SMALL FLANGE LEVEL TRANSMITTER FKY...5 DATA SHEET The FCX -AIII small flange level transmitter accurately measures liquid level and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. FEATURES SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type Static pressure FKY 3 FKY 5 FKY 6 1. Directly connectable to 1-1/2 in. and 2 in. flanges The transmitter is connectable to 1-1/2 in. and 2 in. pipes without a reducer. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART® compatible devices can communicate with FCX -AIII. 4. Application flexibility Various options that render the FCX -AIII suitable for almost any process applications include: – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum service. 5. Programmable output Linearization Function Output signal can be freely programmable. (Up to 14 compensated points at approximation.) 6. Burnout current flexibility (Under Scale: 3.2 to 4.0mA, Over Scale: 20.0 to 22.5mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. Up to flange rating Span limit [kPa] {m bar} Min. 3 {30} 13 {130} 50 {500} Max. 32 {320} 130 {1300} 500 {5000} Range limit [kPa] {m bar} +/− { +/− +/− { +/− +/− { +/− 32 320} 130 1300} 500 5000} Remark: To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower limit of static pressure (vacuum limit) ; Silicone fill sensor: See Fig.1 Fluorinated fill sensor: 66kPa abs (500mmHg abs) at temperature below 60°C. – The maximum span of each sensor can be converted to different units using factors as below. 1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi 1kPa=10mbar=101.9716mmH2O=4.01463inH2O Overrange limit: To maximum static pressure limit Output signal: 4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX7-67h Date Aug. 10, 2011 FKY...5 Process: Load limitations: see figure below [Ω] Load resistance 2000 1500 1474Ω R= E-10.5 (Imax+0.9)x10-3 13th digit of “Code symbols” Fluorinated oil W, A and D Silicone oil H Operating area 24V 250 0 10 −40 to 120°C 2.7kPa abs 0 to 250°C {20.3mmHg abs} Low pressure side contact liquid temperature on transmitter of Code H, S, is 120°C or lower. 45V 16.35 10.5V Power voltage (DC) 50 E[ V ] Note: For communication with HHC(1) (Model: FXW), min. of 250 required. Hazardous locations: See TABLE 2 Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw. Damping: Adjustable from HHC or local configurator unit with LCD display. The time constant is adjustable between 0.06 to 32 seconds. Zero elevation/suppression: −100% to +100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.0mA to 22.5mA from HHC(1) “Output Underscale”: Adjustable within the range 3.2mA to 4.0mA from HHC(1) 4 20 22.5 [mA] Over scale Burnout Normal operating range Under scale Probable under range Burnout Storage:−40 to +70°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following items can be remotely displayed or configured. Note: HHC’s version must be higher than 7.0 (or FXW 1– 4), for FCX -AIII. Local configurator with LCD display (option): Local confi gurator with 3 push button and LCD display can support following items. Items By communication By local configurator with FXW (with 3 push button) Display Set Display Set Tag No. v v v v Model No. v v v v Serial No. & Software Version v — v — Engineering unit v v v v Range limit v — v — Measuring range v v v v Damping v v v v Output mode v — v — Burnout direction v v v v Calibration v v v v Output adjust — v — v Data v — v — Self diagnoses v — v — Printer (In case of FXW with printer option) v — — — External switch lock v v v v Transmitter display v v v v Linearize v v — — Rerange v v v v Saturate current v v v v Write protect v v v v History – Calibration history – Ambient temperature history v v v — v v v — Probable over range Output limits comforming the NAMUR NE43 by order. Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 22.5mA by HHC(1). Temperature limit: Ambient: −15 to +65°C (−15 to +65°C for LCD indicator) (−15 to +60°C for arrester option) (−10 to +60°C for fluorinated oil fill transmitter) (−10 to +60°C for silicon oil “H”, “S”) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326-1: 2006 (Note) (1) HHC: Hand Held Communicator 2 Lower limit of static press 80°C Atmospheric 0 to 250°C pressure S 577Ω Process temperature −20 to Y and G 1000 500 3.2 Fill fluid Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4-20 mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: ±0.25% of span For spans below 1/10 of URL: ( ± 0.17 + 0.08 0.1 x URL % of span Span ) (Option) (Code: 21th digit H, K) For spans greater than 1/10 of URL: ±0.1% of span For span below 1/10 of URL: ( ± 0.05 + 0.05 Mounting position effect: Zero shift, less than 0.3kPa {3m bar} for a 10° tilt in any plane. (No extension) No effect on span. This error can be corrected by adjusting zero. Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100M at 500V DC. Internal resistance for external field indicator: 12 or less 0.1 x URL % of span Span ) Stability: ±0.2% of upper range limit (URL) for 10 years. Temperature effect: Effects per 28°C change between the limits of −15°C and + 65°C Zero shift; ±0.5%/28°C (x equal to 1/2 URL or more) URL Zero shift; ±0.5 %/28°C 2x (x less than 1/2 URL) Total shift; ±0.75%/28°C (x equal to 1/2 URL or more) URL Total shift; ± 0.25+0.5 × %/28°C 2x (x less than 1/2 URL) ( ) ( ) (Option) (Code: 21th digit J, K) Zero shift; ±0.5%/28°C (x equal to 1/6.5 URL or more) URL %/28°C Zero shift; ± 0.5 6.5 x (x less than 1/6.5 URL) Total shift; ±0.75%/28°C (x equal to 1/6.5 URL or more) URL %/28°C Total shift; ± 0.25 +0.5 6.5 x (x less than 1/6.5 URL) Where, x: Calibrated span ( ( URL: ) ) Maximum span (Upper Range Limit) Static pressure effect: Zero shift: ±0.2% of URL/1MPa Overrange effect: Zero shift; ±0.1% of URL for flange rating pressure Supply voltage effect: Less than 0.005% of calibrated span per 1V Update rate: 60 msec Step response: (without electrical damping) Time constant (at 23°C) Dead time 0.3 s 0.12 s 3 FKY...5 Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified. Process connections: LP side: 1/4-18 NPT or Rc1/4. HP side: ANSI, or JIS raised face flange. See OUTLINE DIAGRAM for detailed dimensions. Refer to “Code symbols” Process-wetted parts material: LP side HP side Material code Wetted Process Diaphragm & (7th digit Diaphragm sensor body cover flange face in “Code symbols”) 316 stainless 316L stainless 316 stainless 316L stainless V (*1) 316 stainless 316L stainless 316 stainless 316L stainless J (*1) steel + AU coating 316 stainless 316L stainless 316 stainless Hastelloy-C C (*1) 316 stainless 316L stainless 316 stainless Monel D (*1) 316 stainless 316L stainless 316 stainless Tantalum E (*1) Hastelloy-C 316 stainless Hastelloy-C H Hastelloy-C lining (*1) Monel lining Monel 316 stainless Monel M (*1) Tantalum 316 stainless Tantalum T Tantalum lining (*1) Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM A351/A351M) Remark: Sensor O-rings: Viton O-ring or teflon gasket selectable Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with polyseter coating(standard), or 316 stainless steel (ASTM CF8M), as specified. Bolts and nuts: Cr-Mo alloy (standard) or 304 stainless steel Fill fluid: Silicone oil (standard) or fluorinated oil Mounting flange: 304 stainless steel or carbon steel, as specified. Environmental protection: IEC IP67 and NEMA 6 / 6P Flange mounting: See drawings Mass{weight}: Transmitter approximately 8.2 to 17.2kg without options. Add; 0.8kg for indicator option 4.5kg for stainless steel housing option 1.0kg per 50mm extension of diaphragm Optional features Indicator: A plug-in analog indicator (2.5% accuracy). An optional 5-digit LCD meter with engineering unit is also available. Local configurator with LCD display: An optional 5 digits LCD meter with 3 push buttons can support items as using communication with FXW. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity : 4kV (1.2 × 50µs). Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See Fig.1 Optional tag plate: An extra stainless steel tag with customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. Filled liquid: Silicone (Code Y,G) [kPa abs] {m bar abs} Silicone (Code S) 101 {1010} Operating pressure Physical specifications 53.3 {533} Operating area 13.3 {133} Non-operating area 2.7 {27} –40 0 Fig. 1 4 60 85 120 Process temperature 200 230 250 [°C ] Relation between process temperature and operating pressure ACCESSORIES Oval flanges: (Model FFP, refer to Data Sheet No. EDS6128) Converts process connection to 1/2-14 NPT or to Rc1/2; in carbon steel or in 316 stainless steel. Hand held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) 5 FKY...5 CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 5 6 7 6 Description <Connections> <Process connection> <Oval flange screw> <Conduit connection> <Case type> Rc1/4 7/16-20UNF G1/2 T type 1/4-18NPT 7/16-20UNF 1/2-14NPT T type 1/4-18NPT M10 Pg 13.5 T type 1/4-18NPT M10 M20 × 1.5 T type 1/4-18NPT 7/16-20UNF Pg 13.5 T type Rc1/4 7/16-20UNF G1/2 L type 1/4-18NPT 7/16-20UNF 1/2-14NPT L type 1/4-18NPT M10 Pg 13.5 L type 1/4-18NPT M10 M20 × 1.5 L type 1/4-18NPT 7/16-20UNF Pg 13.5 L type <Mounting flange> Material Size and rating 304 stainless JIS 10K 40A steel JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 11/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 11/2" ANSI/JPI 300LB 2" Carbon steel JIS 10K 40A JIS 10K 50A JIS 20K 40A JIS 20K 50A JIS 30K 40A JIS 30K 50A ANSI/JPI 150LB 11/2" ANSI/JPI 150LB 2" ANSI/JPI 300LB 11/2" ANSI/JPI 300LB 2" <Span limit [kPa] {m bar}> 3 32 { 30 320} 13 130 {130 1300} 50 500 {500 5000} <Material> HP side LP side Process cover Diaphragm Diaphragm & Wetted sensor flange face body 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Diaphragm: 316L stainless steel +Au coating Flange face: 316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C 316 stainless steel 316 stainless steel 316 stainless steel Monel 316 stainless steel 316 stainless steel 316 stainless steel Tantalum 316 stainless steel Hastelloy-C Hastelloy-C lining Hastelloy-C 316 stainless steel Monel Monel lining Monel 316 stainless steel Tantalum Tantalum lining Tantalum F KY 5 5 6 7 8 9 S T V W X 0 1 2 3 4 5 A B C D G H J K L M Q R S T 3 5 6 V J C D E H M T 9 10 11 12 13 14 15 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit 9 10 11 12 Note 1: Note 3: Note 4: Note 6: Note 7: Description <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, custom scale None None Yes Analog, 0 to 100% linear scale Yes Analog, custom scale Yes Digital, 0 to 100% linear scale None Digital, custom scale None Digital, 0 to 100% linear scale Yes Digital, custom scale Yes Digital, 0 to 100% linear scale (Local configurator unit with LCD display) None Digital, custom scale (Local configurator unit with LCD display) None Digital, 0 to 100% linear scale (Local configurator unit with LCD display) Yes Digital, custom scale (Local configurator unit with LCD display) Yes <Approvals for hazardous locations> None (for ordinary locations) TIIS, Flameproof (Cable gland seal) (*4) TIIS, Intrinsic safety FM, Flameproof (or explosionproof) (*7) FM, Intrinsic safety and nonincentive FM Combined of flameproof and intrinsic safety (*7) ATEX Flameproof (*6) ATEX Intrinsic safety ATEX Type n ATEX Combined of flameproof and intrinsic safety (*6) IECEx Scheme, Flameproof (*6) IECEx Scheme, Intrinsic safety CSA, Flameproof (or explosionproof) (*7) CSA, Intrinsic safety and nonincentive NEPSI, Flameproof (or exprosionproof) NEPSI, Intrinsic safety NEPSI, Combined of flameproof and intrinsic safety <Diaphragm extension [mm]> Extension [mm] Applicable material code 0 Any 50 100 (7th digit code "V" only, 11/2 in. flange is not applicable) 150 200 <Options> Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None (*1) None Yes Yes None Yes None Yes Yes (*3) Yes Yes Yes (*1) (*3) (*4) (*6) (*7) Note F KY 9 10 11 12 13 14 15 5 21 Digit No. of code A B D E F H L P Q S 1 2 4 5 Note 4 Note 7 Note 7 Note 6 Note 6 Note 6 Note 7 A C G D H V X K P M R T E J F S U Y A B C D Note 1 Note 3 Note 3 Y B M N P Q Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". Not available for 10th digit code "C". Available for 4th digit code "S". Available for 4th digit code "6", "8", "T", "W". Available for 4th digit code "6", "T". 7 FKY...5 1 2 3 4 5 6 7 8 Digit 13 14 15 21 Description <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V" only) Chlorine service Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E") High temp. 250°C Silicone oil (7th digit code "V", "H") High temp. and vacuum (250°C) Silicone oil (7th digit code "V" only) <O-ring / Gasket and Teflon membrane> Teflon (gasket) Teflon (gasket) / Teflon membrance 7th digit code "V", "J" are available. 11th digit code "Y" only. 13th digit code "H", "S" are not available. <Bolt/nut> (*9) Cr-Mo alloy hexagon socket head cap screw/carbon steel nut Cr-Mo alloy hexagon bolt / carbon steel nut 304 stainless steel bolt / 304 stainless steel nut 316 stainless steel bolt / 316 stainless steel nut <Other options> (*2) High accuracy type Instruction manual attached Low temperature effect type Instruction manual attached H+J Instruction manual attached Opposite Vent/Drain Plug Position Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached Low temperature effect type Instruction manual unattached T+U Instruction manual unattached Opposite Vent/Drain Plug Position Instruction manual unattached Note Note 8 Note 8 F KY 9 10 11 12 13 14 15 Y W G A D H S B D Note 9 A B E U Note 2 Note 2: (*2) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. Note 8: Treatment: Standard. ORDERING INFORMATION When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale / Underscale. Unless otherwise specified, output hold function is supplied. 4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S, 2, 5 on 9th digit). 5. TAG No. (up to 14 alphanumerical characters), if required. 8 21 5 H J K C L T U V P Digit No. of code OUTLINE DIAGRAM (Unit:mm) <AMP. case: L type> φF Standard Corrosionmaterials resistant specification materials specification NOTE1) 5th digit of the code symbols φD 0, G 140 105 84 73 36 4-19 JIS-10K-40A 1, H 155 120 84 100 36 4-19 JIS-10K-50A 2, J 140 105 84 73 39 4-19 JIS-20K-40A φE t N-φh conduit conn. D E F H S G1/2 18 2 Rc 1/4 FLANGE NOTE2) 3, K 155 120 84 100 38 8-19 JIS-20K-50A 4, L 160 120 84 73 42 4-23 JIS-30K-40A 5, M 165 130 84 100 42 8-19 JIS-30K-50A A, Q 127 98.4 84 73 37.5 4-16 ANSI/JPI-150LB-1 1/2B B, R 152 120.6 84 100 39.5 4-20 ANSI/JPI-150LB-2B C, S 156 114.3 84 73 41 4-23 ANSI/JPI-300LB-1 1/2B D, T 165 127 84 100 42.5 8-20 ANSI/JPI-300LB-2B Press. Conn. 4th digit of the code symbols T 1/2-14NPT 16 4 1/4-18NPT V Pg13.5 10.5 4.5 1/4-18NPT W M20×1.5 16 4 1/4-18NPT X Pg13.5 10.5 4.5 1/4-18NPT Oval flange screw 7/16-20UNF SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 M10 SCREW DEPTH15 M10 SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 NOTE1) In case of the 7th digit of type code is V, J. NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T. 11th digit of the code symbols L MASS APPROX. (kg) Y A B C D 0 50 100 150 200 8.2 ∼ 11.7 L1 L2 L3 NOTE4) L4 L5 L6 N HOLES h DIA 309 151 278 320 159 289 8.7 ∼ 15.7 9.2 ∼ 16.2 9.7 ∼ 16.7 304 146 273 315 154 284 10.2 ∼ 17.2 IN CASE OF 4TH DIGIT CODE S, V, W, X 8 103 IN CASE OF 4TH DIGIT CODE T 103 126 φ81 WITH ANALOG IND. B CONDUIT CONN. 41 DETAIL A (PRESS. CONN.) 43 (21) (11) φ18.5 2.5 10 H 8 WITH DIGITAL IND. EARTH TERMINAL 10 ZERO ADJ. SCREW SEE TABLE1 L3 (L6) 41.3 OVAL FLANGE SCREW SEE TABLE1 L1 (L4) VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE3) A PRESS. CONN. DETAIL B (CONDUIT. CONN.) φ15 46 L2 (L5) 27 F VENT/DRAIN PLUG E FLANGE FOR H.P. t D L 20 SEE TABLE1 INNER DIA OF GASKET φ48±1 φ49 φF φE φD OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN) 10th digit code C (Cable gland type) NOTE1) G1/2 DETAIL C φ33.5 φ13 19 <SS TAG PLATE> 106 17 CONNECTION DIAGRAM "C" CONDUIT CONN. G1/2 −/CK− CK+ CABLE GLAND 75 + NOTE1) IN CASE OF 10TH CODE“C” , φ11 CABLE IS SUITBLE. NOTE3) 20 NOTE4) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C, P). WHEN THE 7TH DIGIT OF THE CODE SYMBOLS H, M, T 9 FKY...5 <AMP. case: T type> 5th digit of the code symbols φD φE φF Standard Corrosionmaterials resistant specification materials specification NOTE1) t N-φh 140 105 84 73 36 4-19 1, H 155 120 84 100 36 4-19 JIS-10K-50A 2, J 140 105 84 73 38 4-19 JIS-20K-40A 3, K 155 120 84 100 38 8-19 JIS-20K-50A 4, L 160 120 84 73 42 4-23 JIS-30K-40A 5, M 165 130 84 100 42 8-19 JIS-30K-50A A, Q 127 98.4 84 73 37.5 4-16 ANSI/JPI-150LB-1 1/2B B, R 152 120.6 84 100 39.5 4-20 ANSI/JPI-150LB-2B C, S 156 114.3 84 73 41 4-23 ANSI/JPI-300LB-1 1/2B D, T 165 127 84 100 42.5 8-20 ANSI/JPI-300LB-2B Press. Conn. D E F 5 G1/2 18 2 6 1/2-14NPT 16 4 7 Pg13.5 10.5 4.5 8 M20×1.5 16 4 9 Pg13.5 10.5 4.5 NOTE2) 0, G conduit conn. 4th digit of the code symbols FLANGE H 7/16-20UNF SCREW DEPTH15 7/16-20UNF SCREW DEPTH15 M10 1/4-18NPT SCREW DEPTH15 M10 1/4-18NPT SCREW DEPTH15 7/16-20UNF 1/4-18NPT SCREW DEPTH15 1/4-18NPT JIS-10K-40A NOTE1) In case of the 7th digit of type code is V, J. NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T. Oval flange screw Rc 1/4 ZERO ADJ. SCREW N HOLES h DIA NOTE4) 11th digit of the code symbols L MASS APPROX. (kg) Y A B C D 0 50 100 150 200 8.2 ∼ 11.7 L1 L2 L3 L4 L5 L6 322 151 305 333 159 316 8.7 ∼ 15.7 9.2 ∼ 16.2 317 146 300 328 154 311 9.7 ∼ 16.7 10.2 ∼ 17.2 (11) (21) IN CASE OF 4TH DIGIT CODE 5, 7, 8, 9 8 100 WITH DIGITAL IND. WITH ANALOG IND. IN CASE OF 4TH DIGIT CODE 6 DETAIL A (PRESS. CONN.) φ18.5 127 100 20 H 8 B CONDUIT CONN. 2.5 10 EARTH TERMINAL 10 VENT/DRAIN PLUG (WHEN THE VENT/DRAIN PLUG ATTACHED ON THE UPPER SIDE OF THE DETECTOR) NOTE3) L3 (L6) SEE TABLE1 DETAIL B (CONDUIT. CONN.) φ15 F L2 (L5) A PRESS. CONN. 41.3 L1 (L4) OVAL FLANGE SCREW SEE TABLE1 46 E 27 VENT/DRAIN PLUG FLANGE FOR H.P. L 20 t D SEE TABLE1 INNER DIA OF GASKET φ48±1 φ49 φF φE φD CONNECTION DIAGRAM −/CK− CK+ 75 + <SS TAG PLATE> 20 10 NOTE3) NOTE4) THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS ATTACHED ON THE UPPER SIDE OF THE DETECTOR (WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C, P). WHEN THE 7TH DIGIT OF THE CODE SYMBOLS H, M, T TABLE 2 Authorities ATEX Intrinsic safety Authorities Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual Model code 13th digit Tamb A,B,D Y,G,H,S −40°C to +85°C L,P,1,2 Y,G,H,S −20°C to +80°C Q,S,4,5 Y,G,H,S −20°C to +60°C E,F,H Y,G,H,S −40°C to +60°C – W,A,D −10°C to +60°C Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester), Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameter: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp.=+120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X 9th digit Note) “Seal Not Required” enclosure is allowed. 13th digit Y,G,H,S Y,G,H,S Y,G,H,S Y,G,H,S W,A,D Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Type n Nonincendive Authorities ATEX Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – Flameproof ATEX Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit 13th digit Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH CSA Tamb A,B,D Y,G,H,S −40°C to +85°C L,P,1,2 Y,G,H,S −20°C to +80°C Q,S,4,5 Y,G,H,S −20°C to +60°C E,F,H Y,G,H,S −40°C to +60°C − W,A,D −10°C to +60°C Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH 11 FKY...5 TABLE 2 Authorities ATEX Intrinsic safety Authorities Ex II 1 G Ex ia IIC T5 Tamb = –40°C to +50°C Ex ia IIC T4 Tamb = –40°C to +70°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) Factory Mutual Model code 13th digit Tamb A,B,D Y,G,H,S −40°C to +85°C L,P,1,2 Y,G,H,S −20°C to +80°C Q,S,4,5 Y,G,H,S −20°C to +60°C E,F,H Y,G,H,S −40°C to +60°C – W,A,D −10°C to +60°C Entity Parameters: Vmax=28V, Imax=94.3mA, Pi=0.66W, Ci=35.98nF, Li=0.694mH CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester), Ci=36nF (With Arrester), Li=0.6mH (Without analog meter), Li=0.7mH (With analog meter) TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameter: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=38.4nF, Li=0.694mH IECEx Scheme Ex ia IIC T4 Tamb = –40°C to +70°C Ex ia IIC T5 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator), Ci=36nF (With Arrester), Li=0.7mH (With analog indicator) NEPSI ATEX Ex II 2 GD Ex d IIC T6 IP66/67 T85°C Tamb = −40°C to +65°C Ex d IIC T5 IP66/67 T100°C Tamb = −40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C CSA Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 TIIS Ex do IIB+H2 T4 Tamb max = +60°C Maximum process temp.=+120°C IECEx Scheme Ex d IIC T5 IP66/67 Tamb = −40°C to +85°C Ex d IIC T6 IP66/67 Tamb = −40°C to +65°C NEPSI Ex d IIB+H2 T6 Tamb = −40°C to +60°C Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X 9th digit Note) “Seal Not Required” enclosure is allowed. 13th digit Y,G,H,S Y,G,H,S Y,G,H,S Y,G,H,S W,A,D Tamb −40°C to +85°C −20°C to +80°C −20°C to +60°C −40°C to +60°C −10°C to +60°C Type n Nonincendive Authorities ATEX Ex II 3 GD EEx nL IIC T5 Tamb = −40°C to +50°C EEx nL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=25.18nF, Li=0.694mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH EEx nAL IIC T5 Tamb = −40°C to +50°C EEx nAL IIC T4 Tamb = −40°C to +70°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W, Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Ex ia IIC T4 Ex d IIB+H2 T6 / Ex ia IIC T4 Model code 9th digit A,B,D L,P,1,2 Q,S,4,5 E,F,H – Flameproof Factory Mutual (pending) Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 13th digit 9th digit Entity Parameters: Ui=42.4V, Ii=113mA, Pi=1W, Ci=35.98nF, Li=0.694mH CSA Caution on Safety Tamb A,B,D Y,G,H,S −40°C to +85°C L,P,1,2 Y,G,H,S −20°C to +80°C Q,S,4,5 Y,G,H,S −20°C to +60°C E,F,H Y,G,H,S −40°C to +60°C − W,A,D −10°C to +60°C Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T5 Tamb max = +50°C Temp Code T4 Tamb max = +70°C Entity Parameters: Vmax=28V, Ci=25.18nF (Without Arrester), Ci=35.98nF (With Arrester), Li=0.694mH *Before using this product, be sure to read its instruction manual in advance. International Sales Div Sales Group Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ Information in this catalog is subject to change without notice. Printed in Japan