Translation, (1) (2) orlginallanguage: German EC- TYPE EXAMINA TION CERTIFICA TE Equlpment and protectlve systems intended for use In potentially explosive atmospheres ~Dlrective 9419/EC EC-Type Examination Certificate Number: KEMA 06ATEX0177 Component: Terminal Blocks Types PDU 2.5/4, PDU 2.51413AN, POU 2.S/414AN, PDU 6/10, PDU 6110/3AN, PDU 16, PEI16 and Protectlve Conductor Terminal Blocks Types PPE 2.5/4, PPE 2.51413AN, PPE 2.5/4/4AN, PPE 6/10, PPE 6/10/3AN and PPE 16 Interface U Issue Number: 1 (3) (4) (5) Manufacturer: Weidmüller (6) Address: KlingenbergstraBe GmbH & Co KG (7) This component and any acceptable documents therein referred to. (8) KEMA Quality B.V., notified body number 0344 in accordance with Article 9 of the Council Directive 94/9/EC of 23 March 1994, certlfles that this component has been found to comply with the Essential Health and Safety Requirements relatlng to the design and construction of equipment and protective systems intended for use in potentiaUy explosive atmospheres given In Annex 11to the directive. 16, 0-32758 Oetmold. variation thereto Germany is specified in the schedule to this certificate and the The examinatlon and test results are recorded in confidential report no. 2093377. (9) Compliance with the Essential Health and Safety Requirements has been assured by compliance with: EN 60079~7 : 2003 EN 60079-0 : 2004 EN 50281-1-1 : 1998 + A1 (10) The sign ·U" placed after the certificate number indicates that this certificate describes components and must not be mistaken for a certificate Intended for an equipment or protective system. This EC-Type Examination Certificate may be used as a basis for certification of an equlpment or protective system. (11) This EC-Type Examination Certificate relates only to the design, examination and tests of the specified component according to the Directive 94/9/EC. Further requirements of the directive apply to the manufacturing process and supply of this component. These are not covered by this certificate. (12) The marking ofthe component shall include the following: 112GD Exell Thi5 certlficate 15Issued on 24 August 2006 and, as far as applicable, shall be revised before the date of cessatlon of pre5umption of conformity of (one of) the standards mentloned above as communlcated In the Official Joumal of the European Union. Page 1/4 o Integral publlcallon oftllis certlflcate and adJolnlng relloltS Is allowed. Tllls Certlflcate may only be rellroduced in its en~rety and witllout any ellange KEMA Quality B.V. Utrechtseweg 310, 6812 AR Arnhem P.O. Box 5185,6802 ED Arnhem, The Netherlands T +31 263562000 F +31 263525800 [email protected] WWIN.kema.com Registered Arnhem 09085396 -------------------------- Experienceyou can trust (13) SCHEDULE (14) to EC-Type Examination (15) Descrlption Certificate KEMA06ATEX0177 U The Terminal Blocks PDU 2.5/4, PDU 2.5/4/3AN, PDU 2.5/4/4AN, PDU 16, PEI 16 ae weil as the Protective Conductor Terminal Issue No. 1 PDU 6/10, PDU 6/l0/3AN, Blocks Types PPE 2.5/4, PPE 2.5/4/3AN, PPE 2.5/4/4AN, PPE 6/10, PPE 6/10f3AN and PPE 16 with accessories, are intended for the connection of copper conductors in enclosures in type of protection increased safety "e" cr "D" (dust). Fixing ie made on mounting rails type T5 35 according to EN 60715, Top hat seetion rail TH 35. Operating temperature Electrical data Terminal blocks range: -50 oe .. +100 oe. Type: Rated insulation voltage M Rated voltage M - with jumper M - with skipping jumper ovar PE Type IV] - with 2 parallel skipping jumpers M Nominal current [Al - with jumper [Al Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm2] (AWG) - flexible lmm~ (AWG) Type: Rated insulation voltage M Rated voltage M - with jumper M - with skipping jumper over PE Type [V] - with 2 parallel skipping jumpers M Nominal current [Al - wlth jumper [Al Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm2] (AWG) - flexiblelmm~ (AWG) Type: Rated insulation voltage M Rated voltage M - with jumper M - with skipping jumper over PE Type [V] - with 2 parallel skipping jumpers M Nominal current [A] - wlth jumper [Al Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm2] (AWG) - flexible [mm~ (AWG) MEAN-P-Ex61 v2.1 PDU 2.5/4 500 550 275 176 176 29 25,5 4 PDU 2.5/4/3AN 500 550 275 176 176 29 25.5 4 0,5-6 (20-10) 0,5-4 (20-12) 0,5-6 (20-10) 0,5-4 (20-12) PDU 2.5/4/4AN 500 550 275 176 176 29 26,5 4 PDU 6/10 500 550 275 0,5-6 (20-10) 0,5-4 (20-12) 1,5-6 (16-10) 1,5-10 (16-8) PDU 6/10/3AN 500 550 275 PDU16 500 550 275 275 36,5 29,5 6 110 59 57,5 16 1,5-6 (16-10) 1,5-10 (16-8) 2,5-10 (14-8) 2,5-16 (14-6) 220 37 26,5 6 Page 2/4 (13) SCHEDULE (14) 10 EC.Type Examinalion Certificale KEMA06ATEX0177 Type: Rated insulation voltage M Rated voltage M - with jumper M • with skipping jumper over PE Type M - with 2 parallel jumpers M Nominal current [Al - with PDU 2,5/4 and jumper ZQV 2,5 [Al - with PDU 6/10 end jumper zav 6N [Al Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm2] (AWG) - flexible [mm2] (AWG) Protective conductor terminal Issue No. 1 PEI16 500 550 275 66,5 25 37 16 2,5-10 2,5-16 (14-8) (14-6) blocks Type: Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm~ (AWG) - flexible [mm2] (AWG) Type: Rated cross section [mm2] (AWG) Connectable conductor cross section - rigid [mm2] (AWG) - flexible [mm~ (AWG) Typ.: Rated cross section [mm2J (AWG) Connectable conductor cross section - rigid [mm~ (AWG) - flexible [mm2] (AWG) Installation U PPE 2.514 4 PPE 2.5/413AN 4 0,5-6 (20-10) 0,5-4 (20-12) 0,5-6 (20-10) 0,5-4 (20-12) PPE 2.5/414AN 4 PPE 6/10 6 0,5-6 (20-10) 0,5-4 (20-12) 1,5-6 (16-10) 1,5-10 (16-8) PPE 6/10/3AN 6 PPE16 16 1,5-6 (16-10) 1,5-10 (16-8) 2,5-10 2,5-16 (14-8) (14-6) instructions The Terminal blocks and Protective conductor terminal block is suitable for use in enciosures in atmospheres with f1ammable gases or combustible dust. For f1ammable gases these enclosures must satisty the requirements according to EN 60079-0 and EN 60079-7. For combustible dust these enclosures must satisfy the requirements according to EN 50281-1-1. When assembling with other certmed series and sizes and using belonging creepage distances and ciearances have to be observed. Regarding the use of covers, must be followed. cross-connectors and end brackets accessories, the instructions the required of the manufacturer The Protective Conductor Terminal Block may be used at ambient temperatures of -50 QC to +40 'C at the mounting position in electrical apparatus, e.g. junction and connection boxes, for temperature class T6. When the Terminal Blocks are used in electrical apparatus of temperature classes T1 up to T5, the highest temperature of the insulating material shall not exceed the maximum value of the operating temperature range. MEAN-P-Ex61 v2.1 Page 3/4 (13) SCHEDULE (14) 10 EC-Type Examinalion Cortificalo KEMA06ATEX0177 U Issue No. 1 Routine tests Routine dielectric strength have to be carried out. (16) to EN 60079-7, Clause 7.2 in combination with Clause 6.1, Report KEMA (17) tests according No. 2093377. Special conditions for safe use None. (18) Essential Health and Safety Requirements Covered (19) by the standards listed at (9). Test documentation As Iisted in Test Report MEAN-P-Ex61 v2.1 No. 2093377. Page 4/4