Emerson strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work. ! WARNING Risk of connecting two MPX PEMs to one MPX PRC. Can cause equipment damage, injury or death. Connect only one MPX PEM (Power Entry Module) to an MPX PRC™ (Power Rail Chassis). Connecting more than one MPX PEM could cause cross-conduction. A cross-conduction can cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit current may exceed the OCPD A.I.C. ratings. The MPX PEM centralizes the connectivity of Liebert’s MPX’s power input and communication ports. The MPX PEM securely fastens onto the MPX PRC (Power Rail Chassis) to deliver polyphase power from its power supply cord to the power bus. The Liebert RPC is installed in the MPX PEM for its operating power and connection to the communication bus. The MPX PEM is available in North American models with Variable-Capacity or Fixed-Capacity and in European models with Fixed-Capacity only. Both configurations’ power supply cords are available in a variety of single- and three-phase NEMA, Schuko and IEC plug styles and ratings. The Variable-Capacity models require connection of a detachable MPX IPC (See 2.2.1 - MPX™ IPC™—Input Power Cord/Communication (North American Models Only)) to its power inlet. The power input ratings are determined by the plug type. The user may change the MPX IPC™ with a different plug type and ratings from single phase to three-phase to suit his/her needs. NOTE Up to 30A (24A) per phase is supported for variable capacity North American models; up to 32A per phase is supported for European models. NOTE Up to 60A (48A) per phase is supported for fixed capacity North American models; up to 63A per phase is supported for European models. All models, except Elementary versions, provide power metering of the polyphase inputs, including individual line voltage and current, total kW and total kWH. Additionally, individual line current alarming and operational status are supported. Elementary models of the MPX™ PEM™ are available only in Europe. Elementary models are not equipped with power metering capability. Other important features include: • Three visual phase power indicators alert the user to the current condition of each power input. • Audible alarm is enabled during certain overcurrent conditions. The audible alarm may be tested or silenced by pressing the alarm silence/test button. The alarm may be tested by momentarily pressing the button when an alarm condition is not pending. 6 Liebert® MPX™ System Modules Figure 4 MPX PEM™ (Power Entry Module) features Integral Connector Torx Screw Phase Power Indicators Liebert RPC™ Reset Access Hole Alarm Silence/Test Button Liebert RPC Installed in Slot Hard-Wired Power Input Cable Quick-Connect Power Couplings Integral Connector Torx Screw 2.2.1 MPX™ IPC™—Input Power Cord/Communication (North American Models Only) The MPX IPC is a detachable input power cord that permits changing the input power source for Variable-Capacity versions of the MPX PEM™. A variety of single- and three-phase NEMA and IEC plug types are available. The MPX IPC is not required for the Fixed-Capacity MPX PEM. ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. Do not connect the MPX IPC to power until the MPX PEM is attached to the MPX PRC™ and the MPX IPC is attached to the MPX PEM. If the MPX PEM is not attached to the MPX PRC, conductors with hazardous voltage will be exposed when power is connected. Figure 5 MPX IPC connector Quick-Connect Power Couplings Snap Locks prevent accidental disconnection from the MPX PEM (Power Entry Module) 7 Liebert® MPX™ System Modules 2.3 MPX BRM™—Branch Receptacle Module (Power Output) The MPX BRM provides output power distribution to user load equipment. All MPX BRMs include output receptacles (NEMA, Schuko or IEC) that are overload-protected by 100% rated hydraulicmagnetic circuit breakers. MPX BRMs are hot-swappable to allow user installation without powering down the Liebert MPX. Up to three standard sized (266mm) MPX BRMs can be deployed on a Liebert MPX utilizing the MPX PRC (Power Rail Chassis) for typical 23U racks and up to six standard size MPX BRMs (Branch Receptacle Modules) for units utilizing the 1880mm MPX PRC™ for typical 42U racks. All MPX BRMs include an alphanumeric LED indicator that uniquely identifies the individual module. North American and European models of the MPX BRM are available in the following versions and features: • Elementary version provides power distribution only. Power metering and alarming are not supported. • Branch Monitoring version of the MPX BRM provides power distribution and branch power metering, including voltage, current, kW, kVA, kW-h and power factor. • Receptacle Management version of the MPX BRM provides the same features as the Branch Monitoring models, plus power metering, including crest factor, On/Off control, current alarming, and operational status of individual receptacles. The receptacles may either be turned On or Off remotely or programmed for automatic power-on sequencing. Other important features include: • An alphanumeric indicator to provide module identification and operational status (not Elementary models) of the branch current condition. Additionally, the Branch Monitoring version provides current alarming and operational status of the branch. The unit displays an “o” for an overcurrent condition and a “u” for an undercurrent condition. • For Receptacle Management versions, a visual indicator per receptacle alerts the user to the current condition of the load (not Elementary models). • The circuit breaker may be opened with the use of a tool. Open circuit breaker detection causes the alphanumeric indicator to flash (not Elementary models). • Voltage phasing is determined by the power blade configuration on the bottom of each MPX BRM™, and is clearly marked on the color coded label. • IEC C13 receptacle types are provided with retaining clips to provide strain relief for the load's power supply cord. 8 Liebert® MPX™ System Modules Figure 6 MPX BRM™ (Branch Receptacle Module) Receptacles Receptacle On/ Off Indicators (Receptacle Management Units Only) Branch-Rated Circuit Breaker (100% Rated) Integral Connector 2.4 Branch Numeric Indicator Liebert® RPC™—Rack PDU Card The Liebert RPC centralizes local and remote management for the Liebert MPX™. It provides Web and SNMP management for systems connected to an Ethernet network. The Liebert RPC also serves as the connection point for multiple support capabilities and devices including the RPC Basic Display Module (RPCBDM™), various optional environmental sensors and “sibling” connection to other Liebert MPX™ or Liebert MPH™ systems. The Liebert RPC is equipped with RJ-45 jacks for all connections and requires no custom cables. The card supports 10 and 100 Mbit Ethernet and provides for in-the-field upgrade of firmware. The Liebert RPC is user-installed in a slot in the MPX PEM™ (Power Entry Module). Europe only: The Liebert RPC is factory-installed in all monitored MPX PEMs. Figure 7 Liebert® RPC™ (rack PDU card) in an MPX™ PEM™ (Power Entry Module) Expansion/Management port RPCBDM™ port LAN port Liebert RPC 9 External Sensor port Liebert® MPX™ System Modules 2.4.1 RPCBDM™—RPC Basic Display Module The optional RPCBDM provides local display of monitored data for all connected Liebert MPX™ and Liebert MPH™ systems. Display information is accessed via a navigation switch on the RPCBDM. The RPCBDM is cable-connected to the Liebert RPC allowing the user to locate the display to suit the local reading requirements. A 2-meter cable and general mounting provisions are provided. A single display can be used for up to four Liebert MPX or Liebert MPH Rack PDUs connected in a Rack PDU Array™. The display screen’s orientation may be changed to either landscape (default) or portrait by pressing and holding the scan switch while attaching the cable. Figure 8 RPCBDM 10 Liebert® MPX™ Installation and Assembly 3.0 LIEBERT® MPX™ INSTALLATION AND ASSEMBLY All configuration steps must be completed before attempting to startup equipment connected to the Liebert MPX. 3.1 Installation in a Knurr® Miracel Rack Emerson recommends installing the MPX PRC™ (Power Rail Chassis) in the rack, then attaching the Liebert MPX modules to it. Before beginning, consider how cables will be routed in the rack. Placing the MPX PEM™ (Power Entry Module) at the end of the MPX PRC™ that is nearest the entry point for its input power cable can ease cable routing and help separate control and power cables to reduce electromagnetic interference. A Liebert MPX can be installed in a Knurr® Miracel™ rack on either the upright or horizontal frame member with the included hardware. The unit can be installed on the face of the frame member or on the side of the frame member. Installation requires inserting two spring nuts into the Liebert MPX, screwing Liebert MPX mounting screws into the spring nuts and attaching two brackets to the Knurr Miracel frame members. The Liebert MPX hangs on the brackets and is supported by the Liebert MPX mounting screws. ! WARNING Risk of connecting two MPX PEMs to one MPX PRC. Can cause equipment damage, injury or death. Connect only one MPX PEM™ (Power Entry Module) to an MPX PRC (Power Rail Chassis). Connecting more than one MPX PEM could cause cross-conduction. A cross-conduction can cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit current may exceed the OCPD A.I.C. ratings. 3.1.1 Mounting Hardware Included • • • • • 3.1.2 Z-shaped brackets: 2 L-shaped bracket: 2 Spring-nuts, M5: 6 Screws, M5x10: 6 Liebert MPX mounting screws, 2 Tools Required—Field-Supplied • Slotted screwdriver • 4mm Allen wrench 11 Liebert® MPX™ Installation and Assembly 3.1.3 Prepare the Liebert® MPX™ for Mounting 1. Insert two spring nuts into the T-slot on the back of the MPX PRC™, one near either end (see Figure 9 for how to insert a spring nut). 2. Position the spring nuts where the brackets to be used will be positioned (either the Z-shaped or L-shaped brackets). To move a spring nut, press down on it with a small, pointed object and slide it into position. 3. Thread an MPX mounting screw into the spring nut and tighten a few turns. Leave enough space for the bracket to slip over the screw’s head and rest on the body of the screw. Figure 9 Inserting a spring nut into a T-slot and attaching an MPX™ mounting screw MPX Mounting Screw in back of MPX PRC™ T-slot Spring nut installed in T-slot (leaf spring goes on inner side) 3.1.4 Attach Brackets to a Knurr® Miracel™ Horizontal Frame Member 1. Insert two spring nuts into the T-slot on the upper horizontal frame member. a. To use the Z-shaped bracket, insert the spring nuts into the T-slot on the face of the horizontal frame member (see Figure 10). b. To use the L-shaped bracket, insert the spring nuts into the T-slot on the thinner side of the horizontal frame member (see Figure 10). 2. Position the spring nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts, press down on each with a small, pointed object and slide each into position. 3. Hold the bracket in place and attach it with two of the M5x10 screws with hex heads. 4. Tighten the hex-head screws firmly with the Allen wrench. 5. Repeat Steps 1 through 4 for the lower horizontal frame member. The brackets must be directly in line with each other for the Liebert® MPX to be installed. 6. After the brackets are attached, hang the Liebert MPX in the rack by inserting the Liebert MPX mounting screws into the slots on the brackets (see Figure 12). 7. Tighten the Liebert MPX mounting screws securely. Figure 10 Attaching brackets to a horizontal frame member Z-Shaped Bracket on Knurr Miracel Horizontal Frame Member L-Shaped Bracket on Knurr Miracel Horizontal Frame Member 12 Liebert® MPX™ Installation and Assembly 3.1.5 Attach L-Shaped Brackets to an Upright Frame Member of the Knurr® Miracel™ 1. Insert two spring nuts into the T-slot on a rear upright frame member (see Figure 11). 2. Position the spring nuts to accommodate screws inserted through slots in the brackets. To move the spring nuts, press down on each with a small, pointed object and slide each into position. 3. Hold an L-shaped bracket in place and attach it with two of the M5x10 screws with hex heads. 4. Tighten the hex-head screws firmly with the Allen wrench. 5. Repeat Steps 1 through 4 for the lower L-shaped bracket. The brackets will attach the Liebert® MPX™ more securely if one is near the top of the unit and one is near the bottom. 6. After the brackets are attached, hang the Liebert MPX in the rack by inserting the Liebert MPX mounting screws into the slots on the brackets (see Figure 12). 7. Tighten the Liebert MPX mounting screws securely. Figure 11 Attaching brackets to an upright frame member L-Shaped Bracket on Knurr Miracel Upright Frame Member Figure 12 Hang Liebert MPX on a bracket MPX mounting screw fits through the center of the bracket and slips into a slot The lower screw on the back of the MPX PRC™ will sit in the bottom of the middle slot in either type of mounting bracket used 13 Liebert® MPX™ Installation and Assembly 3.2 Liebert® MPX™ System Assembly 3.2.1 Attach an MPX PEM™ or MPX BRM™ to the MPX PRC™ ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. This unit must be properly and securely installed on the MPX PRC (Power Rail Chassis). Emerson strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work. Connect only one MPX PEM (Power Entry Module) to an MPX PRC (Power Rail Chassis). Connecting more than one MPX PEM could cause cross-conduction. Cross-conduction can cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit current may exceed the OCPD A.I.C. ratings. Whenever the MPX PEM is connected to power, the connectors on the bottom are energized with hazardous voltage. Connect input power only after: • the MPX PEM (Power Entry Module) is properly installed on the MPX PRC (Power Rail Chassis) • the MPX IPC™ (Input Power Cord) is properly connected to the MPX PEM Connect input power to the Liebert MPX only while the MPX IPC is properly connected to the MPX PEM. Failure to do so may subject the user to hazardous voltages. Tools Required • Tamper-resistant No. 1 Torx screwdriver bit, included with MPX PEM • No. 1 PoziDriv screwdriver bit, included with MPX PEM • No. 1 Phillips screwdriver, field-supplied Before beginning to assemble the Liebert MPX: • Ensure that utility power is not connected to any module or component. • Ensure that no equipment is connected to the MPX BRM (Branch Receptacle Module). • Ensure that the circuit breaker on the MPX BRM is Off. After the MPX PRC (Power Rail Chassis) has been installed in the rack, it is ready for attachment of an MPX PEM (Power Entry Module) and then the MPX BRMs (Branch Receptacle Modules). Emerson strongly recommends attaching the MPX PEM first, positioning it at either end of the MPX PRC. The module’s position will not adversely affect operation, but placing it at the end of the chassis will ease cable routing and separation of power and control cables in the rack. Proper orientation of the MPX PRC is required to allow for the best use of the top or bottom entry into your rack. If cables will enter through the top of the rack, be sure that the MPX PRC has the power bus to the right side. This will put the MPX PEM in a position where the input cord will be closest to the top of the rack. If cables will enter through the bottom of the rack, be sure that the MPX PRC is oriented so that the power bus is to the left side. This will put the MPX PEM in a position where the input cord will be closest to the bottom of the rack. To balance the loads, be sure that the installed MPX BRMs have more than one unique line configuration (L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N). This will help to ensure that none of the phases is overloaded. If the MPX PEM is a Variable-Capacity model, an MPX IPC (input power cord) is required. Last, an optional Liebert RPC (rack PDU card) can be installed. 14 Liebert® MPX™ Installation and Assembly Disconnect Loads Before Adding or Removing an MPX™ BRM™ During normal operation, MPX BRMs (Branch Receptacle Modules) are hot-swappable. While adding or removing an MPX BRM, no user loads can be connected to the MPX BRM. Attempting to do so may damage the Liebert® MPX™ or connected equipment. To attach either the MPX PEM™ or a MPX BRM: 1. Orient the module so that the power conducting tabs fit into the power bus on the MPX PRC™ and the communication contacts will fit into the MPX PRC’s communication bus (see Figure 13). 2. Make sure that the integral connectors at each end of the module are oriented so they will fit into the slot on the MPX PRC (Power Rail Chassis). 3. Press the module firmly onto the MPX PRC. 4. Secure the module to the Power Rail Chassis with the Integral Connectors; there is one on each end. a. Use a screwdriver to press each connector down. The Integral Connectors on the MPX PEM have tamper-resistant Torx heads; Integral Connectors on the MPX BRM have PoziDriv heads, however, the same size Phillips head screwdriver can be used. b. Turn the screw until it locks and tightens, about three-quarters of a turn. NOTE Do not overtighten the connector on either end cap. Overtightening can damage the equipment. Figure 13 Attach a module to the MPX PRC Integral Connector locking end on MPX PEM MPX BRM™ shown; Integral Connectors on the MPX BRM have PoziDriv heads; MPX PEM attaches similarly except Integral Connectors on the MPX PEM have tamper-resistant Torx heads. Power Conductors entering MPX PRC Power Bus. MPX PRC Power Bus Screwdriver depresses Integral Connector so the locking portion will fit into slot. MPX PRC Communication Bus Screw head will be flush with end cap when the Integral Connector locks in place. Screws secure end cap to MPX BRM. Never remove these screws. Integral Connector pressed into slot. ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. Do not remove the screws that affix the end cap. Removing the end cap will expose energized parts with hazardous voltage. 5. Repeat Steps 1 through 4 for each additional module. NOTE The Liebert MPX will operate properly if spaces exist between modules, but adding modules will be hampered unless the space left is the size of a standard MPX BRM. Decorative covers are available to reserve the proper space on the MPX PRC and to protect any unused sections of the unit’s surface. 15 Liebert® MPX™ Installation and Assembly Figure 14 Liebert® MPX™ assembled MPX PRC™ (Power Rail Chassis) (under modules) MPX BRMs™ (Branch Receptacle Modules) Liebert RPC™ (Rack PDU Card) MPX PEM™ (Power Entry Module) 16 Liebert® MPX™ Installation and Assembly 3.2.2 Attach an MPX™ IPC™ to an MPX PEM™—Variable-Capacity MPX PEM Only (North American Models Only) ! WARNING Risk of arc flash and electric shock. Can cause equipment damage, injury or death. The MPX PEM contains hazardous voltage that could cause serious injury or death. This unit must be properly and securely installed on the MPX PRC™ (Power Rail Chassis). Emerson strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work. Whenever the MPX PEM is connected to power, the connectors on the bottom are energized with hazardous voltage. Connect input power only after: • the MPX PEM (Power Entry Module) is properly installed on the MPX PRC (Power Rail Chassis) • the MPX IPC™ (Input Power Cord) is properly connected to the MPX PEM Connect input power to the Liebert MPX only while the MPX IPC is properly connected to the MPX PEM. Failure to do so may subject the user to hazardous voltages. Variable-Capacity MPX PEM (Power Entry Module) versions require an MPX IPC (input power cord) to connect to utility power. The MPX IPC is available with various input plugs for single-phase or 3-phase and up to 30A. Quick-connect couplings are attached to the MPX IPC to ease proper connection to the MPX PEM (Power Entry Module). The connectors fit only one way, mating the proper input, ground and neutral wires on the power cord to the MPX PEM. To attach the MPX IPC to an MPX PEM: 1. Ensure that utility power is not connected to any module or component. 2. Ensure that the MPX IPC is not connected to utility power. 3. Insert the quick-connect coupling on the MPX IPC into the connector on the MPX PEM. It will lock into place. Tug on the cord to determine whether it is securely attached to the MPX PEM. Figure 15 Quick-connect couplings on MPX IPC (input power cord) and MPX PEM (Power Entry Module) Quick-connect Coupling on MPX IPC 3.2.3 Quick-Connect Couplings on MPX PEM Install an Optional Liebert RPC in the MPX PEM—North American Models Only Installing a Liebert® RPC (rack PDU card) in the MPX PEM (Power Entry Module) permits monitoring a Liebert MPX either over a network or with an MPX BDM™ (basic display module). For complete details, refer to the Liebert RPC™ user manual, SL-20825, or quick-start guide, SL-20826, each available in the monitoring area of Liebert’s Web site, www.liebert.com 1. Locate the communication card bay on the MPX PEM. You might need to remove a cover. 2. Insert the Liebert RPC into the MPX PEM and secure it with the provided screws. 3. The Liebert RPC has four ports designated by icons: a LAN port, Expansion/Management port, Display port, and Sensor port. Connect an Ethernet cable (not included) to the LAN port, identified by the icon on the right: LAN port icon 4. Connect the Ethernet cable to a computer. 17 Liebert® MPX™ Installation and Assembly 3.3 Temperature/Humidity Sensor Installation—Optional Optional Liebert® SN temperature/humidity sensors are available to assist in monitoring conditions in the rack. Liebert SN sensors are designed for installation in a Knurr® Miracel™ without tools, but each may be placed in any area to monitor temperature and humidity levels. Each connects to the Liebert RPC™, which makes readings available to Liebert MPX™ monitoring methods. Only one mounting method is addressed in this manual: attaching a single sensor with a bracket to a Knurr Miracel frame member. For details on other mounting locations and methods, refer to the Liebert SN quick-start guide, SL-20840, or to the Liebert RPC user manual, SL-20825. Each is available at Liebert’s Web site, www.liebert.com To install a sensor on a Knurr® Miracel™ frame member: 1. Assemble the Liebert SN and sensor bracket: a. Insert the sensor bracket base into one end of the sensor support as shown in Figure 16. b. Snap the sensor into the other end of the sensor support. 2. Choose where in the rack to install the sensor assembly. Emerson recommends placing the sensor in the area that is likely to be warmest. 3. Hold the sensor bracket on a T-slot on the Knurr Miracel frame where the sensor will be placed. 4. Insert the included quarter-turn fastener through the rectangular hole in the sensor bracket base and into the T-slot (see Figure 16). 5. Turn the fastener clockwise 90 degrees, a quarter of a turn. 6. Route the sensor cable to the Liebert RPC and insert it into the card’s external sensor port. For further details, refer to the Liebert RPC user manual, SL-20825, which shipped with the card and is available at Liebert’s Web site: www.liebert.com Figure 16 Temperature/humidity sensor mounting Sensor Support Sensor Bracket Base Liebert SN Sensor Quarter-Turn Fastener Rectangular protrusion passes through bracket slot (above) and into T-slot on Knurr Miracel frame member (below). Liebert SN Sensor Cable 18 Liebert® MPX™ Installation and Assembly Install an Optional RPCBDM™ in the Rack 3.4 The RPCBDM (Basic Display Module) can be mounted in the rack with either the included hardware or with a cable tie through the slot on the back of the module (see Figure 17). Either method permits moving the RPCBDM to a different place in the same rack or to another rack. 3.4.1 Mounting Hardware • • • • Spring nut M5: 1 Spacer sleeve: 1 Special MPX screw: 1 Cable clip: 1 Tools Required • Flat-blade screwdriver 3.4.2 RPCBDM Installation on Knurr® Miracel™ Frame 1. Determine the mounting location in the rack. 2. Insert a spring nut into a T-slot on the frame member where the RPCBDM will be installed (refer to Figure 9). 3. Insert the Liebert® MPX™ screw into the spacer sleeve. 4. Insert the Liebert MPX screw into the spring nut and tighten securely with the screwdriver. 5. Hang the RPCBDM on the Liebert MPX screw with the hooded mounting slot on the back of the RPCBDM (see Figure 17). 6. Connect the RPCBDM to the Liebert RPC™ with an Ethernet cable. Be certain to connect the cable to the correct port on the Liebert RPC (see Figure 18). Figure 17 RPCBDM installation in rack Cable tie fits in small slot on RPCBDM, loops around cabinet member Head of the Liebert MPX Screw in frame fits into hooded slot on back of RPCBDM 19 Liebert® MPX™ Installation and Assembly Figure 18 RPCBDM™ cable connection port on Liebert® RPC™ RPCBDM cable connection port on Liebert RPC 20 System Functional Test 4.0 SYSTEM FUNCTIONAL TEST 4.1 Checklist for Liebert® MPX™ Assembly Follow these guidelines steps to verify that all components are properly assembled. Failure to follow these steps and in the documented sequence could result in a serious injury or equipment damage. ___ 1. MPX PRC™ (Power Rail Chassis) is securely attached to the rack. ___ 2. MPX PEM™ (Power Entry Module) is attached to the MPX PRC. Ensure that the MPX PEM is securely locked onto the MPX PRC. ___ 3. Power input cable is attached to the MPX PEM, if applicable. Variable-Capacity models have detachable cables with quick-connect couplings; FixedCapacity models have integral cables. ___ 4. Optional Liebert RPC™ (Rack PDU Card) is installed in the MPX PEM. ___ 5. MPX BRM™ (Branch Receptacle Modules) are installed; the number of modules that may be attached varies according to the length of the Power Rail Chassis. ___ 6. Maximum electrical load is within values shown on the Liebert MPX module rating labels. ___ 7. The input power supply ratings and connections match the specifications of the unit being installed. 4.2 Test the Liebert MPX’s Functionality Perform these steps to determine whether the Liebert MPX is ready for use. Failure to follow these steps in the documented sequence could result in serious injury or equipment damage. 1. Ensure that all circuit breakers on the MPX BRMs are Off. 2. Connect the Liebert MPX unit to input power. • Validate that only one MPX PEM (Power Entry Module) is installed on the MPX PRC (Power Rail Chassis). • Verify that the MPX PEM (Power Entry Module) and MPX BRM™ (Branch Receptacle Module[s]) operating voltages are the same and match the input power source. 3. Connect equipment to the MPX BRMs. 4. Make sure the equipment to be connected to the Liebert MPX is switched Off. 5. Attach communication cables to the Liebert RPC, if one is installed in the Liebert MPX. 6. Switch On the circuit breaker of each MPX BRM where the load is connected. 7. Check the Phase Power Indicators on the MPX PEM to verify that input power is present (not available on Elementary MPX PEM models). The appropriate number of lights on the MPX PEM should be green and lit but not flashing: • input power is single-phase—L1 should be green • input power is single-phase 208-240VAC (North America only)—L1 and L2 should be green • input power is three-phase—L1, L2 and L3 should be green. 8. Verify that each attached MPX BRM is displaying a non-repeated identifying number in the Number Indicator beside the circuit beaker (the identifying numbers’ order in the display may not match the mapping of their physical location on the MPX PRC) (not available on Elementary MPX BRM models). 9. Switch On the test equipment or connected load to verify proper operation. 10. If any MPX BRMs are Receptacle Management versions, the lights beside the receptacles should be lit. 21 Operation and Configuration 5.0 OPERATION AND CONFIGURATION A Liebert® MPX™ can be operated with or without the optional Liebert RPC™ (Rack PDU Card). The card employs a Web-based interface to enhance monitoring and control, enabling users to manage rack equipment locally or from a remote location. The Liebert RPC can be used to determine power usage, switch receptacles on some units On and Off and troubleshoot input power supply problems. The Liebert RPC will manage and monitor different types of MPX BRMs (Branch Receptacle Modules) installed on the same Liebert MPX. The feature can be valuable when some rack equipment connected to the Liebert MPX requires closer monitoring than other equipment. The Liebert RPC supports managing and monitoring the Liebert MPX with SNMP, Liebert Nform™, Liebert SiteScan® and third-party management systems. When connecting the rack equipment to the Liebert MPX’s receptacles, arrange cables and connections to avoid tangling and crisscrossing the power cables. For power management purposes, record the receptacle where each piece of equipment is connected. Receptacles on the Liebert MPX have a numerical designation. A Liebert MPX with more than one circuit has the outlets named with numbers and are grouped by branch with a number referring to the proper circuit breaker. 5.1 Configure the Liebert RPC The Liebert RPC is factory-configured for DHCP. If you require a Static or BootP network configuration, be sure to change the Boot Mode, as described below: 1. Insert an additional Ethernet cable (not included) into the Liebert RPC’s Expansion/Management port, identified by the icon on the right: Expansion/ Management port icon NOTE The Liebert RPC’s Expansion/Management port should be used ONLY for local configuration through interconnection to a computer or for interconnecting an additional Liebert MPX or Liebert MPH™. 2. Insert the other end of the Ethernet cable into a computer. 3. Configure the computer’s IP settings to communicate on a 192.168.1.X network: IP address 192.168.1.9 Subnet mask 255.255.255.252 Default gateway 192.168.1.1 4. To connect to the card, open a Web browser and enter http://192.168.1.10 into the URL field, then press Enter. 5. Once the Rack PDU Web page is displayed, click the Configure tab, then click Network Settings in the left pane. 6. When prompted for a user name and password, enter Liebert (case sensitive) for both. NOTE Control and configuration capabilities are protected by a username and password combination. After entering Liebert for both the startup default username and password, change it in both places for better security. 7. Click OK. 8. Click Edit in the right pane. 9. The default Speed/Duplex for the Ethernet port is Auto (automatic). To change this, choose from the Speed/Duplex drop-down list. 10. Choose the Boot Mode: DHCP, Static or BootP. (The default is DHCP.) 11. Click Save to save any changes (or Reset to cancel). A Notice window displays a reminder to reinitialize the card. 12. Click OK. 13. Make other changes as needed in the Configuration tab. 14. To complete the configuration, click Reinitialize in the left pane. A Reinitialize button appears in the right side of the window. 15. Click Reinitialize in the right pane to commit the changes and reboot the card. The card is now fully operational. 22 Operation and Configuration 5.1.1 Indicators NOTE Do not continue to use the Liebert® MPX ™if the LED panel or monitoring interface indicators are not in accordance with these operating instructions. Refer all faults to your local dealer, Emerson representative or Emerson Distributed Processing Applications Engineering. One or more Phase Power Indicators on the MPX PEM™ (Power Entry Module) should be green and lit but not flashing to indicate that input power is present and within tolerance. If input power is 3-phase, all three Phase Power Indicators should be lit green; and if input power is single-phase, one Phase Power Indicator should be lit green Each MPX BRM™ should display a non-repeated identifying number in the LED beside the circuit beaker. If any MPX BRMs are receptacle management versions, the LEDs beside the receptacles should be lit. 5.2 Operation With the Liebert RPC™ Instructions for operating a Liebert MPX equipped with a Liebert RPC (Rack PDU Card) are more fully detailed in the card’s user manual, SL-20825, available at the Liebert Web site: www.liebert.com 5.2.1 Connect to the Liebert RPC After the Liebert RPC (Rack PDU Card) is installed and configured, the card is ready to be used to monitor and manage the Liebert MPX as described below. If the card is not installed and configured, refer to 3.2.3 - Install an Optional Liebert RPC in the MPX PEM—North American Models Only and 5.1 - Configure the Liebert RPC. 1. Open a Web browser (Liebert recommends using Microsoft’s Internet Explorer®) and enter http://192.168.1.10 into the URL field, then press Enter to display the Liebert MPX’s Web page. 2. When prompted for a user name and password, enter Liebert (case sensitive) for both. Control and configuration capabilities are protected by a username and password combination. After entering Liebert for both the startup default username and password, change both for security purposes (refer to the user manual, SL-20825). 3. Access information about the Liebert MPX or configure the Liebert MPX by clicking on the appropriate tabs and viewing choices (refer to the views in Figure 20). 23 Operation and Configuration 5.2.2 Viewing PDU and Receptacle Status: PDU Explorer and Device Explorer The PDU Explorer permits browsing components from the highest level of the Liebert® MPX™ to the receptacle level. The PDU Explorer is Web-based software that displays a hierarchical view of the system. Using PDU Explorer, the user is able to browse components starting at the PDU level, through to the branches of the PDU, and down to the receptacles of those branches. Figure 19 Liebert® RPC™ PDU Explorer view PDU Explorer Rack PDU Information System Status Options & Operations The Device Explorer shows the status and identification of all receptacles on a single PDU. This list can be sorted by the supplied fields, allowing quick navigation. Associated links navigate to the PDU Explorer for viewing or configuring a receptacle Figure 20 Liebert RPC Device Explorer view Device Explorer 5.3 Operation Without the Liebert RPC The Liebert MPX can be operated without the optional Liebert RPC (rack PDU card), but it will have reduced functionality. After the unit is installed and assembled, connect rack equipment to the receptacles, connect input power and by switch on the circuit breaker on each MPX BRM™ (Branch Receptacle Module). Start the rack equipment according to the manufacturer’s instructions. 24 Maintenance 6.0 MAINTENANCE The Liebert® MPX™ needs little or no maintenance. Emerson® recommends setting up a maintenance schedule that includes: • Dust the unit’s exterior with a clean, dry cloth. • Check all fittings and connections to ensure they are tight. • If any fuses need replacing, they must be replaced with the same type. 6.1 Maintenance Support The Liebert MPX contains no user-serviceable parts. If you need support or have questions about your Liebert MPX, contact Emerson Network Power Distributed Processing Applications or your local Emerson representative. Do not attempt to service this product yourself. 25 Specifications 7.0 SPECIFICATIONS 7.1 MPX™ PRC™—Model Number Configuration • Prefix: MPXPRC• Mounting: V = Vertical • Length: 1035 = Short (40-3/4"; 1035mm); 1880 = Standard (74"; 1880mm) Table 1 MPX PRC (Power Rail Chassis) specifications Maximum Modules Ratings Model # Length, mm (U.) BRM (266mm) PEM MPXPRC-V1880xxx 1880 (42) 6 (266mm) 1 (220mm) MPXPRC-V1035xxx 1035 (23) 3 (266mm) 1 (266mm) 26 Ampere, A Voltage, V 63 240/415 Weight, lb. (kg) 4.76 (2.16) 2.62 (0.84) Specifications 7.2 MPX™ PEM™—Model Number Configuration • • • • • • Prefix: MPXPEMRegion: N=North America; E=European Type: V = Variable-Capacity; H = Fixed-Capacity Size: A = Small (220mm); B = Standard (266mm) Communication: A=RPC Installed; X=RPC Not Installed; E=Not Available Input Power: • Variable-Capacity PEM Plug Style: X=Standard (APP) Service: A=NA 30A120/208V and EU 32A 230/400V; B=NA 30A 240/415V Remaining Positions Use X • Fixed-Capacity Plug Style: X=Standard (Straight); S=Special; R=Right Angle Service (if Plug=X|R): F=L6-30P; H=L21-30P; I=L22-30P; M=L7-30P; Q= EU IEC309 32A 230V 1P2W+PE; R=EU IEC309 32A 230/400V 3P4W+PE; S=EU IEC309 16A 230V 1P2W+PE; T=EU IEC309 16A 230/400V 3P4W+PE; V=NA CS8365C 50A 3P3W+PE,208240V; W=NA IEC309 60A 120/208-240V 3P4W+PE; X=NA IEC309 60A 208-240V 3P3W+PE; Y=NA IEC309 60A 240/415V 3P4W+PE; Z=EU IEC309 63A 230/400V 3P4W+PE • Cord Length (nominal; if Plug=X|R): Reflect meters with two digits (e.g., 30 = 3.0m) If Plug=S, the Service and Cord fields are combined as a numerical value only, e.g., 001 Table 2 MPX PEM (Power Entry Module) specifications Input Ratings Model # Capacity Strain Relief S=Straight R=Right Angle Ampere Voltage Service Phase 30 (24) 120/208-240 1-3 220 S 2.3 (1.03) Length, mm Weight lb. (kg) North American Applications MPXPEM-NVAXXAXX Variable MPXPEM-NHBXRF30 Fixed 30 (24) 208-240 1 266 R 2.3 (1.03) MPXPEM-NHBXXI30 Fixed 30 (24) 240/415 3 266 S 2.3 (1.03) MPXPEM-NHBXXH30 Fixed 30 (24) 120/208-240 3 266 S 2.3 (1.03) MPXPEM-NHBXRH30 Fixed 30(24) 120/208-240 3 266 R 2.3 (1.03) MPXPEM-NHBXXM30 Fixed 30 (24) 240 1 266 S 2.3 (1.03) MPXPEM-NHBXXW30 Fixed 60 (48) 120/208-240 3 266 S 2.3 (1.03) MPXPEM-NHBXRW30 Fixed 60 (48) 120/208-240 3 266 R 2.3 (1.03) MPXPEM-NHBXXX30 Fixed 60 (48) 208-240 3 266 S 2.3 (1.03) MPXPEM-NHBXRX30 Fixed 60 (48) 208-240 3 266 R 2.3 (1.03) MPXPEM-NHBXXV30 Fixed 50 (40) 208-240 3 266 S 2.3 (1.03) MPXPEM-NHBXRV30 Fixed 50 (40) 208-240 3 266 R 2.3 (1.03) MPXPEM-EHAAXQ30 Fixed 32 230 1 220 S 2.3 (1.03) MPXPEM-EHAEXQ30 Fixed 32 230 1 220 S 2.3 (1.03) MPXPEM-EHAAXR30 Fixed 32 230/400 3 220 S 2.3 (1.03) MPXPEM-EHAEXR30 Fixed 32 230/400 3 220 S 2.3 (1.03) MPXPEM-EHAAXS30 Fixed 16 230 1 220 S 2.3 (1.03) MPXPEM-EHAEXS30 Fixed 16 230 1 220 S 2.3 (1.03) MPXPEM-EHAAXT30 Fixed 16 230/400 3 220 S 2.3 (1.03) MPXPEM-EHAEXT30 Fixed 16 230/400 3 220 S 2.3 (1.03) MPXPEM-EHBAXZ30 Fixed 63 230/400 3 266 S 2.3 (1.03) MPXPEM-EHBEXZ30 Fixed 63 230/400 3 266 S 2.3 (1.03) European Applications 27 Specifications MPX™ BRM™—Model Number Configuration 7.3 • • • • Prefix: MPXBRMRegion: N=North America; E=European Type: B=Branch Monitoring; R=Receptacle Management; E=Elementary (No Monitoring) Size and OL Protection: • A=Small (220mm), B=Standard (266mm), C=Standard w/ Tamper-Proof Screws • Output Power: • Voltage/CB Rating: A=120V,20A; B=208V,20A; C=230V,20A; D=208-240V,20A; E=100V,20A; F=240V,20A • Number of Receptacles: 2 to 7 • Receptacle Type: A=5-20R; F to L=Reserved; N=IEC-C13 Sheet F; O=IEC-C19 Sheet J; P=CEE-7 Type F (Schuko); U=GST18 • Phase Configuration: 1N=L1-N; 2N=L2-N; 3N=L3-N; 12=L1-L2; 23=L2-L3; 31=L3-L1 Table 3 MPX BRM (Branch Receptacle Module) specifications Model # Type Receptacle Ratings No. of Outlets Ampere, A Voltage, V OCB, A Voltage Configuration Length, mm Region Weight lb. (kg) RECEPTACLE MANAGEMENT MODULES North American Applications MPXBRM-NRBA6A1N NEMA 5-20R 6 16 120 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NRBA6A2N NEMA 5-20R 6 16 120 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NRBA6A3N NEMA 5-20R 6 16 120 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NRBD4O12 IEC C19 Sheet J 4 16 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NRBD4O23 IEC C19 Sheet J 4 16 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NRBD4O31 IEC C19 Sheet J 4 16 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NRBD6N12 IEC C13 Sheet F 6 12 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NRBD6N23 IEC C13 Sheet F 6 12 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NRBD6N31 IEC C13 Sheet F 6 12 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NRBF4O12 IEC C19 Sheet J 4 16 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NRBF4O23 IEC C19 Sheet J 4 16 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NRBF4O31 IEC C19 Sheet J 4 16 240 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NRBF6N12 IEC C13 Sheet F 6 12 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NRBF6N23 IEC C13 Sheet F 6 12 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NRBF6N31 IEC C13 Sheet F 6 12 240 20 L3-N 266 NA 2.3 (1.03) RECEPTACLE MANAGEMENT MODULES European Applications MPXBRM-ERBC3P1N Schuko CEE 7/4 3 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-ERBC3P2N Schuko CEE 7/4 3 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-ERBC3P3N Schuko CEE 7/4 3 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-ERBC4O1N IEC C19 Sheet J 4 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-ERBC4O2N IEC C19 Sheet J 4 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-ERBC4O3N IEC C19 Sheet J 4 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-ERBC6N1N IEC C13 Sheet F 6 10 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-ERBC6N2N IEC C13 Sheet F 6 10 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-ERBC6N3N IEC C13 Sheet F 6 10 230 20 L3-N 266 EU 2.3 (1.03) 28 Specifications Table 3 MPX BRM (Branch Receptacle Module) specifications (continued) Model # Type Receptacle Ratings No. of Outlets Ampere, A Voltage, V OCB, A Voltage Configuration Length, mm Region Weight lb. (kg) BRANCH MONITORING MODULES North American Applications MPXBRM-NBBA6A1N NEMA 5-20R 6 16 120 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NBBA6A2N NEMA 5-20R 6 16 120 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NBBA6A3N NEMA 5-20R 6 16 120 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NBBD4O12 IEC C19 Sheet J 4 16 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NBBD4O23 IEC C19 Sheet J 4 16 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NBBD4O31 IEC C19 Sheet J 4 16 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NBBD6N12 IEC C13 Sheet F 6 12 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NBBD6N23 IEC C13 Sheet F 6 12 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NBBD6N31 IEC C13 Sheet F 6 12 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NBBF4O12 IEC C19 Sheet J 4 16 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NBBF4O23 IEC C19 Sheet J 4 16 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NBBF4O31 IEC C19 Sheet J 4 16 240 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NBBF6N12 IEC C13 Sheet F 6 12 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NBBF6N23 IEC C13 Sheet F 6 12 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NBBF6N31 IEC C13 Sheet F 6 12 240 20 L3-N 266 NA 2.3 (1.03) BRANCH MONITORING MODULES European Applications MPXBRM-EBBC3P1N Schuko CEE 7/4 3 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EBBC3P2N Schuko CEE 7/4 3 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EBBC3P3N Schuko CEE 7/4 3 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-EBBC4O1N IEC C19 Sheet J 4 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EBBC4O2N IEC C19 Sheet J 4 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EBBC4O3N IEC C19 Sheet J 4 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-EBBC6N1N IEC C13 Sheet F 6 10 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EBBC6N2N IEC C13 Sheet F 6 10 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EBBC6N3N IEC C13 Sheet F 6 10 230 20 L3-N 266 EU 2.3 (1.03) ELEMENTARY MODULES North American Applications MPXBRM-NEBA6A1N NEMA 5-20R 6 16 120 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NEBA6A2N NEMA 5-20R 6 16 120 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NEBA6A3N NEMA 5-20R 6 16 120 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NEBD4O12 IEC C19 Sheet J 4 16 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NEBD4O23 IEC C19 Sheet J 4 16 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NEBD4O31 IEC C19 Sheet J 4 16 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NEBD7N12 IEC C13 Sheet F 7 12 208-240 20 L1-2 266 NA 2.3 (1.03) MPXBRM-NEBD7N23 IEC C13 Sheet F 7 12 208-240 20 L2-3 266 NA 2.3 (1.03) MPXBRM-NEBD7N31 IEC C13 Sheet F 7 12 208-240 20 L3-1 266 NA 2.3 (1.03) MPXBRM-NEBF4O12 IEC C19 Sheet J 4 16 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NEBF4O23 IEC C19 Sheet J 4 16 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NEBF4O31 IEC C19 Sheet J 4 16 240 20 L3-N 266 NA 2.3 (1.03) MPXBRM-NEBF7N12 IEC C13 Sheet F 7 12 240 20 L1-N 266 NA 2.3 (1.03) MPXBRM-NEBF7N23 IEC C13 Sheet F 7 12 240 20 L2-N 266 NA 2.3 (1.03) MPXBRM-NEBF7N31 IEC C13 Sheet F 7 12 240 20 L3-N 266 NA 2.3 (1.03) 29 Specifications Table 3 MPX BRM (Branch Receptacle Module) specifications (continued) Receptacle Ratings Type No. of Outlets Ampere, A MPXBRM-EEBC3P1N Schuko CEE 7/4 3 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EEBC3P2N Schuko CEE 7/4 3 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EEBC3P3N Schuko CEE 7/4 3 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-EEBC4O1N IEC C19 Sheet J 4 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EEBC4O2N IEC C19 Sheet J 4 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EEBC4O3N IEC C19 Sheet J 4 16 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-EEBC7N1N IEC C13 Sheet F 7 10 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EEBC7N2N IEC C13 Sheet F 7 10 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EEBC7N3N IEC C13 Sheet F 7 10 230 20 L3-N 266 EU 2.3 (1.03) MPXBRM-EEBC9U1N GST18 9 16 230 20 L1-N 266 EU 2.3 (1.03) MPXBRM-EEBC9U2N GST18 9 16 230 20 L2-N 266 EU 2.3 (1.03) MPXBRM-EEBC9U3N GST18 9 16 230 20 L3-N 266 EU 2.3 (1.03) Model # Voltage, V OCB, A Voltage Configuration Length, mm Region Weight lb. (kg) ELEMENTARY MODULES European Applications MPX™ IPC™—Model Number Configuration 7.4 • Prefix: MPXIPC• Region: N=North America; E=European • Input Power and Connection: • Plug: X=attached, N=none • Service: D=L5-30P; F=L6-30P; G=L21-20P; H=L21-30P; I=L22-30P; J=L15-30P; K=L14-20P; L=L14-30P; M=L7-30P • Cord Length: Length in meters, two digits (e.g. 30 = 3.0 meters) Table 4 MPX IPC (Input Power Cord) specifications Input Ratings Model # Ampere, A Voltage, V Service Length mm (ft) Region MPXIPC-NXD30XXX 30 120 1-phase NEMA L5-30P 3.0 (10) NA MPXIPC-NXF30XXX 30 208-240 1-phase NEMA L6-30P 3.0 (10) NA MPXIPC-NXG30XXX 20 120/208-240 3-phase NEMA L21-20P 3.0 (10) NA MPXIPC-NXH30XXX 30 120/208-240 3-phase NEMA L21-30P 3.0 (10) NA MPXIPC-NXI30XXX 30 240/415 3-phase NEMA L22-30P 3.0 (10) NA MPXIPC-NXJ30XXX 30 208-240 3-phase NEMA L15-30P 3.0 (10) NA MPXIPC-NXK30XXX 20 120/208-240 2-phase NEMA L14-20P 3.0 (10) NA MPXIPC-NXL30XXX 30 120/208-240 2-phase NEMA L14-30P 3.0 (10) NA MPXIPC-NXM30XXX 30 240 1-phase NEMA L7-30P 3.0 (10) NA 30 Specifications 7.5 Agency Approvals 120V and 240V Single-Phase and 120/208-240V Three-Phase North American Units • UL60950-1: Information Technology Equipment - Safety, Part 1 General Requirements • CSA C22.2 No. 60950-1: Information Technology Equipment - Safety, Part 1 General Requirements • FCC, Title 47, Part 15 Subpart B for Class B operation as defined by ANSI Standard C63.4. • ISTA Procedure 1A and 2A • RoHS Compliant 230V Single-Phase and 400V Three-Phase European Units • CE Markings GS mark (safety tested) according to DIN EN 60950-1 (VBE 0805-1) 2006/95/EC and EMC Directive (EMD) 2004/108/EC according to the Low-Voltage Directive (LVD) • CE Compliant according to: • Low-Voltage Directive 2006/95/EC • Electromagnetic - Compatibility Directive 2004/108/EC (EMD) • RoHS Directive 2002/95/EC • WEE Directive 2002/96/EC • ISTA Procedure 1 A and 2A • ROHS and WEEE Compliant, Basic Test for Purchased Products according to International Safe Transit Association Table 5 Electrical and environmental specifications Power Consumption, W 22 maximum per fully configured 42U model (RPC, BDM, PEM, 6xBRM-R) 3 per RPC; 0.4 per module + 0.4 per open control (energized condition) Maximum Ratings 240/415V 50/60Hz 63A Insulation Class I, Basic Earthed SELV Electric Strength, VDC 2200 Overcurrent Protection UL489 Overcurrent Circuit Breaker per Branch, 20A, 5000A A.I.C Operating Temperature, °C (°F) 5-55 (41-131) Humidity, % 10-95, non-condensing Altitude, m (ft.) 2000 (6560) Table 6 Metering performance Volts, V ±1 ±2 from 1% to <10% Accuracy, % Current, A (per %rated value) ±1 from 10% to 125% Branch Receptacle Module (BRM™) Power Entry Module (PEM) Branch Receptacle Phase Voltage, 0.1V Measurement, Resolution √ — √ Line Voltage, 0.1V √ — — Line Current, 0.01A √ √ √ Neutral Current, 0.01A √ (3-phase only) — — Total Real Power, 0.1W √ — — Total Real Energy, 0.1kW-hr √ — — Real Power, 0.1W — √ √ Apparent Power, 0.1VA — √ √ Real Energy, 0.1kW-hr — √ √ Power Factor, 0.01 — √ √ Crest Factor, 0.01 — — √ Frequency, 0.1Hz √ — — 31 Dimensional Drawings 8.0 DIMENSIONAL DRAWINGS Figure 21 Liebert® MPX™ assembly dimensions, 1880mm (74") versions 10.5" (266mm) MPX PRC Cover/Spacer 10.5" (266mm) 10.5" (266mm) 10.5" (266mm) 10.5" (266mm) 10.5" (266mm) 74" (1880mm) TOP VIEW 2.9" (75mm) 4.1" (104mm) Input Power Cord 2.9" (75mm) END VIEW 4.1" (104mm) MPX BRM (Branch Receptacle Modules) MPX PRC (Power Rail Chassis) MPX PEM MPX BRM (Power Entry Circuit Breaker Module) Protection Body SIDE VIEW Figure 22 Liebert MPX assembly dimensions, 1035mm (40.6") versions MPX PRC Cover/Spacer 10.5" (266mm) 10.5" (266mm) 10.5" (266mm) 8.7" (220mm) 40.6" (1035mm) TOP VIEW MPX BRM Circuit Breaker Protection Body MPX PEM (Power Entry Module) MPX BRM (Branch Receptacle Modules) Input Power Cord 4.1" (104mm) MPX PRC (Power Rail Chassis) SIDE VIEW 2.9" (75mm) 4.1" [104mm] 2.9" (75mm) 32 Dimensional Drawings Figure 23 RPCBDM™ dimensions Top Mounting Slot Communication Connection 2.6" (66mm) Rear LCD Screen 0.8" (21mm) 4.5" (116mm) 1.1" (29mm) FRONT VIEW SIDE VIEW 0.787" (20mm) 0.063" (1.6mm) 0.059" (1.5mm) 0.122" (3.1mm) 0.472" (12.0mm) Mounting Slot M6 REAR VIEW DETAIL A See Detail A 33 Recycling Information, FCC Compliance, Modifications 9.0 RECYCLING INFORMATION, FCC COMPLIANCE, MODIFICATIONS Notice to European Union Customers: Disposal of Old Appliances This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE. This product uses components that are dangerous for the environment, such as electronic cards and other electronic components. Any component that is removed must be taken to specialized collection and disposal centers. If this unit must be dismantled, this must be done by a specialized center for collection and disposal of electric and electronics appliances or other dangerous substances. The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE). For information regarding the scrapping of this equipment, please browse http://www.eu.emersonnetworkpower.com (“Products” or “Contacts” session) or call our worldwide technical support: • Channel Applications Engineering: 800-222-5877, ext. 1 Outside North America: +800 1155 4499, ext. 1 e-mail: [email protected] • Monitoring Applications Engineering: 800-222-5877, ext. 2 Outside North America: +800 1155 4499, ext. 2 e-mail: [email protected] RoHS Compliance The Liebert® MPX™ modules comply with the Restriction of Hazardous Substances Directive (RoHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder. FCC Compliance This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment Off and On, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorienting or relocating the receiving antenna. • Increasing the separation between the equipment and receiver. • Connecting the equipment into an outlet on a circuit different from that to which the receiver is connected. • Seeking assistance from the local Emerson representative or an experienced radio/TV technician. Do Not Modify Users should be aware that this product must be assembled and operated as stated in this document. Modifying the Liebert MPX or any module may void the user’s authority to operate the equipment. 34 Ensuring The High Availability Of Mission-Critical Data And Applications. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability. Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-20820_REV3_07-12 Emerson Network Power. The global leader in enabling Business-Critical Continuity™ AC Power Connectivity Embedded Computing Embedded Power DC Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling EmersonNetworkPower.com Racks & Integrated Cabinets Services Surge Protection Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.