FUJI EDSX6-117I

REMOTE SEAL TYPE
DIFFERENTIAL PRESSURE TRANSMITTER
FKD...4
DATA SHEET
The FCX – A2 differential pressure transmitter accurately
measures differential pressure, liquid level or gauge pressure
and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon
sensor with state-of-the-art microprocessor technology to
provide exceptional performance and functionality. Totally
welded construction of the seals assures excellent reliability
in high temperature and highly corrosive process conditions.
FEATURES
1. High accuracy
0.2% accuracy for all calibrated spans is a standard
feature for all DP models covering 0.32kPa {3.2mbar}
range to 500kPa {5bar} high differential pressure range.
0.1% accuracy is available as option. Fuji’s microcapacitance silicon sensor assures this accuracy for all
elevated or suppressed calibration ranges without
additional adjustment.
2. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
3. Fuji/HART® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and
HART®. Any HART ® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also
available.
4. Application flexibility
Various options that render the FCX – A2 suitable for
almost any process applications include:
– Analog indicator at either the electronics side or
terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum seals
5. Programmable output Linearization Function
In addition to Linear and Square Root, output signal
can be freely programmable.
(Up to 14 compensated points at approximation.)
6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with
NAMUR NE43.
7. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Static pressure
F KD
3
F KD
5
F KD
6
}
Up to
flange rating
Span limit [kPa]
(m bar}
Max.
Min.
0.32
{ 3.2 }
1.3
{ 13 }
5
{ 50 }
Range limit
[kPa] {m bar}
32
{ 320 }
130
{ 1300 }
500
{ 5000}
+/– 32
{+/– 320}
+/– 130
{+/– 1300}
+/– 500
{+/– 5000}
Remark : To minimize environmental influence, span should be greater
than 1/40 of the max. span in most applications.
– Lower limit of static pressure (vacuum limit),
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: Atmospheric pressure
– The maximum span of each sensor can be converted
to different units using factors as below.
1MPa =103kPa=10bar=10.19716kgf/cm2
=145.0377psi
1kPa=10mbar=101.976mmH2O=4.01463H2O
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
EDSX6-117i
Date
Jun. 1, 2006
FKD...4
Load limitations: see figure below
Authorities
ATEX
[Ω]
Load resistance
2000
1533Ω
1000
600Ω
Factory
Mutual
Operating
area
500
24V
250
10
16.1
10.5V
Power voltage
45V
50
Authorities
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = – 40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = – 40°C to +85°C
Factory
Mutual
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
Class I
Div.1 Groups C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Note) “Seal Not Required” enclosure is allowed.
2
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp. = +120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = – 40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = – 40°C to +65°C
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
CSA
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameters:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = –40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = –40°C to +50°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
Flameproof
ATEX
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
required.
Hazardous locations:
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,C,D,J
L,P,M,1,2,3
Q,S,N,4,5,6
E,F,G,H,K
–
[V]
Note: For communication with HHC(1) (Model: FXW), min. of 250Ω is
CSA
Ex II 1 GD
EEx ia IIC T5 Tamb = –40°C to +40°C
EEx ia IIC T4 Tamb = –40°C to +80°C
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
1500
0
Intrinsic safety
ATEX
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = –40°C to +40°C
EEx nL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
3.2
Normal operating range
Under scale
Probable under range
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
9th digit
A,B,C,D,J
L,P,M,1,2,3
Q,S,N,4,5,6
E,F,G,H,K
–
CSA
13th digit
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
Y,G,H,J,S,T,K
W,A,D
–
IECEx
Scheme
/SAA
–
21.6 [mA]
Tamb
–40°C to +85°C
–20°C to +80°C
–20°C to +60°C
–40°C to +60°C
–10°C to +60°C
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(span odjustment is not available with 9th
digit code “L, P, M, Q, S, N”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC(1).
Temperature limit:
Ambient: – 40 to + 85°C
(– 20 to + 80°C for LCD indicator)
(– 40 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill transmitter)
(– 10 to + 85°C for silicone oil “H”, “S”, “K”)
(+ 20 to + 85°C for silicone oil “J”, “T”)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
20 20.8
Over scale
Burnout
EEx nAL IIC T5 Tamb = –40°C to +40°C
EEx nAL IIC T4 Tamb = –40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
3.8 4
Fill fluid
Code in the
13th digit of
“Code symbols”
Fluorinated oil
W, A and D
– 20 to 120°C
Silicone oil
H
– 15 to 250°C
Process
temperature
J
Lower limit
of
static press.
Atmospheric
pressure
85 to 300°C
Y and G
– 40 to 120°C
S
– 15 to 250°C
T
85 to 300°C
K
– 15 to 200°C
2.7kPa abs
{20mmHg
abs}
0.13kPa abs
{1mmHg abs}
or more
Storage: – 40 to +90°C
Humidity limit:
0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Linear
v
v
Square root
v
v
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
Output mode
(Note)
(1) HHC: Hand Held Communicator
3
FKD...4
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326
(Note)
(1) HHC: Hand Held Communicator
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: 0.2% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.1+0.1
% of span
Span
(Option) (Code; 21th digit H,K)
For spans greater than 1/10 of URL: 0.1% of span
For spans below 1/10 of URL:
0.1 × URL
± 0.05+0.05
% of span
Span
Stability:
± 0.2% of upper range limit (URL) for 3
years.
Temperature effect (*):
Effects per 28°C change between the limits of – 40°C and +85°C
(Standard)
Zero shift: ± 0.35% of URL
Total effect: ± 0.5% of URL
(Option) (Code; 21th digit J,K)
Zero shift: ± 0.3% of URL
Total effect: ± 0.4% of URL
(
)
(
)
Note: * Excluding effect by temperature difference
between the seals.
Static pressure effect:
Zero shift; 0.2% of URL for flange rating
pressure
Span shift: – 0.2% of calibrated span for
flange rating pressure
Overrange effect: Zero shift; 0.1% of URL for flange rating
pressure
Supply voltage effect:
Less than 0.005% fo calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
(Classification: 2-abc: 0.2% span per
SAMA PMC 33.1)
Update period: 120 msec *)
Step response: (without electrical damping)
Range code
Time constant (*)
“3”
2
“5”
1.7 s
“6”
1.7 s
Dead time (*)
s
0.2 s
*) Faster response is available as option (maximum
update rate: 25 times per second).
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
4
Physical specifications
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified.
And 1-conduit or 2-conduit, as specified.
Process connections:
JIS, ANSI, or DIN raised face flanges.
JIS: 10K80A, 10K100A, 30K80A, or
30K100A
ANSI: 150LB 3", 150LB 4", 300LB 3", or
300LB 4"
DIN: PN40 DN80 or PN16 DN100
See OUTLINE DIAGRAM for detailed dimensions.
Diaphragm extension:
0, 50, 100, 150, or 200mm as specified.
(See model code. Extended diaphragm is
available only with 316L stainless steel or
Hastelloy-C diaphragm)
Process-wetted parts material:
Diaphragm: 316L stainless steel, HastelloyC,
Monel, Tantalum, Titanium or
Zirconium
Flange face:316 stainless steel, HastelloyC lining
Monel lining, or Tantalum lining
Extension: 316 stainless steel or HastelloyC
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating (standard), or 316 stainless steel (SCS14 per
JIS G5121), as specified.
Capillary: In case of 11th code “D, E, F, L,
M, N, P”, PVC armored stainless steel.
In case of 13th code “Q, R, S, T, V, W,
X”, stainless steel armored stainless
steel.
Mounting flange: 304 stainless steel or
carbon steel
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting
Mass {weight}:
Transmitter approximately 15kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
[kPa abs]
{mbar abs}
Silicone (Code Y,G)
[kPa abs]
{mbar abs}
Silicone (Code S)
Silicone (Code T)
Sealing liquid:Silicone (Code K)
101
{1010}
53.3
{533}
Operating pressure
Operating pressure
101
{1010}
Operating area
13.3
{133}
Non-operating
area
0.27
{2.7}
0.13
{1.3}
2.7
{27}
–40 –15
60 85 120
Process temperature[°C ]
200 230 250
300
Fig. 1 Relation between process temperature and
operating pressure
Optional features
Indicator:
Operating area
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity:
4kV (1.2 × 50µs)
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig. 1, Fig. 2.
Optional tag plate:
An extra stainless steel tag for customer
tag data is wired to the transmitter.
Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
–15
100
Process temperature[°C ]
200
Fig. 2 Relation between process temperature and
operating pressure
ACCESSORIES
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
5
FKD...4
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Description
<Conduit connection>
G 1/2
(×1)
1/2-14NPT (×1)
Combination with 12th digit code "C, E, P, Q" are not
Pg13.5
(×1) available.
M20 × 1.5 (×1)
G 1/2
(×2)
1/2-14NPT (×2)
Pg13.5
(×2)
M20 × 1.5 (×2)
<Flange>
Flange size and rating
Mounting flange
JIS 10K 80A
304 stainless
JIS 10K 100A
steel
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN16/40 DN80
DIN PN16 DN100
JIS 20K 80A
ANSI/JPI 600LB 3B
JIS 10K 80A
Carbon steel
JIS 10K 100A
JIS 30K 80A
JIS 30K 100A
ANSI/JPI 150LB 3"
ANSI/JPI 150LB 4"
ANSI/JPI 300LB 3"
ANSI/JPI 300LB 4"
DIN PN16/40 DN80
DIN PN16 DN100
JIS 10K 80A
316 stainless
ANSI/JPI 150LB 3B
steel
ANSI/JPI 150LB 4B
ANSI/JPI 300LB 3B
ANSI/JPI 300LB 4B
ANSI/JPI 600LB 3B
3 inch wafer
None
4 inch wafer
(wafer type)
<Span limit (*1) [kPa]{m bar}>
0.32.... 32
{3.2..... 320}
1.3...... 130
{13...... 1300}
5......... 500
{50...... 5000}
<Material/diaphragm extension>
Flange face
Diaph. extension [mm]
Diaphragm
316 stainless
0
316L stainless
steel
50
steel
100
(*2)
150
200
0
Hastelloy-C
Hastelloy-C
50
100
150
200
0
316 stainless stell
316L stainless
+Au coating
0
Monel
Monel
0
Tantalum
Tantalum
0
Titanium
Titanium
(*3)
0
Zirconium
Zirconium
Note 1: (*1)
Note 3: (*3)
6
F KD
9 10 11 12 13
14 15
4
A
B
C
D
S
T
V
W
0
1
2
3
4
5
6
7
8
9
M
R
A
B
C
D
E
F
G
H
J
K
S
T
U
V
W
X
P
Q
Note 1
3
5
6
Note 2
Note 3
V
A
B
C
D
H
F
G
K
L
J
M
T
P
R
100: 1 turn down is possible, but should be used at a span greater than
of the maximum span for better performance.
Available for 13th digit code "S", "T", "K" and 5th digit
code "1", "3", "5", "7", "B", "D", "F", "H", "K", "Q", "U", "W".
Available for 6th code "2", "3" and 5th code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", "P", "M", "R", "S", "T", "W".
1/40
Note 2: (*2)
Note
0
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
Description
9
<Indicator and arrester>
Indicator
Arrester
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale
None
Analog, custom scale
None
Analog, double scale (linear and sq. root)
None Z/S board attached.
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes
Analog, custom scale
Yes
Analog, double scale (linear and sq. root)
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100% square root
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100% square root
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100% square root
(Local adjustment unit with LCD display)
None
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
Digital, 0 to 100% square root
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
10
None (for ordinary locations)
TIIS, Flameproof (Conduit seal)
(Available for 4th digit code "A", "S")
TIIS, Flameproof (Cable gland seal)
(Available for 4th digit code "A", "S")
FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
CSA, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and nonincendive
CSA, Intrinsic safety and nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Capillary and mounting bracket>
11
Capillary
Mounting bracket
armor of capilary
1.5 m
304 Stainless steel
PVC
(*4)
3
304 Stainless steel
PVC
(*4)
5
304 Stainless steel
PVC
(*4)
6
304 Stainless steel
PVC
(*4)
7
304 Stainless steel
PVC
(*4)
8
304 Stainless steel
PVC
(*4)
10
304 Stainless steel
PVC
(*4)
1.5
304 Stainless steel
Stainless steel
(*5)
3
304 Stainless steel
Stainless steel
(*5)
5
304 Stainless steel
Stainless steel
(*5)
6
304 Stainless steel
Stainless steel
(*5)
7
304 Stainless steel
Stainless steel
(*4)
8
304 Stainless steel
Stainless steel
(*4)
10
304 Stainless steel
Stainless steel
(*4)
<Options>
12
Extra SS tag plate
Stainless steel elec. housing
Coating of cell
None
None
None
Yes
None
None
None
Yes
None
(*6)
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
Note 4: (*4) Available for 13th digit code "Y, W, G, A, D".
Inquire about in case of 13th other code.
Note 5: (*5) Available for all 13th digit code.
Note 6: (*6) Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select "Yes".
Note
F KD
9 10 11 12 13
4
14 15
0
21
Digit No.
of code
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
1
2
3
4
5
6
A
B
C
D
E
X
R
G
H
J
K
P
T
V
Note 4
Note 4
Note 4
Note 4
Note 4
Note 4
Note 4
Note 5
Note 5
Note 5
Note 5
Note 4
Note 4
Note 4
Note 6
D
E
L
F
M
N
P
Q
R
S
T
V
W
X
Y
B
C
E
M
N
P
Q
7
FKD...4
1 2 3 4 5 6 7 8
Note
Description
<Special applications and fill fluid>
Treatment
Fill fluid
Standard
Silicone oil
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "A", "B", "C", "D"and "J")
Chlorine service
Fluorinated oil (7th digit code "H", "F", "G", "K", "L"and"T")
High temp. 250°C
Silicone oil 7th digit code "V", "A", "B", "C", "D", "H", "F", "G", "K" and "L"
High temp. 300°C
Silicone oil
(*7)
High temp. and vacuum (250°C) Silicone oil
Note 7
High temp. and vacuum (300°C) Silicone oil 7th digit code "V", "A", "B", "C", and "D"
High temp. and high vacuum Silicone oil
<Teflon membrane>
14
None
Yes (Available for 5th digit code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", "P",
"M", "R", "S", "T", "U", "X" and 7th digit code "V", "H", "M", "T", "P", "R".
Not available for the 13th digit code "H", "J", "S", "T", "K".)
<Other options> (*8)
Note 8
21
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
Note 7: (*7) Treatment; Standard
Note 8: (*8) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
Digit
13
8
F KD
9 10 11 12 13
14 15
4
21
0
Y
W
G
A
D
H
J
S
T
K
Y
C
H
J
K
L
T
U
V
Digit No.
of code
ORDERING INFORMATION
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality
is occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Output mode (linear or square root output)
Unless otherwise specified, output mode is linear.
5. Indication method (indicated value and unit) in case of
the actual scale (code D, H, P, S on 9th digit).
6. Tag No. (up to 26 alphanumerical characters), if required.
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
9
FKD...4
OUTLINE DIAGRAM (Unit:mm)
In case of 4th digit code "A.B.C.D.E"
In case of 4th digit code "S.V.W.X"
In case of 4th digit code "T"
Zero ADJ. screw
ø80
104
Down
88
70
ø80
52.5
105
105
Up
28
38
Fastener
(Flamproof only)
10
8
94.5
MTG. pipe
JIS 50A (2B)
U-bolt M8
58
(27)
201
4 holes
9 dia.
"B" Conduit conn.
"A" Conduit conn.
Note)
Cable gland (option)
With field IND.
Inner of gasket
øE
N holes
h dia.
P
øD
øF
øG
øH
No flange is
attached in
case of 5th
digit code
"P,Q".
20
t
L
270
48 43
Detail "B"
ø13
Detail "A"
(Conduit donn.)
Earth tarminal
ø15
222
K M
17
Electronics
unit
G1/2
J
See table 1
S
L.P.
CONDUIT CONN.
4TH DIGIT
CODE
J
K
M
A, S
G1/2
17
8
B, T
1/2-14NPT 16
5
C, V
D, W
Pg13.5
M20 1.5
8
16
S
2-M8 12
Sensor
unit
H.P.
54
70
120
4.5
5
Table 1
5TH DIGIT OF THE
CODE SYMBOLS
0, A, S
M
2, C
1, B
3, D
4, E, T
6, G, V
R, X
5, F, U
7, H, W
8, J
9, K
Note)
CONNECTION DIAGRAM
øD
øE
185
200
210
210
240
191
210
210
229
254
200
220
150
160
170
175
195
152.5
168
168
190.5
200
160
180
øF øG
øH
t
P
N-øh
(FLANGE)
126
126
126
151
151
126
126
126
151
151
126
151
73
73
73
96
96
73
73
73
96
96
73
96
38
42
48
38
52
44
49
52
44
52
44
40
116
116
116
141
141
116
116
116
141
141
116
141
8-19
8-23
8-23
8-19
8-25
4-20
8-23
8-23
8-20
8-23
8-18
8-18
JIS-10K-80A
JIS-20K-80A
JIS-30K-80A
JIS-10K-100A
JIS-30K-100A
ANSI 150LB 3B
ANSI 300LB 3B
ANSI 600LB 3B
ANSI 150LB 4B
ANSI 300LB 4B
DIN PN40 DN80
DIN PN16 DN100
Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
10
100
100
100
103
103
100
100
100
103
103
100
103
CK CK
7TH DIGIT
CODE
V, J, H, M, T, P, R
L
MASS.APPROX.
(kg)
0
14∼19.5
11TH DIGIT S 11TH DIGIT S
(m)
(m) CODE
CODE
A,F
50
15∼30.5
D, Q
1.5
M, V
B,G
100
15.5∼31
E, R
3
N, W
8
C,K
150
16∼31.5
L, S
5
P, X
10
D,L
200
16.5∼32
F, T
6
7
11
FKD...4
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan