FUJI EDSX6-116K

SMALL FLANGE REMOTE SEAL TYPE
DIFFERENTIAL PRESSURE TRANSMITTER
FKX...4
DATA SHEET
The FCX–A2 small flange remote seal type differential
pressure transmitter accurately measures differential
pressure, liquid level or gauge pressure and transmits a
proportional 4 to 20mA signal. The transmitter utilizes a
unique micromachined capacitance silicon sensor with stateof-the-art microprocessor technology to provide exceptional
performance and functionality. Totally welded construction
of the seals assures excellent reliability in high temperature
and highly corrosive process conditions.
FEATURES
1. Directly connectable to 1-1/2 in and 2in flanges
The transmitter is connectable to 1-1/2 in and 2in pipes
without a reducer.
2. Flow measurement without impulse piping
1/2 in and 3/4 in flange size is also available. This differential pressure transmitter allows connection to 1/2 in
and 3/4 in flanges of a general size for the orifice tap,
which eliminates the need of using a impulse piping.
Problems with the impulse piping, such as clogging, leaks
or corrosion can be solved. In addition, the following
process connection is also available.
Screw connection 1/2-14NPT, 3/4-14NPT, Rc 1/2, Rc 3/4
3. Minimum environmental influence
The “Advanced Floating Cell” design which protects the
pressure sensor against changes in temperature, static
pressure, and overpressure substantially reduces total
measurement error in actual field applications.
4. Fuji/HART® bilingual communications protocol and
FOUNDATION™ fieldbus and Profibus™ compatibility
FCX–A2 series transmitter offers bilingual communications to speak both Fuji proprietary protocol and
HART®. Any HART® compatible devices can communicate with FCX–A2. Further, by upgrading electronics FOUNDATION™ fieldbus and Profibus™ are also
available.
5. Application flexibility
Various options that render the FCX–A2 suitable for
almost any process applications include:
– Analog indicator at either the electronics side or
terminal side
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5 -digit LCD meter with engineering unit
– Stainless steel electronics housing
– Wide selection of materials
– High temperature, high vacuum seals
6. Programmable output Linearization Function
In addition to Linear and Square Root, output signal can
be freely programmable.
(Up to 14 compensated points at approximation.)
7. Burnout current flexibility (Under Scale: 3.2 to 3.8mA,
Over Scale: 20.8 to 21.6mA)
Burnout signal level is adjustable using Model FXW Hand
Held Communicator (HHC) to comply with NAMUR NE43.
9. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry calibration without reference pressure is at equal level as
wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Static pressure, span, and range limit:
Type
Static pressure
Span limit [kPa]
(m bar}
Min.
F KX
3
F KX
5
F KX
6
Up to
flange rating
3
{ 30}
13
{130}
50
{500}
Max.
Range limit
[kPa] {m bar}
32
{ 320 }
130
{1300 }
500
{5000 }
+/– 32
{+/– 320}
+/– 130
{+/– 1300}
+/– 500
{+/– 5000}
– Maximum static pressure limit for screw connction
type: 4.2MPa
– Lower limit of static pressure (vacuum limit),
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: Atmospheric pressure
– The maximum span of each sensor can be converted
to different units using factors as below.
1MPa =103kPa=10bar=10.19716kgf/cm2
=145.0377psi
1kPa=10mbar=101.976mmH2O=4.01463H2O
EDSX6-116k
Date
Apr. 1, 2007
FKX...4
Overrange limit: To maximum static pressure limit
Output signal:
4 to 20mA DC (linear or square root) with
digital signal superimposed on the 4 to
20mA signal.
Power supply:
Transmitter operates on 10.5V to 45V DC
at transmitter terminals.
10.5V to 32V DC for the units with optional
arrester.
Load limitations: see figure below
ATEX
2000
1533Ω
1000
600Ω
Operating
area
24V
250
0
10
45V
16.1
10.5V
Power voltage
50
[V]
CSA
-
TIIS
Ex do IIB+H2 T4
Tamb max = +55°C
Maximum process temp.=+120°C
IECEx
Scheme
/SAA
Ex d IIC T5 IP66/67 pending
Tamb = -40°C to +85°C
Ex d IIC T6 IP66/67 pending
Tamb = -40°C to +65°C
(Note)
2
Class I
Div.1 Groups B, C, D
T6 Type 4X
Class II III
Div.1 Groups E, F, G
T6 Type 4X
Tamb max = +60°C
(1) HHC: Hand Held Communicator
Y,G,H,S
-40°C to +85°C
Y,G,H,S
-20°C to +80°C
Q,S,N,4,5,6
Y,G,H,S
-20°C to +60°C
E,F,G,H,K
Y,G,H,S
-40°C to +60°C
W,A,D
-10°C to +60°C
Class I
Div.1 Groups A, B, C, D
Class II
Div.1 Groups E, F, G
Class III
Div.1
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Imax=93mA, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
Ex ia IIC T4
Tamb max = +60°C
Entity Parameter:
Ui=28V, Ii=94.3mA, Pi=0.66W,
Ci=32.6nF, Li=1.134mH
IECEx
Scheme
/SAA
Ex ia IIC T4 IP66/67
Tamb = -40°C to +70°C
Ex ia IIC T5 IP66/67
Tamb = -40°C to +50°C
Entity Parameter:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=0.033µF, Li=1.034mH
Flameproof
Ex II 2 GD
EEx d IIC T6 IP66/67 T85°C
Tamb = -40°C to +65°C
EEx d IIC T5 IP66/67 T100°C
Tamb = -40°C to +85°C
A,B,C,D,J
L,P,M,1,2,3
CSA
Hazardous locations:
Authorities
Tamb
Entity Parameters:
Vmax=42.4V, Imax=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
required.
Factory
Mutual
Class I II III
Div.1 Groups A, B, C, D, E, F, G
T4 Entity Type 4X
-
Note: For communication with HHC(1) (Model: FXW), min. of 250Ω is
ATEX
Ex II 1 GD
EEx ia IIC T5 Tamb = -40°C to +40°C
EEx ia IIC T4 Tamb = -40°C to +80°C
Model code
13th digit
9th digit
1500
500
Intrinsic safety
Entity Parameters:
Ui=28V, Ii=93.3mA, Pi=0.66W,
Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.134mH
Factory
Mutual
[Ω]
Load resistance
Authorities
ATEX
“Output Underscale”:
Adjustable within the range 3.2mA to
3.8mA from HHC(1)
Type n
Nonincendive
Authorities
Ex II 3 GD
EEx nL IIC T5 Tamb = -40°C to +40°C
EEx nL IIC T4 Tamb = -40°C to +80°C
Specific Parameters:
Model without arrester:
Ui=42.4V, Ii=113mA, Pi=1W,
Ci=27nF, Li=1.134mH
Model with arrester:
Ui=32V, Ii=113mA, Pi=1W,
Ci=34.2nF, Li=1.134mH
3.2
Normal operating range
Under scale
Probable under range
Burnout
Class I II III
Div.2 Groups A, B, C, D, F, G
T4 Entity Type 4X
Model code
13th digit
9th digit
A,B,C,D,J
Y,G,H,S
-40°C to +85°C
Y,G,H,S
-20°C to +80°C
Q,S,N,4,5,6
Y,G,H,S
-20°C to +60°C
CSA
Tamb
L,P,M,1,2,3
E,F,G,H,K
Y,G,H,S
-40°C to +60°C
W,A,D
-10°C to +60°C
Class I
Div.2 Groups A, B, C, D
Class II
Div.2 Groups E, F, G
Class III
Div.2
Temp Code T4 Tamb max = +40°C
Temp Code T3C Tamb max = +85°C
Entity Parameters:
Vmax=28V, Ci=27nF (Without Arrester),
Ci=34.2nF (With Arrester), Li=1.4mH
TIIS
-
IECEx
Scheme
/SAA
-
20 20.8
21.6 [mA]
Over scale
Burnout
EEx nAL IIC T5 Tamb = -40°C to +40°C
EEx nAL IIC T4 Tamb = -40°C to +80°C
Specific Parameters:
Model without arrester:
Umax=42.4V, Imax=113mA, Pmax=1W,
Model with arrester:
Umax=32V, Imax=113mA, Pmax=1W
Factory
Mutual
3.8 4
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjustable
externally from the adjustment screw
(span adjustment is not available with 9th
digit code “L, P, M, Q, S, N”).
Damping:
Adjustable from HHC or local adjustment
unit with LCD display.
The time constant is adjustable between
0.12 to 32 seconds.
Zero elevation/suppression:
–100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter failure, the analog signal will be driven to either “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just before failure happens.
“Output Overscale”:
Adjustable within the range 20.8mA to
21.6mA from HHC(1)
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.8mA through 21.6mA by
HHC(1).
Temperature limit:
Ambient: – 15 to + 65°C
(– 15 to + 60°C for arrester option)
(– 10 to + 60°C for fluorinated oil fill transmitter)
(– 10 to + 60°C for silicone oil “H”, “S”)
For explosionproof units (flameproof or intrinsic safety),
ambient temperature must be within the limits specified in each standard.
Process:
Fill fluid
13th digit of
“Code symbols”
Fluorinated oil
W, A and D
Silicone oil
H
Process
temperature
– 20 to 120°C
0 to 250°C
Y and G
– 40 to 120°C
S
0 to 250°C
Lower limit
of
static press.
Atmospheric
pressure
2.7kPa abs
{20mmHg
abs}
Storage: – 40 to +70°C
Humidity limit: 0 to 100% RH
Communication: With HHC (1) (Model FXW, consult Data
Sheet No. EDS8-47), following information can be remotely displayed or reconfigured.
Note: HHC’s version must be more than
6.0 (or FXW
1– 3), for FCXA2.
Items
Display
Set
Tag No.
v
v
Model No.
v
v
Serial No.
v
—
Engineering unit
v
v
Range limit
v
—
Measuring range
v
v
Damping
v
v
Linear
v
v
Square root
v
v
Burnout direction
v
v
Calibration
v
v
Output adjust
—
v
Data
v
—
Self diagnoses
v
—
Printer
—
—
External switch lock
v
v
Transmitter display
v
v
Linearize
v
v
Rerange
v
v
Output mode
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation function”
from HHC(1).
EMC Conformity: EN61326
3
FKX...4
Static pressure effect:
Zero shift; 0.2% of URL/1MPa (10 bar)
Performance specifications
Reference conditions, silicone oil fill, 316SS isolating diaphragms,
4 to 20mA analog output in linear mode and capillary length 1.5m.
Span shift: – 0.2% of calibrated span /
1MPa
Accuracy rating: (including linearity, hysteresis, and repeatability)
(Standard)
For spans greater than 1/10 of URL: 0.25% of span
For spans below 1/10 of URL:
0.1 x URL
± 0.17+0.08
% of span
Span
(Option) (Code; 21th digit H,K)
For spans greater than 1/10 of URL: 0.1% of span
For spans below 1/10 of URL:
0.1 x URL
± 0.05+0.05
% of span
Span
Stability:
± 0.2% of upper range limit (URL) for 3
years.
Temperature effect:
Effects per 28°C change between the limits of – 15°C and +65°C
Zero shift: ± 0.5%/28°C
(x equal to 1/2 URL or more)
URL
Zero shift; ± (0.5
)%/28°C
2x
(x less than 1/2 URL)
Total shift; ± 0.75%/28°C
(x less than 1/2 URL or more)
URL
Total shift; ± (0.25 + 0.5
)%/28°C
2x
(x less than 1/2 URL)
(option) (Code; 21th digit J,K)
Zero shift: ± 0.5%/28°C
(x equal to 1/6.5 URL or more)
URL
Zero shift; ± (0.5
)%/28°C
6.5 x
(x less than 1/6.5 URL)
Total shift; ± 0.75%/28°C
(x equal to 1/6.5 URL or more)
URL
Total shift; ± (0.25 + 0.5
)%/28°C
6.5 x
(x less than 1/6.5 URL)
Where, x:
Calibrated span
Overrange effect: Zero shift; 0.1% of URL for flange nominal
pressure
Supply voltage effect:
Less than 0.005% fo calibrated span per
1V
RFI effect:
Less than 0.2% of URL for the frequencies of 20 to 1000MHz and field strength
30 V/m when electronics covers on.
Update period: 120 msec *)
Step response: (without electrical damping)
(
)
(
)
URL:
Maximum span (Upper Range
Limit)
Note : Above specifications are based on the conditions that flanges and sensor unit are at
the same temperature and in the same
level. If temperature is different at flanges,
capillary or sensor unit, output variation
may increase.
4
Time constant (*)
1.7 s
Dead time (*)
0.2 s
*) Faster response is available as option
(maximum update rate: 25 times per second).
Dielectric strength:
500V AC, 50/60Hz 1 min., between circuit
and earth.
Insulation resistance:
More than 100MΩ at 500V DC.
Turn-on time:
4 sec.
Internal resistance for external field indicator:
12Ω or less
Physical specifications
Indicator:
A plug-in analog indicator (2.5% accuracy)
can be housed in the electronics compartment or in the terminal box of the housing.
An optional 5-digit LCD meter with engineering unit is also available.
Local adjustment unit with LCD display:
An optional 5-digit LCD meter with Zero/
Span adjustment function, loop-check
function and damping adjustment function, is available.
Arrester:
A built-in arrester protects the electronics
from lightning surges.
Lightning surge immunity: 4kV (1.2 x
50µs).
Oxygen service: Special cleaning procedures are followed
throughout the process to maintain all process wetted parts oil-free.
The fill fluid is fluorinated oil.
Chlorine service: Oil-free procedures as above. Includes
fluorinated oil for fill.
Degreasing:
Process-wetted parts are cleaned, but the
fill fluid is standard silicone oil. Not for use
on oxygen or chlorine measurement.
Vacuum service: Special silicone oil and filling procedure
are applied.
See Fig. 1.
Optional tag plate:
An extra stainless steel tag for customer
tag data is wired to the transmitter.
Coating of cell: Cell's surface is finished with epoxy/polyurethane double coating. Specify if environment is extremely corrosive.
Filled liquid:
Silicone (Code Y,G)
[kPa abs]
{m bar abs}
Silicone (Code S)
101
{1010}
Operating pressure
Electrical connections:
G1/2, 1/2-14 NPT, Pg13.5, or M20 x 1.5 conduit, as specified.
And 1-conduit or 2-conduit, as specified.
Process connections:
JIS
10K, 20K, 30K - 40, 50A
10K, 20K, 30K - 15, 20A (with Adapter)
ANSI/JPI
150LB, 300LB -11/2", 2"
150LB, 300LB - 1/2", 3/4" (with Adapter)
Screw connection (with Adapter);
Rc1/2, Rc3/4, 1/2 - 14NPT, 3/4 - 14NPT
Diaphragm extension:
0, 50, 100, 150, or 200mm as specified.
(See model code. Extended diaphragm is
available only with 316L stainless steel
diaphragm)
Process-wetted parts material:
Diaphragm: 316L stainless steel, Hastelloy-C,
Monel or Tantalum
Flange face: 316 stainless steel, HastelloyC lining
Monel lining, or Tantalum lining
Extension: 316 stainless steel
Non-wetted parts material:
Electronics housing: Low copper die-cast
aluminum alloy finished with epoxy/
polyurethane double coating (standard), or 316 stainless steel (SCSI4 par
JIS G5121), as specified.
Capillary: In case of 11th code “D. E. L.”,
PVC armored stainless steel.
In case of 11th code “Q. R. S”, stainless steel armored stainless steel.
Mounting flange: 304 stainless steel or
carbon steel.
Fill fluid: Silicone oil (standard) or fluorinated oil
Mounting bracket: 304 stainless steel
Environmental protection:
IEC IP67 and NEMA 6/6P
Mounting:
On 60.5mm (JIS 50A) pipe using mounting bracket, direct wall mounting
Mass {weight}:
Transmitter approximately 15kg without
options.
Add; 0.5kg for mounting bracket
0.8kg for indicator option
4.5kg for stainless steel housing
option
1.5kg per 50mm extension of diaphragm
Optional features
53.3
{533}
Operating area
13.3
{133}
Non-operating
area
2.7
{27}
–40 0
60 85 120
Process temperature
200 230 250
[°C ]
Fig. 1 Relation between process temperature and
operating pressure
ACCESSORIES
Hand-held communicator:
(Model FXW, refer to Data Sheet No. EDS
8-47)
Z/S board:
Parts No.=ZZPFCX4-A070
When Z/S board is mounted on the FCX–
A2 amplifier unit, external adjustment
screw will be available for zero and span
adjustment.
5
FKX...4
CODE SYMBOLS
1 2 3 4 5 6 7 8
Digit
4
5
6
7
Description
<Conduit connections>
G 1/2
(×1)
1/2 - 14NPT (×1)
Combination with 12th digit code "C, E, P, Q"are
not available.
Pg13.5
(×1)
M20 × 1.5 (×1)
G 1/2
(×2)
1/2 - 14NPT (×2)
Pg13.5
(×2)
M20 × 1.5 (×2)
<Flange>
Material
Size and rating
304 stainless
JIS 10K 40A
steel
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
JIS 63K 40A
JIS 63K 50A
ANSI/JPI 150LB 1 1/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 1 1/2"
ANSI/JPI 300LB 2"
ANSI/JPI 600LB 1 1/2B
ANSI/JPI 600LB 2B
Carbon steel
JIS 10K 40A
JIS 10K 50A
JIS 20K 40A
JIS 20K 50A
JIS 30K 40A
JIS 30K 50A
JIS 63K 40A
JIS 63K 50A
ANSI/JPI 150LB 1 1/2"
ANSI/JPI 150LB 2"
ANSI/JPI 300LB 1 1/2"
ANSI/JPI 300LB 2"
ANSI/JPI 600LB 1 1/2B
ANSI/JPI 600LB 2B
None
40A, 1 1/2B
(Wafer type)
50A, 2B
Direct mounting adapter connection (* 1)
<Span limit [kPa] {m bar}>
3........32(30...320)
13......130(130...1300) (*2)
50......500(500...5000)
<Material/diapharagm extension>
Flange face
Diaphragm extension(mm)
Diaphragm
0
316L stainless steel 316 stainless steel
50
100
(*3)
150
200
0
316L stainless steel
+Au coating
0
Hastelloy-C
Hastelloy-C
0
Monel
Monel
0
Tantalum
Tantalum
Note 1: (*1)
Note 2: (*2)
Note 3: (*3)
6
Note
F KX
9 10 11 12 13
14 15 16 17 18 19 20
4
A
B
C
D
S
T
V
W
Note 1
Note 2
Note 3
0
1
2
3
4
5
6
7
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V
W
X
Y
3
5
6
V
A
B
C
D
J
H
M
T
Direct mounting adapter type is specified at 16th to 20th digit.
Direct mounting adapter is available only for 7th digit code "V".
100:1 turn down is possible for model FKX, but should be used within indicated span for better performance.
Diaphragm extension is available only for 2" (50A) flanges.
21
Digit No.
of code
1 2 3 4 5 6 7 8
Digit
9
10
11
12
13
14
Description
<Indicator and arrester>
Indicator
Arrester
Note
None
None
Analog, 0 to 100% linear scale
None
Analog, 0 to 100% sq. root scale
None
Z/S board
Analog, custom scale
None
attached.
Analog, double scale(Linear and sq.root)
None
None
Yes
Analog, 0 to 100% linear scale
Yes
Analog, 0 to 100% sq. root scale
Yes
Analog, custom scale
Yes
Analog, double scale(Linear and sq.root)
Yes
Digital, 0 to 100%
None
Digital, custom scale
None
Digital, 0 to 100% square root
None
Digital, 0 to 100%
Yes
Digital, custom scale
Yes
Digital, 0 to 100% square root
Yes
Digital, 0 to 100%
(Local adjustment unit with LCD display)
None
Digital, custom scale
(Local adjustment unit with LCD display)
None
Digital, 0 to 100% square root
(Local adjustment unit with LCD display)
None
Digital, 0 to 100%
(Local adjustment unit with LCD display)
Yes
Digital, custom scale
(Local adjustment unit with LCD display)
Yes
Digital, 0 to 100% square root
(Local adjustment unit with LCD display)
Yes
<Approvals for hazardous locations>
None (for ordinary locations)
TIIS, Flameproof (Conduit seal) (Available for 4th digit code "A", "S")
TIIS, Flameproof (Cable gland seal) (Available for 4th digit code "A", "S")
FM, Flameproof (or explosionproof) (Available for 4th digit code "B", "T")
ATEX, Flameproof
IECEx Scheme/SAA, Flameproof (Approval pending)
TIIS, Intrinsic safety
FM, Intrinsic safety and Nonincendive
ATEX, Intrinsic safety
ATEX, Type n
IECEx Scheme/SAA, Intrinsic safety
FM, Combined of Flameproof and Intrinsic safety
<Capillary and mounting bracket>
mounting bracket Capillary
armor of capillary
Stainless steel
1.5m
PVC
Note5
3m
(*5)
5m
1.5m
Stainless steel
3m
5m
<Options>
Extra ss tag plate
Stainless steel elec. housing Coating of cell
None
None
None
Yes
None
None
None
Yes
None
(*4)
Note4
Yes
Yes
None
None
None
Yes
Yes
None
Yes
None
Yes
Yes
Yes
Yes
Yes
<Treatment/Fill fluid>
Treatment
Fill fluid
Standard
Silicone oil (for general use)
Standard
Fluorinated oil
Degreasing
Silicone oil
Oxygen service
Fluorinated oil (7th digit code "V", "A", "B", "C" and "D")
Chlorine service
Fluorinated oil (7th digit code "H" and "T")
High temp. 250°C
Silicone oil (7th digit code "V", "A", "B", "C", "D" and "H")
High temp. and vacuum (250°C) Silicone oil (7th digit code "V", "A", "B", "C" and "D")
<Teflon membrane>
None
Yes (Available for 7th digit code "V", "H", "M" and "T".
Not available for 5th digit code "Y" and 13th digit code "H", "S".)
Note 4: (*4)
Note 5: (*5)
F KX
9 10 11 12 13
14 15 16 17 18 19 20
4
0
21
Digit No.
of code
A
B
C
D
J
E
F
G
H
K
L
P
M
Q
S
N
1
2
3
4
5
6
A
B
C
D
X
R
G
H
K
P
T
V
D
E
L
Q
R
S
Y
B
C
E
M
N
P
Q
Y
W
G
A
D
H
S
Y
C
Customer tag number can be engraved on standard stainless steel
name plate. If extra tag plate is required, select "Yes".
Available for 13th digit code "Y", "W", "G", "A" and "D".
7
FKX...4
Specifications of Direct Mounting Adapter {for 15, 20A (1/2, 3/4") connection} and others
Note 1. When odering the instrument with direct mounting adapter, specify “Y” in the 5th digit of Code Symbol, and specify
16th digit to 20th digit.
When odering the instrument without direct mounting adapter, nothing should be filled in the 16th to 20th digit.
2. Unless otherwise described in the specifications, leave the 21st digit blank.
1 2 3 4 5 6 7 8
Digit
Description
Note
16, 17 <Process connection (direct mounting adapter)>
JIS 10K 15A
JIS 10K 20A
JIS 20K 15A
JIS 20K 20A
JIS 30K 15A
JIS 30K 20A
ANSI/JPI 150LB 1/2"
ANSI/JPI 150LB 3/4"
ANSI/JPI 300LB 1/2"
ANSI/JPI 300LB 3/4"
Screw connection Rc1/2
Screw connection Rc3/4
Screw connection Rc1/2 - 14NPT
Screw connection Rc3/4 - 14NPT
18
<Material (direct mounting adapter)> (*6)
Note 6
Adapter
Bolts/nuts
(* 6)
316 Stainless Steel
Cr-Mo steel/carbon steel
19
<Vent/drain (for direct mounting adapter)>
Standard
Long type
20
<Gasket (for direct mounting adapter)>
Standard (Teflon) (Only Y, W, G, A and D can be specified on 13th digit).
For high temperature (spiral gasket) (Only H and S can be
specified on 13th digit).
21
Note 7
<Other options> (*7)
High accuracy type
Instruction manual attached
Low temperature effect type
Instruction manual attached
H+J
Instruction manual attached
Instruction manual unattached
High accuracy type
Instruction manual unattached
Low temperature effect type
Instruction manual unattached
T+U
Instruction manual unattached
F KX
Note 6: (*6) For connection of transmitter receiving pressure unit and direct mounting adapter
Note 7: (*7) If other option is not necessary, 21st digit code is blank.
In case of 21st digit code is blank, instruction manual attached.
8
4
9 10 11 12 13
14 15 16 17 18 19 20
21
0
1 1
1 2
2 1
2 2
3 1
3 2
1H
1 T
2H
2 T
SR
S 2
SN
ST
W
A
N
1
2
H
J
K
L
T
U
V
Digit No.
of code
The product conforms to the requirements of the
Electromagnetic compatibility Directive 94/9/EC as detailed
within the technical construction file number TN513035.
The applicable standards used to demonstrate compliance
are :
EMI (Emission)
EN61326 : 1997
Class A (standard for Industrial Location)
Frequency range
MHz
Limits
Reference
standard
30 to 230
40dB (µV/m) quasi peak,
measured at 10m distance
CISPR16-1 and
CISPR16-2
230 to 1000
47dB (µV/m) quasi peak,
measured at 10m distance
EMI (Immunity)
When ordering this instrument, specify:
1. CODE SYMBOLS
2. Measuring range
3. Output orientation (burnout direction) when abnormality is
occurred in the transmitter.
Hold / Overscale (21.6mA) / Underscale (3.2mA)
Unless otherwise specified, output hold function is supplied.
4. Output mode (linear or square root output)
Unless otherwise specified, output mode is linear.
5. Indication method (indicated value and unit) in case of the
actual scale (code D, H, P, S on 9th digit).
6. Tag No. (up to 26 alphanumerical characters), if required.
EN61326: 1997
Annex A (standard for Industrial Location)
Phenomenon
Electrostatic
discharge
ORDERING INFORMATION
Test value
4kV (Contact)
8kV (Air)
Basic
standard
Performance
criteria
EN61000-4-2
B
80 to 1000MHz
Electromagnetic
10V/m
field
80%AM (1kHz)
EN61000-4-3
A
Rated power
frequency
magnetic field
30A/m
50Hz
EN61000-4-8
A
Burst
2kV
5kHz
EN61000-4-4
B
Surge
1.2µs/50µs
1kV (Line to line)
2kV (Line to ground)
EN61000-4-5
B
Conducted RF
0.15 to 80MHz
3V
80%AM (1kHz)
EN61000-4-6
A
Note) Definition of performance criteria
A: During testing, normal performance within the
specification limits.
B: During testing, temporary degradation, or loss of
function or performance which is self-recovering.
9
FKX...4
OUTLINE DIAGRAM (Unit:mm)
In case of 4th digit code "A.B.C.D.E"
In case of 4th digit code "T"
MTG. pipe
JIS 50A (2B)
In case of 4th digit code "S.V.W.X"
Fastene
(Flameproof only)
10
8
94.5
U-bolt M8
ø80
104
105
70
ø80
52.5
105
UP
88
DOWN
38 28
4 holes
9 dia.
58
201
(27)
"B" Conduit conn.
Zero ADJ. screw
Note)
"A" Conduit conn.
Cable gland (option)
With field IND.
N holes
h dia.
71
øD
øE
ø84
ø49
ø48
Inner of gasket
20
L
t
270
48 43
No flange is attached
in case of 5th digit code
W, X"
Earth terminal
Detail "A"
Detail "B"
ø13
Electronics
unit
75
17
K
J
222
M
ø15
<Optional stainless steel tag>
ø1/2
S
20
S
L.P.
2-M8 12
See table 1
70
120
5th digit of
code symbols
0, G
1, H
2, J
3, K
4, L
5, M
6, N
7, P
A, Q
B, R
C, S
D, T
E, U
F, V
øD
øE
t
N-øh
(Flange)
140
155
140
155
160
165
175
185
127
152
156
165
156
165
105
120
105
120
120
130
130
145
98.4
120.6
114.3
127
114.3
127
36
36
38
38
42
42
52
54
37.5
39.5
41
42.5
42.5
45.5
4-19
4-19
4-19
8-19
4-23
8-19
4-25
8-23
4-16
4-20
4-23
8-20
4-23
8-20
JIS-10K-40A
JIS-10K-50A
JIS-20K-40A
JIS-20K-50A
JIS-30K-40A
JIS-30K-50A
JIS-63K-40A
JIS-63K-50A
ANSI/JPI-150LB-1 1/2B
ANSI/JPI-150LB-2B
ANSI/JPI-300LB-1 1/2B
ANSI/JPI-300LB-2B
ANSI/JPI-600LB-1 1/2B
ANSI/JPI-600LB-2B
71
K
17
B, T
1/2-14NPT
C, V
Pg13.5
M20
1.5
M
8
11th digit of
Code symbols
Capillary
length [mm]
16
5
8
4.5
16
5
D, Q
E, R
L, S
1500
3000
5000
7th digit of
Code symbols
L
Mass approx.
[kg]
V, H, M, T, J
A
B
C
D
0
50
100
150
200
14 to 19.5
15 to 30.5
15.5 to 31
16 to 31.5
16.5 to 32
Note : In case of wafer type, flange is excluded
from the scope of supply.
Mount flange, referring to the view.
<Wafer type>
10
G1/2
TABLE 1
20
Note)
62
Conduit conn.
J
D, W
2-M6 screw depth 9
ø84
ø49
Inner of gasket
4th digit of the
Code symbols
3, 4, A, S
Sensor
unit
H.P.
Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
CONNECTION DIAGRAM
CK CK
<With direct mount adaptor>
Vent/drain plug
N holes, h dia.
øF
øE
øD
ø84
25
(102)
Long vent/drain plug
(option)
S
In case of 4th
digit code "A.B.C.D.E"
L. P.
H. P.
t
20
In case of 4th
digit code "S.V.W.X"
In case of 4th digit code "T"
Fastener
(Flameproof only)
8
10
U-bolt M8
94.5
ø80
105
70
ø80
52.5
105
UP
104
MTG. pipe
JIS 50A(2B)
80
88
DOWN
38 28
4 holes
9 dia.
201
58
Note)
(27)
Cable gland (option)
"B" Conduit conn.
With field IND.
"A" Conduit conn.
Detail "A"
Zero ADJ. screw
Detail "B"
CONNECTION DIAGRAM
ø13
ø15
K
17
M
CK CK
Table 1
J
11th digit of
Capillary
Code symbols length [mm]
Conduit conn.
4th digit of the
Code symbols
J
K
M
3, 4, A, S
G1/2
17
8
B, T
1/2-14NPT
16
5
C, V
Pg13.5
8
4.5
D, W
M20 1.5
16
D, Q
E, R
L, S
ø1/2
270
48 43
1500
3000
5000
5
16th digit of 17th digit of
øD
code symbols code symbols
1
1
2
2
3
3
1
1
2
2
Note)
1
2
1
2
1
2
H
T
H
T
95
100
95
100
115
120
89
98
95
117
øE
øF
t
N-øh
Flange
70
75
70
75
80
85
60.3
69.9
66.7
82.5
51
56
51
56
55
60
34.9
42.9
34.9
42.9
12
14
14
16
18
18
11.5
13
14.5
16
4-15
4-15
4-15
4-15
4-19
4-19
4-16
4-16
4-16
4-20
JIS-10K-15A
JIS-10K-20A
JIS-20K-15A
JIS-20K-20A
JIS-30K-15A
JIS-30K-20A
ANSI/JPI-150LB 1/2B
ANSI/JPI-150LB 3/4B
ANSI/JPI-300LB 1/2B
ANSI/JPI-300LB 3/4B
222
Electronics
unit
Earth
terminal
Sensor
unit
2-M8 12
70
120
62
Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
11
FKX...4
<With direct mount adaptor (screw connection type)>
Long vent/drain plug
(option)
25
High press. conn. "D"
ø84
Vent/drain plug
(102)
Low press. conn. D"
S
In case of 4th digit
code "A.B.C.D.E"
20
23
In case of 4th digit
code "S.V.W.X"
U-bolt M8
Fastener
(Flameproof only)
8
94.5
In case of 4th digit
code "T"
10
ø80
105
70
ø80
52.5
105
UP
104
MTG. pipe
JIS 50A (2B)
88
DOWN
38 28
Note)
4 holes
9 dia.
58
201
"A" Conduit conn.
Detail "A"
Cable gland (option)
(27)
"B" Conduit conn
Zero ADJ. screw
With field IND.
270
48 43
Detail "B"
ø13
CONNECTION DIAGRAM
M
ø15
CK CK
Electronics
unit
17
K
J
Earth termina
222
G1/2
Table 1
Conduit conn.
4th digit of the
J
K
M
Code symbols
A, S
G1/2
17
8
B, T
1/2-14NPT
16
5
C, V
Pg13.5
8
4.5
D, W
M20 1.5
16
5
16th digit of
Code symbols
11th digit of
Code symbols
D, Q
E, R
L, S
17th digit of
Code symbols
Capillary
length [mm]
1500
3000
5000
2-M8 12
70
120
Press. conn."D"
S
R
S
N
1/2-14NPT
S
2
Rc 3/4
S
T
3/4-14NPT
Sensor
unit
62
Rc 1/2
Note)
Cable gland is supplied in case of flameproof packing type.
ø11 cable is suitable.
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
Instrumentation Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http://www.fic-net.jp/eng
Information in this catalog is subject to change without notice.
Printed in Japan