Soft-start Solid State Contactors G3J-S CSM_G3J-S_DS_E_2_1 Soft-start Function Starts Motors Smoothly and Economically • The soft-start function allows a smooth startup of motors by holding down the starting current, and functions like an inverter. • Harmonized protection with thermal overload relays complying with IEC 947-4-1 (Class 10A/10); can be used like a standard contactor. • Comply with UL, CSA, IEC, and JEM requirements. • Mount with screws or to DIN tracks. • Compact monoblock construction (W: 80 × H: 100 × D: 100 mm) with a heat sink. • Snubber circuit and varistor are built-in. • Operation indicator. Refer to Safety Precautions for All Solid State Relays. Model Number Structure ■ Model Number Legend G3J-@@@@@@ 1 2 3 4 5 6 7 5. Rated Load Current 11: 11.1 A (200-V models) 05: 4.8 A (200-V models), 5.5 A (400-V models) 03: 2.4 A (400-V) models 6. Terminal Type B: Screw terminals 7. Zero Cross Function L: Not equipped with zero cross function 1. Basic Model Name G3J: Solid State Contactor 2. Load Power Supply Blank: AC output 3. Functions S: Soft-start function 4. Rated Load Power Supply Voltage 2: 200 VAC 4: 400 VAC Appearance Output terminals (power supply) Operation indicator Input terminals Initial torque setting adjuster (default setting: 200%) Ramp-up time setting adjuster (default setting: 1 s) Output terminals (load) 1 G3J-S Ordering Information ■ List of Models Number of elements Insulation method 3 Phototriac Rated supply voltage 12 to 24 VDC Input method No-voltage input (open and shortcircuit input) Applicable motor 2.2 kW (5.5 A) Model 380 to 400 VAC G3J-S405BL 200 to 220 VAC G3J-S211BL 0.75 kW (2.4 A) G3J-S403BL 2.2 kW (11.1 A) 0.75 kW (4.8 A) G3J-S205BL Note: When ordering, specify the rated supply voltage. ■ Accessories (Order Separately) Mounting Bracket Model R99-14 FOR G3J (See note.) Note: Use this Bracket when mounting Thermal Relay to a G3J-series SSR. Specifications ■ Ratings (at an Ambient Temperature of 25°C) Power Supply Rated supply voltage 12 to 24 VDC Operating voltage range 10.2 to 26.4 VDC Current consumption 100 mA max. (at 12 to 24 VDC) Operation Circuit Input current 10 mA max. (at 12 to 24 VDC) Input method No-voltage input (short-circuiting and opening inputs) (See note.) Short-circuiting or opening terminals 1 and COM or 2 (+) and 1 SSR input turned ON: A maximum residual voltage of 2 V between short-circuited terminals SSR input turned OFF: A maximum leakage current of 0.15 mA Relay input: For minute signals Note: Refer to Safety Precautions for the G3J-T, G3J-S, and G3J. Main Circuit Item G3J-S405BL G3J-S403BL G3J-S211BL G3J-S205BL Rated load voltage 200 to 400 VAC (50/60 Hz) 200 to 240 VAC (50/60 Hz) Load voltage range 180 to 440 VAC (50/60 Hz) 180 to 264 VAC (50/60 Hz) Rated carry current 5.5 A (Ta = 40°C) 2.4 A (Ta = 40°C) 11.1 A (Ta = 40°C) 4.8 A (Ta = 40°C) Min. load current 0.5 A Peak-value current resistivity 220 A, 60 Hz, 1 cycle 96 A, 60 Hz, 1 cycle 350 A, 60 Hz, 1 cycle 150 A, 60 Hz, 1 cycle Overload resistance Refer to Information Common to the G3J, G3J-T, and G3J-S. Closed current (effective value) AC3 55 A 24 A 111 A 48 A AC4 66 A 28.8 A 133.2 A 57.6 A Breaking current (effective value) AC3 44 A 19.2 A 88.8 A 38.4 A AC4 55 A 24 A 111 A 48 A Applicable load 3-phase inductive 380 to 400 VAC, 2.2 kW, 380 to 400 VAC, 200 to 220 VAC, 2.2 kW, 200 to 220 VAC, motor (AC3 AC4 5.5 A 0.75 kW, 2.4 A 11.1 A 0.75 kW, 4.8 A AC53-a) Motors passing the AC3-class, AC4-class, and AC53-a-class switching frequency test (Ta = 40°C) under conditions specified by OMRON. Refer to Information Common to the G3J, G3J-T, and G3J-S. Resistive load (AC1) (See note.) 200 to 400 VAC, 5.5 A 200 to 400 VAC, 2.4 A 200 to 240 VAC, 11.1 A 200 to 240 VAC, 4.8 A Note: No single-phase load can be connected. 2 G3J-S ■ Characteristics Item G3J-S405BL G3J-S403BL Ramp-up time Set within a range from 1 to 25 s. Reset time 5/6 cycles of load power supply + 1 ms max. Starting torque Set within a range from 200% to 450% In. G3J-S211BL Output ON-voltage drop 1.8 VRMS max. 1.6 VRMS max. Leakage current 20 mA max. (at 400 VAC) 10 mA max. (at 200 VAC) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength 2,500 VAC, 50/60 Hz for 1 min Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75–mm single amplitude Shock resistance Destruction: 294 m/s2 Ambient temperature Operating: –20°C to 60°C (with no icing or condensation) Storage: –30°C to 70°C (with no icing or condensation) Ambient humidity Operating: 45% to 85% Weight 730 g max. Certified standards UL508 File No. E64562 CSA 22.2 No. 14 File No. LR35535 IEC947-4-1 File No. 96.2597.02 EMC Emission Emission Immunity AC mains Electromagnetic ESD Immunity Electromagnetic Immunity EFT Immunity Surge transient Immunity RF disturbance G3J-S205BL IEC947-4-2, CISPR 11 Class A IEC947-4-2, CISPR 11 Class A IEC947-4-2, IEC801-2: 4 kV contact discharge 8 kV air discharge IEC947-4-2, IEC1000-4-3 10 V/m (80 MHz to 1 GHz) IEC947-4-2, IEC801-4: 2 kV AC power-signal line IEC947-4-2, IEC1000-4-5 1 kV differential mode 2 kV common mode IEC947-4-2, IEC/DIS1000-4-6 10 V (0.15 to 80 MHz) ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 3 Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2008.11 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2008 All Right Reserved.