FUJI EDSX7-67H

SMALL FLANGE LEVEL TRANSMITTER
FKY...5
DATA SHEET
The FCX -AIII small flange level transmitter accurately measures liquid level and transmits a proportional 4 to 20mA
signal. The transmitter utilizes a unique micromachined
capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and
functionality.
FEATURES
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Static
pressure
FKY
3
FKY
5
FKY
6



1. Directly connectable to 1-1/2 in. and 2 in. flanges
The transmitter is connectable to 1-1/2 in. and 2 in. pipes
without a reducer.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX -AIII series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX -AIII.
4. Application flexibility
Various options that render the FCX -AIII suitable for
almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum service.
5. Programmable output Linearization Function
Output signal can be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
Up to
flange
rating
Span limit [kPa] {m bar}
Min.
3
{30}
13
{130}
50
{500}
Max.
32
{320}
130
{1300}
500
{5000}
Range limit
[kPa] {m bar}
+/−
{ +/−
+/−
{ +/−
+/−
{ +/−
32
320}
130
1300}
500
5000}
Remark: To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit) ;
Silicone fill sensor: See Fig.1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
temperature below 60°C.
– The maximum span of each sensor can be converted to
different units using factors as below.
1MPa=103kPa=10bar=10.19716kgf/cm2=145.0377psi
1kPa=10mbar=101.9716mmH2O=4.01463inH2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC with digital signal superimposed on the 4 to 20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
EDSX7-67h
Date
Aug. 10, 2011
FKY...5
Process:
Load limitations: see figure below
[Ω]
Load resistance
2000
1500
1474Ω
R=
E-10.5
(Imax+0.9)x10-3
13th digit of
“Code symbols”
Fluorinated oil
W, A and D
Silicone oil
H
Operating
area
24V
250
0
10
−40 to 120°C 2.7kPa abs
0 to 250°C {20.3mmHg abs}
Low pressure side contact liquid temperature on transmitter of
Code H, S, is 120°C or lower.
45V
16.35
10.5V
Power voltage (DC)
50
E[ V ]
Note: For communication with HHC(1) (Model: FXW), min. of 250 required.
Hazardous locations: See TABLE 2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
−100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to
either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC(1)
4
20
22.5 [mA]
Over scale
Burnout
Normal operating range
Under scale
Probable under range
Burnout
Storage:−40 to +70°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than 7.0
(or FXW
1– 4), for FCX -AIII.
Local configurator with LCD display (option):
Local confi gurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW
(with 3 push button)
Display
Set
Display
Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Output mode
v
—
v
—
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
– Ambient temperature history
v
v
v
—
v
v
v
—
Probable over range
Output limits comforming the NAMUR NE43 by order.
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 22.5mA
by HHC(1).
Temperature limit:
Ambient: −15 to +65°C
(−15 to +65°C for LCD indicator)
(−15 to +60°C for arrester option)
(−10 to +60°C for fluorinated oil fill transmitter)
(−10 to +60°C for silicon oil “H”, “S”)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326-1: 2006
(Note) (1) HHC: Hand Held Communicator
2
Lower limit
of
static press
80°C Atmospheric
0 to 250°C pressure
S
577Ω
Process
temperature
−20 to
Y and G
1000
500
3.2
Fill fluid
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4-20 mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: ±0.25% of span
For spans below 1/10 of URL:
(
± 0.17 + 0.08
0.1 x URL
% of span
Span
)
(Option) (Code: 21th digit H, K)
For spans greater than 1/10 of URL: ±0.1% of span
For span below 1/10 of URL:
(
± 0.05 + 0.05
Mounting position effect:
Zero shift, less than 0.3kPa {3m bar} for
a 10° tilt in any plane. (No extension)
No effect on span.
This error can be corrected by adjusting
zero.
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100M at 500V DC.
Internal resistance for external field indicator:
12 or less
0.1 x URL
% of span
Span
)
Stability:
±0.2% of upper range limit (URL) for 10
years.
Temperature effect:
Effects per 28°C change between the
limits of −15°C and + 65°C
Zero shift; ±0.5%/28°C
(x equal to 1/2 URL or more)
URL
Zero shift; ±0.5
%/28°C
2x
(x less than 1/2 URL)
Total shift; ±0.75%/28°C
(x equal to 1/2 URL or more)
URL
Total shift; ± 0.25+0.5 ×
%/28°C
2x
(x less than 1/2 URL)
(
)
(
)
(Option) (Code: 21th digit J, K)
Zero shift; ±0.5%/28°C
(x equal to 1/6.5 URL or more)
URL
%/28°C
Zero shift; ± 0.5
6.5 x
(x less than 1/6.5 URL)
Total shift; ±0.75%/28°C
(x equal to 1/6.5 URL or more)
URL
%/28°C
Total shift; ± 0.25 +0.5
6.5 x
(x less than 1/6.5 URL)
Where, x:
Calibrated span
(
(
URL:
)
)
Maximum span (Upper Range
Limit)
Static pressure effect:
Zero shift: ±0.2% of URL/1MPa
Overrange effect: Zero shift; ±0.1% of URL for flange rating
pressure
Supply voltage effect:
Less than 0.005% of calibrated span per
1V
Update rate:
60 msec
Step response: (without electrical damping)
Time constant (at 23°C)
Dead time
0.3 s
0.12 s
3
FKY...5
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5
conduit, as specified.
Process connections:
LP side: 1/4-18 NPT or Rc1/4.
HP side: ANSI, or JIS raised face flange.
See OUTLINE DIAGRAM for detailed
dimensions.
Refer to “Code symbols”
Process-wetted parts material:
LP side
HP side
Material
code
Wetted
Process
Diaphragm &
(7th digit
Diaphragm
sensor body
cover
flange face
in “Code
symbols”)
316 stainless 316L stainless 316 stainless 316L stainless
V
(*1)
316 stainless 316L stainless 316 stainless 316L stainless
J
(*1)
steel
+ AU coating
316 stainless 316L stainless 316 stainless Hastelloy-C
C
(*1)
316 stainless 316L stainless 316 stainless Monel
D
(*1)
316 stainless 316L stainless 316 stainless Tantalum
E
(*1)
Hastelloy-C
316 stainless Hastelloy-C
H
Hastelloy-C
lining
(*1)
Monel lining Monel
316 stainless Monel
M
(*1)
Tantalum
316 stainless Tantalum
T
Tantalum
lining
(*1)
Note: (*1) SCS14A per JIS G 5121 (equivalent CF8M per ASTM
A351/A351M)
Remark: Sensor O-rings: Viton O-ring or teflon gasket selectable
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with polyseter
coating(standard), or 316 stainless steel
(ASTM CF8M), as specified.
Bolts and nuts: Cr-Mo alloy (standard) or
304 stainless steel
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting flange: 304 stainless steel or
carbon steel, as specified.
Environmental protection:
IEC IP67 and NEMA 6 / 6P
Flange mounting: See drawings
Mass{weight}:
Transmitter approximately 8.2 to 17.2kg
without options.
Add; 0.8kg for indicator option
4.5kg for stainless steel housing
option
1.0kg per 50mm extension of
diaphragm
Optional features
Indicator:
A plug-in analog indicator (2.5% accuracy).
An optional 5-digit LCD meter with engineering unit is also available.
Local configurator with LCD display:
An optional 5 digits LCD meter with 3
push buttons can support items as using
communication with FXW.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity : 4kV (1.2 ×
50µs).
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all
process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but
the fill fluid is standard silicone oil. Not
for use on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig.1
Optional tag plate:
An extra stainless steel tag with customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating.
Specify if environment is extremely corrosive.
Filled liquid:
Silicone (Code Y,G)
[kPa abs]
{m bar abs}
Silicone (Code S)
101
{1010}
Operating pressure
Physical specifications
53.3
{533}
Operating area
13.3
{133}
Non-operating
area
2.7
{27}
–40 0
Fig. 1
4
60 85 120
Process temperature
200 230 250
[°C ]
Relation between process temperature and
operating pressure
ACCESSORIES
Oval flanges:
(Model FFP, refer to Data Sheet No. EDS6128)
Converts process connection to 1/2-14
NPT or to Rc1/2; in carbon steel or in 316
stainless steel.
Hand held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
5
FKY...5
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
6
Description
<Connections>
<Process connection> <Oval flange screw>
<Conduit connection> <Case type>
Rc1/4
7/16-20UNF
G1/2
T type
1/4-18NPT
7/16-20UNF
1/2-14NPT
T type
1/4-18NPT
M10
Pg 13.5
T type
1/4-18NPT
M10
M20 × 1.5
T type
1/4-18NPT
7/16-20UNF
Pg 13.5
T type
Rc1/4
7/16-20UNF
G1/2
L type
1/4-18NPT
7/16-20UNF
1/2-14NPT
L type
1/4-18NPT
M10
Pg 13.5
L type
1/4-18NPT
M10
M20 × 1.5
L type
1/4-18NPT
7/16-20UNF
Pg 13.5
L type
<Mounting flange>
Material
Size and rating
304 stainless
JIS 10K 40A
steel
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
Carbon steel
JIS 10K 40A
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
ANSI/JPI 150LB 11/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 11/2"
ANSI/JPI 300LB 2"
<Span limit [kPa] {m bar}>
3
32
{ 30
320}
13
130
{130
1300}
50
500
{500
5000}
<Material>
HP side
LP side
Process cover
Diaphragm
Diaphragm &
Wetted sensor
flange face
body
316 stainless steel 316 stainless steel 316 stainless steel 316 stainless steel
316 stainless steel 316 stainless steel 316 stainless steel Diaphragm:
316L stainless steel
+Au coating
Flange face:
316 stainless steel
316 stainless steel 316 stainless steel 316 stainless steel Hastelloy-C
316 stainless steel 316 stainless steel 316 stainless steel Monel
316 stainless steel 316 stainless steel 316 stainless steel Tantalum
316 stainless steel Hastelloy-C
Hastelloy-C lining Hastelloy-C
316 stainless steel Monel
Monel lining
Monel
316 stainless steel Tantalum
Tantalum lining
Tantalum
F KY
5
5
6
7
8
9
S
T
V
W
X
0
1
2
3
4
5
A
B
C
D
G
H
J
K
L
M
Q
R
S
T
3
5
6
V
J
C
D
E
H
M
T
9 10 11 12 13
14 15
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
9
10
11
12
Note 1:
Note 3:
Note 4:
Note 6:
Note 7:
Description
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, custom scale
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, custom scale
Yes
Digital, 0 to 100% linear scale
None
Digital, custom scale
None
Digital, 0 to 100% linear scale
Yes
Digital, custom scale
Yes
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
None
Digital, custom scale
(Local configurator unit with LCD display)
None
Digital, 0 to 100% linear scale
(Local configurator unit with LCD display)
Yes
Digital, custom scale
(Local configurator unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Cable gland seal) (*4)
TIIS, Intrinsic safety
FM, Flameproof (or explosionproof) (*7)
FM, Intrinsic safety and nonincentive
FM Combined of flameproof and intrinsic safety (*7)
ATEX Flameproof (*6)
ATEX Intrinsic safety
ATEX Type n
ATEX Combined of flameproof and intrinsic safety (*6)
IECEx Scheme, Flameproof (*6)
IECEx Scheme, Intrinsic safety
CSA, Flameproof (or explosionproof) (*7)
CSA, Intrinsic safety and nonincentive
NEPSI, Flameproof (or exprosionproof)
NEPSI, Intrinsic safety
NEPSI, Combined of flameproof and intrinsic safety
<Diaphragm extension [mm]>
Extension [mm]
Applicable material code
0
Any
50
100
(7th digit code "V" only, 11/2 in. flange is not applicable)
150
200
<Options>
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
(*1)
None
Yes
Yes
None
Yes
None
Yes
Yes
(*3)
Yes
Yes
Yes
(*1)
(*3)
(*4)
(*6)
(*7)
Note
F KY
9 10 11 12 13
14 15
5
21
Digit No.
of code
A
B
D
E
F
H
L
P
Q
S
1
2
4
5
Note 4
Note 7
Note 7
Note 6
Note 6
Note 6
Note 7
A
C
G
D
H
V
X
K
P
M
R
T
E
J
F
S
U
Y
A
B
C
D
Note 1
Note 3
Note 3
Y
B
M
N
P
Q
Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes".
Not available for 10th digit code "C".
Available for 4th digit code "S".
Available for 4th digit code "6", "8", "T", "W".
Available for 4th digit code "6", "T".
7
FKY...5
1 2 3 4 5 6 7 8
Digit
13
14
15
21
Description
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V" only)
Chlorine service
Fluorinated oil (7th digit code "H", "T", "B", "U", "C" and "E")
High temp. 250°C
Silicone oil (7th digit code "V", "H")
High temp. and vacuum (250°C) Silicone oil (7th digit code "V" only)
<O-ring / Gasket and Teflon membrane>
Teflon (gasket)
Teflon (gasket) / Teflon membrance
7th digit code "V", "J" are available.
11th digit code "Y" only.
13th digit code "H", "S" are not available.
<Bolt/nut> (*9)
Cr-Mo alloy hexagon socket head cap screw/carbon steel nut
Cr-Mo alloy hexagon bolt / carbon steel nut
304 stainless steel bolt / 304 stainless steel nut
316 stainless steel bolt / 316 stainless steel nut
<Other options> (*2)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Opposite Vent/Drain Plug Position
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Opposite Vent/Drain Plug Position
Instruction manual unattached
Note
Note 8
Note 8
F KY
9 10 11 12 13
14 15
Y
W
G
A
D
H
S
B
D
Note 9
A
B
E
U
Note 2
Note 2: (*2) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Note 8:
Treatment: Standard.
ORDERING INFORMATION
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is occurred in the transmitter.
Hold / Overscale / Underscale.
Unless otherwise specified, output hold function is supplied.
4. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S, 2, 5 on 9th digit).
5. TAG No. (up to 14 alphanumerical characters), if required.
8
21
5
H
J
K
C
L
T
U
V
P
Digit No.
of code
OUTLINE DIAGRAM (Unit:mm)
<AMP. case: L type>
φF
Standard
Corrosionmaterials
resistant
specification materials
specification
NOTE1)
5th digit of the
code symbols
φD
0, G
140
105
84
73
36
4-19
JIS-10K-40A
1, H
155
120
84
100
36
4-19
JIS-10K-50A
2, J
140
105
84
73
39
4-19
JIS-20K-40A
φE
t
N-φh
conduit conn.
D
E
F
H
S
G1/2
18
2
Rc 1/4
FLANGE
NOTE2)
3, K
155
120
84
100
38
8-19
JIS-20K-50A
4, L
160
120
84
73
42
4-23
JIS-30K-40A
5, M
165
130
84
100
42
8-19
JIS-30K-50A
A, Q
127
98.4
84
73
37.5
4-16
ANSI/JPI-150LB-1 1/2B
B, R
152
120.6
84
100
39.5
4-20
ANSI/JPI-150LB-2B
C, S
156
114.3
84
73
41
4-23
ANSI/JPI-300LB-1 1/2B
D, T
165
127
84
100
42.5
8-20
ANSI/JPI-300LB-2B
Press. Conn.
4th digit of the
code symbols
T
1/2-14NPT
16
4
1/4-18NPT
V
Pg13.5
10.5
4.5
1/4-18NPT
W
M20×1.5
16
4
1/4-18NPT
X
Pg13.5
10.5
4.5
1/4-18NPT
Oval flange screw
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
SCREW DEPTH15
M10
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
NOTE1) In case of the 7th digit of type code is V, J.
NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T.
11th digit of the
code symbols
L
MASS APPROX. (kg)
Y
A
B
C
D
0
50
100
150
200
8.2 ∼ 11.7
L1
L2
L3
NOTE4)
L4
L5
L6
N HOLES h DIA
309 151 278 320 159 289
8.7 ∼ 15.7
9.2 ∼ 16.2
9.7 ∼ 16.7
304 146 273 315 154 284
10.2 ∼ 17.2
IN CASE OF 4TH DIGIT CODE S, V, W, X
8
103
IN CASE OF 4TH DIGIT CODE T
103
126
φ81
WITH ANALOG IND.
B CONDUIT CONN.
41
DETAIL A
(PRESS. CONN.)
43
(21)
(11)
φ18.5
2.5
10
H
8
WITH DIGITAL IND.
EARTH TERMINAL
10
ZERO ADJ. SCREW
SEE TABLE1
L3
(L6)
41.3
OVAL FLANGE SCREW
SEE TABLE1
L1
(L4)
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE3)
A PRESS. CONN.
DETAIL B
(CONDUIT. CONN.)
φ15
46
L2
(L5)
27
F
VENT/DRAIN PLUG
E
FLANGE FOR H.P.
t
D
L
20
SEE TABLE1
INNER DIA OF
GASKET
φ48±1
φ49
φF
φE
φD
OPTION PARTS FOR FLAMEPROOF OF TIIS (JAPAN)
10th digit code C (Cable gland type)
NOTE1)
G1/2
DETAIL C
φ33.5
φ13
19
<SS TAG PLATE>
106
17
CONNECTION DIAGRAM
"C" CONDUIT CONN.
G1/2
−/CK− CK+
CABLE GLAND
75
+
NOTE1) IN CASE OF 10TH CODE“C”
, φ11 CABLE IS SUITBLE.
NOTE3)
20
NOTE4)
THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C, P).
WHEN THE 7TH DIGIT OF THE CODE SYMBOLS H, M, T
9
FKY...5
<AMP. case: T type>
5th digit of the
code symbols
φD
φE
φF
Standard
Corrosionmaterials
resistant
specification materials
specification
NOTE1)
t
N-φh
140
105
84
73
36
4-19
1, H
155
120
84
100
36
4-19
JIS-10K-50A
2, J
140
105
84
73
38
4-19
JIS-20K-40A
3, K
155
120
84
100
38
8-19
JIS-20K-50A
4, L
160
120
84
73
42
4-23
JIS-30K-40A
5, M
165
130
84
100
42
8-19
JIS-30K-50A
A, Q
127
98.4
84
73
37.5
4-16
ANSI/JPI-150LB-1 1/2B
B, R
152
120.6
84
100
39.5
4-20
ANSI/JPI-150LB-2B
C, S
156
114.3
84
73
41
4-23
ANSI/JPI-300LB-1 1/2B
D, T
165
127
84
100
42.5
8-20
ANSI/JPI-300LB-2B
Press. Conn.
D
E
F
5
G1/2
18
2
6
1/2-14NPT
16
4
7
Pg13.5
10.5
4.5
8
M20×1.5
16
4
9
Pg13.5
10.5
4.5
NOTE2)
0, G
conduit conn.
4th digit of the
code symbols
FLANGE
H
7/16-20UNF
SCREW DEPTH15
7/16-20UNF
SCREW DEPTH15
M10
1/4-18NPT
SCREW DEPTH15
M10
1/4-18NPT
SCREW DEPTH15
7/16-20UNF
1/4-18NPT
SCREW DEPTH15
1/4-18NPT
JIS-10K-40A
NOTE1) In case of the 7th digit of type code is V, J.
NOTE2) In case of the 7th digit of type code is C, D, E, H, M, T.
Oval flange screw
Rc 1/4
ZERO ADJ. SCREW
N HOLES h DIA
NOTE4)
11th digit of the
code symbols
L
MASS APPROX. (kg)
Y
A
B
C
D
0
50
100
150
200
8.2 ∼ 11.7
L1
L2
L3
L4
L5
L6
322 151 305 333 159 316
8.7 ∼ 15.7
9.2 ∼ 16.2
317 146 300 328 154 311
9.7 ∼ 16.7
10.2 ∼ 17.2
(11)
(21)
IN CASE OF 4TH DIGIT CODE 5, 7, 8, 9
8
100
WITH DIGITAL IND.
WITH ANALOG IND.
IN CASE OF 4TH DIGIT CODE 6
DETAIL A
(PRESS. CONN.)
φ18.5
127
100
20
H
8
B CONDUIT CONN.
2.5
10
EARTH TERMINAL
10
VENT/DRAIN PLUG
(WHEN THE VENT/DRAIN PLUG
ATTACHED ON THE UPPER SIDE
OF THE DETECTOR) NOTE3)
L3
(L6)
SEE TABLE1
DETAIL B
(CONDUIT. CONN.)
φ15
F
L2
(L5)
A PRESS. CONN.
41.3
L1
(L4)
OVAL FLANGE SCREW
SEE TABLE1
46
E
27
VENT/DRAIN PLUG
FLANGE FOR H.P.
L
20
t
D
SEE TABLE1
INNER DIA OF
GASKET
φ48±1
φ49
φF
φE
φD
CONNECTION DIAGRAM
−/CK− CK+
75
+
<SS TAG PLATE>
20
10
NOTE3)
NOTE4)
THE PRESSURE CONNECTOR IS LOCATED ON THE DOWN SIDE
SURFACE OF THE DETECTOR, WHEN THE VENT/DRAIN PLUG IS
ATTACHED ON THE UPPER SIDE OF THE DETECTOR
(WHEN THE 21ST DIGIT OF THE CODE SYMBOLS : C, P).
WHEN THE 7TH DIGIT OF THE CODE SYMBOLS H, M, T
TABLE 2
Authorities
ATEX
Intrinsic safety
Authorities
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
Model code
13th digit
Tamb
A,B,D
Y,G,H,S
−40°C to +85°C
L,P,1,2
Y,G,H,S
−20°C to +80°C
Q,S,4,5
Y,G,H,S
−20°C to +60°C
E,F,H
Y,G,H,S
−40°C to +60°C
–
W,A,D
−10°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester), Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameter:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
NEPSI
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp.=+120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
9th digit
Note) “Seal Not Required” enclosure is allowed.
13th digit
Y,G,H,S
Y,G,H,S
Y,G,H,S
Y,G,H,S
W,A,D
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Type n
Nonincendive
Authorities
ATEX
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
Flameproof
ATEX
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
13th digit
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Tamb
A,B,D
Y,G,H,S
−40°C to +85°C
L,P,1,2
Y,G,H,S
−20°C to +80°C
Q,S,4,5
Y,G,H,S
−20°C to +60°C
E,F,H
Y,G,H,S
−40°C to +60°C
−
W,A,D
−10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
11
FKY...5
TABLE 2
Authorities
ATEX
Intrinsic safety
Authorities
Ex II 1 G
Ex ia IIC T5 Tamb = –40°C to +50°C
Ex ia IIC T4 Tamb = –40°C to +70°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
Factory
Mutual
Model code
13th digit
Tamb
A,B,D
Y,G,H,S
−40°C to +85°C
L,P,1,2
Y,G,H,S
−20°C to +80°C
Q,S,4,5
Y,G,H,S
−20°C to +60°C
E,F,H
Y,G,H,S
−40°C to +60°C
–
W,A,D
−10°C to +60°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Pi=0.66W,
Ci=35.98nF, Li=0.694mH
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Imax=94.3mA, Ci=25nF (Without Arrester),
Ci=36nF (With Arrester), Li=0.6mH (Without analog meter),
Li=0.7mH (With analog meter)
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameter:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=38.4nF, Li=0.694mH
IECEx
Scheme
Ex ia IIC T4
Tamb = –40°C to +70°C
Ex ia IIC T5
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=26nF (Without Arrester), Li=0.6mH (Without analog indicator),
Ci=36nF (With Arrester), Li=0.7mH (With analog indicator)
NEPSI
ATEX
Ex II 2 GD
Ex d IIC T6 IP66/67 T85°C
Tamb = −40°C to +65°C
Ex d IIC T5 IP66/67 T100°C
Tamb = −40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
CSA
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
TIIS
Ex do IIB+H2 T4
Tamb max = +60°C
Maximum process temp.=+120°C
IECEx
Scheme
Ex d IIC T5 IP66/67
Tamb = −40°C to +85°C
Ex d IIC T6 IP66/67
Tamb = −40°C to +65°C
NEPSI
Ex d IIB+H2 T6
Tamb = −40°C to +60°C
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
9th digit
Note) “Seal Not Required” enclosure is allowed.
13th digit
Y,G,H,S
Y,G,H,S
Y,G,H,S
Y,G,H,S
W,A,D
Tamb
−40°C to +85°C
−20°C to +80°C
−20°C to +60°C
−40°C to +60°C
−10°C to +60°C
Type n
Nonincendive
Authorities
ATEX
Ex II 3 GD
EEx nL IIC T5 Tamb = −40°C to +50°C
EEx nL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=25.18nF, Li=0.694mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
EEx nAL IIC T5 Tamb = −40°C to +50°C
EEx nAL IIC T4 Tamb = −40°C to +70°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Ex ia IIC T4
Ex d IIB+H2 T6 / Ex ia IIC T4
Model code
9th digit
A,B,D
L,P,1,2
Q,S,4,5
E,F,H
–
Flameproof
Factory
Mutual
(pending)
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
13th digit
9th digit
Entity Parameters:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=35.98nF, Li=0.694mH
CSA
Caution on Safety
Tamb
A,B,D
Y,G,H,S
−40°C to +85°C
L,P,1,2
Y,G,H,S
−20°C to +80°C
Q,S,4,5
Y,G,H,S
−20°C to +60°C
E,F,H
Y,G,H,S
−40°C to +60°C
−
W,A,D
−10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T5
Tamb max = +50°C
Temp Code T4
Tamb max = +70°C
Entity Parameters:
Vmax=28V, Ci=25.18nF (Without Arrester),
Ci=35.98nF (With Arrester), Li=0.694mH
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan