Keeping Business in Business • • • • • • • • Process Fluid Chiller Designed for Marconi Medical MX8000 Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round. Factory-tested, piped, wired and charged for hassle-free startup and operation. Clean, non-ferrous cooling loop, required for sensitive medical equipment. Local service and parts for quick and knowledgeable maintenance and service. Optional switch-over to alternate water source provides redundant, continuous operation. Optional remote monitoring systems keep you informed of chiller operation. ETL/CSA certified. ISO 9001 certified company. MX8000 Specifications Fluid Specified Water or Glycol Max Heat Dissipation—BTUH (kW) 32,400 (9.5) Fluid Temperature Range—°F (°C) 36-57 (2-14) Temperature Gradient 0.5°C/min Fluid Flow Rate—GPM (l/m) 4.4 (16.7) Fluid Pressure Drop—PSI (kPa) 2.2 (15) Process Fluid Chiller Specifications Model Number Fluid Circulated PS048A PS048A PS048A Water Ethylene Glycol Propylene Glycol Net Cooling Capacity—BTUH (kW) 41,200 (12.1) 38,300 (11.2) 36,500 (10.7) Leaving Fluid Temperature—°F (°C) 48 (8.9) 48 (8.9) 48 (8.9) Fluid Flow Rate—GPM (l/m) 8 (30.4) 8 (30.4) 8 (30.4) 2.2 (15.2) 2.2 (15.2) 2.2 (15.2) MX8000 Pressure Drop—PSI (kPa) Chiller Pressure Drop—PSI (kPa) Pump Total Head—PSI (kPa) Head Available for Piping Circuit—PSI (kPa) Pump HP (kW) 8.2 (56.5) 11.1 (76.5) 13.1 (90.3) 46.8 (322.7) 46.8 (322.7) 46.8 (322.7) 36.4 (251) 33.5 (231) 31.5 (217.2) 1 (0.75) 1 (0.75) 1 (0.75) Process Fluid Chiller Designed for Marconi Medical MX8000 1 C A C B C C Model No. A - Width Inches (mm) B - Height Inches (mm) C - Depth Inches (mm) Weight Lbs. (kg) PS048A 53 (4684) 63 (1600)* 36 (918) 532 (241) * Includes added dimensions for thermal storage tank. Standard Features Optional Ship-Loose Accessories • • • • • • • • • • • • • • • • • • • • Indoor/outdoor cabinet Scroll compressor Refrigerant dehydrator Expansion valve Refrigerant receiver Stainless steel expansion tank Pressure relief valve Hot gas bypass valve capacity control Stainless steel pump Optional Features • Refrigerant gauges and expansion tank heater Alternate water source (AWS) module Enviro-source emergency bypass Fluid pressure gauge Check valve Dial thermometer Relief valve Circuit setter Ball valve High temperature thermostat Low flow switch Liebert RCM4 remote alarm monitor Required Special Options • SFA#7055-6, 50 gallon internal storage tank 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Phone: 800.877.9222 Fax: 614.841.6022 Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco Italy Phone: 39.049.9719.111 Fax: 39.049.5841257 Liebert Web Site—http:www.liebert.com 23/F Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong Phone: 852.2.572.2201 Fax: 852.2.572.1182 ©2000 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or regisered trademarks of their respective owners. SL-16559 (07/00) Process Fluid Chiller Designed for Marconi Medical MX8000 2