REMOTE SEAL TYPE DIFFERENTIAL PRESSURE TRANSMITTER FKD...4 DATA SHEET The FCX – A2 differential pressure transmitter accurately measures differential pressure, liquid level or gauge pressure and transmits a proportional 4 to 20mA signal. The transmitter utilizes a unique micromachined capacitance silicon sensor with state-of-the-art microprocessor technology to provide exceptional performance and functionality. Totally welded construction of the seals assures excellent reliability in high temperature and highly corrosive process conditions. FEATURES 1. High accuracy 0.2% accuracy for all calibrated spans is a standard feature for all DP models covering 0.32kPa {3.2mbar} range to 500kPa {5bar} high differential pressure range. 0.1% accuracy is available as option. Fuji’s microcapacitance silicon sensor assures this accuracy for all elevated or suppressed calibration ranges without additional adjustment. 2. Minimum environmental influence The “Advanced Floating Cell” design which protects the pressure sensor against changes in temperature, static pressure, and overpressure substantially reduces total measurement error in actual field applications. 3. Fuji/HART® bilingual communications protocol and FOUNDATION™ fieldbus and Profibus™ compatibility FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and HART®. Any HART ® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also available. 4. Application flexibility Various options that render the FCX – A2 suitable for almost any process applications include: – Analog indicator at either the electronics side or terminal side – Full range of hazardous area approvals – Built-in RFI filter and lightning arrester – 5-digit LCD meter with engineering unit – Stainless steel electronics housing – Wide selection of materials – High temperature, high vacuum seals 5. Programmable output Linearization Function In addition to Linear and Square Root, output signal can be freely programmable. (Up to 14 compensated points at approximation.) 6. Burnout current flexibility (Under Scale: 3.2 to 3.8mA, Over Scale: 20.8 to 21.6mA) Burnout signal level is adjustable using Model FXW Hand Held Communicator (HHC) to comply with NAMUR NE43. 7. Dry calibration without reference pressure Thanks to the best combination of unique construction of mechanical parts (Sensor unit) and high performance electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as wet calibration. SPECIFICATIONS Functional specifications Service: Liquid, gas, or vapour Static pressure, span, and range limit: Type Static pressure F KD 3 F KD 5 F KD 6 } Up to flange rating Span limit [kPa] (m bar} Max. Min. 0.32 { 3.2 } 1.3 { 13 } 5 { 50 } Range limit [kPa] {m bar} 32 { 320 } 130 { 1300 } 500 { 5000} +/– 32 {+/– 320} +/– 130 {+/– 1300} +/– 500 {+/– 5000} Remark : To minimize environmental influence, span should be greater than 1/40 of the max. span in most applications. – Lower limit of static pressure (vacuum limit), Silicone fill sensor: See Fig. 1 Fluorinated fill sensor: Atmospheric pressure – The maximum span of each sensor can be converted to different units using factors as below. 1MPa =103kPa=10bar=10.19716kgf/cm2 =145.0377psi 1kPa=10mbar=101.976mmH2O=4.01463H2O Overrange limit: To maximum static pressure limit Output signal: 4 to 20mA DC (linear or square root) with digital signal superimposed on the 4 to 20mA signal Power supply: Transmitter operates on 10.5V to 45V DC at transmitter terminals. 10.5V to 32V DC for the units with optional arrester. EDSX6-117i Date Jun. 1, 2006 FKD...4 Load limitations: see figure below Authorities ATEX [Ω] Load resistance 2000 1533Ω 1000 600Ω Factory Mutual Operating area 500 24V 250 10 16.1 10.5V Power voltage 45V 50 Authorities Ex II 2 GD EEx d IIC T6 IP66/67 T85°C Tamb = – 40°C to +65°C EEx d IIC T5 IP66/67 T100°C Tamb = – 40°C to +85°C Factory Mutual Class I Div.1 Groups B, C, D T6 Type 4X Class II III Div.1 Groups E, F, G T6 Type 4X Tamb max = +60°C Class I Div.1 Groups C, D Class II Div.1 Groups E, F, G Class III Div.1 Note) “Seal Not Required” enclosure is allowed. 2 TIIS Ex do IIB+H2 T4 Tamb max = +55°C Maximum process temp. = +120°C IECEx Scheme /SAA Ex d IIC T5 IP66/67 pending Tamb = – 40°C to +85°C Ex d IIC T6 IP66/67 pending Tamb = – 40°C to +65°C Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C CSA Class I Div.1 Groups A, B, C, D Class II Div.1 Groups E, F, G Class III Div.1 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS Ex ia IIC T4 Tamb max = +60°C Entity Parameters: Ui=28V, Ii=94.3mA, Pi=0.66W, Ci=32.6nF, Li=1.134mH IECEx Scheme /SAA Ex ia IIC T4 IP66/67 Tamb = –40°C to +70°C Ex ia IIC T5 IP66/67 Tamb = –40°C to +50°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=0.033µF, Li=1.034mH Flameproof ATEX 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D Entity Parameters: Vmax=42.4V, Imax=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH required. Hazardous locations: Class I II III Div.1 Groups A, B, C, D, E, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – [V] Note: For communication with HHC(1) (Model: FXW), min. of 250Ω is CSA Ex II 1 GD EEx ia IIC T5 Tamb = –40°C to +40°C EEx ia IIC T4 Tamb = –40°C to +80°C Entity Parameters: Ui=28V, Ii=93.3mA, Pi=0.66W, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.134mH 1500 0 Intrinsic safety ATEX “Output Underscale”: Adjustable within the range 3.2mA to 3.8mA from HHC(1) Type n Nonincendive Authorities Ex II 3 GD EEx nL IIC T5 Tamb = –40°C to +40°C EEx nL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Ui=42.4V, Ii=113mA, Pi=1W, Ci=27nF, Li=1.134mH Model with arrester: Ui=32V, Ii=113mA, Pi=1W, Ci=34.2nF, Li=1.134mH 3.2 Normal operating range Under scale Probable under range Burnout Class I II III Div.2 Groups A, B, C, D, F, G T4 Entity Type 4X Model code 9th digit A,B,C,D,J L,P,M,1,2,3 Q,S,N,4,5,6 E,F,G,H,K – CSA 13th digit Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K Y,G,H,J,S,T,K W,A,D – IECEx Scheme /SAA – 21.6 [mA] Tamb –40°C to +85°C –20°C to +80°C –20°C to +60°C –40°C to +60°C –10°C to +60°C Zero/span adjustment: Zero and span are adjustable from the HHC(1). Zero and span are also adjustable externally from the adjustment screw (span odjustment is not available with 9th digit code “L, P, M, Q, S, N”). Damping: Adjustable from HHC or local adjustment unit with LCD display. The time constant is adjustable between 0.12 to 32 seconds. Zero elevation/suppression: –100% to +100% of URL Normal/reverse action: Selectable from HHC(1) Indication: Analog indicator or 5-digit LCD meter, as specified. Burnout direction: Selectable from HHC(1) If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale” or “Output Underscale” modes. “Output Hold”: Output signal is hold as the value just before failure happens. “Output Overscale”: Adjustable within the range 20.8mA to 21.6mA from HHC(1) Probable over range Loop-check output: Transmitter can be configured to provide constant signal 3.8mA through 21.6mA by HHC(1). Temperature limit: Ambient: – 40 to + 85°C (– 20 to + 80°C for LCD indicator) (– 40 to + 60°C for arrester option) (– 10 to + 60°C for fluorinated oil fill transmitter) (– 10 to + 85°C for silicone oil “H”, “S”, “K”) (+ 20 to + 85°C for silicone oil “J”, “T”) For explosionproof units (flameproof or intrinsic safety), ambient temperature must be within the limits specified in each standard. Process: Class I Div.2 Groups A, B, C, D Class II Div.2 Groups E, F, G Class III Div.2 Temp Code T4 Tamb max = +40°C Temp Code T3C Tamb max = +85°C Entity Parameters: Vmax=28V, Ci=27nF (Without Arrester), Ci=34.2nF (With Arrester), Li=1.4mH TIIS 20 20.8 Over scale Burnout EEx nAL IIC T5 Tamb = –40°C to +40°C EEx nAL IIC T4 Tamb = –40°C to +80°C Specific Parameters: Model without arrester: Umax=42.4V, Imax=113mA, Pmax=1W Model with arrester: Umax=32V, Imax=113mA, Pmax=1W Factory Mutual 3.8 4 Fill fluid Code in the 13th digit of “Code symbols” Fluorinated oil W, A and D – 20 to 120°C Silicone oil H – 15 to 250°C Process temperature J Lower limit of static press. Atmospheric pressure 85 to 300°C Y and G – 40 to 120°C S – 15 to 250°C T 85 to 300°C K – 15 to 200°C 2.7kPa abs {20mmHg abs} 0.13kPa abs {1mmHg abs} or more Storage: – 40 to +90°C Humidity limit: 0 to 100% RH Communication: With HHC(1) (Model FXW, consult Data Sheet No. EDS8-47), following information can be remotely displayed or reconfigured. Note: HHC’s version must be more than 6.0 (or FXW 1– 3), for FCXA2. Items Display Set Tag No. v v Model No. v v Serial No. v — Engineering unit v v Range limit v — Measuring range v v Damping v v Linear v v Square root v v Burnout direction v v Calibration v v Output adjust — v Data v — Self diagnoses v — Printer — — External switch lock v v Transmitter display v v Linearize v v Rerange v v Output mode (Note) (1) HHC: Hand Held Communicator 3 FKD...4 Programmable output linearization function: Output signal can be characterized with “14 points linear approximation function” from HHC(1). EMC Conformity: EN61326 (Note) (1) HHC: Hand Held Communicator Performance specifications Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4 to 20mA analog output in linear mode. Accuracy rating: (including linearity, hysteresis, and repeatability) (Standard) For spans greater than 1/10 of URL: 0.2% of span For spans below 1/10 of URL: 0.1 × URL ± 0.1+0.1 % of span Span (Option) (Code; 21th digit H,K) For spans greater than 1/10 of URL: 0.1% of span For spans below 1/10 of URL: 0.1 × URL ± 0.05+0.05 % of span Span Stability: ± 0.2% of upper range limit (URL) for 3 years. Temperature effect (*): Effects per 28°C change between the limits of – 40°C and +85°C (Standard) Zero shift: ± 0.35% of URL Total effect: ± 0.5% of URL (Option) (Code; 21th digit J,K) Zero shift: ± 0.3% of URL Total effect: ± 0.4% of URL ( ) ( ) Note: * Excluding effect by temperature difference between the seals. Static pressure effect: Zero shift; 0.2% of URL for flange rating pressure Span shift: – 0.2% of calibrated span for flange rating pressure Overrange effect: Zero shift; 0.1% of URL for flange rating pressure Supply voltage effect: Less than 0.005% fo calibrated span per 1V RFI effect: Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength 30 V/m when electronics covers on. (Classification: 2-abc: 0.2% span per SAMA PMC 33.1) Update period: 120 msec *) Step response: (without electrical damping) Range code Time constant (*) “3” 2 “5” 1.7 s “6” 1.7 s Dead time (*) s 0.2 s *) Faster response is available as option (maximum update rate: 25 times per second). Dielectric strength: 500V AC, 50/60Hz 1 min., between circuit and earth. Insulation resistance: More than 100MΩ at 500V DC. Turn-on time: 4 sec. Internal resistance for external field indicator: 12Ω or less 4 Physical specifications Electrical connections: G1/2, 1/2-14 NPT, Pg13.5, or M20 × 1.5 conduit, as specified. And 1-conduit or 2-conduit, as specified. Process connections: JIS, ANSI, or DIN raised face flanges. JIS: 10K80A, 10K100A, 30K80A, or 30K100A ANSI: 150LB 3", 150LB 4", 300LB 3", or 300LB 4" DIN: PN40 DN80 or PN16 DN100 See OUTLINE DIAGRAM for detailed dimensions. Diaphragm extension: 0, 50, 100, 150, or 200mm as specified. (See model code. Extended diaphragm is available only with 316L stainless steel or Hastelloy-C diaphragm) Process-wetted parts material: Diaphragm: 316L stainless steel, HastelloyC, Monel, Tantalum, Titanium or Zirconium Flange face:316 stainless steel, HastelloyC lining Monel lining, or Tantalum lining Extension: 316 stainless steel or HastelloyC Non-wetted parts material: Electronics housing: Low copper die-cast aluminum alloy finished with epoxy/ polyurethane double coating (standard), or 316 stainless steel (SCS14 per JIS G5121), as specified. Capillary: In case of 11th code “D, E, F, L, M, N, P”, PVC armored stainless steel. In case of 13th code “Q, R, S, T, V, W, X”, stainless steel armored stainless steel. Mounting flange: 304 stainless steel or carbon steel Fill fluid: Silicone oil (standard) or fluorinated oil Mounting bracket: 304 stainless steel Environmental protection: IEC IP67 and NEMA 6/6P Mounting: On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting Mass {weight}: Transmitter approximately 15kg without options. Add; 0.5kg for mounting bracket 0.8kg for indicator option 4.5kg for stainless steel housing option 1.5kg per 50mm extension of diaphragm [kPa abs] {mbar abs} Silicone (Code Y,G) [kPa abs] {mbar abs} Silicone (Code S) Silicone (Code T) Sealing liquid:Silicone (Code K) 101 {1010} 53.3 {533} Operating pressure Operating pressure 101 {1010} Operating area 13.3 {133} Non-operating area 0.27 {2.7} 0.13 {1.3} 2.7 {27} –40 –15 60 85 120 Process temperature[°C ] 200 230 250 300 Fig. 1 Relation between process temperature and operating pressure Optional features Indicator: Operating area A plug-in analog indicator (2.5% accuracy) can be housed in the electronics compartment or in the terminal box of the housing. An optional 5-digit LCD meter with engineering unit is also available. Local adjustment unit with LCD display: An optional 5-digit LCD meter with Zero/ Span adjustment function, loop-check function and damping adjustment function, is available. Arrester: A built-in arrester protects the electronics from lightning surges. Lightning surge immunity: 4kV (1.2 × 50µs) Oxygen service: Special cleaning procedures are followed throughout the process to maintain all process wetted parts oil-free. The fill fluid is fluorinated oil. Chlorine service: Oil-free procedures as above. Includes fluorinated oil for fill. Degreasing: Process-wetted parts are cleaned, but the fill fluid is standard silicone oil. Not for use on oxygen or chlorine measurement. Vacuum service: Special silicone oil and filling procedure are applied. See Fig. 1, Fig. 2. Optional tag plate: An extra stainless steel tag for customer tag data is wired to the transmitter. Coating of cell: Cell’s surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive. –15 100 Process temperature[°C ] 200 Fig. 2 Relation between process temperature and operating pressure ACCESSORIES Hand-held communicator: (Model FXW, refer to Data Sheet No. EDS 8-47) Z/S board: Parts No.=ZZPFCX4-A070 When Z/S board is mounted on the FCX– A2 amplifier unit, external adjustment screw will be available for zero and span adjustment. 5 FKD...4 CODE SYMBOLS 1 2 3 4 5 6 7 8 Digit 4 5 6 7 Description <Conduit connection> G 1/2 (×1) 1/2-14NPT (×1) Combination with 12th digit code "C, E, P, Q" are not Pg13.5 (×1) available. M20 × 1.5 (×1) G 1/2 (×2) 1/2-14NPT (×2) Pg13.5 (×2) M20 × 1.5 (×2) <Flange> Flange size and rating Mounting flange JIS 10K 80A 304 stainless JIS 10K 100A steel JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN16/40 DN80 DIN PN16 DN100 JIS 20K 80A ANSI/JPI 600LB 3B JIS 10K 80A Carbon steel JIS 10K 100A JIS 30K 80A JIS 30K 100A ANSI/JPI 150LB 3" ANSI/JPI 150LB 4" ANSI/JPI 300LB 3" ANSI/JPI 300LB 4" DIN PN16/40 DN80 DIN PN16 DN100 JIS 10K 80A 316 stainless ANSI/JPI 150LB 3B steel ANSI/JPI 150LB 4B ANSI/JPI 300LB 3B ANSI/JPI 300LB 4B ANSI/JPI 600LB 3B 3 inch wafer None 4 inch wafer (wafer type) <Span limit (*1) [kPa]{m bar}> 0.32.... 32 {3.2..... 320} 1.3...... 130 {13...... 1300} 5......... 500 {50...... 5000} <Material/diaphragm extension> Flange face Diaph. extension [mm] Diaphragm 316 stainless 0 316L stainless steel 50 steel 100 (*2) 150 200 0 Hastelloy-C Hastelloy-C 50 100 150 200 0 316 stainless stell 316L stainless +Au coating 0 Monel Monel 0 Tantalum Tantalum 0 Titanium Titanium (*3) 0 Zirconium Zirconium Note 1: (*1) Note 3: (*3) 6 F KD 9 10 11 12 13 14 15 4 A B C D S T V W 0 1 2 3 4 5 6 7 8 9 M R A B C D E F G H J K S T U V W X P Q Note 1 3 5 6 Note 2 Note 3 V A B C D H F G K L J M T P R 100: 1 turn down is possible, but should be used at a span greater than of the maximum span for better performance. Available for 13th digit code "S", "T", "K" and 5th digit code "1", "3", "5", "7", "B", "D", "F", "H", "K", "Q", "U", "W". Available for 6th code "2", "3" and 5th code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", "P", "M", "R", "S", "T", "W". 1/40 Note 2: (*2) Note 0 21 Digit No. of code 1 2 3 4 5 6 7 8 Digit Description 9 <Indicator and arrester> Indicator Arrester None None Analog, 0 to 100% linear scale None Analog, 0 to 100% sq. root scale None Analog, custom scale None Analog, double scale (linear and sq. root) None Z/S board attached. None Yes Analog, 0 to 100% linear scale Yes Analog, 0 to 100% sq. root scale Yes Analog, custom scale Yes Analog, double scale (linear and sq. root) Yes Digital, 0 to 100% None Digital, custom scale None Digital, 0 to 100% square root None Digital, 0 to 100% Yes Digital, custom scale Yes Digital, 0 to 100% square root Yes Digital, 0 to 100% (Local adjustment unit with LCD display) None Digital, custom scale (Local adjustment unit with LCD display) None Digital, 0 to 100% square root (Local adjustment unit with LCD display) None Digital, 0 to 100% (Local adjustment unit with LCD display) Yes Digital, custom scale (Local adjustment unit with LCD display) Yes Digital, 0 to 100% square root (Local adjustment unit with LCD display) Yes <Approvals for hazardous locations> 10 None (for ordinary locations) TIIS, Flameproof (Conduit seal) (Available for 4th digit code "A", "S") TIIS, Flameproof (Cable gland seal) (Available for 4th digit code "A", "S") FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T") CSA, Flameproof (or explosionproof) (Available for 4th digit code "B", "T") ATEX, Flameproof IECEx Scheme/SAA, Flameproof (Approval pending) TIIS, Intrinsic safety FM, Intrinsic safety and nonincendive CSA, Intrinsic safety and nonincendive ATEX, Intrinsic safety ATEX, Type n IECEx Scheme/SAA, Intrinsic safety FM, Combined of Flameproof and Intrinsic safety <Capillary and mounting bracket> 11 Capillary Mounting bracket armor of capilary 1.5 m 304 Stainless steel PVC (*4) 3 304 Stainless steel PVC (*4) 5 304 Stainless steel PVC (*4) 6 304 Stainless steel PVC (*4) 7 304 Stainless steel PVC (*4) 8 304 Stainless steel PVC (*4) 10 304 Stainless steel PVC (*4) 1.5 304 Stainless steel Stainless steel (*5) 3 304 Stainless steel Stainless steel (*5) 5 304 Stainless steel Stainless steel (*5) 6 304 Stainless steel Stainless steel (*5) 7 304 Stainless steel Stainless steel (*4) 8 304 Stainless steel Stainless steel (*4) 10 304 Stainless steel Stainless steel (*4) <Options> 12 Extra SS tag plate Stainless steel elec. housing Coating of cell None None None Yes None None None Yes None (*6) Yes Yes None None None Yes Yes None Yes None Yes Yes Yes Yes Yes Note 4: (*4) Available for 13th digit code "Y, W, G, A, D". Inquire about in case of 13th other code. Note 5: (*5) Available for all 13th digit code. Note 6: (*6) Customer tag number can be engraved on standard stainless steel name plate. If extra tag plate is required, select "Yes". Note F KD 9 10 11 12 13 4 14 15 0 21 Digit No. of code A B C D J E F G H K L P M Q S N 1 2 3 4 5 6 A B C D E X R G H J K P T V Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 5 Note 5 Note 5 Note 5 Note 4 Note 4 Note 4 Note 6 D E L F M N P Q R S T V W X Y B C E M N P Q 7 FKD...4 1 2 3 4 5 6 7 8 Note Description <Special applications and fill fluid> Treatment Fill fluid Standard Silicone oil Standard Fluorinated oil Degreasing Silicone oil Oxygen service Fluorinated oil (7th digit code "V", "A", "B", "C", "D"and "J") Chlorine service Fluorinated oil (7th digit code "H", "F", "G", "K", "L"and"T") High temp. 250°C Silicone oil 7th digit code "V", "A", "B", "C", "D", "H", "F", "G", "K" and "L" High temp. 300°C Silicone oil (*7) High temp. and vacuum (250°C) Silicone oil Note 7 High temp. and vacuum (300°C) Silicone oil 7th digit code "V", "A", "B", "C", and "D" High temp. and high vacuum Silicone oil <Teflon membrane> 14 None Yes (Available for 5th digit code "0", "2", "4", "6", "8", "A", "C", "E", "G", "J", "P", "M", "R", "S", "T", "U", "X" and 7th digit code "V", "H", "M", "T", "P", "R". Not available for the 13th digit code "H", "J", "S", "T", "K".) <Other options> (*8) Note 8 21 High accuracy type Instruction manual attached Low temperature effect type Instruction manual attached H+J Instruction manual attached Instruction manual unattached High accuracy type Instruction manual unattached Low temperature effect type Instruction manual unattached T+U Instruction manual unattached Note 7: (*7) Treatment; Standard Note 8: (*8) If other option is not necessary, 21st digit code is blank. In case of 21st digit code is blank, instruction manual attached. Digit 13 8 F KD 9 10 11 12 13 14 15 4 21 0 Y W G A D H J S T K Y C H J K L T U V Digit No. of code ORDERING INFORMATION The product conforms to the requirements of the Electromagnetic compatibility Directive 94/9/EC as detailed within the technical construction file number TN513035. The applicable standards used to demonstrate compliance are : EMI (Emission) EN61326 : 1997 Class A (standard for Industrial Location) Frequency range MHz Limits Reference standard 30 to 230 40dB (µV/m) quasi peak, measured at 10m distance CISPR16-1 and CISPR16-2 230 to 1000 47dB (µV/m) quasi peak, measured at 10m distance EMI (Immunity) EN61326: 1997 Annex A (standard for Industrial Location) Phenomenon Electrostatic discharge When ordering this instrument, specify: 1. CODE SYMBOLS 2. Measuring range 3. Output orientation (burnout direction) when abnormality is occurred in the transmitter. Hold / Overscale (21.6mA) / Underscale (3.2mA) Unless otherwise specified, output hold function is supplied. 4. Output mode (linear or square root output) Unless otherwise specified, output mode is linear. 5. Indication method (indicated value and unit) in case of the actual scale (code D, H, P, S on 9th digit). 6. Tag No. (up to 26 alphanumerical characters), if required. Test value 4kV (Contact) 8kV (Air) Basic standard Performance criteria EN61000-4-2 B 80 to 1000MHz Electromagnetic 10V/m field 80%AM (1kHz) EN61000-4-3 A Rated power frequency magnetic field 30A/m 50Hz EN61000-4-8 A Burst 2kV 5kHz EN61000-4-4 B Surge 1.2µs/50µs 1kV (Line to line) 2kV (Line to ground) EN61000-4-5 B Conducted RF 0.15 to 80MHz 3V 80%AM (1kHz) EN61000-4-6 A Note) Definition of performance criteria A: During testing, normal performance within the specification limits. B: During testing, temporary degradation, or loss of function or performance which is self-recovering. 9 FKD...4 OUTLINE DIAGRAM (Unit:mm) In case of 4th digit code "A.B.C.D.E" In case of 4th digit code "S.V.W.X" In case of 4th digit code "T" Zero ADJ. screw ø80 104 Down 88 70 ø80 52.5 105 105 Up 28 38 Fastener (Flamproof only) 10 8 94.5 MTG. pipe JIS 50A (2B) U-bolt M8 58 (27) 201 4 holes 9 dia. "B" Conduit conn. "A" Conduit conn. Note) Cable gland (option) With field IND. Inner of gasket øE N holes h dia. P øD øF øG øH No flange is attached in case of 5th digit code "P,Q". 20 t L 270 48 43 Detail "B" ø13 Detail "A" (Conduit donn.) Earth tarminal ø15 222 K M 17 Electronics unit G1/2 J See table 1 S L.P. CONDUIT CONN. 4TH DIGIT CODE J K M A, S G1/2 17 8 B, T 1/2-14NPT 16 5 C, V D, W Pg13.5 M20 1.5 8 16 S 2-M8 12 Sensor unit H.P. 54 70 120 4.5 5 Table 1 5TH DIGIT OF THE CODE SYMBOLS 0, A, S M 2, C 1, B 3, D 4, E, T 6, G, V R, X 5, F, U 7, H, W 8, J 9, K Note) CONNECTION DIAGRAM øD øE 185 200 210 210 240 191 210 210 229 254 200 220 150 160 170 175 195 152.5 168 168 190.5 200 160 180 øF øG øH t P N-øh (FLANGE) 126 126 126 151 151 126 126 126 151 151 126 151 73 73 73 96 96 73 73 73 96 96 73 96 38 42 48 38 52 44 49 52 44 52 44 40 116 116 116 141 141 116 116 116 141 141 116 141 8-19 8-23 8-23 8-19 8-25 4-20 8-23 8-23 8-20 8-23 8-18 8-18 JIS-10K-80A JIS-20K-80A JIS-30K-80A JIS-10K-100A JIS-30K-100A ANSI 150LB 3B ANSI 300LB 3B ANSI 600LB 3B ANSI 150LB 4B ANSI 300LB 4B DIN PN40 DN80 DIN PN16 DN100 Cable gland is supplied in case of flameproof packing type. ø11 cable is suitable. 10 100 100 100 103 103 100 100 100 103 103 100 103 CK CK 7TH DIGIT CODE V, J, H, M, T, P, R L MASS.APPROX. (kg) 0 14∼19.5 11TH DIGIT S 11TH DIGIT S (m) (m) CODE CODE A,F 50 15∼30.5 D, Q 1.5 M, V B,G 100 15.5∼31 E, R 3 N, W 8 C,K 150 16∼31.5 L, S 5 P, X 10 D,L 200 16.5∼32 F, T 6 7 11 FKD...4 Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fesys.co.jp/eng Instrumentation Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http://www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan