IRF IR2137IGBT

International Rectifier • 233 Kansas Street, El Segundo, CA 90245 USA
IGBT Protection in AC or BLDC Motor Drives
by Toshio Takahashi
The new IR2137 IGBT Gate Driver IC integrates Ground Fault and Over-Current Protection
with Soft Shutdown, thus providing a compact and comprehensive IGBT protection scheme.
1. INTRODUCTION
In the last decade, industrial AC drives have become more advanced in performance and more
compact in size. This is largely due to the rapid development of power silicon technology, including
the enhancement of IGBTs and of High Voltage Integrated Circuits. Additionally, this technological
growth has been particularly accelerated for low horsepower (< 5 Hp) AC Drives. Yet the ground fault
protection, a feature sought increasingly in motor drives of all power levels, is available widely only in
the high-end models due to the sensors and other circuitry involved. The market, however, continues
to demand a fully protected, yet inexpensive, system. To meet this demand, International Rectifier
has introduced the IR2137: a new generation 3-phase IGBT gate driver, featuring full IGBT protection and advanced soft shutdown features.
To understand traditional methods of IGBT protection, read Section 2. To understand the working of
the IR2137 skip to Section 3.
2. TRADITIONAL METHODS OF IGBT PROTECTION
2-1 Background Theory for Protecting Against Failure
One of the most common, and fatal, AC drive faults for IGBTs is the Over-Current condition. Table 1
outlines the causes for the three most common Over-Current modes.
Over-Current Mode
Line-to-Line Short
Ground Fault
Shoot Through
Potential Causes
Mis-wiring, Motor leads shorting, Motor phase-to-phase
insulation breaking down
Motor phase-to-phase insulation breaking down
False IGBT turn-on
Table 1: Potential Causes of Over-Current
www.irf.com
1
In order to protect IGBT devices effectively during an Over-Current condition, one needs to focus on
two factors.
First, one needs to detect the type of Over-Current mode and shut the system down. In both Line-toLine and Shoot Through mode, the short-circuit current flows from and to the DC bus capacitors
(Figures 1 and 3). Therefore, a shunt resistor in the ground path can detect these Over-Current
conditions. However in the Ground Fault mode, the current flows from the AC line input, through the
positive DC bus and high side IGBT, to the earth ground (Figure 2). Therefore, the Ground Fault
condition has to be detected either with a shunt resistor on the positive bus line or by detecting the
current in the output lines.
Second, one needs to look at the AC drive architecture. Protection circuitry needs to be built in a manner
that does not disrupt the drive system. For instance, Figure 4 shows a typical Floating Ground Reference Architecture in which the micro-controller (µC) is on the Floating Ground reference. Therefore, any
Over-Current detection circuit needs to be isolated. Alternate architecture may require reduced or no
isolation.
2-2 Traditional Methods of Over-Current Detection
Method 1
One can detect the Line-to-Line Short and Shoot Through currents by inserting a Hall Effect sensor
or a linear opto isolator across the shunt resistor. The device should be in series with the negative
DC bus line. For Ground Fault protection, an additional Hall Effect leakage current sensor could be
placed either on the AC line input or on the DC bus. The protection circuit is then implemented by
using fast comparators. The output of these comparators is ‘OR’d with the micro-controller or PWM
generator to initiate the shutdown of the gate signals.
Method 2
If located in the motor phase output, each Hall Effect sensor uses 2 comparators. This is done
because both positive and negative current polarities flow during a Line-to-Line Short condition.
Another important consideration is the total propagation delay for shutdown. The delay time associated with the optical isolators in the gate drive and the Hall Effect sensor is typically more than 2
microseconds. Therefore, regardless of protection circuitry implementation, this delay should be
added to the circuit delay, before matching it with the IGBT short circuit duration time. As shown in
Figure 4, the configuration requires 2 Hall Effect sensors and/or opto isolators in addition to the
protection circuit. The protection circuitry comprises of comparators (2), voltage references, capacitors, and resistors.
Method 3
Another protection method is to use an IGBT de-saturation circuit. This discrete circuit can be constructed in the secondary side of the opto gate driver. (Opto isolated devices with in-built de-saturation circuits can also be found in the market). This circuit detects voltage build-up across the collector and emitter while the device is fully on. If the voltage exceeds a specified limit, the associated
gate signal is shut off. A discrete circuit would require a comparator with voltage reference, a high
voltage diode, and various resistors and capacitors.
2
www.irf.com
2-3 Traditional Methods of Over-Current Shutdown
For shutting down an IGBT when an Over-Current condition is detected, a soft turn-off is preferred
because it reduces a high voltage spike across the collector and emitter of the IGBT device at fault.
Thus it provides a wider margin for the RBSOA limit during a short-circuit condition, allowing the
snubber circuit to be significantly minimized or even eliminated. When implemented in the discrete
circuit based on the floating ground reference architecture, a soft turn-off circuit can get very complex. Each IGBT gate drive circuit requires an additional fast opto isolator and soft turn-off circuit with
the dedicated totem pole buffer transistors. Given circuit costs and complexities, a snubber circuit is
preferred to the discrete soft shutdown circuit. For low Hp devices, the snubber circuit can be implemented with a high frequency type capacitor across the DC bus, near the IGBTs.
2-4 Problems with the Traditional Method
A. Circuit Control Problems
In a soft shutdown scheme, simultaneous shutdown of all 6 IGBTs is required to prevent a potential
false turn-on while the IGBTs are in the soft shutdown mode. If a high side IGBT is turned off softly
while the other IGBTs are in the middle of a switching transition within a PWM period, that IGBT can
unintentionally be turned back on. It is extremely difficult to synchronize simultaneous shutdown
using traditional architecture.
B. Part Count, Size, and Cost Problems
If the system requires full IGBT protection, including Ground Fault protection, and if it is based on the
floating ground reference architecture, then the gate drive and protection circuit require the following
major components (even without the soft shutdown feature):
• 6 fast opto isolators
• 2 fast Hall Effect sensors or fast linear opto isolators
• 2 comparators
• 4 floating 15V power supplies
Hall Effect sensors and opto isolators are relatively large and bulky, and require a lot more space
than a monolithic IC. In addition, if the system requires a soft shutdown function, 6 additional opto
isolators and 6 buffer circuits (with a provision for soft turn off capability) are required. Thus, whereas
low Hp AC drive systems are today moving toward smaller sizes, the above solutions provide neither
the simplicity nor the integration of the gate drive and protection circuitry that is needed.
The total cost, including assembly of the inverter system, is large due to the large number and
bulkiness of components. Furthermore, components such as the Hall Effect sensors are still subject
to manual assembly.
To circumvent these issues, a small, integrated IC device that is capable of performing all the above
functions is a necessity.
www.irf.com
3
IR2137: 3-PHASE GATE DRIVER WITH INTEGRATED IGBT PROTECTION
International Rectifier has now introduced the IR2137 to the AC drives market. This latest High
Voltage Integrated Circuit provides a monolithic solution to driving all six IGBT gate drivers, while
simultaneously providing full IGBT protection and soft shutdown. In contrast to the Floating Ground
Reference architecture discussed in the previous section, the IR2137 circuit enables a simple structure. The differences between the two architectures are summarized in Table 2.
Gate Drive
IGBT Protection
Additional Circuits
Floating Ground System
Six Fast Optical Isolators
Two Hall Effect sensors and
Two comparators
Four floating power supplies
Snubber circuit or discrete soft
shutdown circuits
Brake IGBT drive circuit with
an optical isolator
IR2137 solution
IR2137
IR2137 integrated function with a
shunt resistor and a comparator
Eliminated (boot strap power)
Eliminated by integrated soft shutdown
function
Eliminated by integrated brake IGBT
driver circuit
Table 2: Solution Comparison of Gate Drive and IGBT Protection
For the IR2137 circuit, as shown in Figure 5, the IR2137 and a micro-controller (µC) share the same
ground potential – the negative DC bus potential. (This architecture is already the industry standard
in the micro AC inverter drive segment). Unlike its traditional counterpart, the IR2137 circuit requires
a single shunt resistor and associated comparator. With this, it can perform all modes of IGBT short
circuit protection.
Additionally, the IR2137 contains IGBT de-saturation logic in the circuit of each high-side gate drive,
as shown in figures 6 and 7. In the event of a Ground Fault condition, the DESAT pin is activated, and
the fault signal is transferred to the low side fault logic circuit. The low side fault logic then initiates the
simultaneous soft shutdown of all 6 IGBTs. When the soft shutdown signal is transferred back to the
high side, the active PMOS/NMOS transistor buffer goes into a high impedance mode and another
weak NMOS transistor becomes active to slowly drive the gate pin low. The shutdown softness can
be programmed by adding an external resistor to the SSD pin – thus allowing the user to optimize
softness for the specific gate charge of the IGBT. To eliminate the dv/dt induced false triggering of the
DESAT pin, there is a blanking filter delay of 2 microseconds at each high-side gate turn-on transition.
Figure 8 shows the oscillogram of the ground fault protection feature in the IR2137. In this measurement, a size 4 IGBT, IRG4BC40KD, was used in conjunction with a turn-on resistor, Rg = 33Ω, turnoff resistor, Rg = 16Ω, and soft turn off resistor, RSSD = 500Ω. The top trace in Figure 8 is the IGBT
gate signal (10V/div), while the middle trace is the VCE voltage (100V/div), and the bottom trace is the
IGBT short circuit current (40A/div). No snubber circuit was used for this test. One can see that the
de-saturation protection activates quickly and the soft shutdown feature virtually eliminates the overshoot voltage across the collector and the emitter.
4
www.irf.com
For contrast, the oscillogram of a ‘hard’ shutdown is shown in Figure 9. The same IGBT, IRG4BC40KD,
and the same PCB pattern were used as in the example shown in Figure 8. The top trace is the IGBT
short circuit current and the bottom trace is the IGBT V voltage (100V/div). As can be seen in
CE
Figure 9, the overshoot voltage reaches approximately 100V above the normal V voltage during
CE
the turn-off transition.
In summary, the IR2137, a monolithic IC, provides excellent protection and soft shutdown features in
an extremely compact and cost-effective package.
Motor
Figure 1: Current Flow during Line-to-Line Short
Motor
Figure 2: Current Flow during Ground Fault
www.irf.com
5
Motor
Figure 3: Current Flow during Shoot Through Mode
M o to r
O P TO
O P TO
O P TO
O P TO
O P TO
O P TO
uP
Figure 4: Overcurrent Protection in Floating Ground Reference System
6
www.irf.com
M oto r
uP
or
DSP
IR2137
3Phase G ate
Driver with
IGBT
protection
Figure 5: IR2137 Gate Driver with IGBT Overcurrent Protection
VB
HO P
PR E
D RIVE R
H ig h S id e G a te
LO P
2 us ec
B lan king
SSD
D E S AT
D e s a t F a ult
3 50 ns ec
F ilt er
VS
S o ft Sh utd o w n
S o ft Sh utd o w n
Im p e d e n ce =
500 ohm s
Figure 6: IR2137 High Side Circuit
www.irf.com
7
VB1
HIN1
LIN1
SCHMIT T
TR IGGER IN PU T
&
SHOOT
THR OUGH
PREVENTION
H IN 1
2 0 0 n s ec
D e ad tim e
LEV E L
S H IF T E R S
LATC H
HOP1
SOFT
SHUT DO W N
SOFT SHU TDOW N
SOFT
SHUT DO W N
D R IV E R
HO N1
DESAT
DE TECTION
HS SD1
DESAT
VS1
UV DE T EC T
DESAT1
VB2
H IN 2
SCHMIT T
TR IGGER
INPUT &
SHOOT
THR OUGH
PREVENTION
HIN2
LIN2
2 0 0 n s ec
D e ad tim e
LEV E L
S H IF T E R S
SOFT SHU TDOW N
DESAT
LATC H
HOP2
SOFT
SHUT DO W N
SOFT
SHUT DO W N
D R IV E R
HO N2
DESAT
DE TECTION
HS SD2
UV DE T EC T
VS2
DESAT2
VB3
HIN3
LIN3
SCHMIT T
TR IGGER IN PU T
&
SHOOT
THR OUGH
PREVENTION
2 0 0 n s ec
D e ad tim e
LEV E L
S H IF T E R S
H IN 3
LATC H
SOFT SHU TDOW N
SOFT
SHUT DO W N
DESAT
HOP3
SOFT
SHUT DO W N
D R IV E R
HO N3
DESAT
DE TECTION
HS SD3
UV DE T EC T
VS3
DESAT3
LOP1
SOFT SHU TDOW N
SD
D R IV E R
LON1
SCHMIT T
TR IGGER
LSSD1
LS1
LOP2
D R IV E R
LON2
SCHMIT T
TR IGGER
IT RIP
LS2
F AUL T
LO G IC
FLTC LR
LSSD2
SCHMIT T
TR IGGER
LOP3
D R IV E R
FAULT
LON3
LS3
VC C
LSSD3
BRIN
VSS
UV
D ETE CT
B R AK E
D R IV E R
BR
COM
Figure 7: IR2137 Block Diagram
8
www.irf.com
Figure 8:
IR2137 Soft Shutdown
Figure 9:
Hard Shutdown
IR WORLD HEADQUARTERS: 233 Kansas St., El Segundo, California 90245 Tel: (310) 252-7105
IR EUROPEAN REGIONAL CENTRE: 439/445 Godstone Rd, Whyteleafe, Surrey CR3 0BL, United Kingdom
Tel: ++44 (0) 20 8645 8000
Data and specifications subject to change without notice.
www.irf.com
2/28/2000
9